Receipt _________________________________________________________________________________________________ 9
Hardware description ______________________________________________________________________________________ 9
Installing the card in the drive________________________________________________________________________________ 9
Connecting to the Ethernet network _____________________________________________________________________________ 10
Card RJ45 connector pinout________________________________________________________________________________ 10
Example of connection to an Ethernet network _________________________________________________________________ 10
Ethernet network connection elements________________________________________________________________________ 11
Ethernet menu _____________________________________________________________________________________________ 12
Access to Ethernet menu via graphic display terminal ____________________________________________________________ 12
Access to Ethernet menu via the integrated display terminal_______________________________________________________ 12
Ethernet menu parameters_________________________________________________________________________________ 13
List of functions to be configured ____________________________________________________________________________ 16
Configuring IP addresses __________________________________________________________________________________ 17
Reserving control ________________________________________________________________________________________ 19
Configuring IO Scanning___________________________________________________________________________________ 19
Configuring the control ____________________________________________________________________________________ 20
Configuring the fault management ___________________________________________________________________________ 23
Configuring monitored parameters ___________________________________________________________________________ 25
Signalling LEDs _________________________________________________________________________________________ 26
Available information _____________________________________________________________________________________ 27
Monitoring the control _____________________________________________________________________________________ 27
Troubleshooting communication interruptions __________________________________________________________________ 28
Troubleshooting the card __________________________________________________________________________________ 29
List of services supported__________________________________________________________________________________ 30
TCP connections ________________________________________________________________________________________ 30
Modbus TCP server _________________________________________________________________________________________ 31
Modbus TCP frames______________________________________________________________________________________ 31
Drive Modbus servers_____________________________________________________________________________________ 31
Ethernet card parameters__________________________________________________________________________________ 32
List of Modbus functions supported __________________________________________________________________________ 35
“Read Holding Registers” (3) function ________________________________________________________________________ 35
“Write Single Register” (6) function___________________________________________________________________________ 36
“Write Multiple Registers” (16 = 16#10) function ________________________________________________________________ 37
“Read/Write Multiple Registers” (23 = 16#17) function____________________________________________________________ 38
“Read Device Identification” (43 = 16#2B) function ______________________________________________________________ 39
IO Scanning service _________________________________________________________________________________________ 40
Setup using PL7 ____________________________________________________________________________________________ 70
Setup using Concept ________________________________________________________________________________________ 76
Setup using ProWORX NxT ___________________________________________________________________________________ 77
4
1. Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain
it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or
equipment damage.
WARNING
Warning indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altivar 61 (ATV61) or Altivar 71 (ATV71) drive
controller. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to
grounding of all equipment.
• Many parts of this drive controller, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use
only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive controller
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement
procedure given in the Installation Manual to verify that the DC voltage is less than 42 V. The drive LED is not an
indicator of the absence of DC bus voltage.
• Install and close all covers before applying power or starting and stopping the drive controller.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not install or operate any drive or drive accessory that appears damaged.The relays, inputs, or outputs of a damaged
drive may not operate in a normal manner, leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control
functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated
transmission delays or failures of the link.*
• Each implementation of an Altivar 71 Modbus TCP/IP Ethernet card must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
* For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for
Selection, Installation and Operation of Adjustable-Speed Drive Systems.”
6
3. Documentation structure
The following Altivar 61 and Altivar 71 technical documents are available on the web site www.us.Telemecanique.com and on the CD ROM
delivered with each drive controller.
b Installation Manual
This manual describes:
• How to assemble the drive controller
• How to connect the drive controller
b Programming Manual
This manual describes:
• The drive controller functions
• The drive controller parameters
• How to use the drive display terminal (integrated display terminal and graphic display terminal)
Installation and Programming Manuals
Drive
Family
ATV610.5–100 1760643
ATV710.5–100 1755843
Range
(hp)
75–800 1760655
75–7001755849
Installation Manual
Module No.
