Field Devices Europe
VZ22, VZ32, VZ42
FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS
Two-way valves, VZ22
Valve Close Off Pressure with Actuators (Kpa)
MZ18A, MZ18B,
DN k
VS
Part no.
MZ18L
(180 N)
15 0.16 721-0702-000 1600 600
15 0.25 721-0706-000 1600 600
15 0.40 721-0710-000 1600 600
15 0.63 721-0714-000 1600 600
15 1.00 721-0718-000 1200 180
15 1.6 721-0722-000 1200 180
20 2.5 721-0726-000 400 50*
20 4.0 721-0730-000 400 50*
*Up to 1000 kPa system pressure.
MZ10T/ MZ95 (95 N)
02
Two-way valves, VZ32
Valve Close Off Pressure with Actuators (Kpa)
DN Kvs Part no. MZ18A, MZ18B,
A AB B AB
MZ18L
(180 N)
MZ10T/ MZ95 (95 N)
15 0.25 0.16 731-0706-000 800 500
15 0.40 0.25 731-0710-000 800 500
15 0.63 0.40 731-0714-000 800 500
15 1.00 0.63 731-0718-000 250 150
15 1.6 1.00 731-0722-000 250 150
20 2.5 1.6 731-0726-000 240 -
20 4.0 2.5 731-0730-000 240 -
20 2.5 1.6 731-0727-000 100 50
20 4.0 2.5 731-0731-000 100 50
Two-way valves with bypass, VZ42
Valve Close Off Pressure with Actuators (Kpa)
DN Kvs Part no. MZ18A, MZ18B,
A AB B AB
MZ18L
(180 N)
kPa kPa
15 0.25 0.16 741-0706-000 800 500
15 0.40 0.25 741-0710-000 800 500
15 0.63 0.40 741-0714-000 800 500
15 1.00 0.63 741-0718-000 250 150
15 1.6 1.00 741-0722-000 250 150
20 2.5 1.6 741-0726-000 240 -
20 4.0 2.5 741-0730-000 240 -
MZ10T/MZ95
(95N)
Schneider Electric
003-1885-3 September 2013
© 2013 Schneider Electric. All rights rese rved.