Field Manual SITRANS FUS1010 NEMA-4X/ IP 65 Clamp-On Multi-Function Flowmeter
SITRANS FUS
8
7
4
3
0
9
6
5
2
1
.
=
MENU
/
*
_
+
HELP
+
/
F1
-
CLR
CTRL
F2F3
ALT
ENTER
DATA
LOG
F3
1010NFM-3J
Siemens Energy & Automation’ s S t andard W arranty
This warranty applies to flow metering and leak detection systems.
SIEMENS ENERGY & AUTOMATION CORPORATION (the Company) warrants to the original
purchaser of this equipment as presented in Section 1 of Siemens Energy & Automation, Inc.
Standard Terms and Conditions of Sale (10/1/2004).
T o obtain repair or replacement within the terms of this Warranty, a Return Merchandise Authorization
number (RMA) must be obtained from Technical Service by calling (631) 231-3600 prior to shipment.
This RMA number must appear prominently on the outside of all returned packages. Returned
merchandise must include packing slip with specification of defect(s) and be shipped freight prepaid,
directly to Siemens Energy & Automation Corporation, 155 Plant Avenue, Hauppauge, NY 11788.
Equipment or material returned for Certification, V alidation, Repair, or Replacement may result in the
loss of memorized pipe site date in equipment computer memory . Siemens Energy & Automation can
save and then restore this data for some NEMA type systems and all Portable systems, if requested at
the time of equipment return. A fee may be imposed for this service.
This Warranty does not extend to costs incurred for removal or reinstallation of the equipment, or to
damage to equipment, accessories or components caused by such removal or reinstallation.
This Warranty does not apply to any equipment or part thereof, which in the opinion of the Company
has been damaged through alteration, improper installation, mishandling, misuse, neglect, lightning
strike, or other accidents. THE EXTENT OF THE COMP ANY’S LIABILITY UNDER THIS W ARRANTY
IS LIMITED TO THE REPAIR OR REPLACEMENT PROVIDED ABOVE AND, IN NO EVENT, SHALL
THE COMPANY’S LIABILITY EXCEED THE PURCHASE PRICE PAID BY PURCHASER FOR THE
PRODUCT.
This Warranty is in lieu of all other express warranties or liabilities. ANY IMPLIED WARRANTIES,
INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE ARE
HEREBY EXCLUDED. IN NO CASE SHALL THE COMP ANY BE LIABLE FOR ANY CONSEQUENTIAL
OR INCIDENT AL DAMAGES FOR BREACH OF THIS OR ANY OTHER W ARRANTY, EXPRESS OR
IMPLIED, WHATSOEVER. No person or representative is authorized to assume for the Company
any liability other than expressed herein in connection with the sale of this equipment
.
FIELD MANUAL
IMPORTANT NOTICE
Controlotron is now part of:
Siemens Energy & Automation, Inc.
Process Instrumentation Business Unit (PI BU)
CoC Ultrasonic Flow
SITRANS FUS 1010N
NEMA-4X CLAMP-ON
MUL TI-FUNCTION FLOWMETER
This equipment contains components that are
susceptible to electrostatic discharge (ESD).
Please observe ESD control measures during
the handling and connection process.
Field Manual 1010NFM-3J
August 2006
For use with Operating System
Software Version 3.01.05B or later
Prepared ByDate
EngineeringDate
FOR TECHNICAL ASSISTANCE:FOR GENERAL INFORMATION:
Call: (800) 275-8480Website: www.controlotron.com
(631) 231-3600E-mail: info.ultrasonicflow@siemens.com
Fax: (631) 231-3334Or: sales.ultrasonicflow@siemens.com
E-mail: TSG .ultrasonicflow@siemens.com
SETUP PROCEDURE FOR “WET-FLOW CALIBRATED” 1010 SYSTEM
Caution: DO NOT use the field manual installation procedure to startup a wet-flow
calibrated system. Doing so could void the calibration by corrupting essential data. This addendum contains the only authorized instructions to
be used when commissioning a wet-flow calibrated 1010 system.
1. INTRODUCTION
When the system 1010 is wet-flow calibrated, the flow computer stores the installation parameters in its storage memory. Each flow calibration is assigned a unique site name. Usually , the
site name corresponds to the pipe size. For example, a 3-inch carbon steel, schedule 40 pipe
would be given the name “3CS40.”
