Siemens SICAM P38, SICAM P39 User Manual

SICAM P38 P39
Preface
Content
3-phase Power Meter with Multi-Tariff function
V1.30
Manual
E50417-H8940-C564-4
NOTE
For your own safety, observe the warnings and safety instructions contained in this document, if available.

Disclaimer of Liability

This document has been subjected to rigorous technical review before being published. It is revised at regular intervals, and any modifications and amendments are included in the subsequent issues. The content of this document has been compiled for information purposes only. Although Siemens AG has made best efforts to keep the document as precise and up-to-date as possible, Siemens AG shall not assume any liability for defects and damage which result through use of the information contained herein.
This content does not form part of a contract or of business relations; nor does it change these. All obligations of Siemens AG are stated in the relevant contractual agreements.
Siemens AG reserves the right to revise this document from time to time.

Copyright

Copyright © Siemens AG 2015. All rights reserved.
The disclosure, duplication, distribution and editing of this document, or utilization and communication of the content are not permitted, unless authorized in writing. All rights, including rights created by patent grant or registration of a utility model or a design, are reserved.

Registered Trademarks

SIPROTEC®, DIGSI®, SIGUARD®, SIMEAS®, and SICAM® are registered trademarks of Siemens AG. Any unauthorized use is illegal. All other designations in this document can be trademarks whose use by third parties for their own purposes can infringe the rights of the owner.
Document Version: V01.10.01
Release date:
06.2018
Siemens Power Automation Ltd. Order No.: E50417-H8940-C564-4

Preface

Purpose of this manual

This manual describes the functions, operation, installation, and commissioning of devices 3-phase Current Power Meter-> In particular, one will find:
• Information regarding the configuration of the scope of the device and a description of the device functions > Chapter 3
• Instructions for Operation and Display > Chapter 4
• Technical Data > Chapter 2

T arget Audience

Protection engineers, commissioning engineers, personnel concerned with adjustment, checking, and service
of selective protective equipment, automatic and control facilities, and personnel of electrical facilities and power plants.

Additional Support

Should further information on the System SICAM be desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the local Siemens represen­tative.
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-7000
Fax: +49 (180) 524-2471
E-mail: support.energy@siemens.com

Notes on Safety

This document is not a complete index of all safety measures required for operation of the equipment (module or device). However, it comprises important information that must be followed for personal safety, as well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree of danger:
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe injuries.
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe injuries.
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
3
Preface
CAUTION
CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken.
Comply with all instructions, in order to avoid moderate or minor injuries.
NOTICE NOTICE means that property damage can result if the measures specified are not taken.
Comply with all instructions, in order to avoid property damage.
NOTE
Important information about the product, product handling or a certain section of the documentation which must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device) described in this document. Qualified electrical engineering personnel in the sense of this manual are people who can demonstrate technical qualifications as electrical technicians. These persons may commission, isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Proper Use
The equipment (device, module) may be used only for such applications as set out in the catalogs and the technical description, and only in combination with third-party equipment recommended and approved by Siemens. Problem-free and safe operation of the product depends on the following:
• Proper transport
• Proper storage, setup and installation
• Proper operation and maintenance
When electrical equipment is operated, hazardous voltages are inevitably present in certain parts. If proper action is not taken, death, severe injury or property damage can result:
• The equipment must be grounded at the grounding terminal before any connections are made.
• All circuit components connected to the power supply may be subject to dangerous voltage.
• Hazardous voltages may be present in equipment even after the supply voltage has been disconnected (capacitors can still be charged).
• Operation of equipment with exposed current-transformer circuits is prohibited. Before disconnecting the equipment, ensure that the current-transformer circuits are short-circuited.
• The limiting values stated in the document must not be exceeded. This must also be considered during testing and commissioning.
4
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018

Contents

1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.2 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.1 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.1 Parameter Measurement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
3.2 Power Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.3 Demand Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.4 Settlement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.5 Time Division . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.6 Event Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.7 Freezing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.8 Limit violation Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.9 Display and Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.10 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.11 Permission and Security Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
3.12 Digital Input and Output Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
4 Operation and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4.1 Full-screen Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.2 Cyclic Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
4.3 Key Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
5 Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
5.1 Total Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.2 Precautions of Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
5.3 Terminals and Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
6 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
6.1 Use of Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
6.2 Introduction of MODBUS-RTU Communication Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
6.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
6.2.2 Function of Application Layer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
6.2.3 CRC Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
6.2.4 Information mapping table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
5
Contents
7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
7.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8 Ordering Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
8.1 Ordering Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018

