This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description and only
in connection with devices or components from other manufacturers which have been approved or
recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage,
positioning and assembly as well as careful operation and maintenance.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Automation and Drives
Postfach 48 48
90437 NÜRNBERG
GERMANY
2.4 Antenna and antenna field...........................................................................................................
3 Power supply...........................................................................................................................................
3.1 Inserting the battery .....................................................................................................................
6.1 Overview of functions...................................................................................................................
6.2 Starting the SIMATIC RF310M software .....................................................................................
6.3 The data editor.............................................................................................................................
6.4 The functions in the "File" menu ..................................................................................................
6.4.1 Loading a file................................................................................................................................
6.4.2 Save .............................................................................................................................................
A Appendix..................................................................................................................................................
A.1 FCC information ..........................................................................................................................
These operating instructions contain information required for starting up and using the
RF310M device.
The documentation is aimed at commissioning engineers and machine operators who start
up the application themselves, and it describes the functions of the "SIMATIC RF310M"
software.
Scope of validity of this document
This documentation is valid for the SIMATIC RF310M Mobile Reader and describes the
delivery status from July 2007.
Further information
The present instructions are a supplement to the operating instructions of the basic device
PSION WORKABOUT PRO.
The documents "Quick Reference Guide" and "Regulatory & Warranty Guide" for
"WORKABOUT PRO C/M-E Hand-Held Computer" are included with the device. Please note
the information they contain.
1
Conventions
History
You can find further information in the PSION User Manual and in the documentation for the
docking station.
The following terms/abbreviations are used synonymously in this document:
● tag, transponder, mobile data memory (MDS), data carrier
● Reader, read/write device (SLG)
Previous editions of these operating instructions:
Edition Remarks
07/2007 First edition
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
SIMATIC RF310M expands the RF300 RF identification system with a powerful mobile
handheld reader for applications in the areas of production and service. In addition, it is an
indispensable aid for startup and testing.
2.1 Application area
The RF300 Mobile Reader is intended especially for the SIMATIC RF300 RFID system. The
enclosed SIMATIC RF310M software allows user-friendly, distributed reading and writing of
all RF300 tags.
The Mobile Reader can also be used in harsh environments. The Mobile Reader is
extremely rugged and protected against spray water. The backlit display is easy to read even
under unfavorable lighting conditions.
2
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
9
Description
2.2 Features
2.2 Features
The SIMATIC RF310M Mobile Reader consists of a powerful, rugged and flexible handheld
computer (PSION WORKABOUT PRO) and an integral read/write unit for the SIMATIC
RF300 RFID system. It meets the requirements of mobile RFID data acquisition in harsh
environments in an extremely user-friendly and ergonomic design. Based on
communications standards, the device guarantees simple integration into existing or planned
infrastructure.
The following functions can be executed:
Functions
● Reading the data from the tag (data memory)
● Writing the data to the tag
● Deleting the entire data memory (overwriting it with a filler)
● Reading and displaying the ID number of the tag
● Reading the data carrier status (MDS status)
● Reading the status of the read/write unit (SLG)
Accessories
● Representing and editing the data in hexadecimal and ASCII format
● Activatable/deactivatable password protection for all write functions and for terminating
the program
● Menu prompting in English and German (switchable)
● Saving of the read-in RF300 data to files. The Mobile Reader has approximately 1.8 MB
available for this purpose.
The RFID read/write unit of RF300 is integrated into the PSION basic unit. Communication
with the basic unit is handled via the internal serial scanner port that also supplies the power
for the RFID unit.
The charging and docking station (including wide-range power supply unit, 100 to 240 V AC,
50 to 60 Hz) for recharging the battery and connecting to PCs via USB port must be ordered
separately. This station has a charging bay for an additional replacement battery. See
Accessories (Page 65).
The RF300 Mobile Reader consists of a basic unit and an integral read/write head (①) of the
SIMATIC RF300.
The basic unit is a PSION Workabout PRO and represents a global standard among mobile
readers.
The SIMATIC RF310M software is stored in an integral flash disk secure against power
failure. The program launches automatically when the Mobile Reader is switched on.
The separately available accessories include a charging and docking station (④) with USB
port for data exchange with the PC.
All RF300 data memories can be edited with the Mobile Reader. It is not possible to edit data
memories of other RFID systems.
Design of the SIMATIC RF310M Item Description
① Read/write head
② Holder for input pen
③ On/off button
④ Charging cradle
⑤ Power supply
⑥ ASCII keypad
⑦ Numeric keys
⑧ Charge indicator (LED)
⑨ Display
⑩ Function indicator (LED) for
read/write operations
LED lights up:
• Green: an action is being
successfully carried out.
This increases the power
consumption of the
RF310M via the
read/write head.