The flow calibration report issued with each wet-flow calibration, includes a flow calibration
“Diagnostic Data Sheet.” This data sheet lists the site name and other necessary information
(such as transducer serial number and spacing information), for setting-up the flowmeter. A
wet-flow calibration applies to a specific flowmeter and set of transducers; identified by serial
numbers on the diagnostic data sheet.
1010FMA-4
NOTE: In order for the flow calibration to be valid, the flow computer and transducers
being used must have the same serial numbers as those listed for the site on
the Calibration Diagnostic Data Sheet.
2. SETUP PROCEDURE
2.1 Transducer Installation
2.1.1Refer to the diagnostic data sheet to find the mounting mode (Direct or Reflect) used
during the wet-flow calibration. Review the transducer installation guidelines in your 1010
field manual.
2.1.2Refer to the diagnostic data sheet for the transducer spacing index utilized during the
flow calibration. Using the mounting configuration employed during the flow calibration,
install the transducers on the pipe at the above noted spacing positions in accordance
with the instructions provided on the transducer installation drawings.
2.1.3Attach the transducer cables noting that the cable marked “UP” attaches to the transducer closest to the source of flow.
NOTE: Before proceeding further, ensure that the pipe is full of liquid. It is not impor-
tant at this point that it be flowing.
1
July 2002
Manual Addendum
2.2Flowmeter Setup
NOTE: The following instructions require the use of the keypad and the menu. The
installer should become familiar with their use before proceeding further.
2.2.1Switch the flowmeter on. Press the <MENU> key .
2.2.2On multi-channel flowmeters, use the arrow keys to select [Dual Channel Flow] or
[Dual Beam Flow] depending on the mode utilized for the wet-flow calibration.
2.2.3Use the arrow keys to select either [Clamp-on], [Flow Tube] or [Clamp-on Spool].
2.2.4Select [Full Site Setup] and use the <Right Arrow> to select [Channel Setup]; then
select [Recall Site Setup].
2.2.5Use the <Down Arrow> to scroll to the site name indicated on the Calibration Diagnostic Data Sheet. Then press <ENT>.
2.2.6The meter will perform a momentary “Makeup” routine that will take a few seconds and
then begin operation.
1010FMA-4
2.2.7Refer to your 1010 field manual for instructions on setting zero flow.
NOTE: Setting zero flow must be performed each time the transducers are installed.
The zero adjustment has no effect on the wet-flow calibration data or the calibration (Kc) factor.
2.2.8Using the arrow keys, scroll to the Data Sp an/Set/Cal menu location. Verify that the [Kc]
(calibration) factor matches the value indicated on the diagnostic data sheet.
2.2.9If you are measuring a liquid other than ambient water, select the [Liquid Class] menu
cell and <Down Arrow> from there to [Viscosity]. Enter the correct viscosity for the
liquid you will be monitoring.
2.2.10 Setup is now complete. Press the <MENU> key twice to view the flow rate display . DO
NOT utilize the [Save Site] command when it appears.
2.2.1 1 When measurements are completed, simply turn off the meter . DO NOT save the site.
This might contaminate the wet-flow calibration data already stored.
NOTE: Contact Siemens’ Technical Services Department if any flow calibration data is
accidentally removed or overwritten.
2
July 2002
Manual Addendum
3.TRANSFER INSTALL FUNCTION
All 1010 flowmeter operating systems (version 3.00.20 and greater) include the installation facility called “Transfer Install.” This function permits the transducers to be repositioned while maintaining all calibration parameters and operation established during the water calibration. The
Transfer Install function allows the transducers to be optimally positioned for a different fluid,
without the need for a new Initial Makeup procedure.
NOTE: Prior to performing Transfer Install make sure that the water calibration proce-
dure was performed and a saved active site exists.
3.1Transfer Install Procedure
To initiate the T ransfer Inst all function, proceed as follows:
3.1.1In the Application Menu press the <Right Arrow> to select the [Liquid Class] menu cell.
Scroll and highlight [Estimated Vs m/s] from the option list.
3.1.2Use the numeric keys to change the Estimated Vs to the Estimated Vs value of the
customer selected liquid.
3.1.3To enter new Estimated Vs value press <ENT>.
1010FMA-4
3.1.4Proceed to the Pick/Install Xdcr menu and select the same transducer , mounting mode
and spacing offset that was selected for the water calibration.
3.1.5Re-space the transducers to the index position indicated by the flowmeter .
3.1.6Scroll to the [Install Completed?] menu cell and select [Transfer Install] from the option
list.