Overview 1

1.1 Introduction 8
1.2 Features 8
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
7
Overview

1.1 Introduction

1.1 Introduction
SICAM P38 & P39 3-phase Multi-function Power Meter integrate measurement, record, power metering, remote communication and control, large screen LCD and network communication functions. This meter can measure various parameters of power grid, such as voltage, current, power, power factor and frequency. It is provided with 2 active and reactive energy. It has multi-tariff energy and multi-tariff demand functions. P38 has two independent RS-485 ports; P39 has 1 RS-485 & 1 Ethernet port. Device supports MODBUS-RTU protocol (serial & TCP/IP). Besides, it has binary input and output.
This product is extensively applicable to power substation and distribution automation system, industrial control and industrial automation system, energy management system and community power monitoring, etc.
This 3-phase electronic multi-function power meter meets following standards:
• IEC 62052-11:2003 (Electricity metering equipment (a.c.) General requirements, tests and test conditions­Part 11: Metering equipment) standard
• IEC 62053-22:2003 static meters for active energy (classes 0.2 S and 0.5 S)
• IEC 62053-23:2003 static meters for reactive energy (classes 2 and 3)
• Modbus-RTU
nd
to 50th harmonic analysis and calculation of multiple power quality parameters. It can calculate

1.2 Features

This meter uses high-precision sampling and metering unit and high-speed MCU data processing unit, support­ing high-precision, wide-range and accurate measurement and quick data analysis; segmented multi-line WVA LCD, realizing various and abundant display; white backlight for LCD, satisfying the need for viewing data in dark environment; NVRAM, supporting long-time data storage without data loss even in the event of power fail­ure; high-precision clock chip with temperature compensation, ensuring accuracy of clock within operating tem­perature range; double communication ports and industrial standard communication protocols, realizing flexible and convenient networking; and different communication modules, satisfying different interface need of differ­ent users.
8
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018

Technical Data 2

2.1 Technical Data 10
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
9
Technical Data

2.1 Technical Data

2.1 Technical Data
Item Technical Data
Product standard IEC61557-12:2007
Input connection 3-phase-3-wire, 3-phase-4-wire, single phase
Voltage
Measurement
Metering
Digital signal
Communication
Environment Operating temp. -25 ... +60
Current
Power
(active, reactive, ap­parent)
Power grid frequency
Harmonic
Active power
Reactive power
Power pulse output
Binary output
Binary input
RS-485 port
Reference voltage U AC57.7 V
: AC380 V, AC220 V, AC100 V,
n
Measuring range: 10 V ... 276 V phase voltage
Maximum measuring range: 400 V phase voltage
Power consumption: < 0.1 VA (single phase @220VAC)
Accuracy: RMS 0.2%
Resolution: 0.01 V
Rated current I
: 1 A, 5 A
n
Measuring range: 0.015 A ... 6 A
Maximum measuring range: 9 A
Power consumption: < 0.3 VA (single phase @5A)
Accuracy: RMS 0.2%
Resolution: 0.001 A
Accuracy: 0.5%
Resolution: 0.001 kW/kVar/kVA
Measuring range: 45 Hz ... 65 Hz
Accuracy: 0.2%
Resolution: 0.01 Hz
nd
th
Frequency: 2
... 50
Precision: 5%
Accuracy level: 0.5 S, Acc. To IEC 62053-22
Resolution: 0.01 kWh, 5000 imp/kWh
Accuracy level: Class 2, Acc. To IEC 62053-23
Resolution: 0.01 kvarh, 5000 imp/kvarh
2 electric energy (active and reactive) pulse outputs
Opto-coupler isolation, 4,000 V
RMS
2 electromagnetic relay output
Normal Open Contact
Contact capacity: AC 250 V /3 A, DC 30 V /3 A
4 dry contact inputs
Opto-coupler isolation, 4,000 V
RMS
Interface type: Twisted Pair, Half Duplex Transmission
Communication rate: 600 bps ... 38,400 bps
Protocol: Modbus-RTU
10
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
Others
Item Technical Data
Operating temp. limit -35 ... +70
Relative humidity 95% (condensation free)
Clock < 0.5 sec./day (-40 .... +85 ℃ )
AC or DC power supply
Operating power supply
Max. input range: 40 V ... 420 V
Power consumption: 2 W, 4 VA
Total dimension (mm): 96×96×95
Dimension
Panel cut out size (mm): 92×92
IP53
Weight Approx. 450 g
Technical Data
2.1 Technical Data
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
11
Technical Data
2.1 Technical Data
12
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018

