Siemens REV24RF, REV24RFDC, RCR10/868 User Instruction

CE1N2206en
24.04.2008
Building Technologies
s
2
REV24RF.. RCR10/868
Radio set with 7-day room temperature controller
REV24RF../SET
Comprising a room temperature controller (with integrated radio transmitter) and receiver with relay outputs
Mains-independent, battery-operated room temperature controller featuring
user-friendly operation, easy-to-read display and large numbers.
Self-learning two-position controller with PID response (patented).
Operating mode selection:
- 7-day automatic mode with max. 3 heating or cooling phases.
- Continuous comfort mode.
- Continuous energy saving mode.
- Protection against frost or overheating.
- Exception day (24 hour operation) with max. 3 heating or cooling phases.
A separate temperature setpoint can be entered in automatic mode and for
the exception day for each heating or cooling phase.
Heating zone control.
Possibility to control cooling equipment.
Advantage for retrofitting, renovating, and reconstruction purposes
(completely wireless room unit).
Use
Room temperature control in:
Single-family and vacation homes.
Apartments and offices.
Individual rooms and professional office facilities.
Commercially used spaces.
Control for the following equipment:
Magnetic valves of an instantaneous water heater.
2 / 18
Siemens Room temperature controller radio set REV24RF../SET CE1N2206en Building Technologies 24.04.2008
Magnetic valves of an atmospheric gas burner.
Forced draught gas and oil burners.
Electrothermal actuators.
Circulating pumps in heating systems.
Electric direct heating.
Fans of electric storage heaters.
Zone valves (normally open and normally closed).
Air conditioning and cooling equipment.
Function
Bidirectional radio transmission.
PID control with self-learning or selectable switching cycle time.
2-point control.
7-day time switch.
Preselected 24-hour operating modes.
Override function.
Holiday mode.
Party mode.
Protection function (protection against frost or overheating).
Information level to check settings.
Reset function.
Sensor calibration.
Heating or cooling.
Minimum limitation of setpoint.
Periodic pump run.
Protection against valve seizure.
Optimum start control in the morning (P.1).
Synchronization to radio time signal from Frankfurt, Germany (REV24RFDC).
Manual override of the receiving relay.
Type summary
Radio set comprising:
- Room temperature controller REV24RF with 7-day time switch, Base and receiver RCR10/868 REV24RF/SET Radio set comprising
- Room temperature controller REV24RFDC with 7-day time switch, Receiver for time signal from Frankfurt, Germany (DCF77), Base and receiver RCR10/868 REV24RFDC/SET
Ordering
Please indicate the type number as per the "Type summary" when ordering.
Delivery
The controller/transmitter REV24RF.. is delivered with batteries.
Mechanical design
Plastic casing with an easy-to-read display and large numbers, easily accessible operating elements, and removable base. The casing accommodates the electronics with the DIP switches. The easily accessible battery compartment allows for easy exchange of two 1.5 V alkaline batteries, type AA.
The base helps attach the room controller to the wall. The supplied table stand allows you to stand the controller anywhere in the room. You can manually attach the table stand without tools.
Room controller and base
Base and table stand
3 / 18
Siemens Room temperature controller radio set REV24RF../SET CE1N2206en Building Technologies 24.04.2008
Plastic housing with large operating elements, removable cover and easily accessible terminal block with lots of space to attach the wires. You can mount and wire the unit on most commercially available recessed conduit boxes or directly on the wall. The potential-free changeover contact and the antenna for reception are integrated in the unit.
1
Display
Change battery
Time of day
Alarm
Room temperature (measured)
Heating mode
Clear text display line (max. 18 spaces)
Cooling mode
Weekday (max. 3 spaces)
0 4 8 12 16 20 24
24 hour timeframe with switching pattern with flashing time cursor
Info
Info
Setpoint for comfort mode
Weekday block
Weekend block
Weekday
Setpoint for absence
h
Time unit
Room temperature
Absence/holiday mode set
Setpoint for frost protection mode
Absence/holiday mode active
Without language selection
Energy saving mode setpoint
Party mode active
Time signal from Frankfurt
°C / °F
Temperature unit °C or °F
Date (day - month - year)
Heating/cooling/pump on
Receiver
Display and operating elements
4 / 18
Siemens Room temperature controller radio set REV24RF../SET CE1N2206en Building Technologies 24.04.2008
2
Operating mode selector
Automatic weekly mode with max. three heating or cooling phases per day.
