SEA USER 1 DG R1B User Manual

®
Sistemi Elettronici
di Apertura Porte e Cancelli
Italiano
English
Français
USER 1 - 24V DG R1B
Español
23024055
APPAR. ELETTRONICA 24V PER CANCELLI SCORREVOLI E BARRIERA
24V ELECTRONIC CONTROL UNIT FOR SLIDING GATES AND BARRIERS ARMOIRE ELECTRONIQUE 24V POUR PORTAILS COULISSANTS ET BARRIERES DISPOSITIVO ELECTRÓNICO 24V PARA CANCELAS CORREDIZOS Y BARRERAS
67411260
SEA S.p.A.
Zona Ind.le S. Atto - 64020 S. Nicolò a Tordino (TE)
Tel. 0861.588341 - Fax 0861.588344
www.seateam.com
e-mail: seacom@seateam.com
REV. 13 - 05/2016
English
DESCRIPTION OF THE COMPONENTS
TECHNICAL SPECIFICATIONS
Control unit power supply: 24 V~ Absorption in stand by: 30 mA Environment temperature: -20°C +50°C Specifications of external enclosure: 305 x 225 x 125 mm - Ip55
USER 1 - 24V DG R1B
RECEIVER RX
CNE
1
CN4
156 mm
CN8
POWER
ENCODER
MASTER/SLAVE
PROG
PR1
EXP
CNP
F1
FUSE
DISPLAY
RD1
CN7
BATTERY
RL1
CN6
MOTOR
CN5
LIGHT
RL2
RD3
CN3
20
CNA
RADIO MODULE
UP
1 2 3 4 5 6 7 8 9 10 11 12 13
Cn1 = Input/Output connector CN2 = Limit switch connector CN3 = JOLLY 3 connector CN4 = Master/slave connector CN5 = Courtesy light output plug CN6 = Motors connector CN7 = Batteries connector - Quick connection CN8 = Power connector CNA = RX Receiver connector CNE = Encoder connector CNP = Programming connector
DOWN
CN1
100 mm
JOLLY 3
OK
CN2
LIMIT SWITCH
1
EXP = External module connector OK = Programming button DOWN = Programming button UP = Programming button RD1 =Motors piloting Mosfet RD3 = Motors piloting Mosfet R1 = Motors command relay R2 = Motors command relay PR1 = Rectifier jumper F1 = Fuse 10 AT
JOLLY 3
POWER (CN8)
MOTOR (CN6)
English
CONNECTIONS
LIGHT (CN5)
Brown
1
USER 1 - 24V DG R1B
ENCODER (CNE)
24V (Red)
LIMIT SWITCH (CN2)
24V~
M
Max 200W
2
1
ANT COM START
Antenna
3 4
Start
Common
Max 100mA
5 6
PEDST
STOP COM PH1 PH2
Stop
Common
START Ped.
White
Green
CN1
7 8
Photocell 1
9
EDGE
Photocell 2
Safety edge
Limit switch Cl.1 (Yellow)
Limit switch Op.1 (Green)
10
11
AUX
COM 24V (FL)-
- -
+ +
Common
AUX Programmable
(24V 300 mA max)
Common (White)
12
13
Flash (-)
(Accessories)
24V 750 mA max
1
JUMPERS
WARNING: The control unit is designed with the automatic detection of not used N.C. inputs (photocells, Stop and Limit switch) except the SAFETY EDGE input. The exclude inputs in self-programming can be restored in the “Check inputs” menu without need to repeat the programming (pag.30).
CN1
2
1
ANT COM START
Antenna
Obligatory jumper without accessory connection.
Optional
3 4
Start
Common
5 6
PEDST
STOP COM PH1 PH2
Stop
START Ped.
7 8
Common
Photocell 1
9
EDGE
Photocell 2
Safety edge
10
11
AUX
COM 24V (FL)-
+ +
AUX Programmable
- -
Common
(24V 300 mA max)
12
13
Flash (-)
(Accessories)
24V 750 mA max
The herein reported functions are available starting from revision 01.00 compatible with Jolly 3.