• Red: Internal error
processing of the
application; no action is
required from the user.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
11
Description
2.4 Antenna and antenna field
2.4 Antenna and antenna field
Read head with integral antenna
The antenna is housed in the read head ① under a cover.
Figure 2-1 Read head with antenna
Direction of propagation of the high-frequency field
The read/write area for transponders is above and below the front part of the housing.
Transponders cannot be read or written to from the end.
The figure below shows the direction of propagation of the HF field of the antenna.
The Mobile Reader's battery is located on the rear of the unit.
Steps for inserting the battery
1.
2. Turn the screws counter-clockwise.
Use the other end of the input pen as a screwdriver:
3
3. To remove the cover, lift the screw side first.
4. Hold the battery at an angle when inserting so that the side of the battery with the direction
arrow is inserted into the battery compartment first.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
13
Power supply
3.2 Charging function
3.2 Charging function
Complete charging of an empty battery takes approximately 5 hours.
Starting the charging operation
The charging operation is started as soon as you insert the PSION Workabout Pro into the
charging cradle.
WARNING
Explosion hazard when using a different charging cradle.
Use only the original charging cradle from PSION. Use of another charging station can
result in explosions and serious personal injury.
Detecting the level of charge
You can check the level of charge via the charge indicator (LED) on the Mobile Reader:
Table 3-1 Status LED
LED color LED status Meaning
Flashing Charging in progress. Green
Permanently lit Battery is fully charged.
Flashing Charging not in progress. Battery fault! Red
Permanently lit External temperature too high.
Other AA batteries can be used in the PSION Workabout Pro . These can be rechargeable
lithium ion batteries or non-rechargeable alkaline batteries.
CAUTION
Information in the PSION manual concerning the use of other batteries
When using other batteries, please note the information in the PSION User Manual!
Unsuitable batteries can result in damage.
3.4 The backup battery
The backup battery in the unit PSION Workabout Pro is used for retaining the application
data when the main batteries are uncharged. The backup battery is a lithium cell that cannot
be charged. Please note that a new backup battery (in the case of an empty or removed
main battery) can only retain the data in the RAM for a few minutes.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
The scope of supply of the RF310M comprises several components.
Ordered components Order No.
Mobile Reader SIMATIC RF310M
with integral RFID read/write unit for RF300
4
6GT2803-0AA00
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
17
Commissioning
4.2 Switching on the device
4.2 Switching on the device
Requirements for startup
● The Mobile Reader SIMATIC RF310M is ready-mounted
● The unit's battery is charged (see
Note
Before switching the device on for the first time, you must insert the Mobile Reader into
the charging cradle and charge it for approximately 5 hours.
Switching on the device
To switch the Mobile Reader on, press and hold the red "ENTER ON" button for at least one
second.
Figure 4-1 <ENTER ON>/<OFF> key
After switching on, the first power-up lasts a few seconds. The RF310M application launches
automatically.
Switching the device off
To switch the SIMATIC RF310M Mobile Reader off, press the blue key and then the
<ENTER ON> key.
Charging function (Page 14)).
Automatic shutdown of the device
The device shuts down automatically if no key is pressed for 5 minutes. After switching on
again, the Mobile Reader continues to operate with the same interface it was using before it
was manually or automatically switched off.
You can set the following menu languages for operating the Mobile Reader SIMATIC
RF310M:
● English
● German
Procedure for selecting the language
Select the desired language in the "Language selection" window of the "Extras > Language"
menu and confirm with "OK".
Figure 4-2 Language selection window
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
19
Commissioning
4.3 Basic settings
4.3.2 Adjusting the acoustic signal volume
The tag functions trigger an acoustic signal indicating whether the operations were
successful or were terminated with an error. You can switch these acoustic
acknowledgements/signals on and off and you can regulate their volume.
Adjusting the volume of the acoustic signals
1. Press the blue key twice in succession so that "BLUE KEY" appears on the right of the
display.
2. Regulate the volume of the acoustic signals using the keys "A" (quieter) and "B" (louder).
Figure 4-3 Keys for regulating the volume
Specific setting of the acoustic signals
Select "My Computer > Control Panel > Volume & Sounds" on the desktop.
On the "Volume" tab, you can regulate the volume between "Soft" and "Loud" using the bar.
You can also permit or deactivate acoustic signals for different messages by activating the
relevant checkboxes.
4.3.3 Adjusting the screen backlighting and contrast
You can adjust the brightness of the screen by pressing the following key:
Pressing a shift key causes a change in the function of the subsequently pressed keys.
