Schneider Electric VW3A3310d User Manual

Altivar® 61 / 71
User's manual 30072-452-37
Retain for future use
Modbus® TCP/IP Daisy Chain Ethernet Card
VW3A3310d
Table of contents
Important Information _________________________________________________________________________________________ 5
Before you begin_____________________________________________________________________________________________ 6
Documentation structure_______________________________________________________________________________________ 7
Introduction_________________________________________________________________________________________________ 8
Presentation _____________________________________________________________________________________________ 8 Notation ________________________________________________________________________________________________ 8
Hardware setup _____________________________________________________________________________________________ 9
Receipt _________________________________________________________________________________________________ 9 Hardware description ______________________________________________________________________________________ 9 Installing the card in the drive________________________________________________________________________________ 9
Connecting to the Ethernet network _____________________________________________________________________________ 10
Card RJ45 connector pinout________________________________________________________________________________ 10 Example of connection to an Ethernet network _________________________________________________________________ 10 Ethernet network connection elements________________________________________________________________________ 11
Ethernet menu _____________________________________________________________________________________________ 12
Access to Ethernet menu via graphic display terminal ____________________________________________________________ 12 Access to Ethernet menu via the integrated display terminal_______________________________________________________ 12 Ethernet menu parameters_________________________________________________________________________________ 13
Configuration ______________________________________________________________________________________________ 16
List of functions to be configured ____________________________________________________________________________ 16 Configuring IP addresses __________________________________________________________________________________ 17 Reserving control ________________________________________________________________________________________ 19 Configuring IO Scanning___________________________________________________________________________________ 19 Configuring the control ____________________________________________________________________________________ 20 Configuring the fault management ___________________________________________________________________________ 23 Configuring monitored parameters ___________________________________________________________________________ 25
Diagnostics ________________________________________________________________________________________________ 26
Signalling LEDs _________________________________________________________________________________________ 26 Available information _____________________________________________________________________________________ 27 Monitoring the control _____________________________________________________________________________________ 27 Troubleshooting communication interruptions __________________________________________________________________ 28 Troubleshooting the card __________________________________________________________________________________ 29
Software setup _____________________________________________________________________________________________ 30
List of services supported__________________________________________________________________________________ 30 TCP connections ________________________________________________________________________________________ 30
Modbus TCP server _________________________________________________________________________________________ 31
Modbus TCP frames______________________________________________________________________________________ 31 Drive Modbus servers_____________________________________________________________________________________ 31 Ethernet card parameters__________________________________________________________________________________ 32 List of Modbus functions supported __________________________________________________________________________ 35 “Read Holding Registers” (3) function ________________________________________________________________________ 35 “Write Single Register” (6) function___________________________________________________________________________ 36 “Write Multiple Registers” (16 = 16#10) function ________________________________________________________________ 37 “Read/Write Multiple Registers” (23 = 16#17) function____________________________________________________________ 38 “Read Device Identification” (43 = 16#2B) function ______________________________________________________________ 39
IO Scanning service _________________________________________________________________________________________ 40
Presentation ____________________________________________________________________________________________ 40 Periodic variables ________________________________________________________________________________________ 40 Address table ___________________________________________________________________________________________ 41
FDR service _______________________________________________________________________________________________ 42
Presentation ____________________________________________________________________________________________ 42 Local configuration _______________________________________________________________________________________ 43 Downloaded configuration _________________________________________________________________________________ 44 Periodic saving __________________________________________________________________________________________ 46 Other commands ________________________________________________________________________________________ 46 Configuration file_________________________________________________________________________________________ 46
3
Table of contents
Standard Web server ________________________________________________________________________________________ 47
Web server functions _____________________________________________________________________________________ 47 Applets ________________________________________________________________________________________________ 48 Access to the Web server__________________________________________________________________________________ 49 Web server user interface__________________________________________________________________________________ 50 “Home” menu ___________________________________________________________________________________________ 50 “Monitoring” menu________________________________________________________________________________________ 50 “Altivar Viewer” page _____________________________________________________________________________________ 51 “Data Viewer” page_______________________________________________________________________________________ 52 “Altivar Chart” page_______________________________________________________________________________________ 53 “Diagnostics” menu_______________________________________________________________________________________ 53 “Ethernet Statistics” page __________________________________________________________________________________ 54 “Setup” menu ___________________________________________________________________________________________ 54 “HTTP password” and “Data write password pages” _____________________________________________________________ 55 “FDR Agent” page________________________________________________________________________________________ 56 “IO Scanner” page _______________________________________________________________________________________ 58 "E-mail" page ___________________________________________________________________________________________ 61 “Documentation” menu ____________________________________________________________________________________ 62
FTP server ________________________________________________________________________________________________ 63
Downloading from the Web server ______________________________________________________________________________ 65
SNMP agent _______________________________________________________________________________________________ 68
Setup using PL7 ____________________________________________________________________________________________ 70
Setup using Concept ________________________________________________________________________________________ 76
Setup using ProWORX NxT ___________________________________________________________________________________ 77
4
1. Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.
WARNING
Warning indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
PLEASE NOTE:
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2008 Schneider Electric. All Rights Reserved.
5
2. Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altivar 61 (ATV61) or Altivar 71 (ATV71) drive controller. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment.
• Many parts of this drive controller, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
• Before servicing the drive controller
- Disconnect all power, including external control power that may be present.
- Place a “DO NOT TURN ON” label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement
procedure given in the Installation Manual to verify that the DC voltage is less than 42 V. The drive LED is not an indicator of the absence of DC bus voltage.
• Install and close all covers before applying power or starting and stopping the drive controller.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not install or operate any drive or drive accessory that appears damaged.The relays, inputs, or outputs of a damaged drive may not operate in a normal manner, leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.*
• Each implementation of an Altivar 71 Modbus TCP/IP Ethernet card must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
* For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.”
6
3. Documentation structure
The following Altivar 61 and Altivar 71 technical documents are available on the web site www.us.Telemecanique.com and on the CD ROM delivered with each drive controller.
b Installation Manual
This manual describes:
• How to assemble the drive controller
• How to connect the drive controller
b Programming Manual
This manual describes:
• The drive controller functions
• The drive controller parameters
• How to use the drive display terminal (integrated display terminal and graphic display terminal)
Installation and Programming Manuals
Drive Family
ATV61 0.5–100 1760643
ATV71 0.5–100 1755843
Range (hp)
75–800 1760655
75–700 1755849
Installation Manual Module No.
(atv61s_installation_manual)
(atv61e_installation_manual)
(atv71s_installation_manual)
(atv71e_installation_manual)
Programming Manual Module No.
1760649 (atv61_programming_manual)
1755855 (atv71_programming_manual)
7
4. Introduction
4. 1. Presentation
The Ethernet card (catalog number VW3A3310d) is used to connect an Altivar 61 / 71 drive to an Ethernet network using the Modbus TCP/IP protocol and Transparent Ready services.
The VW3A3310d card is equipped with two shielded RJ45 Ethernet connectors.
The accessories for connection to the Ethernet network must be ordered separately.
The data exchanges permit the following drive functionality:
• Configuration
• Adjustment
• Control
• Monitoring
• Diagnostics
The standard web server (English only) provides access to the following pages:
• Altivar Viewer
• Data Viewer
• Ethernet
• Security
The standard web server can be adapted or replaced by a customized server depending on the requirements of the application.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.
4. 2. Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets. Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in parentheses. Example: (COM-).
The parameter names displayed on the graphic display terminal are shown in parentheses. Example: [Fallback speed].