21
English
PROGRAMMING
FAST SELF-LEARNING
DISPLAY
---
--
---
UP
DOWN
OK
USER 1 - 24V DG R1B
“Input check
menu"
1 2 3 4 5 6 7 8 9 10 11 12 13
UP DOWN
5 s 5 s
Start quick programming
You can start the quick programming by holding UP for 5 s in the “Input check menu", until the motor starts.
Fast self-learning START command by radio control
You can store the START button of the remote control while pressing DOWN for 5 s in the “Input check menu". Once the writing "Press button" appears, press the button of the transmitter, which you want to store for the START command. By pressing OK, you can exit the menu, otherwise it will be left automatically after 5 seconds.
22
English
PROGRAMMING
USER 1 - 24V DG R1B
MENU
1
LANGUAGE
MENU
2
TRANSMITTERS
MENU
3
MENU
REVERSE
5
MENU
6
(See
page 24)
UP
SEA
UP
SEA
UP
SEA
MOTOR
UP
SEA
MOTOR
UP
SEA
LOGIC
UP
SET
OK
SEA
MENU
ITALIANO
SET
Skip this step if you do not want to program a transmitter
SET
OK
If on the display
appears the item:
SET
SET
OK
SET
OK OK
SEA
MENU
START
MENU
SET
SEA
RECEIVER
MISSING
OK
SET
Choose the type of
motor with
UP or DOWN
Choose "ON" with UP or
DOWN button only if in
programming the motor starts
in opening
With UP or DOWN
choose
the desired logic
QUICK START
SEA
MENU
PRESS
BUTTON
Check if a receiver has
been connceted
(see page 20)
OKOK
SET
OK
Press the
button of the
TX to be
stored
To confirm and return
to main menu
To confirm and return
to main menu
SEA
MENU
STORED
If the motor has
magnetic limit switches,
select "Magnetic"
in the special menu:
104 - SELECT LIMIT SWITCH
Return to menu 7,
place the gate halfway
and repeat
the times programming
SET
Menu or press
the next TX to
PROGRAMMING
BUTTONS
DOWNUP
OK to exit
the button of
be stored
OK
7
8
9
(See
page 24)
10
15
SEA
MENU
SET
PAUSE TIME
UP
SEA
MENU
SET
START IN
PAUSE
UP
SEA
MENU
SET
PROGRAM-
MING
UP
SEA
MENU
SET
TEST START
UP
SEA
MENU
SET
END
OK OK
choose a delay for
With UP or DOWN
To confirm and return
automatic closing
With UP or DOWN
OK OK
To confirm and return
Choose ON
OK OK
With UP or DOWN choose ON
to start times learning
The gate will execute a CLOSING-OPENING-CLOSING CYCLE
Skip this step if a TX has already been stored
OK OK
UP or DOWN Choose
OK
With
ON to start test
Press OK to return to the
display of the inputs state.
to main menu
to main menu
At the end of the selflearning
the control unit returns automatically
To confirm and return to
Skip this step
if you wna tto work
in half-automatic
logic
to the main menu
main menu
UP
SEA
16
MENU
SPECIAL
MENU
SET
OK
Press OK to enter the special menu.
ALL OTHER PARAMETERS HAVE DEFAULT SETTINGS WHICH ARE USEFUL FOR THE 90% OF THE APPLICATIONS
BUT CAN BE HOWEVER SET THROUGH THE SPECIAL MENU. FOR ENTERING INTO THE SPECIAL MENU MOVE
ON ONE OF THE MENU AND PRESS THE UP AND DOWN BUTTONS AT THE SAME TIME FOR 5 S.
