Siemens FS-DACT Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS Model FS-DACT Serial Digital Alarm Communicator Transmitter (DACT)
The FS-DACT Digital Alarm Communicator Transmitter Board is an optional module for the FS-250 and FS-250C Fire Alarm System Control Panels. The FS-DACT provides telephone line connections for communication with a DACR (Digital Alarm Communicator Receiver). The FS-DACT Board is mounted on the Main Board. The FS-DACT Board options are set through the control panel programming sequence.
PARTS SUPPLIED
1 FS-DACT Board 4 Spacers, 1” 1 Keps Nut, #6-32 1 Instruction Sheet
FS-DACT MOUNTING for FS-250 OR FS-250C
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this instruction sheet.
Step 2.) Disconnect BATTERY and AC prior to working on
equipment.
Step 3.) Mount DACT Board as shown, using four spacers
to the Main Board. NOTE: Check to see that the header and
connectors are mated properly.
Step 4.) Attach ground wire as shown, using the nearest
main board mounting screw as shown. Step 5.) Attach conduit and run wires as required. Step 6.) Connect wires to the fire alarm system control unit
as required. Step 7.) Apply power to system. Step 8.) Program for proper operation of functions.
a) Tech Level>>Outputs>Option Mods>DACT CFG
(Set DACT line and general configurations)
b) Tech Level>>Outputs>Option Mods>DACT ACCTS
(Set DACT account configurations)
c) Maint Level>>Disable/Enable>Outputs>DACT
>Enabled
NOTE: See Programmer’s Manual (P/N 315-
049403[C]) for more details on programming.
Step 9.) Check for proper operation of functions.
Siemens Industry, Inc. Siemens Canada Limited Building Technologies Division Building Technologies Division Florham Park, NJ 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
P/N 315-699464-10 (v10-21-10)
Page 2
FS-DACT WIRING
Telephone Line Connection Ratings: Power Limited Supervised Voltage: 24VDC nominal, 0.054A max. Ringer Equivalence: 0.4B
RED
GREEN
GREY
BROWN
RED
GREEN
GREY
BROWN
8-PIN
MODULAR
PLUG
8-PIN
MODULAR
PLUG
RJ31X
JACK
RJ31X
JACK
TIP
RING
TIP
RING
TIP
RING
TIP
RING
Telephone Line #1
Connection from TELCO
Optional Output to telephone
(Note: The DACT may seize
the line to report events)
Telephone Line #2
Connection from TELCO
Optional Output to telephone
(Note: The DACT may seize
the line to report events)
NOTE: The RJ31X provides a convenient connection allowing the DACT to be installed and removed without requiring re-wiring and can be installed by the telephone installer.
NOTE: If installed in Canada, the signal receiving centre must not share a common communication channel with the protected premises. A dedicated line must be installed for use only by the FS-DACT.
FS-DACT FORMAT DESCRIPTION
Format Description
SIA DCS 8 Security Industry Association - Digital Communications Standard. Format may send up to eight events a call.
SIA 1997 Level Ia compatibility with support for O (old) blocks and 300 Baud (FAST) operation. Sends an account number (up to 6 digits), a 2 character code and 3-digit identifier up to four times with FSK
frequency encoding. SIA DCS 20 See SIA DCS 8, except format may send up to twenty events a call. Ademco Contact ID Sends a 4-digit account number, a 3-digit code and 3-digit identifier up to four rounds of dual tone multiple
frequency with 1400 and 2300 Hz handshake frequency. 3/1 1400HZ Sends a 3-digit account number and a 1-digit code up to four rounds at 20 pps with 1400 Hz handshake
frequency. 3/1 2300HZ Sends a 3-digit account number and a 1-digit code up to four rounds at 20 pps with 2300 Hz handshake
frequency. 4/2 1400HZ Sends a 4-digit account number and a 2-digit code up to four rounds at 20 pps with 1400 Hz handshake
frequency. 4/2 2300HZ Sends a 4-digit account number and a 2-digit code up to four rounds at 20 pps with 2300 Hz handshake
frequency.
COMPATIBLE RECEIVERS/FORMATS
Receiver
Manufacturer
Osborne-Hoffman, Inc. Osborne-Hoffman, Inc. Radionics, Inc. D6500 3x1 3x1 4x2 4x2 Silent Knight Security Corp. Silent Knight Security Corp. Silent Knight Security Corp.
Compatible
Receivers
QUICKALERT!