The parameter codes displayed on the integrated 7-segment display terminal are shown in round brackets. Example: (LFF).
Formats
Hexadecimal values are written as follows: 16# Binary values are written as follows: 2#
8
5. Hardware setup
5. 1. Receipt
• Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damaged in transit.
CAUTION
STATIC SENSITIVE COMPONENTS
Avoid damage to the Modbus TCP/IP card by electrostatic discharge. Observe the electrostatic precautions below when handling controller circuit boards or when testing components.
Failure to follow these instructions can result in injury or equipment damage.
Observe the following precautions for handling static-sensitive components:
• Keep static-producing material such as plastic, upholstery, and carpeting out of the immediate work area.
• Store the Modbus TCP/IP card in its electrostatic protective packaging when it is not installed in the drive controller.
• When handling the Modbus TCP/IP card, wear a conductive wrist strap connected to the card through a minimum of 1 megohm resistance.
• Avoid touching exposed conductors and component leads with skin or clothing.
5. 2. Hardware description
LEDs
Shielded female RJ45 Ethernet connector (Port 2)
5. 3. Installing the card in the drive
See the ATV61 or ATV71 Installation Manual.
MAC address label
on the Ethernet card
Shielded female RJ45 Ethernet connector (Port 1)
9
6. Connecting to the Ethernet network
6. 1. Card RJ45 connector pinout
The Ethernet card is equipped with a shielded RJ45 connector. The shielding is connected to the drive ground. Use STP (shielded twisted pair) Ethernet cable.
Pin Signal
1TD+
2TD-
3 RD+
4
5
6 RD-
8........................1
The transmission speed is detected automatically by the card (10 Mbps or 100 Mbps).
The card can operate in half duplex or full duplex mode, whether connected to a hub or switch, regardless of the transmission speed (10 Mbps or 100 Mbps).
The card supports the ETHERNET 2 frame format (IEEE 802-3 not supported).
6. 2. Example of connection to an Ethernet network
7
8
PLC
Daisy chain and/or star topology (1)
ATV61/71 ATV61/71 ATV61/71 ATV61/71 ATV61/71
Ethernet switch
(1)When the topology is a daisy chain, if one drive is turned off, the other drive(s) stop in response to a communication network fault (CNF).
Redundancy can be added by connecting the first and last drive in the daisy chain to a hub or switch to create a loop.
10
6. Connecting to the Ethernet network
6. 3. Ethernet network connection elements
Please consult our catalog “Ethernet TCP/IP and the Web” (available on the web site www.telemecanique.com).
Connecting cables
Description Use Length Catalog number
From To m
Straight shielded twisted pair cables
2 RJ45 connectors
Hubs and switches
Description Characteristics Catalog number
Hubs 4 × 10BASE-T ports 499 NEH 104 10
Switches 5 × 10BASE-T/100BASE-TX ports
ATV71 (+ VW3A3310d card)
4 × 100BASE-TX ports 499 NEH 141 10
3 × 10BASE-T ports 2 × 10BASE-FL ports, multimode fiber, ST (BFOC) connectors
Unmanaged basic
4 × 10BASE-T/100BASE-TX ports 1 × 100BASE-FX port, multimode fiber, SC connectors Unmanaged
3 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, multimode fiber, SC connectors Unmanaged
4 × 10BASE-T/100BASE-TX ports 1 × 100BASE-FX port, monomode fiber, SC connectors Unmanaged
3 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, monomode fiber, SC connectors Unmanaged
8 × 10BASE-T/100BASE-TX ports Unmanaged
7 × 10BASE-T/100BASE-TX ports Managed
5 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, multimode fiber, SC connectors Managed
5 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, monomode fiber, SC connectors Managed
Hubs 499 N
pH 1pp 10
Switches
pS 171 00
499 N
2 490 NTW 000 02
5 490 NTW 000 05
12 490 NTW 000 12
40 490 NTW 000 40
80 490 NTW 000 80
499 NOH 105 10
499 NES 251 00
499 NMS 251 01
499 NMS 251 02
499 NSS 251 01
499 NSS 251 02
499 NES 181 00
499 NES 271 00
499 NOS 271 00
499 NSS 271 00
11
7. Ethernet menu
7. 1. Access to Ethernet menu via graphic display terminal
The [ETHERNET] submenu is used to configure and display the Ethernet card parameters and can be accessed via the
[1.9 - COMMUNICATION] menu.
If you are using the FDR (Faulty Device Replacement) function, you must also configure the device name in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu, [DEVICE NAME] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
RDY NET +0.00 Hz 0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
RDY NET +0.00 Hz 0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
Code Quick
ENT
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS/OUTPUTS CFG
Code << >> Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
ENT
RUN NET +50.00 Hz 80A
1.9 COMMUNICATION
COM. SCANNER OUTPUT
MODBUS HMI
MODBUS NETWORK
CANopen
ETHERNET
Code << >> Quick
7. 2. Access to Ethernet menu via the integrated display terminal
The (EtH-) submenu is used to configure and display the Ethernet card parameters. It can be accessed via the (COM-) menu.
Note: The device name required for the FDR (Faulty Device Replacement) function cannot be configured via the integrated display terminal.
Power-up
Displays the drive state
XXX
ENT
ESC
SIM-
ESC
FLt-
ESC
ESC
CON-
FCS-
ENT
ESC
EtH-
ESC
LAC-
12
7. Ethernet menu
7. 3. Ethernet menu parameters
Code Description
(bdr) M [Bit rate]
(PAn-)
(IPC-)
(IPC1) (IPC2) (IPC3) (IPC4)
Transmission speed detected on the network by the Ethernet card
Type: Display (read-only)
Possible values:
Default value: [0 Mbps] (0M)
b [DEVICE NAME]
Device name used by FDR service. Accessible with an ATV71 from V1.2 and a ATV61 from V1.3 version. Use the navigation selector button to increment the character (alphabetical order) and << and >> (F2 and F3) to switch to the next or previous character respectively. Use F1 to change to ABC, abc, 123, *[-.
Type: Configuration (read and write)
Possible values: 16 characters on 1 or 2 lines.
Default value: [0]
b [IP card]
M [139.160.069.241] (139) (160) (069) (241)
Ethernet card IP address
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
[0 Mbps] (0M): Automatic detection of the Ethernet network speed [10 Mbps] (10M): 10 Mbps [100 Mbps] (100M): 100 Mbps
Display (read-only)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPC1, IPC2, IPC3 and IPC4.
• If the value is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for an address from a BOOTP or DHCP server.
Note: If you enter a value other than [0.0.0.0] (0) (0) (0) (0), dynamic addressing by a BOOTP or DHCP server is disabled. Note: After dynamic addressing by a BOOTP or DHCP server, the value [0.0.0.0] (0)(0)(0)(0) is replaced by the address supplied.
(IPM-)
(IPM1) (IPM2) (IPM3) (IPM4)
(IPG-)
(IPG1) (IPG2) (IPG3) (IPG4)
b [IP Mask]
M [255.255.254.0] (255) (255) (254) (0)
Subnet mask
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPM1, IPM2, IPM3 and IPM4.
• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the address supplied.
b [IP Gate]
M [0.0.0.0] (0) (0) (0) (0)
Gateway IP address
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPG1, IPG2, IPG3 and IPG4.
• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the address supplied.
13
7. Ethernet menu
Code Description
(IPP-)
(IPP1) (IPP2) (IPP3) (IPP4)
(IPF-)
(IPF1) (IPF2) (IPF3) (IPF4)
(ISA) M [IO Scan.activ.]