NOTE: If [Transfer Install] does not appear in the option list then either the Estimated
Vs or the transducer size was improperly entered. In this case, recall the water
calibration site and start the procedure again at Step 3.1.1 above.
3.1.7For MultiPath systems repeat Step 3.1.6 above for the remaining p aths.
3.1.8The flowmeter should now be operational at the new spacing location.
NOTE: Depending on the size of the pipeline, the change in the estimated sonic veloc-
ity (Vs) and the repositioning of transducers, the flowmeter may not operate out
of Fault even if the spool or pipe is filled with liquid. This can be expected when
performing a Transfer Inst all for liquified gases or for clamp-on natural gas flowmeters.
3.2Saving New Transfer Install Site
3.2.1To save the Transfer Installed site, scroll to the Channel Setup menu and press the
<Right Arrow>. Press the <Right Arrow> again to select the [Save/Rename] menu cell.
3.2.2Use the numeric keys to rename the Transfer Installed site with the same site name
used in Step 3.1.2 above, but with a “T” appended to the end of the site name (e.g.,
3CS40T).
3.2.3Press <ENT> to store data.
3
July 2002
MANUAL
ADDENDUM
SYSTEM 1010
1010FMA-14
EXPANDED I/O OPTION
(For Systems Equipped With 1010N-7 Modules)
Manual Addendum
May 2002
FOR TECHNICAL ASSISTANCE:FOR GENERAL INFORMATION:
Call: (800) 275-8480Website: www.controlotron.com
(631) 231-3600E-mail:info.ultrasonicflow@siemens.com
Fax: (631) 231-3334Or: sales.ultrasonicflow@siemens.com
E-mail: TSG .ultrasonicflow@siemens.com
The 1010N-2 I/O Module and 1010N-7 Expanded I/O Module both provide current (Io1, Io2), voltage
(V01 and Vo2) and pulse rate (Pgen 1 and Pgen 2) analog output s. The Expanded I/O Module Option
allows users to drive as many as four additional 4-20 mA loop-powered instrumentation outputs. The
following information is intended to be used with the I/O Data Control and Span Data sections and
Analog Output Trim Menu in the field manual.
The System 1010 flowmeter provides an Analog Output Setup menu (see below) that allows the user
to assign data functions for these output signals (refer to Analog Output Setup in the appropriate 1010
field manual). In addition, refer to Installation Drawings 1010N-2-7 and 1010N-7-7 in the field manual
appendices for additional connection information and terminal block numerical designators.
NOTE: All meters in the System 1010N and DN product family can accept the Expanded I/O
Module Option except 4-Channel meters.
Use this menu to
assign data functions
to analog ou tp uts .
Siemens Dual Path SITE1
Assign Data to Analog Outputs
Analog Out Setup
Relay Setup
Analog Input Setup
I/O Data Control
EXPANDED I/O MODULE OPTION
The Expanded I/O Module Option provides expanded Io analog outputs. It is implemented through the
use of a 1010N-7 Expanded I/O Module occupying the same position as the 1010N-2 I/O Module. This
option allows users to drive up to four additional 4-20mA loop-powered instrumentation outputs. Note
that the meter menu does not indicate that these supplementary outputs are present and available.
The outputs, in addition to being loop-powered, are isolated from one another as well as the meter .
Expanded I/O Module Option Identification
To verify that your meter has the Expanded I/O Module Option installed check the following:
The designation A1 should be part of the flowmeter part number .
For example: 1010ENRE-T1A1KGS
1
May 2002
Manual Addendum1010FMA-14
1010N-2 I/O Module
The conventional 1010N-2 I/O module provides the following:
zT wo self-powered, isolated 4-20 mA current loop s (signals Io1 and Io2) that are assignable and
spannable by the user to many flowmeter variables such as flow , sonic velocity , signal strength,
etc. These self-powered outputs also provide an industry-standard fault indication by dropping
to 2 mA if assigned to flow rate and under fault conditions. Note that these outputs, thoughisolated from the system, are NOT isolated from each other.
zTwo 0-10 Vdc outputs (signals Vo1 and Vo2) that are also assignable and spannable by the
user as above. These are also self-powered, but are not isolated from the system.
zT wo 0-5000 Hz Pgen signals (Pgen1 and Pgen2) also assignable and spannable by the user.
These are TTL level pulses.