(atv61s_installation_manual)
(atv61e_installation_manual)
(atv71s_installation_manual)
(atv71e_installation_manual)
Programming Manual
Module No.
1760649
(atv61_programming_manual)
1755855
(atv71_programming_manual)
7
4. Introduction
4. 1. Presentation
The Ethernet card (catalog number VW3A3310d) is used to connect an Altivar 61 / 71 drive to an Ethernet network using the Modbus
TCP/IP protocol and Transparent Ready services.
The VW3A3310d card is equipped with two shielded RJ45 Ethernet connectors.
The accessories for connection to the Ethernet network must be ordered separately.
The data exchanges permit the following drive functionality:
• Configuration
• Adjustment
• Control
• Monitoring
• Diagnostics
The standard web server (English only) provides access to the following pages:
• Altivar Viewer
• Data Viewer
• Ethernet
• Security
The standard web server can be adapted or replaced by a customized server depending on the requirements of the application.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.
4. 2. Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets.
Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in parentheses.
Example: (COM-).
The parameter names displayed on the graphic display terminal are shown in parentheses.
Example: [Fallback speed].
The parameter codes displayed on the integrated 7-segment display terminal are shown in round brackets.
Example: (LFF).
Formats
Hexadecimal values are written as follows: 16#
Binary values are written as follows: 2#
8
5. Hardware setup
5. 1. Receipt
• Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damaged in transit.
CAUTION
STATIC SENSITIVE COMPONENTS
Avoid damage to the Modbus TCP/IP card by electrostatic discharge. Observe the electrostatic precautions below when handling
controller circuit boards or when testing components.
Failure to follow these instructions can result in injury or equipment damage.
Observe the following precautions for handling static-sensitive components:
• Keep static-producing material such as plastic, upholstery, and carpeting out of the immediate work area.
• Store the Modbus TCP/IP card in its electrostatic protective packaging when it is not installed in the drive controller.
• When handling the Modbus TCP/IP card, wear a conductive wrist strap connected to the card through a minimum of 1 megohm
resistance.
• Avoid touching exposed conductors and component leads with skin or clothing.
5. 2. Hardware description
LEDs
Shielded female RJ45
Ethernet connector
(Port 2)
5. 3. Installing the card in the drive
See the ATV61 or ATV71 Installation Manual.
MAC address label
on the Ethernet card
Shielded female RJ45
Ethernet connector
(Port 1)
9
6. Connecting to the Ethernet network
6. 1. Card RJ45 connector pinout
The Ethernet card is equipped with a shielded RJ45 connector. The shielding is connected to the drive ground.
Use STP (shielded twisted pair) Ethernet cable.
PinSignal
1TD+
2TD-
3RD+
4
5
6RD-
8........................1
The transmission speed is detected automatically by the card (10 Mbps or 100 Mbps).
The card can operate in half duplex or full duplex mode, whether connected to a hub or switch, regardless of the transmission speed
(10 Mbps or 100 Mbps).
The card supports the ETHERNET 2 frame format (IEEE 802-3 not supported).
6. 2. Example of connection to an Ethernet network
7
8
PLC
Daisy chain and/or star topology (1)
ATV61/71 ATV61/71 ATV61/71 ATV61/71 ATV61/71
Ethernet switch
(1)When the topology is a daisy chain, if one drive is turned off, the other drive(s) stop in response to a communication network fault (CNF).
Redundancy can be added by connecting the first and last drive in the daisy chain to a hub or switch to create a loop.
10
6. Connecting to the Ethernet network
6. 3. Ethernet network connection elements
Please consult our catalog “Ethernet TCP/IP and the Web” (available on the web site www.telemecanique.com).
7. 1. Access to Ethernet menu via graphic display terminal
The [ETHERNET] submenu is used to configure and display the Ethernet card parameters and can be accessed via the
[1.9 - COMMUNICATION] menu.
If you are using the FDR (Faulty Device Replacement) function, you must also configure the device name in the [7. DISPLAY CONFIG.]
menu, [7.1 USER PARAMETERS] submenu, [DEVICE NAME] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert](EPr).
