The OpenAir direct coupled 24 Vac, non-spring return (NSR) rotary electric actuator
is designed for floating control of building HVAC dampers.
EA GBB/GIB-2
Features
Application
Product Numbers
221 lb-in (25 Nm)
310 lb-in (35 Nm)
• Unique self-centering shaft coupling
• All metal housing
• Manual override
• Independently adjustable dual auxiliary switches available
• Built in potentiometer option
• Two torque ranges available
• UL, CE and cUL listed
These actuators are used in constant or variable air volume installations for the
control of return air, mixed air, exhaust,
221 lb-in (25 Nm) or 310 lb-in (35 Nm) torque.
Table 1.
24 Vac Operating Voltage
Torque Cabling Standard
Standard GBB131.1U GBB132.1U GBB136.1U
Plenum GBB131.1P GBB132.1P GBB136.1P
Standard GIB131.1U GIB132.1U GIB136.1U
Plenum GIB131.1P — GIB136.1P
Potentiometer
Only
Auxiliary
Switches
Only
Siemens Industry, Inc.
Technical Instructions OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control
Operating voltage 24 Vac, ±20%
Operating voltage Class 2, in accordance with UL/CSA
Feedback potentiometer (GBB132x)
Document No. 155-177P25
June 22, 2015
Warning/Caution Notations
WARNING:
CAUTION:
Specifications
Frequency 50/60 Hz
Power supply
Equipment rating
Auxiliary features
Power consumption: 7 VA/7W
Plenum type actuators as whole device Class 2, in accordance with UL/CSA
Sliding contact (P2) 0 to 1000 ohm
Load <1W
Voltage <24 Vac/dc
Control signal adjustment
Offset (start point) Between 0 to 5 Vdc
Factory setting 0 Vdc
Span Between 2 to 30 Vdc
Dual auxiliary switches
AC rating (standard cable) 24 to 250 Vac
AC 6A resistive
AC 2A general purpose
AC rating (Plenum cable) 24 Vac
AC 4A resistive
AC 2A general purpose
DC rating (Standard/Plenum cable) 12 to 30 Vdc
DC 2A
Switch Range
Switch A0 to 90° with 5° intervals
Recommended range usage 0 to 45°
Factory setting 5°
Switch B0 to 90° with 5° intervals
Recommended range usage 45 to 90°
Factory setting 85°
Switching hysteresis 2°
Personal injury/loss of life may occur if you do not perform a procedure
as specified.
Equipment damage or loss of data may occur if you do not perform a
procedure as specified.
Page 2 Siemens Industry, Inc.
WARNING:
Apply only line voltage or only Class 2 voltage to the switching outputs of both
auxiliary switches A and B. Mixed operation is not permissible. See Wiring for
details.
OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control Technical Instructions
Running torque
Shaft size 3/8 to 1-inch (8 to 25.6 mm) diameter
Enclosure NEMA 2 in vertical position to 90°
Ambient temperature
UL listed to UL873
Pre-cabled connection 18 AWG
Document No. 155-177P25
June 22, 2015
Specifications,
Continued
Function
Mounting
Housing
Ambient condi tions
GBB… 221 lb-in (25 Nm)
GIB… 310 lb-in (35 Nm)
Runtime for 90° opening or closing 150 seconds at 50 Hz
125 seconds at 60 Hz
Nominal angle of rotation 90°
Maximum angular rotation 95°
1/4 to 5/8-inch (6 to 18 mm) square
Minimum shaft length 3/4-inch (20 mm)
to the left and right of vertical
See Figure 14.
NEMA 3R rated when installed with
ASK75.1U Weather Shield in the
vertical position. See Accessories.
IP54 according to EN 60 529
Material Die-cast aluminum alloy
Gear lubrication Silicone-free
operation -25°F to 130°F (-32°C to 55°C)
storage and transport -40°F to 158°F (-40°C to 70°C)
Ambient humidity (non-condensing) 95% rh
Agency certification
cUL certified to Canadian Standard
C22.2 No. 24-93
CE conformity:
Low-voltage directive 2006/95/EC
Miscellaneous
Cable length 3 feet (0.9 m) length
Life cycle Designed for over 60,000 full strokes
and a minimum of 1.5 million
repositions at rated torque and
temperature
Noise level <45 dBA (running)
Dimensions See Figure 26.
