Siemens MOJ6024DCL Owners Manual

Page 1
Siemens Energy & Automation, Inc. Bellefontaine, Ohio 43311 U.S.A.
Installation Instructions
Item:
For use with: See Table Below Page 1 of 6 Pc. No. 710055B00
DESCRIPTION
Hazardous voltage. Will cause death or severe injury.
Turn off and lock out all power supplying circuit breaker and motor operator before installing or servicing.
SAFETY INSTRUCTIONS
CATALOG NO’S: MOF6125DC (L)
MOF6048DC (L) MOF6024CD (L) MOJ6125DC (L) MOJ6048DC (L) MOJ6024DC (L) MOLMD6125DC (L) MOLMD6048DC (L) MOLMD6024DC (L)
MOTOR
OPERATOR
FRAME
FOR USE WITH: SIEMENS® CIRCUIT BREAKERS AND SWITCH TYPES.
MOF6024DC MOF6024DCL MOF6048DC MOF6048DCL MOF6125DC
F6
FD6
FF
F6, HF6, FJ6, HFJ6, CLF, FXD6, HFXD6, HHFDX6, FD6, HFD6, HHFD6, CFD6, SFD6, SHFD6, SCFD6, FFC, and FFF.
MOF6125DCL MOJ6024DC
MOJ6024DCL MOJ6048DC MOJ6048DCL MOJ6125DC MOJ6125DCL
J6
JD6
L6
LD6
JF, LF
JD2, JJ6, JL6, HJ6, CLJ, LJ6, LL6, HL6, CLL, JXD2, JXD6, HJXD6, HHJXD6, JD6, HJD6, HHJD6, CJD6, LXD6, HLXD6, HHLXD6, LD6, HLD6, HHLD6, CLD6, SJL, SLL, SJD6, SHJD6, SCJD6, SLD6, SHLD6, SCLD6, JFC, JFF, LFC, and LFF.
MOLMD6024DC MOLMD6024DCL MOLMD6048DC MOLMD6048DCL
LMD
LMD6, LMXD6, HLMD6, and HLMXD6.
MOLMD6125DC MOLMD6125DCL
The motor operated mechanism is designed to open, close and reset a circuit breaker or switch by re­mote control. The customer must supply the circuit breaker or switch, normally ON and OFF push-but­tons, external wiring, a control power source, and all control logic.
The motor operator is hinged for opening to the right. NOTE: For Automatic Reset Operation a separate
auxiliary contact must be provided by the customer.
Page 2
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 2 of 6
Pc. No. 710055B00
Installation Instructions
INSTALLATION
1. Turn off and lock out all power supplying circuit breaker and motor operator before installation or servicing.
2. Attach the circuit breaker to its mounting sur­face using the mounting hardware supplied with the motor operator. (See Figures #1 and #2)
NOTE: On J6, JD6, L6, LD6, JF, & LF circuit break-
ers and switches, the following additional steps must be performed.
Hazardous voltage. Will cause death or severe injury.
T urn off and lock out all power supplying circuit breaker and motor operator before installing or servicing.
2.1 Remove the four shield screws and two lug
shields (A). (See Figure #1)
2.2 For JD6, LD6, JF, & LF Frames, simply
replace the shields with those provided with the motor operator and discard the shields which were removed.
2.3 For J6 and L6 Frames, drill or punch out
the two 0.531” diameter knockouts and replace the shields. (See Figure #1a)
3. With its cover open, attach the motor operator to the circuit breaker using the spacers (Not used with F Frame) and screws provided. (See Figure #2)
4. To reclose cover, move bottom screw hole cover, align motor operator mechanism rollers and circuit breaker handle by rotating the lead screw with a screw driver (to the close cover position as shown by position indicator located on motor operator front). Lead screw access hole is at the bottom of motor operator. (See Figure #2)
.531
[13.48]
FIGURE 1
DIMENSIONS
INCHES
[MILLIMETERS]
.52
[13.2]
5. Close and latch the mechanism cover.
6. Complete the desired control connections and electrically test the motor operator system beofore reenergizing the breaker power termi­nals in accordance with the electrical operation.