RDYNET +0.00 Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
RDYNET +0.00 Hz0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
ENT
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS/OUTPUTS CFG
Code<<>>Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
ENT
RUNNET+50.00 Hz 80A
1.9 COMMUNICATION
COM. SCANNER OUTPUT
MODBUS HMI
MODBUS NETWORK
CANopen
ETHERNET
Code<<>>Quick
7. 2. Access to Ethernet menu via the integrated display terminal
The (EtH-) submenu is used to configure and display the Ethernet card parameters. It can be accessed via the (COM-) menu.
Note: The device name required for the FDR (Faulty Device Replacement) function cannot be configured via the integrated display terminal.
Power-up
Displays the drive state
XXX
ENT
ESC
SIM-
ESC
FLt-
ESC
ESC
CON-
FCS-
ENT
ESC
EtH-
ESC
LAC-
12
7. Ethernet menu
7. 3. Ethernet menu parameters
CodeDescription
(bdr)M [Bit rate]
(PAn-)
(IPC-)
(IPC1)
(IPC2)
(IPC3)
(IPC4)
Transmission speed detected on the network by the Ethernet card
Type:Display (read-only)
Possible
values:
Default value:[0 Mbps](0M)
b [DEVICE NAME]
Device name used by FDR service. Accessible with an ATV71 from V1.2 and a ATV61 from V1.3 version.
Use the navigation selector button to increment the character (alphabetical order) and << and >> (F2 and F3) to switch
to the next or previous character respectively. Use F1 to change to ABC, abc, 123, *[-.
Type:Configuration (read and write)
Possible values:16 characters on 1 or 2 lines.
Default value:[0]
b [IP card]
M [139.160.069.241] (139)(160)(069)(241)
Ethernet card IP address
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
[0 Mbps](0M): Automatic detection of the Ethernet network speed
[10 Mbps] (10M): 10 Mbps
[100 Mbps](100M): 100 Mbps
Display (read-only)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPC1, IPC2, IPC3 and IPC4.
• If the value is [0.0.0.0](0) (0) (0) (0), the Ethernet card waits for an address from a BOOTP
or DHCP server.
Note: If you enter a value other than [0.0.0.0](0) (0) (0) (0), dynamic addressing by a BOOTP
or DHCP server is disabled.
Note: After dynamic addressing by a BOOTP or DHCP server, the value [0.0.0.0](0)(0)(0)(0)
is replaced by the address supplied.
(IPM-)
(IPM1)
(IPM2)
(IPM3)
(IPM4)
(IPG-)
(IPG1)
(IPG2)
(IPG3)
(IPG4)
b [IP Mask]
M [255.255.254.0] (255)(255)(254)(0)
Subnet mask
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPM1, IPM2, IPM3 and IPM4.
• If the value of the IP address [IP card] is [0.0.0.0](0) (0) (0) (0), the Ethernet card waits for
a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the
address supplied.
b [IP Gate]
M [0.0.0.0] (0) (0) (0) (0)
Gateway IP address
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPG1, IPG2, IPG3 and IPG4.
• If the value of the IP address [IP card] is [0.0.0.0](0) (0) (0) (0), the Ethernet card waits for
a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the
address supplied.
13
7. Ethernet menu
CodeDescription
(IPP-)
(IPP1)
(IPP2)
(IPP3)
(IPP4)
(IPF-)
(IPF1)
(IPF2)
(IPF3)
(IPF4)
(ISA)M [IO Scan.activ.]
(tOUt)M [time out]
b [IP Master]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the device that retains control
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
b [IP FDR]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the FDR server
Type:Display (read-only)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
Enable IO Scanner
Type:Configuration (read and write)
Possible
values:
Default value:[Yes](YES)
Display (read-only) if the address is supplied by a DHCP server
• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.