Exception day with max. three heating or cooling phases.
Continuous comfort mode (= continuous comfort temperature).
Continuous energy saving mode (= continuous energy saving temperature).
Protection mode (protection against frost or overheating).
3
INFO
Pressing the Info button once illuminates the display. Illumination automatically turns off after a short period of time.
Pressing the Info button again activates the information display: is lit. The unit first displays queued error messages followed by important information (e.g. time switch programs, etc.).
4
Plus button
Increase values, set time, or make a selection.
5
Override button / party mode
In the time switch program, this button allows you to quickly change from the active temperature level to the next and back.
Thus, you can quickly change to energy saving temperature when you leave the apartment for a short period of time, thus saving energy.
The display indicates the change. It is valid only until the next switching time.
ty mode: Press the button for 3 seconds.
Party mode is available only in operating modes and . In party mode, the controller controls to a freely selectable temperature for a freely selectable period of time.
In party mode, symbol is displayed along with the end of party mode.
6
Minus button
Decrease values, set time, or make a selection.
5 / 18
Siemens Room temperature controller radio set REV24RF../SET CE1N2206en Building Technologies 24.04.2008
7
Program selection slider
Time
Day – Month – Year (2 spaces for day, month, and year).
Weekday, weekend, or individual day blocks.
1, 2, or 3 comfort phases.
Start Comfort phase 1
Start Comfort phase 2
Start Comfort phase 3
Setpoint Comfort phase 1
Setpoint Comfort phase 2
Setpoint Comfort phase 3
End Comfort phase 1
End Comfort phase 2
End Comfort phase 3
Energy saving temperature in the automatic mode and exception day time switch programs.
Start of absence.
Temperature setpoint during absence.
End of absence.
RUN
Slider position RUN allows for closing the cover.
Operating modes
The controller offers the two time switch programs and .
Enter a start time and end time for each comfort phase. Also comfort temperature setpoint can be freely entered for each comfort phase. Between the comfort phases the controller always switches to the same, freely selectable energy saving temperature setpoint.
2205Z04
16
°C
18
20
22
06
08
18 22
h
Heating phase 1
12
14
21
Heating phase 2
Heating phase 3
The controller also offers the three 3 continuous modes comfort mode,
energy saving mode and frost protection mode.
Operation with time switch program
Example with 3 heating phases
Continuous operating modes
6 / 18
Siemens Room temperature controller radio set REV24RF../SET CE1N2206en Building Technologies 24.04.2008
You can freely adjust the setpoints for the weekly and 24-hour operating modes. Setting range for all setpoints without setpoint limitation 3…35 °C. Setting range for all setpoints with setpoint limitation 16…35 °C.
Factory setting for heating
Factory setting for cooling
, , ,
20 °C 24 °C
,
16 °C 28 °C
8 °C 35 °C
12 °C 30 °C
Factory settings: Switching times
Comfort phases P1 P2 P3 P4 P5 P6
1. 07:00 23:00 PASS PASS PASS PASS
2. 06:00 08:00 17:00 22:00 PASS PASS
3. 06:00 08:00 11:00 13:00 17:00 22:00
Three different switching patterns are available to simplify entry of switching times. These can be assigned as blocks to the corresponding weekdays 1…5 and weekend days 6…7. As a result, you need to adapt the switching times and room temperatures only once for each block.
Switching pattern
Blocks
You can also enter individual days .
You can enter the beginning, temperature and end of your holidays. At the beginning of the holidays, the controller switches to the desired holiday temperature and returns to the previously set operating mode at the end of the holidays.
In holiday mode, symbol is displayed along with the end of holiday mode.
Proceed as follows to enter your settings:
Set slider to position 15 (start of absence): Press or to set the start date for your holidays.
Set slider to position 16 (temperature during absence): Press or to set the desired temperature while on holidays.
Set slider to position 17 (end of absence): Press or to set the end date for your holidays.
RUN
Return the slider to position RUN. Symbol is displayed to the left of the symbol.
Press , , , or move the slider to end holiday mode prematurely.
Setpoints
Factory setting
7-day time switch
Enter holidays or absences
Loading...