Siemens RF340R01, RF350R01 User Manual

0 (0)

System integration

8

The communication modules (interface modules) are links between the RFID components (reader and transponder) and the higher-level controllers (e.g. SIMATIC S7), or PCs or computers.

8.2Introduction

RF310R, RF340R, RF350R and RF380R readers are connected to the controller via the following interface/communication modules:

ASM 452

ASM 456

ASM 473

ASM 475

RF170C

RF180C

RF182C

8xIQ-Sense

Function blocks, interface modules/communication modules and readers

Function blocks are used for integration into the SIMATIC. Using these, the input parameters are transferred to the reader using the "init_run"(RESET) command.

You can find more detailed information on the software parameterization in Product Information "FB 45 and FC 45 input parameters for RF300 and ISO transponders" (http://support.automation.siemens.com/WW/view/en/33315697) or the Function Manual FB 45 (http://support.automation.siemens.com/WW/view/en/21738808) from edition A3 onwards.

SIMATIC RF300

209

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.2 Introduction

Interface modules/communication modules and function blocks

The following table shows the most important features of the interface modules/communication modules, as well as the compatible function blocks.

Table 8- 1 Overview of interface modules/communication modules

 

 

 

 

 

 

 

 

 

 

 

ASM/

Interfaces to

Interfaces to the

Function

Reader

Dimensions

Temperatu

Degree

communicatio

the

reader

blocks

connections

(W x H x D) in

re range

of

n module

application

 

 

 

mm

 

protectio

 

(PLC)

 

 

 

 

 

n

ASM 452

PROFIBUS

2 x 8-pin socket,

FC 45

1

134 x 110 x 55

0 °C to +55

IP67

 

DP-V1

M12

 

 

 

°C

 

ASM 456

PROFIBUS

2 x 8-pin socket,

FB 45

2 (parallel) *

60 x 210 x 54

0 °C to

IP67

 

DP-V1

M12

FC 55

 

or 79

+55 °C

 

 

 

 

FC 56

 

 

 

 

ASM 473

PROFIBUS

2 x 8-pin socket,

FC 45

1

87 x 110 x 55

0 °C to +55

IP67

 

DP-V1

M12

FB 45

 

 

°C

 

 

 

 

FC 55

 

 

 

 

ASM 475

S7-300

Via screw

FC 45

2

40 x 125 x 120

0 °C to +60

IP20

 

(central),

terminals in front

FB 45

 

 

°C

 

 

ET200M

connector

FC 55

 

 

 

 

 

(PROFIBUS)

 

 

 

 

 

 

 

 

 

 

 

 

SIMATIC

PROFIBUS

2 x 8-pin socket,

FB 45

2 (parallel) *

90 x 130 x 60

-25 °C to

IP67

RF170C

DP-V1

M12

FC 55

 

 

+55° C

 

 

PROFINET IO

 

 

 

 

 

 

SIMATIC

PROFINET IO

2 x 8-pin socket,

FB 45

2 (parallel) *

60 x 210 54

0 °C to

IP67

RF180C

 

M12

 

 

 

+60° C

 

 

 

 

 

 

 

 

 

SIMATIC

PROFINET IO

2 x 8-pin socket,

__

2 (parallel) *

60 x 210 x 30

0 to +60 °C

IP67

RF182C

 

M12

 

 

 

 

 

8xIQ-Sense

8xIQ-Sense

Via screw

FC 35

2 (parallel) *

40 x 125 x 120

0 °C to +60

IP20

 

 

terminals in front

 

 

 

°C

 

 

 

connector

 

 

 

 

 

*) If 2 readers are used on one ASM, the following restrictions apply:

The maximum operating temperature is 35 °C

The input voltage is 24 V ±10%

Current consumption ≤ 425 mA per reader

210

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

8.3ASM 452

8.3.1Features

Area of application

The ASM 452 interface module is a MOBY module for operating MOBY and RF300 components with RS422 over PROFIBUS DP-V1 on

Any computers and PCs

Any PLCs

When operating the interface module on a SIMATIC S7, function blocks are made available to the user.