The 1010N/DN class of meters has a total of six analog outputs as indicated above. In addition (refer to
Installation Drawings 1010N-2-7 and 1010N-7-7):
zAlarms/Status/Totalizer pulses are generally presented as relay closures as either Mercury
Wetted Form 1A or Dry Reed Form C relays.
zAnalog inputs, when provided, are in the form of 4-20 mA non-isolated inputs.
zThe meter also has four non-isolated totalizer command lines providing Totalizer Clear and
T otalizer Hold (NoTot) functionality.
1010N-7 Expanded I/O Module Option
The Expanded I/O Module Option provides all of the above plus the following outputs:
zThe four signals that drive the pulse generator outputs (Pgen 1 and Pgen2) and voltage outputs
(Vo1 and Vo2) of the meter create four current outputs: Aux Io1, Aux Io2, Aux Io3 and Aux Io4
(see diagram on next page).
zBy spanning and assigning a system variable to 0-10 volt (Vo1 and Vo2) or 0-5000 Hz pulse
output (Pgen1 and Pgen2) the module simultaneously outputs these signals to the Expanded
I/O Module Option Aux outputs. For a 2-Channel meter the programming assignments are as
follows:
TYPICAL 2-CHANNEL METER EXPANDED I/O OPTION CONNECTIONS
CHANNELSIGNALAUX IoMETER MENU DISPLAY
CH1Pgen1Io1V o1
Vo1Io3Pgen1
CH2Pgen2Io2V o1
Vo2Io4Pgen1
zNote that the four Aux Io outputs are externally powered.
2
May 2002
Manual Addendum
EXP ANDED I/O MODULE OPTION PROGRAMMING
The diagram below illustrates the Expanded I/O Module Option programming for a Single Channel
meter with a 1010N-7 Expanded I/O Module.
FLOW COMPUTER
INTERNAL
CONNECTIONS
OUTPUT
TERMINAL STRIP
1010FMA-14
Io1
``
Io1
Pgen1
z
Aux Io1
```
Pgen2
Vo1
z
z
Aux Io2
Aux Io3
`
Vo2
NOTE: The 1010N-7 Expanded I/O Module auxiliary output signals (Aux Io1 - Aux Io4) geneated
from Pgen1, Pgen2, Vo1 and Vo2 are “mirrored” output currents. For example, if Vo1
is a 5 Vdc signal then Aux Io3 will be 12 mA.
NOTE: The method used to create auxiliary current loops makes it impractical to generate the
2 mA fault current produced by the primary 4-20 mA output s of the meter.
z
Aux Io4
3
May 2002
1010NFM-3J Table Of Contents
TABLE OF CONTENTS
Section 1
1.Getting Started ................................................................................................ 1-1
Example of a Spectra Display Screen ..................................................... 7-5
7.10Cursor Use On The Spectra Graph .............................................................. 7-6
7.1 1How To Use Spectra Graph Data and Controls ........................................... 7-6
7.12Available Adjustments To Spectra Graph ..................................................... 7-7
7.13Reflexor Diagnostic Data ............................................................................... 7-8
Diagnostic Data ....................................................................................... 7-8
7.14Display of “F” At No Flow Conditions ........................................................... 7-9
7.15Selection Of Liquid Composition .................................................................. 7-9
7.16Other Menu Entries ........................................................................................ 7-9
APPENDICES
Appendix A - Couplant Inst allation Instructions (if applicable)
Appendix B - Site Setup Considerations for 1010N Blind Systems
Appendix C- Engineering Drawings
INDEX
Pipe Table
viii
1010NFM-3JSection 1
1.GETTING STARTED
1.1INTRODUCTION
Congratulations on your purchase of the Siemens SITRANS FUS1010 NEMA Permanent Flowmeter.
Intended for dedicated applications, this versatile transit-time flowmeter is easy to set up and operate.
The Model FUS1010 flowmeter represents the state-of-the-art in computerized instrumentation. We
are confident that in a very short time, you will appreciate its unrivaled performance and features;
especially Siemens’s ground breaking enhanced transit-time Digitally Coded MultiPuls technology and
the on-line automatic and interactive site setup facility . This manual covers FUS1010 Single Channel,
Dual Channel/Dual Path and 4-Channel/4-Path flowmeter types in NEMA-4 or NEMA-7 enclosures.
Only the Model 1010FTN and 1010AN flowmeters are equipped to utilize the flow tubes shown in
Section 6.