Weight 4.4 lbs (2 kg)
Electromagnetic compatibility 2004/108/EC
Siemens Industry, Inc. Page 3
Technical Instructions OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control
ASK71.1U:
OpenAir actuators. Kit should be used for
in
a foot
Kit contains:
Support bearing ring to minimize side
Required mounting fasteners
ASK71.2U:
actuators directly to a damper frame. Kit
should be used with louvers and vents and
in applications where use of the floor
mount kit is not possible.
Kit contains:
Support bearing ring to minimize side
Required mounting fasteners
ASK71.3
to provide an auxiliary linear drive. Kit can
be used to simultaneously drive a set of
opposing or adjacent dampers with a
single actuator.
Kit contains:
Required mounting fasteners
ASK71.4: Allows economical mounting of
an OpenAir actuator to a variety of
surfaces. Kit should be used in
applications where the actuator can be
rigidly surface mounted and a linear stroke
output is required. Kit contains:
Document No. 155-177P25
June 22, 2015
Accessories
NOTE: Neither the auxiliary switches nor the feedback potentiometer can be added in
the field. Order the product number that includes these options.
Allows foot mounting of the
-the-air stream applications or anywhere
-mounted actuator can be mounted.
• Crank arm for changing angular
Figure 1. Floor Mount Kit.
Figure 2. Frame Mount Kit.
rotation into a linear stroke
•
loading on the actuator’s output
bearing
• Mounting bracket
•
Allows mounting of OpenAir
• Crank arm to change the angular
rotation into a linear stroke
•
loading on the actuator’s output
bearing
• Mounting bracket
•
Page 4 Siemens Industry, Inc.
Figure 4. Crank Arm Kit with Mounting
Figure 3. Crank Arm Kit.
Bracket.
: Allows a direct-coupled actuator
• Crank arm to attach to the splined
hub of the shaft adapter
•
• Crank arm to attach to the splined
hub of the shaft adapter
• Mounting bracket
• Required mounting fasteners
OpenAir™ GBB/GIB Series Non-spring Return, 24 Vac, Floating Control Technical Instructions
Accessories,
continued
inch (25 mm) jackshafts that are slightly
Document No. 155-177P25
June 22, 2015
ASK73.1: Bracket provides an extended
Figure 5. Tandem Mount Bracket.
anti-rotation pin that allows two GIB13x
OpenAir actuators to directly drive a
single damper shaft. For use with threeposition actuators.
ASK74.1U: Shaft adapter attaches to a
1.05-inch (26.6 mm) diameter shaft;
whereas, the standard self-centering
adapter accepts up to a 1.00-inch
(25.4 mm) diameter shaft.
Figure 6. Special Shaft Adapter.
Figure 7. NEMA 3R Weather Shield.
Figure 8. NEMA Type 4X Weather Shield.
Adapter can be used for coupling to
1oversized. Adapter is 13/16-inches (20
mm) shorter than the height of the selfcentering shaft adapter.
985-052P20: (no picture) Small shaft
insert (package of 20) when using the
GIB actuator on a damper shaft less than
3/4-inch (20 mm) diameter.
ASK75.1U: GBB/GIB actuators are UL
listed to meet NEMA 3R requirements (a
degree of protection against rain, sleet,
snow, and damage from external ice
formation) when installed with the
ASK75.1U Weather Shield and
outdoor-rated conduit fittings in the
vertical position.
For dimensions, see Figure 24.
ASK75.7U: GBB and GIB Actuators are
UL listed to meet NEMA Type 4X
requirements (a degree of protection
against falling dirt, rain, sleet, snow,
windblown dust, splashing water, hosedirected water, corrosion, and damage
from external ice formation) when
installed with an ASK75.7U Weather
Shield and outdoor-rated conduit fittings.
This weather shield may be mounted in
any orientation.
For dimensions, see Figure 25.
Siemens Industry, Inc. Page 5
985-106: Provides protection for GIB,
GBB and GCA OpenAir actuators in an
outside low temperature. Assembly
includes:
• Weather Shield (ASK75.1U)
• Heater Kit (985-105)
Figure 9. Heater/Weather
Shield Assembly.
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.