Figure 8-1 Interface module ASM 452

The ASM 452 is the result of consistent development of the familiar ASM 450/451 interface modules. Optimal data throughput can be achieved even in large-scale PROFIBUS configurations thanks to the use of acyclic data traffic on PROFIBUS DP V1. The minimum cyclic data load of the ASM 452 on the PROFIBUS provides the user with the guarantee that other PROFIBUS nodes (e.g. DI/DO) can still be processed at great speed.

The ASM 452 is an interface module for communication between PROFIBUS and the RF310R with RS422 interface. Through the ASM 452, the data on the RF300 transponder can be physically addressed ("Normal" addressing). In SIMATIC S7, FC 45 is available for this purpose.

8.3.2

Ordering data

 

 

 

Table 8- 2 Ordering data for ASM 452 and accessories

 

 

 

 

 

 

 

Product description

Order No.

 

 

ASM 452 interface module for PROFIBUS DP-V1, 1x RF3xxR with

6GT2002-0EB20

 

 

RS422 interface, without connector for 24 V DC and PROFIBUS

 

 

 

Accessories:

 

 

 

Connector for PROFIBUS DP and 24 V supply

6ES7194-1AA00-0XA0

 

 

Connecting cable RF3xxR ↔ ASM 452

 

SIMATIC RF300

211

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

Product description

Order No.

Plug-in cable, pre-assembled, length: 2 m (standard length)

6GT2891-1CH20

Plug-in cable, pre-assembled, length: 5 m

6GT2891-1CH50

Opt. Cable connector without read/write device cable

6GT2090-0BC00

(for cable lengths > 20 m) ASM 452 ↔ reader

 

M12 blanking cap for unused RF310R connection (1 pack =

3RX9802-0AA00

10 pieces)

 

CD "RFID Systems Software & Documentation" with FC 45, GSD

6GT2080-2AA10

file

 

Replacement part:

 

Connector plate; T functionality for PROFIBUS connection

6ES7194-1FC00-0XA0

FC 45 Reference Manual

 

German

Available in electronic form on

English

the CD "RFID Systems

French

Software & Documentation"

The ASM 456 plug-in cables 6GT2891-0Fxxx can be used as extension cables.

212

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

8.3.3Pin assignment and display elements

Pin assignments

The figure below illustrates the pin assignments of ASM 452.

 

 

 

 

 

$60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6)

 

 

 

 

 

 

 

 

 

%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

'& 9

 

 

 

;

6/*

;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

;

 

 

 

 

 

5['

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35( (55

 

35( (55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

;

 

 

;

 

 

 

 

 

 

 

6/*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5['

 

;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1RW DYDLODEOH IRU 5)

6RFNHW

3LQ DVVLJQPHQW

; DQG ;

 

6LJQDO

%

 

 

3(

 

 

352),%86 '3

 

 

 

 

 

 

3(

 

 

 

 

6LJQDO

$

 

 

/

 

 

 

 

0

 

 

 

 

 

 

 

;

 

3(

 

 

6XSSO\

 

/

 

 

YROWDJH

 

0

 

 

 

 

3(

 

 

 

 

/

 

 

 

 

0

 

 

1RW FRQQHFWHG

Figure 8-2 Pin assignment and LEDs of ASM 452

/('V IRU 352),%86 '3

6)

6\VWHP

)DXOW

%)

%XV

)DXOW

21 /LJKWV XS ZKHQ WKHUH LV $60 LV JHQHUDWHG E\ WKH 9 VXSSO\ YROWDJH9 '& /LJKWV XS ZKHQ WKH 9 VXSSO\ YROWDJH LV FRQQHFWHG WR WKH $60

/('V IRU 5) DQG$60

5['