Functions 3

3.1 Parameter Measurement 14
3.2 Power Metering 15
3.3 Demand Measurement 16
3.4 Settlement 17
3.5 Time Division 17
3.6 Event Record 18
3.7 Freezing 18
3.8 Limit violation Alarm 19
3.9 Display and Buttons 20
3.10 Communication 20
3.11 Permission and Security Management 20
3.12 Digital Input and Output Interface 21
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
13
Functions

3.1 Parameter Measurement

3.1 Parameter Measurement
This meter is provided with various measuring functions. Power grid parameters and index measurable are as follows:
• Voltage of each phase and mean voltage
• Voltage of each line and mean voltage
• Current of each phase, average current and neutral current
• Total and separate active power, reactive power and apparent power of each phase
• Phase angle of voltage and current of each phase
• Total and separate power factor of each phase
• Power grid frequency and measuring range 45 Hz to 65 Hz
nd
• Effective value and ratio of 2
- Harmonic voltage ratio:
to 50th harmonic voltage and harmonic current of each phase
where, Uh - No. h harmonic voltage (RMS); U1 - fundamental voltage (RMS).
- Harmonic current ratio:
where, I
- No. h harmonic current (RMS); I1 - fundamental current (RMS).
h
• Total harmonic voltage distortion and total harmonic current distortion of each phase
- Total harmonic voltage distortion:
- Total harmonic current distortion:
• Voltage wave crest factor (CF) of each phase, indicating peak of distorted waveform
14
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
Functions

3.2 Power Metering

• Current K coefficient K
of each phase, a critical index measuring current quality
f
where, I
- effective value of No. h harmonic current (RMS); k - range 1 to 50, configurable with communi-
h
cation, factory default 50.
• Telephone harmonic form factor (THFF) of each phase
Harmonic interference will generate communication system noise, reducing quality of connection. Consul-
tative Committee of International Telephone and Telegraph (CCITT) measures harmonic interference to telecommunication using weight coefficient Ph of noise, expressed with THFF.
where, P
- weight coefficient of noise.
h
3.2 Power Metering
This meter can meter various energy:
• Combined active and supply and demand active energy
• Combined reactive and four-quadrant reactive energy
• Fundamental active power and total harmonic active energy
• Import and export active energy of each phase, combined reactive energy of each phase, fundamental active energy and harmonic active energy
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
15
Functions

3.3 Demand Measurement

3.3 Demand Measurement
1. Terms and Definitions
Demand means average power within specified period. The maximum value of demand recorded within
specified period is maximum demand.
Current demand means average current within specified period. The maximum current value recorded within
specified period is called maximum current demand.
Demand cycle means continuous equal intervals for measuring average power.
Sliding window time means time interval for measuring maximum demand through recursion. It is less than
demand interval.
Temporary unit means the memory unit of the meter, used for temporary storage of power value or current
value when calculating maximum demand.
Demand interval can be selected from 5, 10, 15, 30 and 60 min. Sliding window time can be selected from
1, 2, 3 and 5 min. Demand interval is five times the sliding window time and is 60 at maximum.
2. In the event of power-on, zero clearing, clock adjustment and interval change of voltage line, the meter will execute demand measurement depending on demand interval from current moment. When the first demand interval is completed, maximum demand will be recorded at slip interval. Maximum demand will not be re­corded within an incomplete demand interval.
3. When power direction changes, temporary demand unit will be cleared. Temporary demand unit will not be
cleared when across rate period to ensure continuity of maximum demand measurement. Zero clearing of temporary unit is necessary when:
• Overall clearing of meter;
• Clearing maximum demand upon communication command;
• Clearing maximum demand manually through button;
• Change of power direction;
• Settlement among different months.
4. This meter is capable of various maximum demand calculation functions, including import/export active demand and occurrence time, combined reactive and four-quadrant reactive maximum demand and occur­rence time, import/export apparent demand, maximum current demand of Phase A, Phase B and Phase C and occurrence time.
5. Combined reactive maximum demand means the quadrant with maximum demand value among reactive quadrant participating in combined computation. For example, value of reactive combined status character 2 is 05 H. Typical combined reactive 1 = 1st quadrant reactive + 2nd quadrant reactive. Assuming reactive maximum demand of 1
st
quadrant in a demand interval is 100kvar and the same of 2nd quadrant is 200 kvar,
maximum demand value of combined reactive demand 1 within the same demand interval will be 200 kvar.
6. This meter is provided with two types of zero clearing for demand: clearing via communication and manual clearing with button. For description of the latter, see subsequent content.
7. For time generating maximum demand, minute synchronization or clock synchronization is available. This is controlled by parameter mode character 2. For mode character 2, see the table below. Such mode supports parameter setting and alteration through communication.
Bit Function Bit Value vs Function Default
Bit 7 Reserved 0
Bit 6 Reserved 0
Bit 5 Demand synchronization mode
1: minute synchronization 0: clock syn-
chronization
1
Bit 4 Extreme value settlement 1: daily 0: monthly 0
Bit 3 Reserved 0
Bit 2 Reserved 0
16
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
Bit Function Bit Value vs Function Default
Bit 1 Reserved 0
Bit 0 Reserved 0
3.4 Settlement
1. Settlement means the meter can save current electric energy and demand data at the settlement time preset. It is also called cross month settlement.
2. Settlement day (automatic reading day) can be set through communication and any time within the 1 day can be set.
3. When crossing settlement day in case of power failure, cross month settlement will be applied depending on number of months crossed. But, when more than 3 months, data of only 3 months will be settled.
4. The meter can save historical settlement data of previous 12 months. Historical settlement data include electric energy data and demand data.
Functions