The following keys of the SIMATIC RF310M are shift keys:
● <SHIFT>
● <CTRL>
● <ALT>
● <ORANGE>
(changes the key assignment in accordance with the orange-colored labeling on the
keypad)
● <BLUE>
(changes the key assignment in accordance with the blue-colored labeling on the keypad)
5
Activating the shift keys:
When you press a shift key, the name of the selected switch key appears in lowercase in the
task bar, e.g. "org key", "blue key". Any subsequently pressed key then changes its function,
the display in the task bar disappears and the shift key is deactivated again.
Defining shift keys
If the shift key is to remain set, it must be pressed twice in succession. The display in the
task bar then appears in uppercase, e.g. "ORG KEY, "BLUE KEY".
If the shift key is pressed a third time, it is deactivated again and the display in the task bar
disappears.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
Enable navigation to the left, right, up and down in the
display.
Closes the currently open menu, dialog window or started
application and leads back to the previous interface.
Shift key:
Changes the function of other keys
Inserting spaces.
In a Windows dialog window, checkboxes can be
activated or deactivated with the <SPACE> key.
Display of uppercase letters (A-Z) and symbols also
specified on the numeric keys (e.g. &, *,...).
⑦
⑧
⑨
⑩
<BKSP> Moves the cursor to the left to delete the last entered
character.
<DEL>
(blue key and
<BKSP>)
<ORANGE>
<ALT>
<TAB>
Removes the character following the cursor.
Shift key:
Changes the function of other keys
Moves the cursor to the right or down at specific intervals.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
23
Operation
5.2 The SIMATIC RF310M menu
5.2 The SIMATIC RF310M menu
The menu bar of the SIMATIC RF310M program comprises five main menus:
● File
● Tag
● Editor
● Extras
● ?
The functions of the individual menus can be selected with the help of the shortcuts [see
Overview of functions (Page 25) ] or via the touchscreen (with input pen).
Press <ALT> together with the underlined letter in the menu in each case for the relevant
shortcut.
Operation of the SIMATIC RF310M software is described in detail in the next chapter.
After switching on the Mobile Reader, the Editor appears on the display. You can now view
the data, enter new data or call a function via the menu.
Function Shortcut Description
File
Tag
Editor
Extras
? About <ALT+ORANGE+?+B> Manufacturer data
Load <ALT+F+L> Load file from the integral PSION flashdisk to the
work memory
Save <ALT+F+S> Save read-in tag (MDS) data to the flashdisk
Exit <ALT+F+X> Exit RF300 application
Read <Ctrl+R> or
<ALT+T+R>
Read OTP <ALT+T+E> Read OTP area of the tag
Read Config. Data <ALT+T+C> Read configuration data of the tag
Write <Ctrl+W> or
<ALT+T+W>
Write OTP <ALT+T+O> Write to the OTP area of the tag
MDS Status <ALT+T+M> Read tag (MDS) status
Read TagId <ALT+T+T> Read ID number of the tag (MDS)
Init <Ctrl+I> or
<ALT+T+I>
Jump to Address <ALT+E+J> Jump to a specific address in the editor
Display <ALT+E+D> Change the display options
Clear <ALT+E+C> Fill data in the editor
Data Edit <ALT+E+E> Edit the data at the cursor position in different
Password <ALT+X+P> Change password for the application
Language <ALT+X+L> Set menu language
Address Setup <ALT+X+A> Define inputs for the commands "Read/write
Tag Type Selection <Ctrl+S> or
<ALT+X+T>
SLG Status <ALT+X+G> Read the status of the RFID read/write unit
Read data from tag (MDS)
Write data to tag (MDS)
Write a specific value to a tag
formats
MDS"
Set the tag memory size
6
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
25
SIMATIC RF310M software
6.2 Starting the SIMATIC RF310M software
6.2 Starting the SIMATIC RF310M software
If the SIMATIC RF310M software is not started when the device is switched on, it can be
started using the "RF310M" icon on the desktop or via "Desktop > My Computer >
Flash Disk > RF310M".
6.3 The data editor
The transponder data (MDS data) can be edited in the editor window in hex or ASCII format.
You can toggle between the two in the Editor/Display menu. (See
Display (Page 41))
Figure 6-1 Data editor
The entire size of a tag (MDS) memory is always represented in the editor. You can reach
the individual addresses using the input pen. A jump can be made to any address with the
menu point "Editor/Jump to Address". (see
The data at which the cursor is located is represented
alternatively in the formats hexadecimal, decimal, ASCII or
binary. The data field can be modified with the Data Edit
42) function.
(Page
③ The editor window contains the MDS data. The size of the
represented data depends on the MDS type.
④ MDS addresses are represented in hexadecimal or decimal
format.
The "current area"
Current area Description
The "current area" is displayed in green in the editor. All other data
areas of the MDS are against a white background.
The current area shows the last edited, read or overwritten data
area. When reading/writing, the address of the current area is
preassigned as the value for the read/write command. However,
this value can be adapted when executing the command.