5HDGHU

DFWLYH

ZLWK

35( (55

7UDQVSRQGHU SUHVHQW RU HUURU

 

GLVSOD\

 

 

 

35( (55

IRU UHDGHU

 

 

7KH WUDQVSRQGHU SUHVHQW GLVSOD\ DOZD\V WDNHV SULRULW\ 7KH HUURU LV RQO\ LQGLFDWHG ZKHQ D WUDQVSRQGHU LV QRW

SUHVHQW

7UDQVSRQGHU SUHVHQW 7KH /(' LV SHUPDQHQWO\ 21 ,I PRUH WKDQ RQH WUDQVSRQGHU LV LQ WKH ILHOG WKH QXPEHU RI WUDQVSRQGHUV LV LQGLFDWHG E\ VKRUW LQWHUUXSWLRQV $ IDXOW LV QRW RXWSXW

(UURU GLVSOD\

7KH /(' LV SHUPDQHQWO\ 2)) 7KH ODVW HUURU QXPEHU LV LQGLFDWHG E\ EULHI OLJKW SXOVHV

5HDGHU 5HDGHU LV VHOHFWHG

5HDGHU 5HDGHU LV VHOHFWHG 2QO\ UHDGHU FDQ EH VHOHFWHG

6RFNHW

3LQ DVVLJQPHQW UHDGHU

 

 

 

 

UHG

 

5['

 

; ;

 

 

 

 

 

7['

 

 

 

7['

 

JUHHQ

 

5['

 

 

 

3(

 

 

 

 

 

; ;

 

;

;

 

 

9

9

 

 

'$

'(

 

 

9

9

 

 

'$

'(

 

 

3(

3(

 

 

 

 

SIMATIC RF300

213

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

8.3.4Configuration

Configuration

Hardware description

The ASM 452 has the same housing as the distributed I/O system ET 200X. General information on ASM 452 (e.g.: assembly, operation and wiring; general technical data) is available in the ET200X manual (Order No. 6ES7 198-8FA00-8AA0). Descriptions of accessories and network components can also be found in this manual.

Configuration

352),%86 '3 0DVWHU PRGXOH H J 6 &38

352),%86

$60

WR RWKHU 352),%86

EXV QRGHV

9 IRU $60b H J

5) 5

7DJ 0'6

Figure 8-3 Configuration of ASM 452

PROFIBUS configuration

The ASM 452 is integrated into the hardware configuration by means of a GSD file. The ASM can then be configured using the HW Config of SIMATIC Manager or another PROFIBUS tool.

A GSD file is provided for ASM 452 on the CD "RFID Systems Software & Documentation".

214

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

Operating mode of the ASM 452

The approved operating modes of ASM 452 are described in the GSD file. It is set using the hardware configuration tool (e.g. STEP 7 HW Config).

Reader connection system

A reader always occupies two M12 connector sockets on the ASM 452.

A pre-assembled cable therefore ensures easy connection of the reader (see figure below). The connecting cable is available in lengths of 2 m (standard) and 5 m. Extensions are possible up to 1000 m using connecting cables 6GT2891-… .

$60 VLGH

 

 

5HDGHU VLGH

 

 

 

JUHHQ

 

 

 

;

 

 

 

 

 

ZKLWH

 

 

 

;

 

 

 

 

 

EURZQ

 

 

 

;

 

 

 

 

 

 

 

 

 

 

\HOORZ

 

 

 

;

 

0 SLQ

;

;

;

SLQN

 

7ZR SLQ 0

 

 

 

 

 

 

 

JUD\

 

FLUFXODU FRQQHFWRUV

;

 

 

 

 

;

 

 

 

 

 

VKLHOG

 

 

 

;

 

 

Figure 8-4 Connecting cable (2 m) ASM 452/473 ↔ RF3xxR reader with RS422 (6GT2891-1CH20)

Cable installation

Signal

M12 (reader side)

Cable

 

