DESCRIPTION OF THE COMPONENTS
TECHNICAL SPECIFICATIONS
Control unit power supply: 24V
Switching power pack input voltage: (90 - 132~ / 180 - 264~) 50/60 Hz
Absorption in stand by: 30 mA
Environment temperature : -20°C +50°C
Specifications of external enclosure: 305 x 225 x 125 mm - Ip55
MF1 - MF2 = Mosfet motor 2
MF3 - MF4 = Mosfet motor 1
PROG = Programming connector
RL1 - RL2 = Relay motor 2
RL3 - RL4 = Relay motor 1
F1 = Fuse 10AT
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
®
English
USER 2 - 24V DG
HYDRO
CONNECTIONS
14
CN2
15
16 17
Limit Switch closing M1
Limit Switch opening M1
Limit Switch opening M2
18 19
Limit Switch closing M2
13
Common
12
20
Electric lock
(12V 15VA max)
11 10
21
AUX
22
Light (+)
(24VL 500mA max)
98
23
(500 mA max)
CN1
76
CN3
24
25 26
M1M2
5
4
3
2
1
+
28V Battery charger
CN5
S
Positive battery
-
Negative battery charger
AUX
Flash (-)
(24VL 500mA max)
WARNING: The control unit is designed with the automatic detection of not used N.C. inputs (Photocells, Stop and Limit
switch) except the SAFETY EDGE input. The exclude inputs in self-programming can be restored in the “Check inputs”
menu without need to repeat the programming (page 37).
24V Aux
Common
Edge
Photocell 2
(250 mA max)
JUMPERS
Photocell 1
Stop
Common
Start
Antenna
Ped. START
Common
CN1
12
13
Obligatory jumper
without accessory
connection.
Flash (-)
Optional
6741183025REV 01 - 12/2015
AUX
(24VL 500mA max)
11 10
24V Aux
Common
(250 mA max)
98
Edge
Photocell 2
76
Photocell 1
5
4
Stop
Common
Ped. START
3
2
1
Start
Antenna
Common
The herein reported
functions are
available starting
from revision 43.
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
MENU
1
LANGUAGE
MENU
2
TRANSMITTERS
MENU
3
MENU
ONE SINGLE
4
MENU
5
UP
SEA
UP
SEA
UP
SEA
MOTOR
UP
SEA
LEAF
UP
SEA
REVERSE
MOTOR
UP
®
SET
OK
SEA
MENU
ITALIANO
SET
Skip this step if you do not want to program a transmitter
SET
OK
If on the display
appears the item:
SET
OK
SEA
MENU
SET
START
MENU
RECEIVER
MISSING
Choose the type of
motor with
UP or DOWN
OK
SEA
Skip this step if you are working in double leaf mode
SET
OK
SET
OKOK
With UP or DOWN choose
ON only if in single
leaf mode (Motor 1)
Choose ON with
UP or DOWN
if you want to reverse
the direction of
the motor rotation
English
PROGRAMMING
QUICK START
SEA
MENU
PRESS
BUTTON
Check if a receiver has
SET
been connceted
(see page 24)
OK
SET
Press the
button of the
TX to be
stored
To confirm and return
to main menu
OK
To confirm and return
To confirm and return
to main menu
SEA
MENU
STORED
to the main menu
SET
Menu or press
the next TX to
OK to exit
the button of
be stored
USER 2 - 24V DG
HYDRO
PROGRAMMING
BUTTONS
DOWNUP
OK
6
(See
page 27)
7
8
9
(See
page 27)
10
15
SEA
MENU
SET
LOGIC
UP
SEA
MENU
SET
PAUSE TIME
UP
SEA
MENU
SET
START IN
PAUSE
UP
SEA
MENU
SET
PROGRAM-
MING
UP
SEA
MENU
SET
TEST START
UP
SEA
MENU
SET
END
OKOK
choose
With UP or DOWN
To confirm and return
the desired logic
OKOK
With UP or DOWN
choose a delay for
To confirm and return
automatic closing
With UP or DOWN
OKOK
To confirm and return
Choose ON
OKOK
With UP or DOWN choose ON
to start times learning
The gate will execute a CLOSING-OPENING-CLOSING CYCLE
Skip this step if a TX has already been stored
OKOK
UP or DOWN Choose
OK
With
ON to start test
Press OK to return to the
display of the inputs state.