(tOUt) M [time out]
b [IP Master]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the device that retains control
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
b [IP FDR]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the FDR server
Type: Display (read-only)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
Enable IO Scanner
Type: Configuration (read and write)
Possible values:
Default value: [Yes] (YES)
Display (read-only) if the address is supplied by a DHCP server
• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.
• If the value is [0.0.0.0] (0) (0) (0) (0), writing of the control word (CMd) is accepted by the Ethernet card regardless of which device has sent it.
• If the value is other than [0.0.0.0] (0) (0) (0) (0) only the device which has the IP address
[IP Master] is authorized to write the control word (CMd).
Note: This configuration also affects the type of communication monitoring.
• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.
• If the value is [0.0.0.0] (0) (0) (0) (0), there is no server.
[No] (nO): IO Scanner disabled.
[Yes] (YES): IO Scanner enabled.
Ethernet communication monitoring time out
Type: Configuration (read and write)
Possible values:
Default value: [2.0 s] (2.0)
(FdrU) M [FDR validation]
Enable FDR service
Type: Configuration (read and write)
Possible values:
Default value: [Yes] (YES)
(LCFG) M [FDR Local Config.]
Selection of local or server configuration
Type: Configuration (read and write)
Possible values:
Default value: [No] (nO)
(FdrF) M [FDR Error Mgt.]
Enable FDR file error detection
Type: Configuration (read and write)
Possible values:
Default value: [Yes] (YES)
[0] (0): Monitoring disabled.
[0.5 s] (0.5) to [60.0 s] (60.0): Time out value (unit: 0.1 s).
[No] (nO): FDR service disabled.
[Yes] (YES): FDR service enabled.
[No] (nO): The drive configuration is downloaded from an FDR server.
[Yes] (YES): The drive configuration is local and saved in a FDR server.
In the event of a problem with the FDR file (missing or invalid):
[No] (nO): The Ethernet card does not trigger an [FDR fault] (Fdrd).
[Yes] (YES): The Ethernet card triggers an [FDR fault] (Fdrd).
14
7. Ethernet menu
Code Description
(FdrA) M [FDR Action]
FDR service command
Type: Command (read and write)
Possible values:
Default value: [IDLE] (IdLE)
(FdrS) M [FDR autosave]
Enable periodic saving of the FDR service
Type: Configuration (read and write)
Possible values:
Default value: [No] (nO)
(Fdrt) M [FDR t.autosave]
Interval for periodic saving of the FDR service
Type: Configuration (read and write)
Possible values:
Default value: [10] (10)
(FdrE) M [FDR state]
[IDLE] (IdLE): No command.
[SAVE] (SAUE): Command: save.
[REST] (rESt): Command: download.
[DEL] (dEL): Command: delete. The command remains displayed during the action then reverts to the value [IDLE] (IdLE).
[No] (nO): Automatic saving disabled.
[Yes] (YES): Automatic saving enabled.
[2] (2) to [9999] (9999): 2 min to 9999 min.
FDR service state
Type: Display (read-only)
Possible values:
Default value: [IDLE] (IdLE)
(Fdrd) M [FDR Error Code]
FDR service status code
Type: Display (read-only)
Possible values:
Default value: [0] (0)
[IDLE] (IdLE): “Idle”.
[INIT] (INIt): Initialization.
[CONF] (CONF): Configuration.
[RDY] (rdY): Ready.
[GET] (GEt): Download the current configuration.
[SET] (SEt): Save the current configuration.
[APP] (APP): Write the FDR server configuration to the drive.
[OPE] (OPE): Operational.
[UCFG] (UCFG): Not configured.
[0] (0): No communication interruption
[2] (2): The FDR configuration file is not compatible with the drive type (example: the drive is not the same rating as that defined in the FDR file).
[3] (3): Error reading the FDR configuration file on the server.
[4] (4): Error writing the FDR configuration file to the server.
[7] (7): Time-out for receipt of the FDR configuration file from the server.
[9] (9): Duplication of IP address.
[12] (12): The FDR configuration file is missing.
15
8. Configuration
8. 1. List of functions to be configured
The table below gives the list of configuration functions and how they can be accessed:
Functions
Entering the IP addresses ppp
FDR (Faulty Device Replacement)
IO Scanning
Reserving control (IP master) pppp Communication monitoring pppp
Security of access to the standard web server
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section.
Configuration using the standard web server is explained in the “Standard web server” section.
For configuration using the PowerSuite software workshop, refer to the PowerSuite online help.
Notes:
• The Ethernet card saves its configuration (IP address, mask, gateway, etc.) to the EEPROM each time the configuration is modified.
• For performance reasons, Schneider Electric recommends using the Ethernet IO Scanner, not the drive communication scanner.
• Configuration must be performed with the motor stopped.
Entering the device name pp Configuration (time delay, etc.) pppp Commands (save, etc.) pp p Enable IO Scanner pppp Configuring the IO Scanner variables pp
Changing the “username” p Changing the “HTTP password” p Changing the “Write password” pp
Graphic
display
terminal
Integrated
display
terminal
PowerSuite
software
workshop
Standard
web
server
16
8. Configuration
8. 2. Configuring IP addresses
b Assigning IP addresses
The drive needs 3 IP addresses:
• The drive IP address.
• The subnet mask.
• The gateway IP address (not always required).
®
Note: Some controllers, such as Prosoft address must be set in menu 1.9 of the drive, as well as in the software for the master device.
These IP addresses can be entered:
• Using the integrated display terminal.
• Using the graphic display terminal.
• Using the PowerSuite software workshop.
They can be provided by:
• A BOOTP server (correspondence between the MAC address and the IP addresses).
• A DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).
If an IP address other than 0.0.0.0 has been entered using the display terminal or the PowerSuite software workshop, assignment using a server is disabled.
The BOOTP service is enabled:
• When no IP address other than 0.0.0.0 has been entered and
• The FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).
and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This
The DHCP service is enabled:
• When no IP address other than 0.0.0.0 has been entered and
• The FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).
Power-up
Initialization
No address has been entered
[IP card] = 0.0.0.0
Dynamic
addressing
[FDR validation] = [Yes]
FDR
An address has been entered
[IP card] <> 0.0.0.0
[FDR validation] = [No]
[DEVICE NAME] blank
[DEVICE NAME] has been
entered
Static
addressing
BOOTP
DHCP
17
8. Configuration
b Entering IP addresses in the terminal
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu, enter the following IP addresses:
- [IP card] (IPC1) (IPC2) (IPC3) (IPC4).
- [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4).
- [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4) (not always required).
Note: Some controllers, such as Prosoft address must be set in menu 1.9 of the drive, as well as in the software for the master device.
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the IP addresses are not taken into account.
Note: Before entry begins, the IP address displayed is the active IP address. If this address is modified, the new IP address entered is displayed. This IP address will be effective the next time the drive is turned on.
b Configuring BOOTP
The BOOTP service is used to assign IP addresses from the MAC address. The MAC address consisting of 6 octets (00-80-F4-80-xx-yy) must be entered in the BOOTP server. The MAC address appears on the label attached to the Ethernet card.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Do not enable the FDR service: [FDR validation] (FdrU) = [No] (nO).
b Configuring FDR
The FDR service (based on DHCP) is used to assign the IP addresses and other parameters from the device name that must be entered in the drive and in the FDR server (DHCP).
®
and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES). For the FDR function, select the drive configuration as either:
• Local: [FDR Local Config.] (LCFG) = [Yes] (YES).