X1 / Data

X2

24 V DC

1

Pink

-

1

TX -

2

Yellow

4

-

GND

3

Gray

-

3

TX +

4

Green

1

-

RX +

5

white

2

-

RX -

6

brown

3

-

-

 

 

-

-

Shield

8 + terminal piece

Shield

5

5

Cable assignment ASM 452/473 ↔ RF3xxR reader with RS422 (6GT2891-1CH20)

A reader cable connector with screw-type terminals is provided for users who want to individually pre-assemble their own cables (see figure below). Cables and reader cable connectors can be ordered from the MOBY catalog.

SIMATIC RF300

215

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

 

$60 FDEOH *7

 

3* FDEOH JODQG

 

PD[ FDEOH GLDPHWHU

 

PP RQO\ VFUHZ GRZQ

 

DIWHU DVVHPEOLQJ WKH

 

 

 

FRQQHFWRU

 

VFUHZV

 

IRU RSHQLQJ

 

WKH FRQQHFWRU

 

 

'HJUHH RI SURWHFWLRQ ,3 &RQQHFWRU 0 WR $60

&RQQHFWRU FRYHU UHPRYHG

 

 

 

 

 

 

 

6

 

 

 

6

 

 

 

 

Figure 8-5 Cable connector ASM 452/473 ↔ RF3xx reader with RS422 (6GT2090-0BC00)

Pin assignment for ASM 452/473 cable connector

Connector pin

Connection to pin of the reader

Wire color

1

4

Note data sheet provided by the

2

5

manufacturer

 

3

6

 

4

2

 

5

3

 

6

1

 

 

-

 

S

8 + terminal piece

 

Pin 7 must not be connected.

PROFIBUS cable with 24 V supply

The ASM 452 can also be operated with the "green" PROFIBUS cable. It is important to ensure that a 24 V cable is connected from X12 to X13. The 24 V cable can be connected to pins 5 and 6 in plug X12.

 

 

;

 

 

 

 

 

 

 

;

 

 

 

 

 

 

 

 

 

 

 

;

 

 

 

 

 

 

 

 

 

 

 

;

;

 

 

 

 

 

 

 

 

 

 

 

 

;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 8-6 PROFIBUS cable with 24 V supply

216

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

PROFIBUS address and terminating resistor

You must remove the connector plate from the ASM before you set the

PROFIBUS address or connect the terminating resistor. The connector plate covers the DIL switch. The position of the DIL switch in ASM is shown in the figure below with one setting example for each case.

([DPSOH 7HUPLQDWLQJ UHVLVWRU 2II$V GHOLYHUHG VWDWH

RQ

2II

([DPSOH 352),%86 DGGUHVV RQ GHOLYHU\

21

6WDQGDUG PRGHXVH *6' ILOH 6,(0 %

Figure 8-7 Setting the PROFIBUS address/connecting the terminating resistor

Note

The PROFIBUS address in ASM 452 must always match the PROFIBUS address defined in the configuring software for this ASM.

To ensure that the terminating resistor functions correctly, you must always switch both DIL switches of the terminating resistor to "on" or "off".

8.3.5Technical data

Table 8- 3 Technical data for ASM 452

 

Serial interface to the user

PROFIBUS DP-V1

 

 

Procedure after connection

EN 50170 Vol. 2 PROFIBUS

 

 

 

PG 11 cable gland

 

 

 

PROFIBUS and power supply connectors are not included

 

 

in the scope of delivery

 

 

Transmission rate

9600 baud to 12 Mbaud (automatic detection)

 

 

Max. block length

2 words cyclic/240 bytes acyclic

 

 

Serial interface to the RF3xxR

 

 

 

Connector

2 x M12 coupler plug

 

 

Max. cable length

2 m = Standard length, 5 m, 10 m, 20 m and 50 m,

 

 

 

(up to 1000 m on request)

 

 

Readers that can be connected

1x RF3xxR with RS422 interface

 