UPDOWN
23
English
USER 1 - 24V DG R1B
MENU FUNCTIONS TABLE USER1 24V DG R1B
MENU
1 - LANGUAGE
2 - TRANSMITTERS
3 - MOTOR
5 - REVERSE MOTOR
6 - LOGIC
(See page 25)
7 - PAUSE TIME
8 - START IN PAUSE
9 - PROGRAMMING
(See page 25)
10 - TEST START 15 - END
16 - SPECIAL MENU
24
SET
Italiano
English
Français
Español
Dutch
Start
Pedestrian Start
External module
Stop
Unloch
Delete a transmitter
Clear memory
End
Sliding
Saturn Fast - Saturn Super Fast
Joint Sprint 3 meters
Sprint 4 meters
Sprint 5 meters
Storm 5 meters Storm 6 meters Storm 7,5 meters Saturn
Mercury 800 VergL.5 meters VergL.4 meters VergL.3 meters Erg Maxi
Erg Verg
Reversible sliding gate Mercury Fast Mercury Fast
Saturn 1500
Off
On
Automatic
Open-stop-close-stop-open Open-stop-close-open
2 buttons
Safety
Dead man
Off
1 240
Off
On
Off On
Off On
Press OK to return to the display of the firmware version and to the one of inputs state.
Press OK to enter the special menu.
Italian English
French Spanish Olandese
Start Pedestrian Start External module
Stop
Storing of a command for unlocking an electric brake
Delete single transmitter
Delete transmitter memory
“Transmitters” menu output
Sliding/B 200/B 500
Saturn Fast - Saturn Super Fast
Joint Sprint 3 meters Sprint 4 meters Sprint 5 meters Storm 5 meters Storm 6 meters
Storm 7 and 7.5 meters
Saturn
Mercury 800
VergL.5 meters VergL.4 meters VergL.3 meters Erg Maxi Erg
Verg C500 - Puma
Saturn 1500
Synchronized right motor Synchronized left motor
Automatic
Step by step type 1 Step by step type 2 Two buttons Safety
Dead man OFF
(semi-automatic logics) Setting from 1s to 4min.
In pause start is not acceped In pause start is accepted
Times learning start
Start command
Description
Default
Italiano
Start
Pedestrian
Start
Sliding
Off
Open-stop­close-open
Off
Off
Off
Off
Set value
English
USER 1 - 24V DG R1B
WORKING TIMES SELF LEARNING
NOTE: When using a B200 motor or magnetic limit switches in general; make sure that the control unit is set on magnetic limit switch before learning. MENU 104 - SELECT LIMIT SWITCH - “Magnetic”
1) Disconnect the power supply, release the motor (Fig. 1) and put the leaves manually next to the stop in closing (Fig. 3-4).
2) Reset the mechanical lock (Fig. 2)
3) Select 9 - PROGRAMMING on the display, press OK and than one of the UP or DOWN buttons. Now the gate will automatically execute a closing, opening and reclosing cylce. Note: If the motor starts in opening, remove and re-put power supply, select on the display 5 - REVERSE MOTOR. And through the UP and DOWN button put it on ON, or if you have the JOLLY 3 programmer, activate the motor and limit switch exchange function. If the motor starts in closing and stops, remove the power supply and reverse the motor cables, then repeat the programming procedure.
4)The self-learning is done.
ATTENTION: This procedure is potentially dangerous and should only be performed by qualified personnel in safety conditions.
The control unit is pre-set with the default settings, to start the control unit with the DEFAULT settings just keep pressed the UP and DOWN buttons at the same time power supplying the control unit the display shows the message “Init”. The DEFAULT settings are shown in the Menues table.
Fig. 1
Fig. 2
Fig. 3
Fig.4
FUNCTION LOGIC
AUTOMATIC LOGIC
A start impulse opens the gate. A second impluse during the opening will not be accepted. A start impulse during closing reverses the movement.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semi-automatic. NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8- START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
SECURITY LOGIC
A start impulse opens the gate. A second impulse during opening reverses the movement. A start impulse during closing reverses the movement.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semi-automatic. NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8- START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
STEP BY STEP TYPE 1 LOGIC
The start impulse follows the OPEN-STOP-CLOSE-STOP-OPEN logic.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semi-automatic. NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8- START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
STEP BY STEP TYPE 2 LOGIC
The start impulse follows the OPEN-STOP-CLOSE -OPEN logic.