The current area is changed automatically when you edit and
overwrite data in the editor, or when you write data.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
27
SIMATIC RF310M software
6.4 The functions in the "File" menu
6.4 The functions in the "File" menu
The following file functions are available that you can select in the menu via "Tag" (or
<ALT+F>):
● Load
● Save
● Exit
Figure 6-2 The file functions
6.4.1 Loading a file
You can load a file from the "Flash Disk" folder via "File > Load" (or <ALT+F+L>) if the file
● has previously been saved with the command "File > Save" or
● has been transferred from the PC to the "Flash Disk" folder of the PSION Workabout Pro
[see also
All the files of the "Flash Disk" folder are displayed. You can select the desired file via the
touchscreen or by entering the filename under "Name" and <OK>.
6.4.2 Save
Via "File > Save" (or <ALT+F+S>), you can save data currently displayed in the editor of the
Mobile Reader to a file on the PSION Workabout Pro.
The filename can be up to 20 (alphanumeric) characters in length. When saving, the
extension ".HEX" (data) is automatically added to the filename [see also
and to the Mobile Reader (Page
Copying data from and to the Mobile Reader (Page 50)].
You can exit the SIMATIC RF310M program using "File > Exit" (or <ALT+F+X>) or the
<ESC> key. You then reach the WinCE operating system level of the PSION Workabout Pro.
You require the password relevant to the application for this, if you have previously assigned
one.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
29
SIMATIC RF310M software
6.5 The functions in the "Tag" menu
6.5 The functions in the "Tag" menu
The following tag functions are available that you can select in the menu via "Tag" (or
<ALT+T>):
The tag (MDS) functions carry out communication with the transponder. They indicate the
progress of the currently executing function and any timeout, if applicable:
Progress display in the case of the tag function
During data transfer, the progress of the executing function is displayed as a percentage,
e.g. "Read Tag 10 %":
Figure 6-4 Progress display in the case of the tag function
The tag (MDS) function is not interrupted if you briefly move the tag out of the read field.
Timeout display in the case of the tag function
If the tag remains unedited for longer than 30 seconds, the function is interrupted and the
"TIMEOUT" message window appears:
Figure 6-5 Timeout display in the case of the tag function
You can now stop the command completely with "Cancel" or continue it with "Retry". If you
retry, the interrupted command is continued at the point of interruption.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
31
SIMATIC RF310M software
6.5 The functions in the "Tag" menu
6.5.2 Requirements for operating the tag functions
To enable execution of the tag functions, you must set the memory size of the tag and the
minimum distances between the Mobile Reader and the tag.
Setting the memory size of the tag (Tag Type Selection)
Set the memory size of the tag using "Extras" > "Tag Type Selection" ( or <Ctrl+S>). See
Tag Type Selection (Page 46).
also
Distance limits to be observed between the Mobile Reader and the tag
The ranges listed in the table below are distance limits in the field maximum of the read
head.
Table 6-1 Ranges between Mobile Reader and transponders
Avoid several tags in the field of the SIMATIC RF310M
Please ensure that when executing the tag functions, the minimum distances from
transponders are observed, that is, distances between 100 and 500 mm depending on the
tag type. (See the System Manual SIMATIC RF300 > RF300 planning the system > Field
data of transponders, readers and antennas).
Tags that follow each other closely, and are therefore in the area of the SIMATIC RF310M
at the same time, can result in errors in reading and writing the tag data.
Figure 6-6 Tag acquisition area of the reader
Tag in the blue area [①] Tag is being edited
Tag in the gray area [①] Tag can still be edited
Tag outside the gray area [③]: Tag is not being edited
Only one tag must be located within the combined blue and gray area (① and ②).
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
33
SIMATIC RF310M software
6.5 The functions in the "Tag" menu
6.5.3 Read tag (MDS)
Note
Distance limits between the tag and the Mobile Reader
Please observe the maximum distance limits between the Mobile Reader and the tag when
reading a tag. See
32)
(Page
Reading the data area of a tag
Using "Tag > Read" (<Ctrl+R> or <ALT+T+R>), you can read from the tag a data area with a
freely definable start and end address.
In the "Read Tag" window, enter the "Start Address" and "Length" of the read area and
confirm with <OK>.
Read/write distances between the Mobile Reader and the RF300 tag
Figure 6-7 Entering the start address and length for the read area
You can enter any start address in the specified address range (see System Manual RF300,
Chapter "Transponders" > "Memory configuration of the RF300 tag"). This is accepted by the
Mobile Reader and compared with the tag (MDS) size.
If you enter the value "01" under "Length" in the "Read Tag", only one byte will be read.