SIMATIC RF300

 

217

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.3 ASM 452

Software functions

Programming

Depending on the PROFIBUS DP master

Function blocks for SIMATIC S7

FC 45

Transponder addressing

Direct access via addresses

Commands

Initialize transponder, read data from transponder, write

 

data to transponder

Multi-tag capability

No

S7 data structures via UDTs

Yes

Power supply

 

Rated value

24 V DC

Permissible range

20 V to 30 V DC

Current consumption

Max. 180 mA; typ. 130 mA (without reader)

Digital inputs

none

Digital outputs

none

Ambient temperature

 

Operation

0 °C to +55 °C

Storage and transport

-40 °C to +70 °C

Dimensions (W x H x D) in mm

134 x 110 x 55 (without bus connector)

Fixing

4 M5 screws;

 

for mounting on any plate or wall

Weight, approx.

0,5 kg

Degree of protection

IP67

MTBF (at 40 °C)

30 • 104 hours = 34 years

8.3.6PROFIBUS Diagnosis

The following table lists possible error indications with their meanings and provides remedies.

Table 8- 4 LED indication for PROFIBUS diagnosis

 

"BF" LED

"SF"LED

Cause of error

Error correction

 

ON

*

ASM 452 is in start-up mode.

-

 

 

 

 

 

 

 

 

The connection to the DP master

Check the PROFIBUS DP

 

 

 

has failed.

connection.

 

 

 

ASM 452 not detecting a baud

Check the DP master.

 

 

 

rate.

 

 

 

 

 

 

 

 

 

Bus interrupt

Check all cables on your

 

 

 

DP Master not functioning

PROFIBUS DP network.

 

 

 

 

Check whether the connector

 

 

 

 

plugs for PROFIBUS DP are

 

 

 

 

securely plugged into the

 

 

 

 

ASM 452.

 

 

 

 

 

218

 

 

 

SIMATIC RF300

 

 

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

 

 

 

 

System integration

 

 

 

 

8.3 ASM 452

 

 

 

 

 

 

"BF" LED

"SF"LED

Cause of error

Error correction

 

flashes

on

The configuration data sent to

Check the configuration of

 

 

 

the ASM 452 by the DP master

the ASM 452 (input/output,

 

 

 

do not match the configuration of

PROFIBUS address).

 

 

 

the ASM 452.

Correct GSD file being used?

 

 

 

 

– SIEM80B6.GSD for

 

 

 

 

ASM 452

 

 

 

 

 

 

Flashes

Off

ASM 452 has detected the baud

Check the PROFIBUS

 

 

 

rate, but is not being addressed

address set on the ASM 452

 

 

 

by the DP Master.

or in the configuration

 

 

 

ASM 452 has not been

software.

 

 

 

configured.

Check the configuration of

 

 

 

 

the ASM 452 (station type).

 

 

 

 

 

 

on

Flashes

There is a hardware defect in the

Replace the ASM 452.

 

 

 

ASM 452.

 

 

 

 

 

 

8.3.7Dimension drawing

The following figure shows the dimensional drawing of an ASM 452 with bus connectors. You must add the length of the PG cable gland and the radius of the cable used to the measured overall width and depth.

 

 

 

 

 

 

 

 

 

 

 

 

Figure 8-8 Dimensional drawing of ASM 452

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

219

System integration 8.4 ASM 456

Example of stripped lengths

The following diagram shows an example of stripped lengths. The lengths apply to all cables which can be connected to the connector plugs. You must twist any shield braid present, plug into a core end sleeve and cut off any excess.