• If the value is [0.0.0.0](0) (0) (0) (0), writing of the control word (CMd) is accepted
by the Ethernet card regardless of which device has sent it.
• If the value is other than [0.0.0.0](0) (0) (0) (0) only the device which has the IP address
[IP Master] is authorized to write the control word (CMd).
Note: This configuration also affects the type of communication monitoring.
• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.
• If the value is [0.0.0.0](0) (0) (0) (0), there is no server.
• [No](nO): IO Scanner disabled.
• [Yes](YES): IO Scanner enabled.
Ethernet communication monitoring time out
Type:Configuration (read and write)
Possible
values:
Default value:[2.0 s](2.0)
(FdrU)M [FDR validation]
Enable FDR service
Type:Configuration (read and write)
Possible
values:
Default value:[Yes](YES)
(LCFG)M [FDR Local Config.]
Selection of local or server configuration
Type:Configuration (read and write)
Possible
values:
Default value:[No](nO)
(FdrF)M [FDR Error Mgt.]
Enable FDR file error detection
Type:Configuration (read and write)
Possible
values:
Default value:[Yes](YES)
• [0](0): Monitoring disabled.
• [0.5 s](0.5) to [60.0 s](60.0): Time out value (unit: 0.1 s).
• [No](nO): FDR service disabled.
• [Yes](YES): FDR service enabled.
• [No](nO): The drive configuration is downloaded from an FDR server.
• [Yes](YES): The drive configuration is local and saved in a FDR server.
In the event of a problem with the FDR file (missing or invalid):
• [No](nO): The Ethernet card does not trigger an [FDR fault](Fdrd).
• [Yes](YES): The Ethernet card triggers an [FDR fault](Fdrd).
14
7. Ethernet menu
CodeDescription
(FdrA)M [FDR Action]
FDR service command
Type:Command (read and write)
Possible
values:
Default value:[IDLE](IdLE)
(FdrS)M [FDR autosave]
Enable periodic saving of the FDR service
Type:Configuration (read and write)
Possible
values:
Default value:[No](nO)
(Fdrt)M [FDR t.autosave]
Interval for periodic saving of the FDR service
Type:Configuration (read and write)
Possible
values:
Default value:[10] (10)
(FdrE)M [FDR state]
• [IDLE](IdLE):No command.
• [SAVE](SAUE): Command: save.
• [REST](rESt): Command: download.
• [DEL](dEL): Command: delete.
The command remains displayed during the action then reverts to the value [IDLE](IdLE).
• [No](nO): Automatic saving disabled.
• [Yes](YES): Automatic saving enabled.
• [2](2) to[9999](9999): 2 min to 9999 min.
FDR service state
Type:Display (read-only)
Possible
values:
Default value:[IDLE](IdLE)
(Fdrd)M [FDR Error Code]
FDR service status code
Type:Display (read-only)
Possible
values:
Default value:[0](0)
• [IDLE](IdLE): “Idle”.
• [INIT](INIt): Initialization.
• [CONF](CONF): Configuration.
• [RDY](rdY): Ready.
• [GET](GEt): Download the current configuration.
• [SET](SEt): Save the current configuration.
• [APP](APP): Write the FDR server configuration to the drive.
• [OPE](OPE): Operational.
• [UCFG](UCFG): Not configured.
• [0](0): No communication interruption
• [2](2): The FDR configuration file is not compatible with the drive type
(example: the drive is not the same rating as that defined in the FDR file).
• [3](3): Error reading the FDR configuration file on the server.
• [4](4): Error writing the FDR configuration file to the server.
• [7](7): Time-out for receipt of the FDR configuration file from the server.
• [9](9): Duplication of IP address.
• [12](12): The FDR configuration file is missing.
15
8. Configuration
8. 1. List of functions to be configured
The table below gives the list of configuration functions and how they can be accessed:
Functions
Entering the IP addressesppp
FDR
(Faulty Device Replacement)
IO Scanning
Reserving control (IP master)pppp
Communication monitoringpppp
Security of access
to the standard web server
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section.