3.4 Settlement

st
to 28th

3.5 Time Division

1. The meter has a built-in high-precision real-time clock backed up by battery, carrying calendar and supporting automatic switching for leap year.
2. 6 tariffs, 14 periods, 8 daily periods, 14 yearly time zones and 100 public holidays can be set maximally and weekend period can be set. If tariff number of certain period is over number of tariffs (error), default tariff (tariff
1) will be used.
3. Electric energy and maximum demand data recorded by the meter include 6 tariffs, but time-shared data will not be recorded for each phase (A, B and C).
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
17
Functions

3.6 Event Record

3.6 Event Record
1. Instantaneous extreme value of power grid will be recorded. The meter can record maximum value and minimum value of each phase voltage, line voltage, phase current, neutral current, active power, reactive power and apparent power within cycle time. Cycle time can be "month" or "day" and is set through parameter mode character 2. At most extreme values of three cycles can be saved.
2. Zero clearing, demand clearing and event clearing can be recorded. The meter records 10 latest zero clear­ing events.
3. Power failure event can be recorded. The meter records 10 latest power failure events, containing start time and end time of power failure.
4. Timing event can be recorded. The meter records 10 latest timing events, containing pre-timing time and post-timing time.
5. Voltage and current unbalance event can be recorded. The meter records 10 latest voltage unbalance events and 10 latest current unbalance events. Decision limit and decision delay time of voltage and current unbal­ance events are set by parameter.
Voltage unbalance ratio = (3-phase voltage maximum difference / 3-phase voltage mean) x 100%, where 3-
phase voltage maximum difference is the largest difference between effective values of each phase voltage (only Uab and Ubc for 3-phase-3-wire) and 3-phase voltage mean is the mean of effective values of 3-phase voltage.
Current unbalance ratio = (3-phase current maximum difference / 3-phase current mean) x 100%, where 3-
phase current maximum difference is the largest difference between effective values of each phase current (only Iab and Ibc for 3-phase-3-wire) and 3-phase current mean is the mean of effective values of 3-phase current.
6. Statistic data of voltage eligibility rate can be recorded. The meter records statistic voltage eligibility of each phase within recent 12 months. Upper and lower limits for voltage assessment are set by parameter. Statistic data of voltage eligibility include voltage monitoring time, voltage limit violation time, voltage eligibility and voltage limit violation rate.
7. Relay closing event can be recorded. The meter has 2 relay outputs. When manual control is set for relay, the meter will record 10 latest manual closing records of relay output. Closing time and status will be record­ed.
8. SOE event can be recorded. The meter can record SOE events of 4 digital binary inputs and save 50 latest records. Time of switch motion (exact to 1 msec), shift status and switch port number are recorded.