 

 

7ZLVWHG DQG

WUXQFDWHG VKLHOG EUDLGLQJ

Figure 8-9 Length of stripped insulation for PROFIBUS cables

8.4ASM 456

Configured with ASM 456

352),%86 '3 0DVWHU PRGXOH 6,0$7,&b6

$60b

352),%86

9 IRU

$60 DQG UHDGHU

9 WR RWKHU 352),%86

EXV QRGHV

WR RWKHU 352),%86

EXV QRGHV

H J

H J

5) 5

5) 5

7DJV 0'6

7DJV 0'6

Figure 8-10 Configuration of ASM 456

For more detailed information, please refer to ASM 456 Operating Instructions (http://support.automation.siemens.com/WW/view/en/32629442).

220

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.5 ASM 473

8.5ASM 473

8.5.1Features

Field of application

The ASM 473 interface module is an RF300 module for SIMATIC S7. It can be plugged into the ET 200X distributed I/O station and DESINA. ET 200X is operated by the user over PROFIBUS DP V1. An S7-300 or S7-400 with integrated PROFIBUS connection can be used as the controller.

ASM 473 supplements the SIMATIC S7 interface module ASM 475. The IP67 degree of protection means that it can be installed and operated in the process without the need for an additional protective housing.

To operate the ASM 473, an ET 200X basic module BM 141/142 with the order number 6ES7141-1BF11-0XB0 or 6ES7142-1BD21-0XB0 or a BM 143 is required.

The transponder data are accessed by means of physical addressing of the transponder.

For operation in a SIMATIC S7, the function FC 45 is available. The hardware of the ASM 473 is configured with an object manager (OM) that is integrated in the SIMATIC Manager.

Figure 8-11 Interface module ASM 473

Other features:

Up to 7 ASM 473 interface modules can be operated simultaneously in an ET 200X station.

Any other I/O modules from the ET 200X spectrum can be operated with the ASM 473.

8.5.2Ordering data

 

Table 8- 5

Ordering data for ASM 473 and accessories

 

 

 

 

 

Product description

Order No.

 

Interface module ASM 473

 

 

1x RF3xxR reader with RS422 interface

6GT2002-0HA10

 

Accessories:

 

 

SIMATIC RF300

 

221

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.5 ASM 473

Product description

Order No.

Connecting cable ASM 473 ↔ Reader RF3xxR

 

Plug-in cable, pre-assembled, length 2 m (standard length)

6GT2891-1CH20

Plug-in cable, pre-assembled, length 5 m

6GT2891-1CH50

Opt. Cable connector without reader cable

6GT2090-0BC00

(for cable lengths > 20 m) ASM 473 ↔ Reader

 

CD "RFID Systems Software & Documentation" with FC 45,

6GT2080-2AA10

GSD file

 

FC 45 Reference Manual

 

German

Available in electronic form on the

English

CD "RFID Systems Software &

French

Documentation"

222

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.5 ASM 473

8.5.3Pin assignment and display elements

Pin assignments

The figure below illustrates the pin assignment for the read/write device and the display elements.

6RFNHW 3LQ DVVLJQPHQW UHDGHU

;

 

5['

 

 

7['

 

 

7['

 

 

5['

 

 

3(

 

 

 

;

 

9

 

 

Q F

 

 

9

 

 

Q F

 

 

3(

/('V IRU 352),%86 '3

*HQHUDO LQGLFDWRUV 6) %) 21 9'& DUH ORFDWHG RQ WKH EDVLF PRGXOH RI WKH (7 ;

/('V IRU 02%<

5[' 5HDGHU DFWLYH ZLWK FRPPDQG

35( ,QGLFDWHV WKH SUHVHQFH RI D WUDQVSRQGHU (55 (UURU LQGLFDWHG E\ IODVKLQJ VHTXHQFH

7KH IROORZLQJ $60 VWDWHV DUH DOVR LQGLFDWHG ZLWK WKH /('V 35( DQG(55

35(

(55

'HVFULSWLRQ &DXVHV 5HPHG\

 

 

 

2)) 21

21 SHUP

+DUGZDUH LV GHIHFWLYH 5$0 IODVK

21

2))

&KDUJHU LV GHIHFWLYH FDQ RQO\ EH UHSDLUHG LQ WKH

 