This section shows how to install the System FUS1010 flowmeter with a minimal amount of effort. It
will show how to use the Installation Menu to set up the system for transit-time, Reflexor and Flow T ube
Clamp-on operation. It also shows the basic connections to and from the flowmeter. For additional
information on connections, see the drawings at the end of manual.
1.2IMPORTANT SAFETY CONSIDERATIONS
The FUS1010 NEMA Permanent meter operates from either an external AC or DC power source.
Please observe all the electrical safety codes, etc., that apply to your application. We recommend that
only experienced personnel with knowledge of local electrical codes and safety operating procedures
perform the installation and wiring. It is solely the user’s responsibility to operate this equipment safely.
Siemens cannot accept responsibility for any damage that may occur due to failure to observe any
local safety rules.
If this equipment is used for a hazardous application (high line pressure, hostile liquid characteristics,
perilous atmosphere, etc.), the end-user must ensure that only properly trained personnel are involved
in its installation and operation.
Please do not let the size of the Installation Menu intimidate you. Almost all menu cells already contain
default parameters. To begin operation, you only need to access the menu cells that control a required
parameter , such as the pipe outer diameter. You will see that by accepting most defaults, you can set
up the meter in about five minutes.
1.3FLOWMETER INSTALLATION STEPS
Typical steps to complete the installation procedure.
zCollect the site data (pipe and liquid data, part numbers, etc.)
zChoose a mounting location for the flow computer and transducers.
zMount the flow computer at the selected location.
zPrepare pipe for transducer mounting.
zAccess the Installation Menu and create a site (see paragraph 1.7.3).
zEnter pipe parameters (see paragraph 2.2).
zInvoke transducer install procedure (see paragraph 2.4).
zMount transducers on pipe and connect to flow computer (see Section 3).
zComplete transducer install menu operation (see paragraph 2.4).
1-1
1010NFM-3JSection 1
1.4THE KEYPAD ENABLE SWITCH
All System 1010N models provide a keypad enable/disable switch to prevent unauthorized access to
the Installation Menu. In addition, a password entry option is available (see Channel Setup). The keypad
enable/disable switch is located inside the lockable enclosure just above the I/O wiring terminal. Please
switch to the enable position before proceeding further. If necessary, see Drawings 1010N-7, 1010DN7 or 1010MN-7 for location details.
1-2
Flow Measurement Sub- system ( 4 channel system depicted here)
TYPICAL SYSTEM - 1010N PERMANENT CLAMP-ON SYSTEM
1010NFM-3JSection 1
1.5THE 1010N KEYPAD
The 1010N integral keypad provides 32 numeric and function keys (see table below). Use these keys to
enter, review or edit the site data. Certain keys control the graphics display, Datalogger and Totalizer.
“Blind Models,” having no keypad or display, must be setup by using their serial dat a port (see Appendix B).
KEYPAD FUNCTION CHART
KEY USAGE
MENUPress to activate the Installation Menu.
ENTPress <ENT> to store numeric data, select from option lists, etc.
LEFT, RIGHT ARROWSMenu navigation keys move cursor in respective directions.
UP, DOWN ARROWSSame as <Left> and <Right>. Also scrolls option list and graphic
display screen.
CLRClear Key for erasing data, or selecting list options.
NUMBERS 0-9Use to type numeric data.
DECIMAL POINTUse for decimal points in numeric data.
MATH OPERATORSAllows 4-function math operations in numeric entry cells.
“F” KEYS 1-3Totalizer control and special function keys.
“F4” KEYCAUTION: SYSTEM RESET KEY (during power up)
CTL & ALTUsed as shift keys for alternate key functions.
DATALOGTriggers immediate Datalogger report.
PLUS/MINUS [+/-]Changes the sign of numeric data.
NOTE: The keypad does not have alphabetic keys. Scrolling lists provide alphanumeric char-
acters as needed.
1.6INTRODUCTION TO THE 1010N MENU SCREENS
The figure below shows a typical 1010N menu screen (in this case, the Pipe Data Menu).
Menu Prompt LineWhen you select a menu cell, a highlighted text prompt appears on the top of
the screen to explain the function of the cell.
Current Selected[2 Channel] indicates Dual Channel meter operating mode selected.
Meter Type
Selected ChannelThe [1] indicates that measurement Channel 1 is currently selected.
Highlighted MenuThe menu cursor (highlight bar) shows where you are currently working by
Cellreversing the display colors for that cell (white type on black).