When reading an RFID tag, the entire tag is read if you select the setting "Complete Tag"
under Read / Write in the "Address Setup" window of "Extras" > "Address Setup>
(<ALT+X+A>):
Figure 6-8 "Address Setup" settings for reading the complete tag
This setting remains in force for all further read/write operations until the values are changed
again. See also
6.5.4 Read OTP
You can execute reading of the OTP area of a tag using "Tag > Read OTP" in the menu (or
<ALT+T+E>).
Please observe the limit distances between the tag and the Mobile Reader here too.
Note
Tag cannot be written to after reading of the OTP area
After the OTP area of a tag has been read, the tag cannot be written to. However, the
function "Write OTP" is possible if needed.
Before the tag can be written to again, the menu command "Tag > Read" must be executed.
Address Setup (Page 45).
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
35
SIMATIC RF310M software
6.5 The functions in the "Tag" menu
6.5.5 Reading the tag configuration data
You can execute reading of the configuration data of a tag using the menu command "Tag >
Read Config. Data" (or <ALT+T+C>), if you keep the tag at the minimum distance from the
read head of the Mobile Reader.
Byte address EEPROM Functional description
0xFF1f Bank switch (bits 1 and 0) Memory bank
0xFF1e MDS delay (bits 7:5); LFD (bit 4) MDS delay/LFD bit
0xFF1d Reserved
0xFF1c Limit value A for LFD quotients LFD (A)
0xFF1b Limit value B for LFD quotients LFD (B)
0xFF1a Reserved
0xFF19 Memory configuration, INIT (bits
7...1)
0xFF18 Range for lock bits Lock bits
0xFF17 Tag ID, byte 3 Tag ID (b24-b31)
0xFF16 Tag ID, byte 2 Tag ID (b16-b23)
0xFF15 Tag ID, byte 1 Tag ID (b8-b15)
0xFF14 Tag ID, byte 0 Tag ID (b0-b7)
Using "Tag > Write" (<Ctrl+W> or <ALT+T+W>), you can write to a tag that is at a sufficient
distance from the Mobile Reader.
In the "Write Tag" window, enter the "Start Address" and "Length" of the write area and
confirm with <OK>.
Figure 6-9 Entering the start address and length for the write area
You can enter any start address in the specified address range (see System Manual RF300,
Chapter "Transponders" > "Memory configuration of the RF300 tag"). This is accepted by the
Mobile Reader and compared with the tag (MDS) size.
A data area can be written to the tag. The data area valid in the editor is displayed as default
for each write operation.
If you have previously read data from a tag with the Mobile Reader, these values will be
written to the tag with the next write operation. You can use the menu command "Editor >
Clear" (<ALT+E+C) to specify values to be written to the tag. See
Clear (Page 41).
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
37
SIMATIC RF310M software
6.5 The functions in the "Tag" menu
6.5.7 Write OTP
CAUTION
The "Write OTP" key is non-reversible.
Please note that the OTP memory area can only be written to once. It is not possible to
change the values in the OTP area of a tag at a later time.
Using "Tag > Write OTP" (or <ALT+T+O>), you can write once to the OTP area of a tag that
is at a sufficient distance from the Mobile Reader.
Confirm the message "After acknowledging with OK, the selected memory blocks can no
longer be modified (read only)".
For OTP memory areas of the RF300 tags, see the System Manual RF300, transponders,
memory configuration of the RF300 tag.
The OTP areas refers to 5 block addresses FF80, FF84, FF88, FF8C and FF90. A write
command to this block address with a valid length (4, 8, 12, 16, 20 depending on the block
address) protects the written data from subsequent overwriting.
Note
When the OTP area is used, it must be ensured that the blocks are used without gaps,
time for writing than the high-speed FRAM memory (approx. 11 ms/byte). For time-critical
applications with a write function, it is therefore recommended that FRAM tags are used (e.g.
RF340T, RF350T, RF360T).
You can read and display the status data of the transponder using "Tag > MDS Status"
(or <ALT+T+M>).
The following tag status information is displayed here:
● Tag ID (8-character hexadecimal representation)
● Tag memory size (20 bytes EEPROM, 8KB FRAM , 32KB FRAM, 64KB FRAM)
● Status of the lock-bit register (write-protection status) in hexadecimal representation
● Field strength
● ASIC vers.
Figure 6-10 Read tag status
6.5.9 Reading the tag ID
You can read and display the serial number of the tag using "Tag > Read TagID" (or
<ALT+T+T>). The ID number is allocated at the factory and cannot be changed.
The tag ID is displayed in hexadecimal format.
6.5.10 Initialize the tag
You can initialize a tag with "Tag > Init" (<ALT+T+I>).
The "Init" function is used to overwrite the complete tag extremely quickly with a specific
value. The relevant value can be entered in the "Init Dialog" window. After writing, the
memory in the editor is also set to the entered value. For this purpose, you must have set the
correct tag memory size, see
hexadecimal or ASCII depending on the setting under "Editor > Display".