 

IDFWRU\

+]

2))

)LUPZDUH ORDGLQJ LV DFWLYH RU QR

 

 

ILUPZDUH GHWHFWHG

 

 

/RDG ILUPZDUH

 

 

$60 PXVW QRW EH VZLWFKHG RII XQWLO ORDGHG

+]

+]

)LUPZDUH ORDGLQJ WHUPLQDWHG ZLWK HUURUV

 

 

5HVWDUW UHTXLUHG

 

 

/RDG ILUPZDUH DJDLQ

 

 

&KHFN XSGDWH ILOHV

+]

+]

2SHUDWLQJ V\VWHP HUURU

 

 

6ZLWFK $60 RU (7 ; EDVH VWDWLRQ 2)) 21

2))

[ IODVK

$60 KDV ERRWHG DQG LV ZDLWLQJ IRU D 5(6(7

 

HYHU\ V

LQLWBUXQ IURP WKH XVHU

 

 

 

Figure 8-12 Interfaces and indicators of the ASM 473 for RF300

SIMATIC RF300

223

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.5 ASM 473

8.5.4Configuration

352),%86 '3 0DVWHU PRGXOH 6,0$7,&b6

%DVLF PRGXOH (7 ; %0 (7 ; %0 (7 ; %0

'(6,1$ %0 $60b

352),%86

WR RWKHU 352),%86

EXV QRGHV

9 VXSSO\ IRU (7 ; (OHFWURQLFV

9 VXSSO\ )RU UHDGHU

H J 5) 5

0'6 7DJ

Figure 8-13 Configuration of ASM 473

Note

It differs from ASM 452 in that for ET 200X the 24 V supply must be connected to the PROFIBUS connector and on the load voltage connector (see the ET 200X manual).

Basic module - Requirements for operation of ASM 473

The following table indicates the status of the ET 200X basic module of 10/2002. The functionality of new basic modules is stored in HW Config of the SIMATIC Manager.

Table 8- 6 Requirements for operation of ASM 473

 

Order number of the ET 200X

For operation with ASM 473

For operation with ASM 473

 

basic module

(6GT2002-0HA00)*

PARAM (6GT2002-0HA10)

 

6ES7141-1BF00-0XB0

No

No

 

6ES7141-1BF00-0AB0

Yes

Yes

 

6ES7141-1BF01-0XB0

No

No

 

6ES7141-1BF10-0XB0

No

No

224

 

 

SIMATIC RF300

 

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

 

 

 

System integration

 

 

 

8.5 ASM 473

 

 

 

 

 

Order number of the ET 200X

For operation with ASM 473

For operation with ASM 473

 

basic module

(6GT2002-0HA00)*

PARAM (6GT2002-0HA10)

 

6ES7141-1BF11-0XB0

Yes

Yes

 

6ES7141-1BF40-0AB0

Yes

Yes

 

6ES7142-1BD10-0XB0

No

No

 

6ES7142-1BD11-0XB0

No

No

 

6ES7142-1BD20-0XB0

No

No

 

6ES7142-1BD21-0XB0

Yes

Yes

 

6ES7142-1BD22-0XB0

No

Yes**

 

6ES7143-1BF00-0AB0

Yes

Yes

 

6ES7143-1BF00-0XB0

Yes

Yes

 

6ES7147-1AA00-0XB0

No

No

 

6ES7147-1AA01-0XB0

No

Yes

 

* Discontinued

 

 

 

** Notes on operation:

 

 

 

In HW Config, please parameterize the module 6ES7142-1BD21-0XB0.