NOTE 1: To have the automatic closing it is necessary to set a pause time, otherwise all the logic will be semi-automatic. NOTE2: It is possible to choose, whether to accept or not, the start in pause, selecting in the MENU the item 8- START IN PAUSE and choosing ON or OFF. By default, the parameter is OFF.
DEAD MAN LOGIC
The gate opens as long as the START button of opening is pressed; releasing it the gate stops. The gate closes as long as the button connected to the PEDESTRIAN START is pressed; releasing it the gate stops. To execute complete opening and/or closing cycles the related pushbuttons must be constantly pressed.
2 PUSHBUTTONS LOGIC
One start opens, one pedestrian start closes. In opening the closing will not be accepted. In closing a start command reopens, a pedestrian start command (closes) will be ignored.
25
English
USER 1 - 24V DG R1B
SPECIAL MENU
PRESS AT THE SAME TIME FOR 5 SECONDS TO ENTER OR TO EXIT THE SPECIAL MENU
UPDOWN
SPECIAL MENU FUNCTIONS TABLE USER 1 24V DG R1B
For entering into the special menu move on one of the menu and press the UP and DOWN
buttons at the same time for 5 s. For exiting the special menu press END or move on one of the
menu and press the UP and DOWN buttons at the same time for 5 s.
MENU SP
17 - OPENING SPEED 1 * 18 - CLOSING SPEED 1 *
21 - OPENING SLOWDOWN SPEED 1 *
22 - CLOSING SLOWDOWN SPEED 1 *
25 - LEARNING SPEED *
28 - OPENING TORQ 1 *
29 - CLOSING TORQ 1 *
32 - ENCODER *
47 - ENCODER PAR.1 * 48 - ENCODER TOT.1 *
32 - ENCODER *
33 - OPENING SENSITIVITY MOTOR1 *
34 - CLOSING SENSITIVITY MOTOR1 *
57 - WORKING CURRENT
59 - OPENING SLOWDOWN 1 *
SET
30 100
30 100
30 100
30 100
30 100
10 100
10 100
On
xxx.
xxx.
Off
10% (Fast intervention) 99% (Slow intervention)
Off (Intervention excluded)
10% (Fast intervention) 99% (Slow intervention)
Off (Intervention excluded)
- - - - -
Off
5 100
Description
Setting from 30 to 100 Setting from 30 to 100
Setting from 30 to 100
Setting from 30 to 100
Setting from 30 to 100
Opening torq
Closing torq In ON enables the Encoder Encoder impulses during operation Encoder impulses stored in programming
In OFF disabled the Encoder Adjusts the intervention time
of the Encoder in opening Disabled
Adjusts the intervention time of the Encoder in closing
Disabled
Shows the absorbed current
by the motor during the
movement. The letter H at the
left of the current value
indicates the exceeding of the
set inversion threshold. Disabled
Setting from 5 to 100
Default
* 80
* 80
* 40
* 40
* 80
* 70
* 70
Off
Off
10
10
* 30
Set Value
60 - CLOSING SLOWDOWN 1 *
64 - ACCELERATION *
70 - OPENING POSITION RECOVERY
71 - CLOSING POSITION RECOVERY
Note: Menus 47 and 48 are only present if the encoder is ON.
26
Off
5 100
0 %
100%
0 15
0 15
Disabled Setting from 5 to 100
Acceleration ramp. Adjusts the motor start.
Retrieves the inertia of the motor in opening after Stop or reversing Retrieves the inertia of the motor in closing after Stop or reversing
* 30
* 70
6 %
6 %