Configuration using the standard web server is explained in the “Standard web server” section.
For configuration using the PowerSuite software workshop, refer to the PowerSuite online help.
Notes:
• The Ethernet card saves its configuration (IP address, mask, gateway, etc.) to the EEPROM each time the configuration is modified.
• For performance reasons, Schneider Electric recommends using the Ethernet IO Scanner, not the drive communication scanner.
• Configuration must be performed with the motor stopped.
Entering the device namepp
Configuration (time delay, etc.)pppp
Commands (save, etc.)pp p
Enable IO Scannerpppp
Configuring the IO Scanner variablespp
Changing the “username”p
Changing the “HTTP password”p
Changing the “Write password”pp
Graphic
display
terminal
Integrated
display
terminal
PowerSuite
software
workshop
Standard
web
server
16
8. Configuration
8. 2. Configuring IP addresses
b Assigning IP addresses
The drive needs 3 IP addresses:
• The drive IP address.
• The subnet mask.
• The gateway IP address (not always required).
®
Note: Some controllers, such as Prosoft
address must be set in menu 1.9 of the drive, as well as in the software for the master device.
These IP addresses can be entered:
• Using the integrated display terminal.
• Using the graphic display terminal.
• Using the PowerSuite software workshop.
They can be provided by:
• A BOOTP server (correspondence between the MAC address and the IP addresses).
• A DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).
If an IP address other than 0.0.0.0 has been entered using the display terminal or the PowerSuite software workshop, assignment using
a server is disabled.
The BOOTP service is enabled:
• When no IP address other than 0.0.0.0 has been entered and
• The FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).
and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This
The DHCP service is enabled:
• When no IP address other than 0.0.0.0 has been entered and
• The FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).
Power-up
Initialization
No address has been entered
[IP card] = 0.0.0.0
Dynamic
addressing
[FDR validation] = [Yes]
FDR
An address has been entered
[IP card] <> 0.0.0.0
[FDR validation] = [No]
[DEVICE NAME] blank
[DEVICE NAME] has been
entered
Static
addressing
BOOTP
DHCP
17
8. Configuration
b Entering IP addresses in the terminal
In the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu, enter the following IP addresses:
Note: Some controllers, such as Prosoft
address must be set in menu 1.9 of the drive, as well as in the software for the master device.
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the IP addresses are not
taken into account.
Note: Before entry begins, the IP address displayed is the active IP address.
If this address is modified, the new IP address entered is displayed. This IP address will be effective the next time the drive is turned on.
b Configuring BOOTP
The BOOTP service is used to assign IP addresses from the MAC address. The MAC address consisting of 6 octets (00-80-F4-80-xx-yy)
must be entered in the BOOTP server. The MAC address appears on the label attached to the Ethernet card.
In the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu:
• Leave the IP address [IP card](IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0](0) (0) (0) (0).
• Do not enable the FDR service: [FDR validation](FdrU) = [No](nO).
b Configuring FDR
The FDR service (based on DHCP) is used to assign the IP addresses and other parameters from the device name that must be entered
in the drive and in the FDR server (DHCP).
®
and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This
In the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu:
• Leave the IP address [IP card](IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0](0) (0) (0) (0).
• Enable the FDR service: [FDR validation](FdrU) = [Yes](YES).
For the FDR function, select the drive configuration as either:
• Local: [FDR Local Config.](LCFG) = [Yes](YES).
• Downloaded. In this case, it is essential to consult the “FDR Service” section.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert](EPr).
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
Note: The FDR function cannot be fully configured using the integrated display terminal as it does not provide access to the device name.
18
8. Configuration
8. 3. Reserving control
It is strongly recommended that control should be reserved for a single master device.
If control were not to be reserved for a master device (for example a PLC):
• Any other Modbus TCP Ethernet client could send unwanted commands.
• Other clients could use the 8 available TCP connections and prevent the master from having control.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that a valid address for the IP master device has been specified.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Use the [IP Master] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified
using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended operation.