3.7 Freezing

1. Cyclic freezing: The meter can save data of 72 latest cyclic freezing actions. Start time and interval of freezing are set with parameter. The content is import/export total active energy.
2. Daily freezing: The meter can save data of 8 latest daily freezing actions, including total active energy, total reactive energy, four-quadrant reactive energy and total active maximum demand.
18
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
3.8 Limit violation Alarm
1. This product is provided with limit violation alarm function. User may select from voltage, current, power, power factor and frequency parameters at most 6 data groups at the same time as detection object and set upper and lower limits and judgment condition for them. Alarm will be activated when measured value is over the set limit. This product is provided with 2 relay outputs. When alarm parameters are configured that output is made from certain relay which is at automatic mode (not manual), limit violation alarm signal can be output through such relay.
2. At most 6 limit violation alarm parameters can be set at the same time within the product. Configuration flow of each limit violation alarm parameter: select type of detected data-set threshold of detected data-set judgment condition-select output relay for alarm signal.
• Code of various detected data: (hexadecimal number for Modbus-RTU code)
MODBUS code Content of data MODBUS code Content of data
00 Phase A power factor 14 Phase A active power
01 Phase B power factor 15 Phase B active power
02 Phase C power factor 16 Phase C active power
03 Total power factor 17 Total active power
06 Frequency 18 Phase A reactive power
07 Phase A voltage 19 Phase B reactive power
08 Phase B voltage 1A Phase C reactive power
09 Phase C voltage 1B Total reactive power
0B Uab line voltage 1C Phase A apparent power
0C Ubc line voltage 1D Phase B apparent power
0D Uca line voltage 1E Phase C apparent power
0F Phase A current 1F Total phase apparent power
10 Phase B current 20 Active demand
11 Phase C current 21 Reactive demand
12 Neutral current 22 Apparent demand
Functions

3.8 Limit violation Alarm

When code of detected data is FF, limit violation alarm function of such group is off.
• Threshold of detected data: threshold judging whether detected value is limit violation; Different units for
different data types: such as voltage-V, current-A, active-KW, reactive power-KVAR, apparent-KVA, frequency-Hz.
• Judging condition: 0 means alarm activated when exceeding limit; 1 means alarm activated when falling
below limit.
• Alarm signal output relay: 0 means no alarm signal output; 1 means alarm signal outputted from relay 1;
2 means alarm signal outputted from relay 2; 3 means alarm signal outputted from relay 1 and relay 2 at the same time.
3. Example of alarm parameter setting. Set one limit violation alarm parameter to automatic detection and alarm for "Phase A voltage", assuming that alarm threshold is 240 V, judging criterion is "over limit” and signal is outputted from relay 2.
Use MODBUS RTU protocol to set alarm parameter: set 0110 address to "07", 0111 to "0000", 0112 to "5DC0"
(multiply "240" by 100 to generate "24,000" and convert it into "00005DC0"), 0113 to "00" and 0114 to "02".
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
19
Functions

3.9 Display and Buttons

3.9 Display and Buttons
This product uses large-screen WVA multi-line LCD to provide visual and various display. The screen is provided with white backlight, enabling clear display in dark environment. Specific data information can be obtained through display with button operation. For details, see Chapter Operation and Display.

3.10 Communication

RS485 port is provided for parameter setting and reading of various data. Two independent RS485 communication ports are default configuration.

3.11 Permission and Security Management

1. This product is provided with programming permission management function.
• L0 password: used for meter reset, setting all parameters and modifying L0, L2 and L4 passwords;
• L2 password: used for meter reset, setting all parameters and modifying L2 and L4 passwords;
• L4 password: used for parameter setting, demand clearing and modifying L4 password, not for meter reset, event clearing, clearing extreme values and PT/CT ratio setting.
All level default PASSWORD is "000000"
2. Parameter setting is available only when this product is in programmable state. Steps for entering
programming state: press " " and " " at the same time to enter "PASS" screen; input correct password and press " " to enter "SET" screen and enable programmable state. After entering programmable state, programmable state prompt appears on the bottom right corner of LCD. Programmable state will remain valid in 10 minutes after program button is pressed and become invalid after power down.
3. If incorrect password is used to set this product continuously (including communication setting and button
programming) up to specific number of times (factory default 5 times), parameter setting function will be locked (factory default 60 minutes). Error count will be reset after setting once using correct password if such count is less than specific limit. Error count of password and lock time can be set (available in factory state).
4. Broadcast timing is available only once each day and time for adjustment is no more than 5 min.
20
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual
E50417-H8940-C564-4, Release Date 06.2018
3.12 Digital Input and Output Interface
Power Pulse Output
This meter provides two power pulse outputs: active and reactive, with internal opto-isolation, pulse output width (80±20) ms, maximum allowable passing current 10 mA (DC) and operating voltage range 5 V to 80 V (DC).
Functions

3.12 Digital Input and Output Interface

Figure 3-1 Circuit Diagram of Power Pulse Output Interface
Binary Input Interface
This product is provided with 4-digit binary inputs interface based on passive dry contact. Terminals are identi­fied as DI1, DI2, DI3, DI4 and COM. COM is the common terminal.
Figure 3-2 Circuit Diagram of Binary Input Interface
SICAM P38 P39, 3-phase Power Meter with Multi-Tariff function, User Manual E50417-H8940-C564-4, Release Date 06.2018
21
Loading...
+ 49 hidden pages