• Downloaded. In this case, it is essential to consult the “FDR Service” section.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu. This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr). Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken into account.
Note: The FDR function cannot be fully configured using the integrated display terminal as it does not provide access to the device name.
18
8. Configuration
8. 3. Reserving control
It is strongly recommended that control should be reserved for a single master device.
If control were not to be reserved for a master device (for example a PLC):
• Any other Modbus TCP Ethernet client could send unwanted commands.
• Other clients could use the 8 available TCP connections and prevent the master from having control.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that a valid address for the IP master device has been specified.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Use the [IP Master] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended operation.
To configure this reservation, enter an IP address other than [0.0.0.0] (0) (0) (0) (0) in the [1.9 COMMUNICATION] (COM-) menu,
[ETHERNET] (EtH-) submenu, [IP Master] submenu.
• If control has been reserved: Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging. 2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections (8 maximum) and the control master no longer being able to access the drive Modbus TCP server.
Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint). When control has been reserved and another device attempts to write the control word (CMd):
- via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.
- via Modbus TCP messaging: Control is denied.
• If control has not been reserved ([IP Master] = [0.0.0.0] (0) (0) (0) (0)), control can come from any IP address.
8. 4. Configuring IO Scanning
Refer to the “IO Scanning Service” section.
The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via parameter [IO Scan.activ.] (IOSA).
It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).
To configure IO Scanning, use the standard web server or the PowerSuite software workshop.
19
8. Configuration
8. 5. Configuring the control
Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters Manual. The following configurations are just some of the possibilities available.
b Control via Ethernet in I/O profile
The command and setpoint come from Ethernet. The command is in I/O profile.
Configure the following parameters:
Parameter Value Comment
Profile I/O profile The run command is simply obtained by bit 0 of the control word.
Setpoint 1 configuration Network card The setpoint comes from Ethernet.
Command 1 configuration Network card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [I/O profile] (IO)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Cmd channel 1] (Cd1) [Com. opt card] (nEt)
b Control via Ethernet or the terminals in I/O profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals. The command is in I/O profile.
Configure the following parameters:
Parameter Value Comment
Profile I/O profile The run command is simply obtained by bit 0 of the control word.
Setpoint 1 configuration Network card Setpoint 1 comes from Ethernet.
Setpoint 1B configuration Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
Command 1 configuration Network card Command 1 comes from Ethernet.
Command 2 configuration Terminals Command 2 comes from the terminals.
Command switching Input LI5 Input LI5 switches the command.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [I/O profile] (IO)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Cmd channel 1] (Cd1) [Com. card] (nEt)
[Cmd channel 2] (Cd2) [Terminals] (tEr)
[Cmd switching] (CCS) [LI5] (LI5)
[1.7 APPLICATION FUNCT.] (FUn-) [REFERENCE SWITCH.]
[Ref.1B channel] (Fr1b) [Ref. AI1] (AI1)
[Ref 1B switching] (rCb) [LI5] (LI5)
1B).
20
8. Configuration
b Control via Ethernet in CiA402 (Drivecom) profile
The command and setpoint come from Ethernet. The command is in CiA402 profile.
Note: The term Drivecom has been in use since 1991. Recently, the term has changed to DSP402, and currently is CiA402. This profile requires a specific sequence of commands to control the drive. The profile is a standard that is available for use by many brands and products to facilitate interchangeability of similar products from different manufacturers. Refer to the Communications Parameters and Programming guides for additional details.
Configure the following parameters:
Parameter Value Comment
Profile Not separate The run commands are in CiA402 profile, the command and the setpoint come
Setpoint 1 configuration Network card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Not separ.] (SIM) (factory setting)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
b Control via Ethernet or the terminals in CiA402 profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals. The command is in CiA402 profile.
from the same channel.
Configure the following parameters:
Parameter Value Comment
Profile Not separate The run commands are in CiA402 profile, the command and the setpoint
Setpoint 1 configuration Network card Setpoint 1 comes from Ethernet.
Setpoint 2 configuration Analog input 1 on the terminals Setpoint 2 comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
Note: Setpoint 2 is directly connected to the drive setpoint limit. If switching is performed, the functions that affect the setpoint (summing, PID, etc.) are disabled.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Not separ.] (SIM)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Ref.2 chan] (Fr2) [Ref. AI1] (AI1)
[Ref. 2 switching] (rFC) [LI5] (LI5)
come from the same channel.
2) and the command.
21
8. Configuration
b Command in CiA402 (Drivecom) profile via Ethernet and setpoint switching at the terminals
The command comes from Ethernet. The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet and the terminals. The command is in CiA402 profile.
Configure the following parameters:
Parameter Value Comment
Profile Separate The run commands are in CiA402 profile, the command and the setpoint
Setpoint 1 configuration Network card Setpoint 1 comes from Ethernet.
Setpoint 1B configuration Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
Command 1 configuration Network card Command 1 comes from Ethernet.
Command switching Channel 1 Channel 1 is the command channel.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Separate] (SEP)
[1.7 APPLICATION FUNCT.] (FUn-) [REFERENCE SWITCH.]
can come from different channels.
1B).
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Cmd channel 1] (Cd1) [Com. card] (nEt)
[Cmd switching] (CCS) [Ch1 active] (Cd1)
[Ref.1B channel] (Fr1b) [Ref. AI1] (AI1)
[Ref 1B switching] (rCb) [LI5] (LI5)
22
8. Configuration
8. 6. Configuring communication interruption management
b Communication monitoring
The Ethernet card can detect 2 types of communication interruptions:
- Network management (server missing, duplication of IP address, etc.).
- Communication (time out on the master traffic, etc.).
The associated information is:
Ethernet interruption type
Network management Communication
Associated drive parameter Code:
Configuring the communication interruption or file error detection settings
Configuring the drive’s response
[External fault com.] (EPF2)
Parameter:
[FDR Error Mgt.] (FdrF)
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[ETHERNET] (EtH-)
Parameter:
[External fault mgt] (EPL)
Menu:
[1.8 FAULT MANAGEMENT] (FLt-)
Submenu:
[EXTERNAL FAULT] (EtF-)
b Network management
The IP address duplication management detection cannot be configured.
Code:
[Com. network] (CnF)
Parameter:
[time Out] (tOUt)
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[ETHERNET] (EtH-)
Parameter:
[COM. fault mgt] (CLL)
Menu:
[1.8 FAULT MANAGEMENT] (FLt-)
Submenu:
[COM. FAULT MANAGEMENT] (CLL-)
If the FDR (Faulty Device Replacement) service has been configured, the FDR communication interruption detection can be disabled via the [FDR Error Mgt.] (FdrF) parameter, which can be accessed via the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu.
In factory settings mode, a network management interruption will trigger a resettable drive stop condition [External fault com.] (EPF2) and initiate a freewheel stop.
b Communication
It is strongly recommended that control should be reserved for a single master device. Monitoring begins when the first control word is received.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that a valid address for the IP master device has been specified.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Use the [IP MASTER] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended equipment operation.
• If control has been reserved: A communication interruption is triggered if the Ethernet card does not receive a Modbus TCP request within a predefined period of time (time out). Any type of Modbus request from the master device [IP Master] is taken into account (write operation, read operation, etc.).
• If control has not been reserved: A communication interruption is triggered if the Ethernet card does not receive a control word write request (CMd) within a predefined period of time (time out). Receipt of the command (CMd) is taken into account regardless of the sender’s IP address.