Highlighted DataThe right-hand column shows the current value highlighted. Pressing the
<Right Arrow> provides access to an option list or numeric field where you
can change the current value as required.
Menu CellA menu cell is an individual location within a menu (in this case Pipe Data)
that stores a parameter (either a numeric entry or an option list selection.
Menu Cell DataThe right-hand column shows the current value stored by left-hand column
menu cell. The Pipe Data Menu includes option list items and numeric entries.
Current SelectedThe highlighted bar at the bottom of the screen shows the name of the menu
Menuthat you are accessing (e.g., Pipe Data).
1.7HOW TO USE THE INSTALLATION MENU
This section introduces the System 1010 Installation Menu. It explains how to access and leave the
Installation Menu and how to enter site data. The Installation Menu consists of sub-menus, each providing individual menu locations (menu cells) that store site data. For convenience, this manual refers
to sub-menus simply as menus (e.g., the Pipe Data Menu). Shown below is the Clamp-on, Full Site
Setup screen for Channel 1 of a dual-channel meter. Single and four channel systems are identical.
Siemens 2 Channel [1]
Create-Name-Recall-Enable & Delete Site
Channel Setup
Pipe Data
Application Data
Pick/Install Xdcr
Operation Adjust
Flow/Tot al Units
Data Span/Set/Cal
Stripchart Setup
Datalogger Setup
I/O Data Control
Diagnostic Data
Clamp-on
1-4
1010NFM-3JSection 1
1.7.1 ACCESSING AND LEAVING THE MENU
Upon first turning the meter on you see a Siemens graphic. This means that there is no active site
setup currently stored in memory . Note that this screen identifies the software version of the meter on
the upper right-hand corner of the display .
ver. 3.01.00
Software
Version
(x.xx.xx)
Make sure the keypad enable switch is in the correct position then press the <MENU> key to select the
menu. The first time you access the Installation Menu, you can leave it only by saving a site or by
turning the meter off. After installing and activating a site, use the <MENU> key to toggle between a
graphic display screen and the last accessed menu location.
Siemens 2 Channel [1] Channel 1
Select Meter Type
Meter Type >Dual Channel Flow
Meter Facilities Dual Beam Flow
Using the Menu Ch 1 + 2 Flow
Ch 1 - 2 Flow
Liquid Class
Top menu screen for dual-channel system Top menu screen for single-channel system
Siemens Site [1]
Select Meter Type
Meter Type Single Channel
Meter Facilities
When you press the <MENU> key , the cursor arrives at the first level of the installation menu. Refer to
the sample screens above. The left screen is from a dual-channel model. The right screen is from a
single channel model. Note that two columns, one on the left-hand side and the other on right-hand
side, divide the screen. The first left-hand item, [Meter T ype], is highlighted (white type on black). [Meter
Type] allows you to choose a meter configuration from the highlighted right-hand column list. Withsingle channel models, the only option is [Single Channel]. The next left-hand selection is [Meter Facilities]. Use the [Meter Facilities] menu to set global meter options and controls.
1.7.2 HOW TO ENTER DATA
The left-hand column shows the menu cells (described previously). Another way to think about lefthand column items is to consider them menu questions. Then you can see that the right-hand column
answers these questions. Right-hand column answers can be:
zAnother series of menu cells (may become left column items when selected).
zAn item from a scrollable option list (e.g., a class of liquids).
zA numeric entry (e.g., a pipe outer diameter).
zAn alphanumeric string (e.g., a site name).
1-5
1010NFM-3JSection 1
Selecting Items from an Option List
Examine the screen below. It shows how to use an option list to select a liquid for your application. How
to access this menu will be explained later. Note that the menu name [Application Data] appears
highlighted on lower left of the screen. Note also that the menu cell [Liquid Class] is highlighted - the
right-hand column shows the answer [Water 20C/68F].
Siemens 2 Channel [1] Channel 1
Select Liquid Class from Liquid T able
Liquid ClassWater 20C/68F
T emperature Range-40F to 250F
Pipe ConfigurationFully Developed
Anomaly Diams10
Application Data
Pressing the <Right Arrow> changes the left-hand column to [Select Liquid]. Pressing the <Right Arrow> again accesses the option list. This expands the highlighted area to show the list contents. Note
that a cursor (arrow) points to the top item on the list.