SIMATIC RF300

225

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.5 ASM 473

Example for a maximum configuration of ASM 473 on an ET 200X

0D[ $60 FDQ EH RSHUDWHG LQ DQ (7 ;

6,0$7,&

6,0$7,&

6,0$7,&

6,0$7,&

6,0$7,&

6,0$7,&

6,0$7,&

5) [[5

5) 5

5) 5

5) 5

5) 5

5) 5

5) 5

5) 5

 

5) [[7

6,0$7,&

5) 7

Figure 8-14 Example for a maximum configuration of ASM 473 on an ET 200X

Depending on the PROFIBUS master, up to 123 ET 200X modules can be run on one PROFIBUS branch.

Hardware configuration

The ASM 473 is integrated in the hardware configuration of the SIMATIC Manager by calling Setup.exe in the directory daten\S7_OM on the "RFID Systems Software & Documentation" CD. Currently, the ASM 473 cannot be integrated in masters of other manufacturers.

Reader connection system

A reader always occupies the two M12 connection sockets X3 and X4 on the ASM 473. A prefabricated cable makes it easy to connect the reader. The standard version of the connecting cable is 2 m in length. Other cable lengths are available on request.

For customers who want to assemble their own cables, an ASM cable connector with screw-

226

SIMATIC RF300

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

Siemens RF340R01, RF350R01 User Manual

System integration 8.5 ASM 473

type terminals is available. Cables and ASM cable connectors can be ordered from the MOBY catalog.

8.5.5Technical data

Table 8- 7 Technical specifications for ASM 473

Interface for ET 200X

Communication

Command buffer in ASM

Serial interface to the reader

Connector

Max. cable length

Readers that can be connected

Software functions

Programming

Function blocks for SIMATIC S7

MDS addressing

Commands

PROFIBUS Diagnosis

S7 diagnostics

Reloadable firmware

Power supply 1

Rated value

Permissible range Current consumption

Power dissipation of the module

Digital outputs/inputs

Ambient temperature

Operation

Transport and storage

Dimensions (W x H x D) in mm

Single unit

Width module

SIMATIC S7 I/O bus cyclic/acyclic services

2 words cyclic/238 bytes acyclic

142 x 238 bytes

2 x M12 coupler plug

2 m = standard length; other pre-assembled cables = 5 m, (up to 1000 m on request)

1 x RF3xxR reader with RS422

Depending on the PROFIBUS DP master FC 45, FB 45, FC 55

Direct access via addresses

Initialize transponder, read data from transponder, write data to transponder, etc.

Yes; in accordance with ET 200X basic station Yes, can be called up via S7 OM

Yes, via S7 OEM

24 V DC

20.4 V to 28.8 V DC

Typ. 75 mA; max. 500 mA

(or see Technical specifications of the connected reader)

Typically 1.6 W

Via expansion modules from the ET 200X spectrum

0 °C to +55 °C -40 °C to +70 °C

87 x 110 x 55

60 x 110 x 55

SIMATIC RF300

227

System Manual, 11/2009 - Zwischenstand 17.09.2009, A5E01642529-04

System integration 8.5 ASM 473

Fixing

2 M5 screws (customer side)

 

2 M3 screws (product side)

Degree of protection

IP67

Weight, approx.

0.275 kg

For installation instructions and general technical data, see the ET 200X manual.

8.5.6Dimensional drawings

Dimension drawing for mounting holes

The figure below shows the dimensions for the position of the holes for the fixing screws for a basic module and an ASM 473 expansion module.

 

 

 

 

 

 

 

Q [

 

 

 

 

 

)RU 0 IL[LQJ

 

VFUHZ

 

%0

$60b

 

Q 1XPEHU RI H[SDQVLRQ PRGXOHV

Figure 8-15 Dimensions for fixing holes for basic modules and expansion modules

Example of stripped lengths

The following diagram shows an example of stripped lengths. The lengths apply to all cables which can be connected to the connector plugs. You must twist any shield braid present, plug into a core end sleeve and cut off any excess.

 

 

7ZLVWHG DQG

WUXQFDWHG VKLHOG EUDLGLQJ

Figure 8-16 Length of stripped insulation for PROFIBUS cables