Tag Type Selection (Page 46). The value can be entered in
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
39
SIMATIC RF310M software
6.6 The functions in the "Editor" menu
6.6 The functions in the "Editor" menu
The following Editor functions are available that you can select in the menu via "Editor" (or
<ALT+E>):
● Jump to Address
● Display
● Clear
● Data Edit
Figure 6-11 The Editor functions
6.6.1 Jump to Address
You can enter a memory address in decimal or hexadecimal format using "Editor > Jump to
Address" (or <ALT+E+J>).
This address will then be set as the start address in the Editor.
You can make the following settings in the "Display" menu (or <ALT+E+D>):
● Toggling the Editor between "Hex" and "ASCII" representation.
● Toggling the data between "Hex", "Dec", "ASCII" and "Bin" representation.
● Toggling addresses between "Dec" and "Hex" representation.
6.6.3 Clear
Figure 6-12 Display
You can overwrite the entire memory or a previously selected memory area in the Editor with
a value of your choice using "Editor > Clear" (or <ALT+E+C>).
Figure 6-13 Clear
You can specify the desired values in the window "Clear". The transponder is not accessed
during this action.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
41
SIMATIC RF310M software
6.6 The functions in the "Editor" menu
6.6.4 Data Edit
There are two ways of modifying the values of a memory cell in the display:
● Select the relevant cell direct via the touchscreen and enter the desired value using the
keypad.
● Select "Editor > Data Edit" (or <ALT+E+E>) to enter the desired value in the "Data Edit"
window.
Figure 6-14 Data Edit
The value is entered in the cell at which the cursor is currently located.
The Extras menu contains the following functions that you can select via "Extras" (or
<ALT+X>):
● Password
● Language
● Address Setup
● Tag Type Selection
● SLG Status
Figure 6-15 Extras functions
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
43
SIMATIC RF310M software
6.7 The functions in the "Extras" menu
6.7.1 Password
You can assign an optional password. Select "Extras > Password" (or <ALT+X+P>).
Figure 6-16 Password change
Enter a password with up to 8 characters under "New Password".
The password is queried before a write function. An entered password remains valid until the
Mobile Reader is switched off. This means you only have to enter the password once in the
case of several consecutive write commands. The password is also required to exit the
application.
Default password
The password has no value on delivery.
NOTICE
Returning the device if the password is forgotten
If you have forgotten your password, there is no way of retrieving it. The device must be
returned.
6.7.2 Language
You can set English or German as the menu language of the SIMATIC RF310M software.
Select the desired language in the "Language selection" window of the "Extras > Language"
(<ALT+X+L>) menu and confirm with "OK". For more detailed information, please refer to
Setting the language (Page 19).
The Address Setup function defines the call of the commands "Read/Write MDS".
Select "Extras > Address Setup" (or <ALT+X+A>) for this purpose. The following window
appears:
Figure 6-17 Address Setup
"Start Address and"
Under "Read / Write", you can choose the parameters "Length" and "End Address".
Parameters Description
Start Address and
"Read / Write"
Under "Read / Write", you can choose the parameters "selected range" and "complete tag".
This setting refers to the default setting in the case of execution of a tag command.
Parameters Description
Read/Write
Length The tag address in the case of the command Read/Write is
entered via a start address and the length of the data to be
edited.
End address The tag address in the case of the Read/Write command is
entered via a start address and an end address.
Selected
range
Complete tag When reading/writing a tag, the entire tag is always edited.
When reading/writing a tag, the currently active (previously
defined) range is always displayed as the range to be
read/written.
The read/write function is started immediately. It is not
possible to enter a partial range of the tag.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
45
SIMATIC RF310M software
6.7 The functions in the "Extras" menu
6.7.4 Tag Type Selection
Figure 6-18 Tag Type Selection
Memory size of the tag to be edited
Set the memory size of the tag using "Extras" > "Tag Type Selection" (or <Ctrl+S or
<ALT+X+T>). Possible settings:
● 20-byte EEPROM
● 8K Byte FRAM
● 32K Byte FRAM
● 64K Byte FRAM
This setting also defines the memory area in the editor. It is not possible to access tag
memory addresses beyond the memory size.
Memory areas (read/write memory) see the System Manual "Transponders", Chapter
"Features" of the relevant tag.
The data read from the tag are automatically stored on the Mobile Reader to a file with the
name "READ_RF300.HEX" in the "Flash Disk" folder. Every subsequent read command
overwrites this file.
When writing to the tag, the write data are written from the Editor to the tag and also to the
"Flash Disk" folder of the Mobile Reader under the name "WRITE_RF300.HEX". Every
subsequent write command overwrites this file.
