Siemens G120XA Instruction Manual

Page 1
Date: 2019-12-11 DF MC SNC CSA TCC
- 1 -
Instructions for G120XA FSH-J X9 terminal
How to use the X9 connector which only use in G120XA FSH-J
Tang Huang
Abstract: When many customers use G120XA FSH-J power section products for the first time, F7862 alarm will appear after power on operation. Preliminary inspection shows that there is no obvious abnormality in wiring, and it is impossible to locate the cause of the problem when they are not familiar with the product.
KeywordsX9F7862external fault
1Fault analysis
Page 2
Date: 2019-12-11 DF MC SNC CSA TCC
- 2 -
As shown in the figures above, the reason of the appearance of F7862, according to the user manual of G120XA, is that the input signal of the signal source r402.1 of external fault 3 is low, and the state of r4022.0~3 is controlled by X9 terminal. Therefore, when F7862 fault occurs, it is necessary to confirm whether X9 terminal has been correctly connected!
2X9 terminal
1. Mechanical installation of G120XA FAH-J X9 terminal
Page 3
Date: 2019-12-11 DF MC SNC CSA TCC
- 3 -
2. G120XA FAH-J X9 terminal function Terminal strip X9 is used to connect external 24V DC power supply and main contactor or bypass contactor. To connect the terminal strip X9, remove the front cover of the converter. Its DIs can be connected with fault signal and alarm signal. When the converter is connected to the power supply through the main contactor, it is necessary to connect the external 24V DC power supply. The power supply must be near the converter (such as in the same control cabinet), and the cable length to terminal block X9 shall not exceed 5 meters.
Terminal
Name
meaning
Input/output
Technical data
1
P24
External power supply
Input
Voltage24V DC20.1V ~28.8V Current consumption: 2A
maximum
2 M Electronic grounding
Reference 3
External
External
Input
Voltage: -3V ...+30V
Page 4
Date: 2019-12-11 DF MC SNC CSA TCC
- 4 -
alert
alarm
Current consumption:
6.4 mA at 24V DC ✓ 1.3 mA when < 5V ✓ 4 mA when > 15V ✓ 8 mA at 30V
Level (including waviness):
High level15V ...30V ✓ Low level-3V ...+5V
4
External fault
External fault
Input
5
Stop 0
Emergency OFF, category 0
Input
6
Stop 1
Emergency stop category 1
Input 7 M
Reference
8
DC link charged
Enable signal, U DC link charged
Output
Voltage:24V DC Maximum load current: 500mA Continuous short circuit protection The output current is taken from the power supply via X9 terminal
9
NC
Not connected
10
NC
Not connected
11
Activation line
contactor
Line contactor control
Output
Contact type: NO contact Maximum load current: 4A 230V ACcosφ = 0.6ind Floating potential For feeders with contactless outputs (e.g.4A/250V fuses), a protection device is required to prevent overload and short circuit. The overvoltage limiter must be connected to the excitation coil of the main contactor (e.g. RC circuit). The following relay contact characteristic values are applicable to the control of the main contactor: 250V AC10ANC and
NO)currency, 85
24V DC, 10ANC and
NO), currency, 85
30V DC,8ANO)、6A
NC, currency, 85
B300NC and NO,
general purpose,85
R300NC and NO,
general purpose, 85
24V AC, 2.0ANC and
NO, general purpose,
12
Activation Line contactor
Line contactor control
Output
Page 5
Date: 2019-12-11 DF MC SNC CSA TCC
- 5 -
85
Note: 1The input is low level active
All signal inputs are low level active (anti break).
2Terminal 3~6 not used
When terminal 3~6 is not in use, DC 24V must be applied. To do this, use an external power supply or terminal 9 on the control unit. Terminal 2 and 7 with reference potential X9 and terminal 28 on the control unit. Refer to terminals 2 and 7 with potential X9 and terminal 28 on the control unit.
3Main contactor control
When power is supplied to the main contactor via terminals 11 and 12, it is not necessary to disconnect from the power supply system via the control transformer. 250V/8A fuse must be used as protection measure.
4Strain relief
The cables for the control unit and terminal X9 must be fixed to the terminal block in the cable channel under terminal X9 for strain relief. If the cable is introduced into the cable channel from the side (at the height of terminal X9), the strain relief must be performed outside the power module.
5Wiring standard
Maximum connection cross section: 2.5 mm²(14AWG) Minimum connection cross section: 0.2 mm²(25AWG) Maximum tightening torque: 0.5 Nm (4.4 lbf.in)
3Troubleshooting
1. According to the actual use requirements, the wiring should be correct to ensure that r4022.03 input is high when there is no abnormal external alarm/alarm and emergency stop signal.
2. If the current hardware wiring cannot be completed, the alarm can be shielded by setting parameters. Since pins 3 to 6 on X9 terminal correspond to external alarm 3, external fault 3, emergency stop category 1 and emergency stop category 2 respectively, all the 4 corresponding bic0 parameters need to be set high. The specific settings are as follow:
parameter
meaning
Default value
Setting value
P2117.0
BI: set the signal source of external alarm 3.
r4022.0
1
P2108.0
BI: set the signal source of external fault 3.
r4022.1
1
P849.0
BI: no fast stop/ fast stop (OFF3) signal source 2/
r4022.2
1
Page 6
Date: 2019-12-11 DF MC SNC CSA TCC
- 6 -
OFF3 signal source 2
P845.0
BI: without slow stop/ slow stall (OFF2) signal source 2
r4022.3
1
Loading...