The “time out” can be set to between 0.5 and 60 s via the graphic display terminal or integrated display terminal in the
[1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via the [time Out] (tOUt) parameter. The default value is 2 s.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication interruption will trigger a resettable stop condition [Com. network] (CnF) and initiate a freewheel stop.
23
8. Configuration
b Drive response
The drive response to an Ethernet communication interruption can be configured via the graphic display terminal or the integrated display terminal from the [1.8 FAULT MANAGEMENT] (FLt-) menu:
RDY NET +0.00Hz 0A
For communication faults in the [COM. FAULT MANAGEMENT] (CLL-) submenu via parameter [COM. fault mgt] (CLL)
For network management faults in the [EXTERNAL FAULT] (EtF-) submenu via the [External fault mgt] (EPL) parameter
Network fault mgt : Freewheel
CANopen fault mgt : Freewheel
Modbus fault mgt : Freewheel
External fault mgt : Freewheel
COM. FAULT MANAGEMENT
Code Quick
RDY NET +0.00Hz 0A
EXTERNAL FAULT
Code Quick
The values of parameters: [COM. fault mgt] (CLL) that will trigger a stop response from the drive [Com. network] (CnF) and [External fault mgt] (EPL) that will trigger a stop response from the drive [External fault com.] (EPF2) are:
[Freewheel] (YES): Freewheel stop (factory setting). [Ramp stop] (rMP): Stop on ramp. [Fast stop] (FSt): Fast stop. [DC injection] (dCI): DC injection stop.
The values of parameters [COM. fault mgt] (CLL) and [External fault management] (EPL) which will not trigger a stop response from the drive are:
[Ignore] (nO): Communication interruption detection is disabled. [Per STT] (Stt): Stop according to configuration of [Stop type] (Stt). [fallback spd] (LFF): Change to fallback speed, maintained as long as the communication interruption persists and the run command has
not been removed.
[Spd maint.]
and the run command has not been removed.
The fallback speed can be configured in the [1.8 - FAULT MANAGEMENT] (FLt-) menu via the [Fallback speed] (LLF) parameter.
(rLS): The drive maintains the speed at the time the communication interruption occurred, as long as the interruption persists
24
8. Configuration
8. 7. Configuring monitored parameters
It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu on the graphic display terminal.
The selection is made via the [6 - MONITORING CONFIG.] menu, [6.3 - COM. MAP CONFIG.] submenu.
Each parameter in the range [Address 1 select.] … [Address 4 select.] is used to select the parameter logic address. Select an address of zero to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCR): logic address 3204; signed decimal format.
• Parameter 2 = Motor torque (OTR): logic address 3205; signed decimal format.
• Parameter 3 = Last fault occurred (LFT): logic address 7121; hexadecimal format.
• Disabled parameter: address 0; default format: hexadecimal format.
One of the three display formats below can be assigned to each monitored word:
Format Range Terminal display
Hexadecimal 0000 … FFFF [Hex]
Signed decimal -32,767 … 32,767 [Signed]
Unsigned decimal 0 … 65,535 [Unsigned]
RDY NET +0.00Hz 0A
6.3 COM. MAP CONFIG.
Word 1 add. select. : 3204
Format word 1 : Signed
Word 2 add. select. : 3205
Format word 2 : Signed
Word 3 add. select. : 7121
Code Quick
Format word 3 : Hex
Word 4 add. select. : 0
Format word 4 : Hex
25
9. Diagnostics
9. 1. Signalling LEDs
The VW3A3310d Ethernet card features 5 LEDs, which are visible through the Altivar 61 / 71 cover.
1.1
1.2
1.3
1.4
1.5
Port 1 activity
2.1
Port 2 activity
2.2
Link status
2.3
2.4
NS “Network status”
2.5
MS “Module status”
The first 2 LEDS are respectively dedicated to each Ethernet port. The third LED is relative to the IP level. The last 2 LEDs are specific to EtherNet/IP and CIP communication protocol.
LED Color/ state Description
2.1 Off No link
Flashing Green/yellow Power up testing.
Green ON Link at 100 Mbps.
Yellow ON Link at 10 Mbps.
Green BLINK Activity at 100 Mbps.
Yellow BLINK Activity at 10 Mbps.
2.2 Off No link
Flashing Green/yellow Power up testing.
Green ON Link at 100 Mbps.
Yellow ON Link at 10 Mbps.
Green BLINK Activity at 100 Mbps.
Yellow BLINK Activity at 10 Mbps.
2.3 Off Physical connections unplugged - No IP address obtained
Flashing Green/red Power up testing.
Green ON At least one port is connected and an IP address has been obtained.
Green flashing 3 times All ports are unplugged, but the card has an IP address.
Green flashing 4 times Error: Duplicated IP address (1)
Green flashing 5 times The card is performing a BOOTP or DHCP sequence
2.4
“NS”
2.5
“MS”
(1)The Ethernet card detects IP address duplication each time it connects to the network (power-up or connection to the network).
Off The device does not have an IP address or powered off.
Flashing Green/red Power up testing.
Green ON The device has at least one established Modbus connection (even to the Message Router).
Green flashing The device has not established Modbus connections, but has obtained an IP address.
Off No power is supplied to the device
Flashing Green/red Power Up testing.
Green ON The device is ready.
Green flashing The device is not ready (waiting for cable connection, ...).
Red flashing The device has detected a [Network fault] (CnF).
Red ON The device has detected a [internal com. link] (ILF) communication interruption.
If the card detects that another device is using the same IP address as itself, it abandons the use of the IP address and triggers the status: [External fault com.] (EPF2). If a device with an IP address identical to that of the drive is connected to the network during operation, the condition will not be detected by the drive (it is the new station that has to disconnect).
26
9. Diagnostics
9. 2. Available information
In addition to the LEDs, the table below summarizes the diagnostic information available by various means.
Functions Graphic display
Control-signal diagnostics
• Control word
• Setpoint
• Active channel
•Etc.
Communication diagnostics
• Transmission counter
• Reception counter
• Collision counter
•Etc.
terminal
p
Integrated display
terminal
PowerSuite software
workshop
Standard
web server
ppp
pp
9. 3. Monitoring the control
On the graphic display terminal only, the [1.2 - MONITORING] menu, [COMMUNICATION MAP] submenu can be used to display control signal diagnostic information between the drive and the Ethernet PLC:
Active command channel
Value of control word used
to send a command to the drive
(unit 0.1 Hz) used to control the drive
Values of the four monitored words selected by the user.
The address and display format of these parameters
can be configured in the [6 - MONITORING CONFIG.] menu,
[6.3 - COM. MAP CONFIG.] submenu
(see “Configuration” section on page 16
The value of a monitored word is equal to “-----” if:
- Monitoring has not been activated (address equal to W0)
- The parameter is protected
- The parameter is not known (e.g., W3200)
Use not recommended for Ethernet
Frequency setpoint from Ethernet
(hexadecimal format)
Active setpoint channel
Value of frequency setpoint
Value of status word
(hexadecimal format)
Communication scanner:
for performance reasons
Control word from Ethernet
[COM. card cmd.] (CMd3)
[Com. card ref.] (LFr3)
RUN NET +50.00 Hz 80A
COMMUNICATION MAP
Command Channel : Com. card
Cmd value : 000F
Channel ref. active : Com. card
Frequency ref. : 500.0
Status word : 8627
Code Quick
).