The function "File/Load File" shows all files with the extension ".HEX". You can select one of
these. This file is then loaded into the Editor. The file is not saved with the name
READ_x.HEX or WRITE_x.HEX.
The function "File/Save" saves the data from the Editor to a file with the extension ".HEX" in
the "Flash Disk" folder of the Mobile Reader. You can enter any name with 1 to 8
alphanumeric characters.
Note
When you read the data from the tag, modify them in the Editor and then save them, the
modified data are saved to the .HEX file.
7
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
49
Advanced functions
7.2 Copying data from and to the Mobile Reader
7.2 Copying data from and to the Mobile Reader
7.2.1 Prerequisites
● USB driver for the PSION Workabout Pro.
● The ActiveSync program from Microsoft
● A USB cable for connecting the PC to the PSION Workabout PRO .
(Included in the scope of supply of the docking station.)
The ActiveSync program provides a connection via the USB to PSION Workabout Pro . You
can now copy data and programs very easily in the manner familiar from Explorer. You only
have to select the point "Mobile Device" in Explorer. It is also possible to reach the
Workabout PRO directly via ActiveSync .
Requirements for opening the PSION workstation
● The PSION Workabout Pro is connected in the docking station via the USB cable
● Active Sync. is installed
Opening the PSION workstation via Explorer and Mobile Device:
Select "Mobiles Gerät" or "Mobile Device" in Explorer:
Figure 7-1 Opening the PSION workstation via Explorer
Then select the "Flash Disk" folder.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
51
Advanced functions
7.2 Copying data from and to the Mobile Reader
Opening the PSION workstation via ActiveSync and "Explore":
Select the "Explore" button (on installation, this appears as the German: "Durchsuchen") in
order to reach the Workabout PRO device via ActiveSync .
Figure 7-2 Access to Workabout PRO via Active Sync "Explore"
There you will find the file "READ_RF310.hex" and the files you have stored with the
extension ".hex". You can now drag and drop or copy these files from the drive of the PSION
Workabout Pro to the PC drive.
The file READ or WRITE has a length that corresponds to the size of the read MDS:
READ_RF310.hex:
The contents of the file can now be displayed and modified using the relevant editor on the
PC:
● If ASCII data have been read from the tag:
any editor can be used: NOTEPAD, WRITE, WORD, etc.
● If binary data are exchanged with the tag:
a HEX editor is used. HEX editors are available on the shareware market (e.g. Hedit,
etc.) or on the professional market (e.g. "Codewright").
7.2.3 Organization of the file READ.HEX
The file READ_x.HEX contains only the pure data that are also available on the tag. The
length of the file is identical with the memory size of the tag (in bytes).
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
53
Advanced functions
7.3 The automatic power-saving function
7.3 The automatic power-saving function
The PSION Workabout Pro has an automatic shutdown function. This is activated if no key
on the Mobile Reader is pressed for approximately 5 minutes.
In addition, the "SIMATIC RF310M" software has a further power-saving function. If no tag is
detected for 30 seconds after starting a tag command, or if the tag currently being edited
exits the field for longer than 30 seconds, the current tag command is interrupted. The
following message appears (see also
Figure 7-5 Timeout display
You can now stop the command completely with "Cancel" or continue it with "Retry". If you
retry, the interrupted command is continued at the point of interruption.
Progress and timeout display (Page 31): TIMEOUT:
7.4 System reset
After inserting the batteries and switching on for the first time, the Mobile Reader carries out
a system reset. This reset is the same as a hardware reset.
Restoring the delivery status of the device
A system reset can also be carried out manually. This restores the delivery status of the
device. Press and hold the orange, blue and red keys simultaneously for approximately 6
seconds.
The messages in the table below can occur during operation. They are displayed in a
separate window. An error message can appear as follows:
Figure 8-1 Typical error message
The first number designates the interface function with which the error occurred. The second
number provides more detailed information about the error.
The meanings of the numbers are explained in the subsequent text (always in English).
8
The actual action is shown in the title of the display.
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
55
Error messages of the SIMATIC RF310M application
General errors
General errors communicated by the read/write device are displayed as error code 101 to
131. These errors can occur with all functions.
Error
code
101 No tag with selected
105 Wrong command Parameterization error, possible causes:
106 Field error Air interface faulty
112 Memory write error The tag memory cannot be written, possible causes:
113 Tag address error Error in the specified memory address (access attempted to non-
119 Low buffer error Buffer overflow: Insufficient buffer available in the reader for saving
120 Watchdog error Major system fault (hardware fault)
121 Reset parameter
125 Active command
128 Antenna error The antenna is already switched off or on
130 Wrong telegram
131 Command break
Error
message/display
ID in field
error
error
length
error
Meaning
Presence error, possible causes:
• The active command was not carried out completely
• The tag has left the field while the command is being processed
• Communication fault between reader and tag
• Unknown command
• Incorrect parameter
• Function not allowed
• Hardware fault (memory faulty)
• Memory write-protected (corresponding OTP area has already
been written)
existent or non-accessible memory areas).