FIGURE 1a
Page 3
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 3 of 6
Pc. No. 710055B00
Installation Instructions
BREAKER & MOTOR OPERATOR
LEFT HAND VERSION SHO W N
Motor Operator (Shown in the Open Position)
(4) 10-32 Truss Head Mounting Screws
Mounts Base Plate To Breaker
Mounting Hardware
Hazardous voltage. Will cause death or severe injury.
T urn off and lock out all power supplying circuit breaker and motor operator before installing or servicing.
Lead Screw Access Hole
Spacer (Not Used With F Frame)
Circuit Breaker Mounting Hardware (4)
Tap Panel 1/4-20
Motor Operator Mounting Base Plate
Circuit Breaker
Mounting Panel
Flat Washer, Lock Washer, and Nut (Use When Mounting Panel Can Not Be Tapped)
FIGURE 2
Page 4
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 4 of 7
Pc. No. 710055B00
Installation Instructions
Hazardous voltage. Will cause death or severe injury.
T urn off and lock out all power supplying circuit breaker and motor operator before installing or servicing.
ELECTRICAL OPERATION
With the breaker and the operating mechanism in the OFF position, press the ON button to energize the motor. This action will close the break er. When
Electrical Characteristics Tab le
the breaker handle reaches the ON position, the motor circuit is disconnected by an internal limit
CAT.# VOLTS AMPS
MOF6125DC (L) MOJ6125DC (L) MOLMD6125DC (L)
MOF6048DC (L) MOJ6048DC (L) MOLMD6048DC (L)
MOF6024DC (L) MOJ6024DC (L) MOLMD6024DC (L)
125 VDC
48 VDC
24 VDC
13.6 Amps in Rush
6.4 Amps in Running
22.0 Amps in Rush
13.0 Amps in Running
45.0 Amps in Rush
26.8 Amps in Running
switch. With the breaker and the operating mechanism in
the ON position, press the OFF button to energize the motor. This action will open the breaker . When the breaker handle reaches the OFF position, the motor circuit is disconnected by an internal limit switch.
When the circuit breaker trips automatically, there is no external indication that the breaker has tripped unless a separate bell alarm accessory (Contact Siemens for appropriate Catalog Number) is pro­vided to energize a customer furnished warning
Closing or Opening Time: 0.3 seconds
device. After the circuit breaker trips automatically , it is necessary to press the OFF button to move the breaker handle to the reset position.
WIRING DIAGRAM MOTOR-OPERATED MECHANISM (DC)
(ALL SWITCH CONTACTS SHOWN WITH CIRCUIT BREAKER IN THE ‘ON’ POSITION)
MOTOR OPERATED MECHANISM
(-) (+) (+)
GREEN GROUND
BLACK
YELLOW
RED
COMMON
CLOSE
OPEN
BLACK BLACK
INTERLOCK
FIGURE 3
RED
YELLOW
DOOR
• •
• •
LIMIT SWITCHES
Page 5
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 5 of 6
Pc. No. 710055B00
Installation Instructions
Hazardous voltage. Will cause death or severe injury.
T urn off and lock out all power supplying circuit breaker and motor operator before installing or servicing.
AUTOMATIC RESET
Consult the factory for suggested control wiring dia­gram for automatic reset operation.
0.8 [20.3]
MANUAL OPERATION
Operate the two cover latches and swing the hinged motor operator cover away from the breaker to ex­pose the breaker handle. To return to electrical op­eration, follow the installation instructions on page 2 of 6, deleting steps 2 and 3. After operation checks are complete, restore to normal operation.
DIMENSIONS
INCHES
[MILLIMETERS]
11
[279.4]
7.5
[190.5]
FRONT VIEW
[198.1]
BOTTOM VIEW
DIMENSIONS
FRAMES: J6, JD6, JF
L6, LD6, LF
FIGURE 4
7.8
9.9
[251.4]
8.4
[213.3]
BOTTOM VIEW
Page 6
Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A.
Page 6 of 6
Pc. No. 710055B00
© Siemens Energy & Automation, Inc. 1988
Installation Instructions
Hazardous voltage. Will cause death or severe injury.
T urn off and lock out all power supplying circuit breaker and motor operator before installing or servicing.