W3204 : 53
W3205 : 725
W7132 : 0000
W0 : -----
COM. SCANNER INPUT MAP
COM SCAN OUTPUT MAP
CMD. WORD IMAGE
FREQ. REF. WORD MAP
MODBUS NETWORK DIAG
MODBUS HMI DIAG
CANopen MAP
SCANNER CARD PROG.
Hex
Hz
Hex
Hex
Hex
27
9. Diagnostics
9. 4. Troubleshooting communication interruptions
b Communication monitoring
Ethernet faults are indicated by the drive display and the Module Status LED on the Ethernet card.
The Ethernet card can detect 2 types of communication interruptions:
- Network management (server missing, duplication of IP address, etc.).
- Communication (time out on the master traffic, etc.).
In factory settings mode, a network management interruption will trigger a resettable drive stop response [External fault com.] (EPF2) and initiate a freewheel stop.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication interruption will trigger a resettable drive stop response [Com. network] (CnF) and initiate a freewheel stop.
The drive’s response in the event of an Ethernet communication interruption can be changed. Refer to the Configuration section beginning on page 17.
The associated information is:
Ethernet communication interruption type
Network management Communication
Associated drive parameter Code:
Extended communication interruption code
[External fault com.] (EPF2)
[FDR fault] (Fdrd)
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[ETHERNET] (EtH-)
Code:
[Com. network] (CnF)
[Network fault] (CnF)
Menu:
[1.10 DIAGNOSTICS] (dGt-)
Submenu:
[MORE FAULT INFO] (AFI-)
Parameter [Network fault] (CnF) is used to obtain more detailed information about the origin of the last communication interruption
[Com. network] (CnF). It can be accessed on the graphic display terminal only, in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-) submenu.
Value Description of the values of the [Network fault] (CnF) parameter
0 No communication interruption
1 Modbus TCP time out
10 Network overload
11 Loss of Ethernet carrier
The [FDR fault] (Fdrd) Ethernet communication interruption status is used to obtain more detailed information about the origin of the last fault [External fault com.] (EPF2). It can be accessed on the graphic display terminal only, in the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu.
Value Description of the values of the [FDR fault] (Fdrd) Ethernet communication interruption code parameter
0 No communication interruption
2 The FDR configuration file is not compatible with the drive type (example: the drive is not the correct rating).
3 Error reading the FDR configuration file on the server.
4 Error writing the FDR configuration file to the server.
7 Time-out for receipt of the FDR configuration file from the server.
9 Duplication of IP address (1).
12 FDR configuration file missing.
203 Inconsistent hardware configuration
(1)The Ethernet card detects IP address duplication each time it connects to the network (power-up or connection to the network).
If the card detects that another device is using the same IP address as itself, it abandons the use of the IP address and triggers the status: [External fault com.] (EPF2). If a device with an IP address identical to that of the drive is connected to the network during operation, the condition will not be detected by the drive (it is the new station that has to disconnect).
28
9. Diagnostics
9. 5. Troubleshooting the card
The [internal com. link] (ILF) status appears when the following conditions occur:
- Hardware becomes inoperative on the Ethernet card.
- Dialog interruption between the Ethernet card and the drive.
The drive’s response in the event of an [internal com. link] (ILF) status cannot be configured, and the drive stops with a freewheel stop. This event cannot be reset.
Two diagnostic parameters are used to obtain more detailed information about the origin of the [internal com. link] (ILF) status:
- [Internal link fault 1] (ILF1) if the interruption has occurred on option card no. 1 (installed directly on the drive).
- [Internal link fault 2] (ILF2) if the interruption has occurred on option card no. 2 (installed on option card no. 1).
The Ethernet card can be in position 1 or 2.
The [Internal link fault 1] (ILF1) and [Internal link fault 2] (ILF2) parameters can only be accessed on the graphic display terminal in the [1.10 DIAGNOSTICS] (dGt-) menu, [MORE FAULT INFO] (AFI-) submenu.
Value Description of the values of the [Internal link fault 1] (ILF1) and [Internal link fault 2] (ILF2) parameters
0 No communication interruption
1 Loss of internal communication with the drive
3 Error in the EEPROM checksum
101 Unknown card
102 Exchange problem on the drive internal bus
103 Time out on the drive internal bus (500 ms)
29
10. Software setup
10. 1. List of services supported
• Modbus TCP server, with the support of the “IO Scanning” periodic service.
• IP protocol (version 4).
• TCP and UDP protocol.
• HTTP server for configuring, adjusting and monitoring the drive.
• ICMP client for supporting certain IP services, such as the “ping” command.
• BOOTP client for assignment of an IP address by an address server.
• FTP protocol for file transfer.
• DHCP client for dynamic assignment of IP addresses by an address server.
• FDR service for replacement of a faulty device.
• SNMP protocol for network management.
• ARP protocol for detecting a competing IP address (IP address already in use).
10. 2. TCP connections
Number of simultaneous connections limited to 8 maximum (port 502).
The table below gives the number of connections consumed for each service:
Client Service Number of connections
Controller (PLC)
Web browser
Example: If the “Altivar Viewer” page is viewed in two different windows of a web browser, on the same PC, four connections are consumed. If the drive is controlled by a PLC, two connections are consumed by IO Scanning and Modbus messaging, so the total number of connections consumed is then six. Two connections are still available, since the maximum number of simultaneous connections is eight.
If control is reserved for a device ([IP Master] (IPP-) configured), 2 connections are reserved for this device, even if it is not present on the network.
If the maximum number of connections has been exceeded, any new connection attempt will be rejected by the Ethernet card.
IO Scanning 1
Modbus messaging 1
“Home” page 0
“Monitoring\Altivar Viewer” page 2
“Monitoring\Data Viewer” page 1
“Monitoring\Altivar chart” page 1
“Diagnostics\Ethernet Statistics” page 1
“Setup\Security\HTTP password” page 0
“Setup\Security\Data write password” page 0
“Setup\FDR agent” page 1
“Setup\IO Scanner” page 1
30
11. Modbus TCP server
11. 1. Modbus TCP frames
Modbus TCP frames consist of a header and a Modbus request.
Header format:
Byte Description Comments
0
Transaction identifier
1 low order
2
Protocol identifier
3 low order
4
Length of data
5 low order
6 Destination identifier (Unit ID)
7 Modbus request function code
The frame header returned by the Altivar 71 server is identical to that of the frame sent by the client.
11. 2. Drive Modbus servers
The destination identifier (Unit ID) is used to access 4 drive Modbus TCP servers:
Unit ID Modbus TCP server Accessible parameters
0 Variable speed drive See the Altivar 71 Communication parameters Manual.
251, AMOC Ethernet card See the “Ethernet card parameters” section.
252, AMOA Controller Inside card 2048 words (%MW0 to %MW2047).
255 IO Scanner See the “IO Scanner” section.
high order
high order
high order
This identifier always equals 0.
Number of bytes in the Modbus request +1. The frame length is always less than 256 bytes, the value of the significant byte therefore equals 0.
31
11. Modbus TCP server
11. 3. Ethernet card parameters
Comments:
• Parameters on 2 words are double words (low order in address word n, high order in address word n+1).
• Parameters 60 019 to 60 043 and 60 066 to 60 068 can be accessed in both read and write mode. They can be reset using a write operation.
• The current IP addresses (60006 to 60017) are the ones displayed on the terminal. The EEPROM IP addresses (60075 to 60079) are the ones used by the card.