the command
Parameter assignment error: faulty parameter in RESET command
Previous command is still active
Incorrect number of characters in frame
Internal program error: Running command cancelled by reset
Open Com Port - 1
Interface
function
1 1 invalid handle Invalid access number
1 2 SetCommState failed Error when setting the port parameter
1 3 Set CommMask failed Error when setting the port parameter
1 10 failed to turn on 5V Error when switching on the 5V power supply
Processor Intel Xscale PXA 255 - 400 MHz, ARM
RAM 128 MB
ROM 32 MB Flash ROM
User program RF310M.exe
Screen Color touch display, 320x240 vertical format
Keypad Alphanumerical
Sound Piezo signal transmitter
Power supply Lithium-ion battery (3.7V; 3000 mAh) fast
Interfaces LIF interface (low insertion force socket) for
Operating system Microsoft Windows CE.NET 4.2
File management MS-DOS-compatible
Integrated software SIMATIC RF310M
Technical Specifications Complete unit
Dimensions 222 x 92 x 42 [mm] 280 x 92 x 42 [mm]
Weight Approximately 450 g Approximately 500 g
Relative humidity 5% to 95%, no condensation
Degree of protection IP54, IEC 529 (splash-proof)
EMC EN 55022
Electrostatic; RF; EFT IEC 801–2; IEC 801–3; IEC 801–4
Transmission frequency for power/data 13,56 MHz
Compatibility With all SIMATIC RF300 data carriers (tags)
Read/write distance to transponder Max. 20 mm
Data transmission rate Read, write: approx. 3,100 bytes/s
10
chargeable; automatic shutdown or 3x of type AA
Backup battery: 3 V lithium cell CR 1620
battery charging and communication with PC,
USB and Ethernet via charging cradle
Read head/antenna
(incl. batteries)
Operation -10°C to +50°C Temperature
Storage -25°C to +60°C (without battery)
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
FCC ID NXW-RF310M01
This device complies with Part 15 of the FCC rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received, including interference that may cause
undesired operation.
Caution
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Canada
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
A
A.2 Accessories
Accessories Order No.
SIMATIC RF handheld charging/docking station.
Charging cradle for Workabout PRO
Incl. wide-range power supply unit with universal adapter
and cable
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
6GT2898-0BA00
65
Appendix
A.3 Ordering components for advanced functions
A.3 Ordering components for advanced functions
The advanced functions of the SIMATIC RF310M Mobile Reader, require components that
are not supplied by Siemens.
If you require these components for your application, please contact PSION direct or its
representative in your country. You can find addresses and order lists for PSION on the
Internet at
You can also find the PSION representative in your country at this Internet address.
In Germany, PSION components are supplied by WAROK (Tel. 07721/202630).
For other PSION components, such as
● Memory expansion
● Fast chargers
please also ask PSION direct or their representatives. These components are not required
for the RF300 application. They can become necessary if you want to program your own
identification application on the Mobile Reader.
www.psionteklogix.com
A.4 Developing user applications
User applications require the SDK development package from PSION (Psion Teklogix
Mobile Devices SDK for MS Visual Studio, MS Embedded Visual C++).
Communauté Européenne (product mark of the European Union)
FZP idle error counter
Error counter (passive)
HF field
High-frequency field
LFD
Field strength
MDS
Mobile data memory (see transponder)
OTP
One Time Programmable
RAM
Random Access Memory
Read/write devices (SLG)
See readers
SIMATIC RF310M Mobile Reader
Operating Instructions, 07/2007, J31069-D0191-U001-A1-7618
71
Glossary
Readers
Readers ensure fast, secure data transfer between mobile data storage units and higherlevel systems. The data, energy included, are transmitted across an electromagnetic
alternating field. This principle enables contact-free data transmission, ensures high
industrial compatibility and works reliably in the presence of contamination or through nonmetallic materials.
RFID
Radio Frequency Identification Devices
RFID systems
SIMATIC RF identification systems control and optimize material flow and
production sequences. They identify reliably, quickly and economically, use non-contact
data communication technology, and store data directly on the product. They are also
resistant to contamination.
Tag
Transponder
See transponder
An invented word from transmitter and responder. Transponders are used on the product,
the product carrier, the object, or its transport or packaging unit, and contain production and
manufacturing data, i.e. all application-specific data. They follow the product through
assembly lines, transfer and production lines and are used to control material flow.
Because of their wireless design, transponders can be used, if necessary, at individual work
locations or manufacturing stations, where their data can be read and updated.