Siemens 2 Channel [1] Channel 1
Access Liquid Option List
Select Liquid >Water 20C/68F
Estimated Vs m/sWater 50C/122F
Viscosity cSWater 75C/167F
Density SGensWater 100C/212F
Water 125C/257F
Water 150C/302F
Water 175C/347F
Water 200C/392F
Water 225C/437F
Water 250C/482F
Acetic Acid
Liquid Class
The <Up and Down Arrows> scroll the option lists. Every press moves the cursor to the next item in
sequence. Due to the size of display screen, some option lists include more items than the display can
show. For example, on the screen above the last option shown is [Acetic Acid]. However , this option list
has more listings. Continue to press the <Down Arrow> to see more liquid selections. When you arrive
at the last item on a list, the next <Down Arrow> press brings you back to the top of the list; because
the option lists are of the “wrap-around” type.
To select an option list item, move the cursor to the item and then press the <ENT> key.This places
your selection at the top of the list and moves you out of the option list to the next menu cell. Examine
screen on next page. The option list item: [Diesel Fuel] has been selected. Note that this appears on
the right-hand column and that the highlighted area moves to the next menu cell in sequence: [Estimated Vs m/s].
1-6
1010NFM-3JSection 1
Siemens 2 Channel [1] Channel 1
Access Liquid Option List
Select LiquidDiesel
Estimated Vs m/s1600
Viscosity cS2.00
Density SG1.030
Liquid Class
Multiple Select Option Lists
Certain option lists allow you to make more than one selection. For instance, the Datalogger Data
option list allows you to select any or all of the available data items for your reports. You can use the
<Up and Down Arrows> to move the cursor through the list. If you press <ENT> to select an item, a
plus sign (+) appears next to that item. The cursor remains so that you can make other selections. To
deselect a previously selected item, move cursor next to that item and press <CLR>. Use <Left Arrow> to leave a multiple select option list.
Siemens 2 Channel [1]1
Select Datalogger Data
Datalogger Mode+Site Id
Datalogger Data+Date
Log Time Interval+Time
Datalogger Events Flow
Display Datalogger+Average Flow
Raw Flow
Total
Liquid Class
Entering Numeric Data
When a menu cell requires a numeric answer, press the <Right Arrow> to access a number entry
field; an equal sign (=) appears before current entry . You can now use the number keys and the decimal point key to type a new value. If applicable, you can use <+/-> keys to change the mathematical
sign of the number. Press <ENT> to store the numeric data.
NOTE: All Numeric Data cells provide a four-function calculator via the keypad’s arithmetic
An alphanumeric string is a series of numbers and letters; and also the Quotation Mark and the Pound
Sign symbol. You can also use a space. The meter uses these to identify a specific site setup or usermodified table. The 1010N keypad does not provide letter keys. However, when you access a menu
cell that requires an alphanumeric string answer, the menu cell right-hand column provides an eightcharacter entry field. Press the <Right Arrow> to access the field. This selects the first character
position. Note that the prompt changes to a question mark (?). With the cursor at the first character
position, use the <Up> or <Down Arrows> to scroll through a single-character list. For example, as
shown below, an <Up Arrow> at the first character position produces the letter: uppercase [A]. Pressing the <Right Arrow> moves the cursor to the second position.
Controlotron Dual Path Channel 1
Right Arrow & Enter Creates a new Site
Recall Site Setup
Channel EnableNo
Create/Name Site?A
Site SecurityOff
Delete Site SetupNo Sites
Save/Rename Site
Channel/Path Setup
Use the <Right and Left Arrows> to move through the character positions. If you wish touse numbers
in your string, you can type them directly from the keypad. After you finish selecting your string, press
<ENT> to register it.
1.7.3 THE METER TYPE MENU
This is the first list presented upon entering the Installation Menu. Select the type of meter required for
your application. The meter automatically conditions Installation Menu choices to suit the selected
meter type. The following paragraphs introduce the available meter types for dual channel systems.
NOTE: On Single Channel systems, you do not get a choice of meter types, sincethis requires
two independent measurement channels. However, you can operate the single channel with any optionally supplied measurement technology. Some four channel models
provide four-path and channel summing operation.
1-8
1010NFM-3JSection 1
Dual Channel
Dual Channel provides two independent measurement channels that operate simultaneously. Depending on the specific model, Dual Channel supports: Clamp-on Transit-time, In-line Transit-time,
Reflexor.