Model II OH2000 SIA 1 SIA 1 Ademco
SIA DCS 8 SIA DCS
20
Ademco
Contact ID
Ademco
Contact ID Contact ID
3/1
1400HZ
Fast 3+1
1400HZ
Fast 3+1
1400HZ
3/1
2300HZ
Fast 3+1
2300HZ
Fast 3+1
2300HZ
4/2
1400HZ
Fast 4+2
1400HZ
Fast 4+2
1400HZ 9000 SIA 8 SIA 20 SK 3/1 SK 3/1 SK 4+2 SK 4+2 9500 SIA DCS SIA DCS Ademco
SK 3/1 SK 3/1 SK 4+2 SK 4+2
Contact ID
9800 SIA DCS SIA DCS Ademco
SK 3/1 SK 3/1 SK 4+2 SK 4+2
Contact ID
4/2
2300HZ
Fast 4+2
2300HZ
Fast 4+2
2300HZ
P/N 315-699464-10
2
Page 3
FS-DACT EVENT CODES
SIA DCS
*
FB 2nn 1 571 4nn FU 2nn 3 571 4nn
TX 30 1 601 030 9 99
(8 or 20)
FA tuvw 1 110 xyz FH tuvw 3 110 xyz SA tuvw 1 113 xyz SH tuvw 3 113 xyz
SS tuvw 1 203 xyz SR tuvw 3 203 xyz
FT tuvw 1 373 xyz
FJ tuvw 3 373 xyz
FB tuvw 1 571 xyz
FB 298 1 571 298 8 84
FU tuvw 3 571 xyz
FU 298 3 571 298 7 74
FX tuvw 1 604 xyz
Event Type
Fire Point Alarm Fire Point Alarm Restore Waterflow Point Alarm Waterflow Point Restore General Alarm FA 298 1 110 298 0 01 Supervisory Point Active Supervisory Point Restore AC Trouble AT 0 1 301 000 8 80 AC Trouble Restore AR 0 3 301 000 7 70 Power Up/Reset RR 0 3 305 000 7 70 Fire Point Trouble Fire Point Trouble Restore Fire Trouble Restore (All Clear) FJ 9 3 373 009 7 79 Fire Point Device Bypass (Disable) Group, Zone or Panel Relay Bypass (Disable) Releasing Circuits Bypassed (Disable) SS 298 1 203 298 6 66 Releasing Circuits Unbypassed (Enable) SR 298 3 203 298 7 76 Fire Point Device Unbypass (ReEnable) Group, Zone or Panel Relay Unbypass (ReEnable) NAC Bypass (Disable) NAC Unbypass (ReEnable) System Battery Trouble YT 298 1 302 298 8 87 System Battery Trouble Restore YR 298 3 302 298 7 77 NAC Circuit nn Trouble FT 2nn 1 373 4nn NAC Circuit nn Trouble Restore FJ 2nn 3 373 4nn NAC Circuit Ground Fault FT 299 1 373 299 8 89 NAC Circuit Ground Fault Restore FJ 299 3 373 299 7 73 FDLC Ground Fault Trouble FT 299 1 373 299 8 83 FDLC Ground Fault Trouble Restore FJ 299 3 373 299 7 73 FDLC Trouble FT 30d 1 373 298 8 83 Phone Line 1 Trouble LT 1 1 351 001 8 81 Phone Line 1 Trouble Restore LR 1 3 351 001 7 71 Phone Line 2 Trouble LT 2 1 352 002 8 82 Phone Line 2 Trouble Restore LR 2 3 352 002 7 72 Dialer Data Lost RT 30 1 354 030 8 88 Fire Test (Drill) begin FI 0 1 604 000 9 90 Fire Test (Drill) end FK 0 3 604 000 9 92 Quick Test Begin FT 298 1 373 298 8 83 Quick Test Stop FJ 298 3 373 298 7 73 System Trouble qrs FT qrs 1 373 qrs System Trouble qrs Restore FJ qrs 3 373 qrs Auto Test – System Normal RP 30 1 602 030 9 93 Manual Test – System Normal*** Point Active in Quick Test
***
Note: Below Panel Firmware revision 6.3, this code is always pair ed with the Auto Test Code (RP 30, etc.) during the daily automatic test.
nn denotes NAC circuit number 1-12. d denotes FDLC number.
Important: Account 1 and Account 2 must be set for the same reporting format. See the FS-250 Programming Manual, P/N 315-049403, or the FS-250C Programming Manual, P/N 315-049403C, as applicable, for details on setting the reporting format.
(Through Reset)
Ademco
Contact ID**
1400 Hz or
2300HZ
0 01 2 21 0 02 2 22
6 66 7 76
8 83 7 73
8 84
7 74
8 84 7 74
8 83 7 73
8 83 7 73
9 91
3/1
4/2
1400 Hz or
2300HZ
P/N 315-699464-10
3
Page 4
SIA DCS
*EVENT CODE IDENTIFIER DESCRIPTIONS
4 Digit Code t u v w
Device Address Loop (1-4) Address (001-252)
**EVENT CODE IDENTIFIER DESCRIPTIONS
Input Group # Address (001 – 240)
ADEMCO CONTACT ID
x y z
SIA / ADEMCO
SYSTEM TROUBLE CODES
Trouble Type q r s
Network Trouble 2 9 0 DACT General Trouble 2 9 1 DACT Account 1 2 9 2 DACT Account 2 2 9 3 General Trouble 2 9 8
FCC Requirements - Part 68
This equipment complies with Part 68 of the Federal Communication Commission (FCC) Rules and Regulations. On the bottom is a label that contains, among other information, the FCC Registration Number and Ringer Equivalence Number (REN) for this equipment. If requested, this information must be provided to the telephone company.
FCC Registration Number: ABK USA-34988-AL-E USOC telephone jack: RJ31X Ringer Equivalence Number (REN): 0.4B The REN is useful to determine the quantity of devices which may connect to the telephone line. Excessive REN’s on
the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the REN’s should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total REN’s, contact the telephone company to determine the maximum REN for the calling area.
If the FS-DACT equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify you of the discontinuance as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe it is necessary.
The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the operation of your telephone equipment. If this happens, the telephone company will provide advance notice so that you can modify your equipment as required to maintain uninterrupted service.
If you experience trouble with the FS-DACT Board for repair and/or warranty information please contact an authorized Siemens Fire Safety representative.
If the trouble is causing harm to the telephone network, the telephone company may request you disconnect to equipment from the network until the problem is solved. You should not attempt to repair this equipment yourself. This equipment contains no customer or user serviceable parts.
This device may not be used on public coin or party line services. Changes or modifications not expressly approved by Siemens Fire Safety could void your authority to operate this
equipment.
P/N 315-699464-10
4