To configure this reservation, enter an IP address other than [0.0.0.0](0) (0) (0) (0) in the [1.9 COMMUNICATION](COM-) menu,
[ETHERNET](EtH-) submenu, [IP Master] submenu.
• If control has been reserved:
Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging.
2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections
(8 maximum) and the control master no longer being able to access the drive Modbus TCP server.
Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint).
When control has been reserved and another device attempts to write the control word (CMd):
- via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.
- via Modbus TCP messaging: Control is denied.
• If control has not been reserved ([IP Master] = [0.0.0.0](0) (0) (0) (0)), control can come from any IP address.
8. 4. Configuring IO Scanning
Refer to the “IO Scanning Service” section.
The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET] (EtH-)
submenu via parameter [IO Scan.activ.](IOSA).
It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).
To configure IO Scanning, use the standard web server or the PowerSuite software workshop.
19
8. Configuration
8. 5. Configuring the control
Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters
Manual.
The following configurations are just some of the possibilities available.
b Control via Ethernet in I/O profile
The command and setpoint come from Ethernet.
The command is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Setpoint 1 configurationNetwork card The setpoint comes from Ethernet.
Command 1 configurationNetwork card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Ethernet or the terminals in I/O profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet
and the terminals.
The command is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Setpoint 1 configurationNetwork cardSetpoint 1 comes from Ethernet.
Setpoint 1B configurationAnalog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from Ethernet.
Command 2 configurationTerminalsCommand 2 comes from the terminals.
Command switchingInput LI5Input LI5 switches the command.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Ethernet in CiA402 (Drivecom) profile
The command and setpoint come from Ethernet.
The command is in CiA402 profile.
Note: The term Drivecom has been in use since 1991. Recently, the term has changed to DSP402, and currently is CiA402. This profile
requires a specific sequence of commands to control the drive. The profile is a standard that is available for use by many brands and
products to facilitate interchangeability of similar products from different manufacturers. Refer to the Communications Parameters and
Programming guides for additional details.
Configure the following parameters:
ParameterValueComment
ProfileNot separateThe run commands are in CiA402 profile, the command and the setpoint come
Setpoint 1 configurationNetwork cardThe command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Ethernet or the terminals in CiA402 profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet
and the terminals.
The command is in CiA402 profile.
from the same channel.
Configure the following parameters:
ParameterValueComment
ProfileNot separateThe run commands are in CiA402 profile, the command and the setpoint
Setpoint 1 configurationNetwork cardSetpoint 1 comes from Ethernet.
Setpoint 2 configurationAnalog input 1 on the terminalsSetpoint 2 comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Note: Setpoint 2 is directly connected to the drive setpoint limit. If switching is performed, the functions that affect the setpoint (summing,
PID, etc.) are disabled.
Configuration via the graphic display terminal or the integrated display terminal:
b Command in CiA402 (Drivecom) profile via Ethernet and setpoint switching at the terminals
The command comes from Ethernet.
The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet
and the terminals.
The command is in CiA402 profile.
Configure the following parameters:
ParameterValueComment
ProfileSeparateThe run commands are in CiA402 profile, the command and the setpoint
Setpoint 1 configurationNetwork cardSetpoint 1 comes from Ethernet.
Setpoint 1B configurationAnalog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from Ethernet.
Command switchingChannel 1Channel 1 is the command channel.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
8. 6. Configuring communication interruption management
b Communication monitoring
The Ethernet card can detect 2 types of communication interruptions:
- Network management (server missing, duplication of IP address, etc.).
- Communication (time out on the master traffic, etc.).
The associated information is:
Ethernet interruption type
Network managementCommunication
Associated drive parameterCode:
Configuring the communication
interruption or file error detection
settings
Configuring the drive’s
response
[External fault com.](EPF2)
Parameter:
[FDR Error Mgt.](FdrF)
Menu:
[1.9 COMMUNICATION](COM-)
Submenu:
[ETHERNET](EtH-)
Parameter:
[External fault mgt](EPL)
Menu:
[1.8 FAULT MANAGEMENT](FLt-)
Submenu:
[EXTERNAL FAULT](EtF-)
b Network management
The IP address duplication management detection cannot be configured.