Address Size
(in words)
60 000 6 MAC address R 00-80-F4-80-xx-yy
60 006 4 Current value of IP Address
60 010 4 Current value of Subnet mask
60 014 4 Current value of Gateway Address
60 018 1 Transmission speed
60 019 2 OK transmission counter R/W
60 021 1 Store-and-forward transmission counter R/W
60 022 1 Late collision counter R/W
60 023 1 Buffer (Tx) error counter R/W
60 024 2 OK reception counter R/W
60 026 1 CRC error counter R/W
60 027 1 Frame error counter R/W
60 028 1 Buffer (Rx) error counter R/W
60 029 1 Collision counter R/W
60 030 1 Multiple collision counter R/W
60 031 1 OverRun counter R/W
60 032 2 Sent Modbus TCP message counter R/W IO Scanning messages not included
60 034 2 Received Modbus TCP message counter R/W IO Scanning messages not included
60 036 1 Modbus TCP message error counter R/W IO Scanning messages not included
60 037 2 Sent IO Scanning message counter R/W
60 039 2 Received IO Scanning message counter R/W
60 041 1 IO Scanning message error counter R/W
60 042 1 Active traffic (msg/s) R/W
60 043 1 Max. traffic (msg/s) R/W
60 044 1 Number of active TCP connections R 8 maximum
Description Access Possible values, comments
00: 60 000 80: 60 001 F4: 60 002 80: 60 003 xx: 60 004 yy: 60 005
[IP card] (IPC-)
[IP Mask] (IPM-)
[IP Gate] (IPG-)
[Bit rate] (bdr)
R/W IPC1.IPC2.IPC3.IPC4
R/W IPM1.IPM2.IPM3.IPM4
R/W IPG1.IPG2.IPG3.IPG4
R= 0:
IPC1: 60 006 IPC2: 60 007 IPC3: 60 008 IPC4: 60 009
IPM1: 60 010 IPM2: 60 011 IPM3: 60 012 IPM4: 60 013
IPG1: 60 014 IPG2: 60 015 IPG3: 60 016 IPG4: 60 017
Speed not defined
= 10:
10 Mbps
= 100:
100 Mbps
32
11. Modbus TCP server
Address Size
(in words)
60 045 1 Communication monitoring
60 046 1 Drive type R = 2 ATV71
60 047 1 Reserved R = 0
60 048 1 Enable IO Scanner
60 049 1 Reserved R = 0
60 050 4 IP address of Master [IP Master] (IPP-) R/W IPP1.IPP2.IPP3.IPP4
60 054 4 IP address of DHCP-FDR server
60 058 1 Enable FDR service
60 059 1 Select local configuration
60 060 1 Enable FDR file error detection
60 061 1 FDR service command
60 062 1 FDR service state
60 063 1 Ethernet communication interruption
Description Access Possible values, comments
time out [time out] (tOUt)
[IO Scan. activ.] (IOSA)
[IP FDR] (IPF-)
[FDR validation] (FdrU)
[FDR Local Config.] (LCFG)
[FDR Error Mgt.] (FdrF)
[FDR Action] (FDrA)
[FDR state] (FDrE)
[FDR fault] (Fdrd)
R/W Unit: 0.1 s; min. = 5 (0.5 s); max. = 600 (60.0 s)
R/W = 0 [No] (nO) : IO Scanning disabled.
= 1 [Yes] (YES) : IO Scanning enabled.
IPP1 = 60 050 IPP2 = 60 051 IPP3 = 60 052 IPP4 = 60 053
R IPF1.IPF2.IPF3.IPF4
R/W 0 = [No] (nO) : FDR service disabled
R/W 0 = [No] (nO) : The drive configuration is
R/W In the event of a problem with the FDR file (missing or invalid)
R/W 0 =
R0 =
R When an Ethernet communication interruption is present, this
IPF1 = 60 054 IPF2 = 60 055 IPF3 = 60 056 IPF4 = 60 057
1 = [Yes] (YES) : FDR service enabled
1 = [Yes] (YES) : The drive configuration is local
0 = [No] (nO) : The Ethernet card does not trigger
1 = [Yes] (YES) : The Ethernet card triggers an
[IDLE] (IdLE)
20 =
[SAVE] (SAUE)
21 =
[REST] (rESt)
22 =
[DEL] (dEL)
[IDLE] (IdLE)
1 =
[INIT] (INIt)
2 =
[CONF] (CONF)
3 =
[RDY] (rDY)
4 =
[GET] (GEt)
5 =
[SET] (SEt)
6 =
[APP] (APP
7 =
[OPE] (OPE)
8 =
[UCFG] (UCFG)
parameter is used to determine the cause. The code remains saved after the disappearance of the condition.
2 = The FDR configuration file is not compatible with the
drive type (example: the drive is not the correct rating)
3 = Error reading the FDR configuration file on the server
4 = Error writing the FDR configuration file to the server
7 = Time out for receipt of the FDR configuration file from the
server
9 = Duplication of IP address
12 = The FDR configuration file is missing
downloaded from an FDR server
an Ethernet communication interruption
Ethernet communication interruption
: No command : Command: save : Command: download : Command: delete
: “Idle” : Initialization : Configuration : Ready : Downloading the current
configuration
: Saving the current configuration
)
: Writing the FDR server configuration to the drive : Operational : Not configured
33
11. Modbus TCP server
Address Size
(in words)
60 064 1 Enable periodic saving
60 065 1 Interval for saving
60 066 1 Number of FDR save
60 067 1 Number of FDR restore
60 068 1 Number of FDR deletions R/W
60 069 1 FDR file checksum R
60 070 5 Reserved R
60 075 4 IP address
60 079 4 Subnet mask
60 083 4 Gateway
60 087 20 Reserved R
60 107 1 Method of assigning IP
60 108 4 Adresse IP serveur
60112 1 E-mail activation R/W Bit 0: Error detected by drive actuation (ETA.3)
60113 1 E-mail status (of the
60114 1 E-mails number
60115 1 Number of errors R/W
60116 1 Last error code R
60117 85 E-mail address of the
60202 85 E-mail address of the
Description Access Possible values, comments
of the FDR service
[FDR autosave]
(FdrS)
the FDR service
[FDR t. autosave]
(Fdrt)
operations
operations
(EEPROM value)
(EEPROM value)
(EEPROM value)
addresses
E-mail
option board)
successfully sent
destination
sender
R/W 0 = [No] (nO) : Periodic saving is disabled
1 = [Yes] (YES) : Periodic saving is enabled
R/W 2 to 9999, unit: min
R/W
R/W
R IPC1.IPC2.IPC3.IPC4
IPC1 = 60 075 IPC2 = 60 076 IPC3 = 60 077 IPC4 = 60 078
R IPM1.IPM2.IPM3.IPM4
IPM1 = 60 079 IPM2 = 60 080 IPM3 = 60 081 IPM4 = 60 082
R IPG1.IPG2.IPG3.IPG4
IPG1 = 60 083 IPG2 = 60 084 IPG3 = 60 085 IPG4 = 60 086
R 0 = Configuration via the display terminal or PowerSuite
1 = Configuration via BOOTP 2 = Configuration via DHCP
R/W
Bit 1: Drive alarm activation (ETA.7) Bit 2: Ethernet error activation Bit 3: Controller Inside message activation
R
R/W
R/W
R/W
34
11. Modbus TCP server
11. 4. List of Modbus functions supported
Code
(decimal)
3 = 16#03 Read Holding Registers Read N output words 63 words max.
6 = 16#06 Write Single Register Write one output word -
16 = 16#10 Write Multiple Registers Write N output words 61 words max.
23 = 16#17 Read/Write Multiple Registers Read/write N words 20/20 words max.