Channel 1
Flow
PIPE `A'
PIPE `B'
Channel 2
Flow
Pipe 'A' Flow Rate
Pipe 'B' Flow Rate
Dual Path
Dual Path uses two measurement channels to achieve a single output via a “virtual” third channel. The
resultant data is the average of the two channels. Only clamp-on or in-line transit-time operation allowed. Benefits include highest available precision and enhanced immunity to distorted flow profile
conditions.
Channel 1
Flow
Pipe
Ch1 + Ch2
2
Output
(average of
Ch 1 & Ch 2)
Channel 2
Flow
Channel 1+2 and Channel 1-2
Arithmetic operation produces data output via a virtual Channel 3, proportional to sum or difference of
the liquid and energy flow of two independent pipes. This requires setting the two channels to operate
independently . Only clamp-on or in-line transit-time operation is supported.
P
Channel 1
PIPE `A'
PIPE `B'
Channel 2
I
P
E
`
A
'
F
L
O
W
R
A
T
E
Ch1 [+/-] Ch2
E
T
A
R
W
O
L
F
'
B
`
E
P
I
P
Output
sum or difference
of Ch1 & Ch2
Channel 1-2 produces a data output via a virtual Channel 3, proportional to the difference of the liquid
and energy flow of two independent pipes. You have to set-up the two channels independently. Only
clamp-on or in-line transit-time operation is supported.
1-9
1010NFM-3JSection 1
1.7.4ESSENTIAL INFORMATION FOR USERS OF MULTI-CHANNEL 1010’s
Multi-Channel Meter Type
If your 1010 is a multi-channel model, it offers 2 or 4 independent measurement channels. The meter’s
resources are divided among these channels equally. This means that analog Input/Output, relays
and digital command lines will be fewer than for single channel machines. We’ll show you later how to
“get around” this limitation for times when you need all your multi-path meter’s resources for a single
measurement channel.
If one, two or three channels are running when you are trying to setup the last channel, it could take a
very long time for the setup; some 10 to 15 minutes should be expected. A great time saver would be to
turn each channel off after setup (setup one channel at a time) and reactivate all after everything is
setup; then the setup time goes very quickly .
Your datalogger and site storage memory, being bulky resources, are not divided up at all, and
remain available for each channel’s use. You will be able to save and recall sites to and from the
various channels as long as they share an identical measurement technology (Reflexor, clamp-on,
flowtube, etc.). Be aware, however, that moving a site from one channel to another like this, will likely
require a new initial installation to achieve its best potential. This is especially true if the new target
installation is not on the same pipe or uses another pair of transducers whose nominal characteristics
are identical. Note that datalogger reports will be interleaved in memory and their frequency is controlled by the interval that was selected for each channel. Providing each site with a unique name will
enable you to sort these out when analyzing the data later .
Arithmetic Operation
The dual channel instruments provide a modality of operation which permits the user to arithmetically
combine (through addition or subtraction) the results of the two independent measurement channels.
Installation of each channel is done via the dual channel menu. Site Saving andRecalling automatically recall the contributing sites. While the displays for each physical channel provide you all the data
(flow rate, totals, etc.) that are provided via independent channel operation, user Input/Output is largely
oriented toward the virtual channel - Channel 3.
Multi-Path Operation
In many cases, the performance of an ultrasonic transit time meter can be improved by allowing it to
interrogate the flow field with more than one beam. Imperfect flow profile conditions such as non-axial,
cross-flow or an off-center higher-rate flow core, which can cause a single path machine to mis-report
the flow rate, are often remedied in this way . The multi-p ath installation is similar to arithmetic operation; except for the fact that the virtual, or output channel has pipe dimension attributes (which in the
arithmetic meter channel it does not). This means that when you install a multi-path meter, pipe datamust be installed in Path 1 and Path 2. Your 1010 meter facilitates this by copying pipe data that you
installed as Path 1 and Path 2 data to the other paths. It is seldom, if ever , necessary to “trim” the pipe
data for the individual path channels - although you may install different size or type transducers for
each path. Once you define the pipe, move the menu to the individual paths using Select Path for the
physical installation of each channel. This is accomplished in the same way that individual channels
are installed.
Save andRestore Operations for multi-path sites execute on all the component channels simultaneously; the individual paths of multi-path sites do not have any existence or autonomy as
single channel sites. You will also find that individual path channels possess a reduced set of user-accessible menu functions. For example, although you may zero each individual path, the meter
provides Kc control (slope correction) for the virtual channel (system channel) only. You will find that
the features and functions provide for each physical channel to focus mainly on the physical measure-
1-10
Loading...
+ 202 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.