Code:
[Com. network](CnF)
Parameter:
[time Out](tOUt)
Menu:
[1.9 COMMUNICATION](COM-)
Submenu:
[ETHERNET](EtH-)
Parameter:
[COM. fault mgt](CLL)
Menu:
[1.8 FAULT MANAGEMENT](FLt-)
Submenu:
[COM. FAULT MANAGEMENT](CLL-)
If the FDR (Faulty Device Replacement) service has been configured, the FDR communication interruption detection can be disabled via
the [FDR Error Mgt.](FdrF) parameter, which can be accessed via the [1.9 COMMUNICATION](COM-) menu, [ETHERNET](EtH-)
submenu.
In factory settings mode, a network management interruption will trigger a resettable drive stop condition [External fault com.](EPF2) and
initiate a freewheel stop.
b Communication
It is strongly recommended that control should be reserved for a single master device.
Monitoring begins when the first control word is received.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that a valid address for the IP master device has been specified.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Use the [IP MASTER](IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified
using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended equipment
operation.
• If control has been reserved:
A communication interruption is triggered if the Ethernet card does not receive a Modbus TCP request within a predefined period
of time (time out).
Any type of Modbus request from the master device [IP Master] is taken into account (write operation, read operation, etc.).
• If control has not been reserved:
A communication interruption is triggered if the Ethernet card does not receive a control word write request (CMd) within a predefined
period of time (time out).
Receipt of the command (CMd) is taken into account regardless of the sender’s IP address.
The “time out” can be set to between 0.5 and 60 s via the graphic display terminal or integrated display terminal in the
[1.9 COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu via the [time Out](tOUt) parameter. The default value is 2 s.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication interruption will trigger a resettable stop
condition [Com. network](CnF) and initiate a freewheel stop.
23
8. Configuration
b Drive response
The drive response to an Ethernet communication interruption can be configured via the graphic display terminal or the integrated display
terminal from the [1.8 FAULT MANAGEMENT](FLt-) menu:
RDYNET+0.00Hz0A
For communication faults
in the [COM. FAULT MANAGEMENT](CLL-) submenu
via parameter [COM. fault mgt](CLL)
For network management faults
in the [EXTERNAL FAULT](EtF-) submenu
via the [External fault mgt](EPL) parameter
Network fault mgt:Freewheel
CANopen fault mgt:Freewheel
Modbus fault mgt:Freewheel
External fault mgt:Freewheel
COM. FAULT MANAGEMENT
CodeQuick
RDYNET+0.00Hz0A
EXTERNAL FAULT
CodeQuick
The values of parameters: [COM. fault mgt](CLL) that will trigger a stop response from the drive [Com. network](CnF)
and [External fault mgt](EPL) that will trigger a stop response from the drive [External fault com.](EPF2) are:
[Freewheel](YES): Freewheel stop (factory setting).
[Ramp stop](rMP): Stop on ramp.
[Fast stop](FSt): Fast stop.
[DC injection](dCI): DC injection stop.
The values of parameters [COM. fault mgt](CLL) and [External fault management](EPL) which will not trigger a stop response from the
drive are:
[Ignore](nO): Communication interruption detection is disabled.
[Per STT](Stt): Stop according to configuration of [Stop type] (Stt).
[fallback spd](LFF): Change to fallback speed, maintained as long as the communication interruption persists and the run command has
not been removed.
[Spd maint.]
and the run command has not been removed.
The fallback speed can be configured in the [1.8 - FAULT MANAGEMENT](FLt-) menu via the [Fallback speed](LLF) parameter.
(rLS): The drive maintains the speed at the time the communication interruption occurred, as long as the interruption persists
24
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.