Installation Instructions
Models FS-TRI-M
Contact Monitoring Module
Fire Safety
The SIEMENS FS-TRI-M Contact Monitoring Module,
as shown in Figure 1, interfaces normally open contact
devices to an Addressable Device Circuit of a fire
alarm control unit.
The FS-TRI-M supports Style B (Class B) Initiating
Device Circuit wiring. Each module uses one address
on the Addressable Device Circuit. It does not require
any mechanical address programming. Use the FS-FPI
Programmer/Tester to program and test the module.
PROGRAMMING INSTRUCTIONS
CAUTION:
1. To prevent damage to the FS-FPI, do not
connect modules to the FS-FPI until the
Addressable Device Circuit wiring is
disconnected.
2. Only one device must be connected to the
FS-FPI at a time.
1. Connect the red and black wires of the FS-TRI-M
to the SIEMENS FS-FPI Programmer/Tester. Use
the cable provided with the Programmer/Tester
and the 2 alligator clips provided.
2. Set the address for the module by following the
instructions in the FS-FPI Programmer/Tester
Manual (P/N 315-699480).
3. Record the device address on the label located
on the module. The module can now be installed
and wired to the system.
MOUNTING
The FS-TRI-M must be installed in a
UL Listed electrical box.
Refer to Figure 2.
1. Connect the appropriate wires using wire nuts.
Tuck the FS-TRI-M module inside the electrical
box and dress the wiring as required.
2. Fasten the cover plate (user supplied) to the box.
Figure 1
FS-TRI-M Module
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-699487-1
EARTH
GND
GRN
-
+
ORG
ORG
ED
T
I
M
BLK
RED
ALSAREPOWER LI
N
S-TRI-M
TOCONTROLPANEL
F
STR.
ORPREVIOUSADDRESSABLE DEVICE
IN
ALLTERMI
MODEL:
REFERTOINSTL.
P/N315-699487
DEVICEADDR.__________
SiemensBuildingTechnologies,Inc.
FlorhamPark,New Jersey 07932
NOTE:
DO NOT USE
REAR CONDUIT ENTRY
FS-TRI-M
SINGLE GANG
SWITCHBOX
SINGLE GANG
SWITCHPLATE (BLANK)
(USER SUPPLIED)
(USER SUPPLIED)
Figure 2
FS-TRI-M Mounting
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN

WIRING
Remove all system power before installation, first battery and then AC.
(To power up, connect AC first then battery.)
Refer to the wiring diagram and wire the module accordingly.
+
ADDRESSABLE DEVICE CIRCUIT
24VDC NOMINAL, SUPERVISED
FS-TRI-M
INITIATING DEVICE CIRCUIT
SUPERVISED, SEE NOTE 3
RED
BLACK
GREEN
ORANGE
ORANGE
CONTACT DEVICE
TO NEXT
ADDRESSABLE DEVICE
-
+
FROM ADDRESSABLE DEVICE
CIRCUIT OF A COMPATIBLE
CONTROL UNIT OR PREVIOUS
ADDRESSABLE DEVICE
-
GROUND
SEE NOTES 4 AND 5
END OF LINE RESISTOR
3.6K, 1/4W, 5%
P/N 140-820185
Figure 3
FS-TRI-M Wiring
NOTES:
1. All circuits are power limited.
2. In supervisory:
FS-TRI-M draws 1.5mA
3. Initiating Device Circuit ratings:
Style B, Class B
See NFPA 72 standard for the number of normally open contact devices allowed.
Voltage (max.): 5 VDC (during polling)
Supervisory current (max.): 0.5mA (during polling)
Alarm current (max.): 0.8mA (during polling)
IDC cable requirements:
Wire size: 18 to 14 AWG
Wire resistance (max.): 2 ohms
Cable length (max.): 200 feet
Cable Type: Data grade, twisted pair
4. If Earth Ground is available, the green wire should be connected to earth ground.
5. If Earth Ground is NOT available, the IDC wiring should be limited to the same room.
P/N 315-699487-1