to main menu
to main menu
to main menu
the control unit returns automatically
To confirm and return to
Skip this step
if you want to work
in half-automatic
logic
At the end of the selflearning
to the main menu
main menu
UP
SEA
16
MENU
SPECIAL
MENU
SET
OK
Press OK to enter the special menu.
ALL OTHER PARAMETERS HAVE DEFAULT SETTINGS WHICH ARE USEFUL FOR THE 90% OF THE APPLICATIONS
BUT CAN BE HOWEVER SET THROUGH THE SPECIAL MENU. FOR ENTERING INTO THE SPECIAL MENU MOVE
ON ONE OF THE MENU AND PRESS THE UP AND DOWN BUTTONS AT THE SAME TIME FOR 5 S.
67411830
26
REV 01 - 12/2015
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
®
English
USER 2 - 24V DG
HYDRO
MENU FUNCTIONS TABLE USER 2 24V DG HYDRO
MENU
1 - LANGUAGE
2 - TRANSMITTERS
3 - MOTOR
SET
Italiano
English
Français
Español
Dutch
Start
Pedestrian Start
External module
Stop
Delete a transmitter
Clear memory
End
Hydraulic
Compact
HT270DC
Italian
English
French
Spanish
Olandese
Start
Pedestrian Start
External module
Stop
Delete single transmitter
Delete transmitter memory
“Transmitters” menu output
Hydraulic
Compact
Half Tank 270 DC
Description
HT390DCHalf Tank 390 DC
Default
Italiano
Start
Pedestrian
Start
Ht270DC
Set value
4 - ONE SINGLE
LEAF *
5 - REVERSE MOTOR *
6 - LOGIC
(See page 29)
7 - PAUSE TIME
8 - START IN PAUSE
9 - PROGRAMMING
(See page 28)
Hydraulic R
Off
On
Off
On
Automatic
Open-stop-close-stop-open
Open-stop-close-open
2 buttons
Safety
Dead man
Off
1 240
Off
On
Off On
Hydraulic R
Disabled
In ON activates single leaf
mode (Motor 1)
Synchronized right motor
Synchronized left motor
Automatic
Step by step type 1
Step by step type 2
Two buttons
Safety
Dead man
OFF
(semi-automatic logics)
Setting from 1s to 4min.
In pause start is not acceped
In pause start is accepted
Times learning start
Off
Off
Automatic
Off
Off
Off
10 - TEST START
15 - END
16 - SPECIAL MENU
Off On
Press OK to return to the display of the firmware version
Press OK to enter the special menu.
Start command
and to the one of inputs state.
Off
Note 1: The * indicates that the default value or the menu may change depending on the selected motor type.
6741183027
REV 01 - 12/2015
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
®
English
USER 2 - 24V DG
HYDRO
WORKING TIMES SELF LEARNING
Note1: Put a jumper on SAFETY EDGE contact if not used.
Note2: It is not necessary to put a jumper on the limit switches, photocells and Stop if they are not used.
1) Check the right operation of the accessories (photocells, buttons etc.). If necessary set the leaf delay.
2) If necessary adjust the selflearning speed.
3) Switch off power supply, release the motors and manually place the leaf on the middle of the stroke.
Restore the mechanical lock .
4) Power the control unit .
5) Choose the desired motor type; use (default HT270DC).
6) Select 9-PROGRAMMING on the display, press OK and then UP and DOWN to start the programming.
Note3: If on single leaf mode set 4-ONE SINGLE LEAF on ON.
Note4: If one or both motors start in opening, switch off power and invert the motor(s) cable starting in opening o
the function of menu
5-REVERSE MOTOR. Afterwards repeat the procedure starting from point 4.
7) Both leaves will start a CLOSE - OPEN - CLOSE cycle automatically (CLOSE M2 - CLOSE M1 - OPEN M1 OPEN M2 - CLOSE M2 - CLOSE M1). End of selflearning.
The control unit is pre-set with the default settings, to start the control unit with the DEFAULT
settings just keep pressed the UP and DOWN buttons at the same time power supplying the
control unit the display shows the message “Init”. The DEFAULT settings are shown in the
Menues table.
r use
SELFLERNING OPERATION TIME WITH POTENTIOMETER
When the potentiometer is installed, it is necessary to select “Potentiometer” in the 32-ENCODER menu. Start
programming and make sure that leaf 2 starts as first in closing. The gate will automatically execute the following cycle:
CLOSING M2 - CLOSING M1 - OPENING M1 - OPENING M2 - CLOSING M2 - CLOSING M1.
Note: For stop detection sensitivity setting refer to the special menu.
WORKING TIMES SELFLEARNING THROUGH IMPULSES (Required for SB version)
ATTENTION: This procedure is potentially dangerous and should only be performed by qualified people in
safety conditions.
When the potentiometer is installed, it is necessary to select “Potentiometer” in the 32-ENCODER menu.
1) Turn off electricity, release the motors and manually position the leaves on halfway.
Reset the mechanical lock.
2) Connect the control board to the power supply.
3) Select 9-PROGRAMMING on the display, press OK and than one of the UP or DOWN buttons.
4) At this point the gate will start the following cycle: CLOSING M2 - CLOSING M1 - OPENING M1 - OPENING M2 CLOSING M2 - CLOSING M1. During cycle, to store the respective stops, press UP or DOWN or START at every
point of stop of the leaf.
5) The self-learning is done.
6741183028REV 01 - 12/2015
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
®
English
USER 2 - 24V DG
HYDRO
FUNCTION LOGIC
AUTOMATIC LOGIC
A start impulse opens the gate. A second impluse during the opening will not be accepted.
A start impulse during closing reverses the movement.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semiautomatic.
NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
SECURITY LOGIC
A start impulse opens the gate. A second impulse during opening reverses the movement.
A start impulse during closing reverses the movement.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semiautomatic.
NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
STEP BY STEP TYPE 1 LOGIC
The start impulse follows the OPEN-STOP-CLOSE-STOP-OPEN logic.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semiautomatic.
NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
STEP BY STEP TYPE 2 LOGIC
The start impulse follows the OPEN-STOP-CLOSE -OPEN logic.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semiautomatic.
NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
DEAD MAN LOGIC
The gate opens as long as the START button of opening is pressed; releasing it the gate stops. The gate closes as long
as the button connected to the PEDESTRIAN START is pressed; releasing it the gate stops. To execute complete
opening and/or closing cycles the related pushbuttons must be constantly pressed.
2 PUSHBUTTONS LOGIC
One start opens, one pedestrian start closes. In opening the closing will not be accepted. In closing a start command
reopens, a pedestrian start command (closes) will be ignored.
6741183029REV 01 - 12/2015
Sistemi Elettronici
di Apertura Porte e Cancelli
International registered trademark n. 804888
®
English
USER 2 - 24V DG
HYDRO
SPECIAL MENU
PRESS AT THE SAME TIME FOR 5 SECONDS TO ENTER OR TO EXIT THE SPECIAL MENU
UPDOWN
SPECIAL MENU FUNCTIONS TABLE USER 2 24V DG HYDRO
For entering into the special menu move on one of the menu and press the
buttons at the same time for 5 s. For exiting the special menumove on one of the
menu and press the buttons at the same time for 5 s.