43 = 16#2B Read Device Identification Identification -
Modbus name Description Size of data
11. 5. “Read Holding Registers” (3) function
This Modbus request is used to read the values of a number (No. of Points) of adjacent words starting at the address indicated (Starting Address). The values read are restored one after another, at the end of the response (First Point Data
Request format:
Byte Meaning
0 Function Code = 16#03
1 Starting Address Hi
2 Starting Address Lo
3 No. of Points Hi (0)
4 No. of Points Lo (1 - 125)
Response format:
Byte Meaning
0 Function Code = 16#03
1 Byte Count (B = 2 × No. of Points)
2 First Point Data Hi
3 First Point Data Lo
………………………
B Last Point Data Hi
B+1 Last Point Data Lo
Last Point Data).
Exception response format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#83
01 (Illegal Function)
1 Exception Code
02 (Illegal Data Address) 03 (Illegal Data Value) 04 (Illegal Response Length)
35
11. Modbus TCP server
11. 6. “Write Single Register” (6) function
This Modbus request is used to write a given value (Preset Data) to the address supplied (Register Address).
Request format:
Byte Meaning
0 Function Code = 16#06
1 Register Address Hi
2 Register Address Lo
3 Preset Data Hi
4 Preset Data Lo
Response format:
Byte Meaning
0 Function Code = 16#06
1 Register Address Hi
2 Register Address Lo
3 Preset Data Hi
4 Preset Data Lo
Exception response format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#86
01 (Illegal Function)
1 Exception Code
02 (Illegal Data Address) 03 (Illegal Data Value) 04 (Illegal Response Length)
36
11. Modbus TCP server
11. 7. “Write Multiple Registers” (16 = 16#10) function
This Modbus request is used to write a number (No. of Registers) of adjacent words starting at a given address (Starting Address). The values to be written are supplied one after another (First Register Data
Request format:
Byte Meaning
0 Function Code = 16#10
1 Starting Address Hi
2 Starting Address Lo
3 No. of Registers Hi (0)
4 No. of Registers Lo (1 - 100)
5 Byte Count (B = 2 × No. of Registers)
6 First Register Data (Hi)
7 First Register Data (Lo)
……………
B+4 Last Register Data (Hi)
B+5 Last Register Data (Lo)
Response format:
Byte Meaning
0 Function Code = 16#10
1 Starting Address Hi
2 Starting Address Lo
3 No. of Registers Hi (0)
4 No. of Registers Lo (1 - 100)
V Last Register Data).
Exception response format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#90
01 (Illegal Function)
1 Exception Code
02 (Illegal Data Address) 03 (Illegal Data Value) 04 (Illegal Response Length)
37
11. Modbus TCP server
11. 8. “Read/Write Multiple Registers” (23 = 16#17) function
The “Read/Write Multiple Registers” service is reserved for setting up the IO Scanning service (see “IO Scanning” section).
Request format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#17 16#17
1 Read Reference Address Hi 0 (not handled)
2 Read Reference Address Lo 0 (not handled)
3 Quantity to Read Hi (0) 0
4 Quantity to Read Lo (1 - 125) 32
5 Write Reference Address Hi 0 (not handled)
6 Write Reference Address Lo 0 (not handled)
7 Quantity to Write Hi (0) 0
8 Quantity to Write Lo (1 - 100) 32
9 Byte Count (2 × Quantity to Write) 64
10 Write Data 01 (Hi)
11 Write Data 01 (Lo)
…………………… ……………………
72 Write Data 32 (Hi) PKW output: PKE (Hi)
73 Write Data 32 (Lo) PKW output: PKE (Lo)
Value of 1st IO Scanner output register (by default: value of the control word (CMd))
Response format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#17 16#17
1 Byte Count (2 × Quantity to Write) 64
2 Read Data 01 (Hi)
3 Read Data 01 (Lo)
…………………… ……………………
64 Read Data 32 (Hi) PKW input: PKE (Hi)
65 Read Data 32 (Lo) PKW input: PKE (Lo)
Exception response format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#97
1 Exception Code
Value of 1st IO Scanner input register (by default: value of the status word (EtA))
01 (Illegal Function) 02 (Illegal Data Address) 03 (Illegal Data Value) 04 (Illegal Response Length)
38
11. Modbus TCP server
11. 9. “Read Device Identification” (43 = 16#2B) function
Request format:
Byte Meaning With the VW3A3310d Ethernet card
0 Function Code = 16#2B 16#2B
1 Type of MEI 16#0E
2 Read Device ID code
3 Object ID 16#00
Response format:
Byte(s) Meaning With the VW3A3310d Ethernet card
0 Function code = 16#2B 16#2B
1 Type of MEI 16#0E
2 ReadDeviceId code 16#01
3 Degree of conformity 16#02
4 Number of additional frames 16#00 (a single frame)
5 Next object ID 16#00
6 Number of objects
7 Object no. 1 ID 16#00 = Vendor Name
8 Length of object no. 1 (A) 13
9…21 Value of object no. 1 (A ASCII characters) “Telemecanique”
22 Object no. 2 ID 16#01 = Product Code
23 Length of object no. 2 (B) 11 (for the following example only)
24…23+B Value of object no. 2 (B ASCII characters) (1) Example: “ATV71HU15M3”
24+B Object no. 3 ID 16#02 = Major.Minor Revision
25+B Length of object no. 3 (C) 4
26+B…29+B Value of object no. 3 (C ASCII characters) Example: “0201” for version 2.1
30+B Object no. 4 ID 16#06 = Application Name (2)
32+B…31+B+D Value of object no. 4 (D ASCII characters) (1) Example: “MACHINE 4”
16#01: Basic 16#02: Regular 16#03: Extended
3 for Basic 4 for Regular or Extended
for Regular and Extended31+B Length of object no. 4 (D) 8 (for the following example only)
(1)The length of this field is variable. Use the “Length of object no. X” field associated with it to determine the length.
(2)In the case of the drive, this data item corresponds to [DEVICE NAME].
The response to a “drive identification” request does not cause an exception response.
39
12. IO Scanning service
12. 1. Presentation
The IO Scanning service is used to exchange periodic I/O data between:
• A controller or PLC (IO Scanner).
• Devices (IO Scanning servers).
This exchange is usually performed by implicit services, thus avoiding the need to program the controller (PLC). The IO Scanner periodically generates the Read/Write Multiple Registers (23 = 16#17) request.
The IO Scanning service operates if it has been enabled in the PLC and the drive. The drive parameters assigned to IO Scanning have been selected by default. This assignment can be modified by configuration.
The table below indicates the tools which can be used to modify these configurations:
Functions Graphic display
terminal
Enable IO Scanning pppp Configuring the IO Scanning variables pp
The drive IO Scanning service can also be configured by the Ethernet card Modbus server.
When the IO Scanning service has been enabled in the Altivar 61/71 drive:
• A TCP connection is assigned to it.
• The parameters assigned in the periodic variables are exchanged cyclically between the Ethernet card and the drive.
• The parameters assigned to the periodic output variables are reserved for IO Scanning. They cannot be written by other Modbus services, even if the IO Scanner is not sending its periodic output variables.
Integrated
display
terminal
PowerSuite
software
workshop
Standard
web server
12. 2. Periodic variables
Output variables (written by IO Scanner) Input variables (read by IO Scanner)
No. Meaning/default assignment Configurable No. Meaning/default assignment Configurable
0 Reserved no 0 Reserved no
1 Control word (CMd) yes 1 Status word (EtA) yes
2 Speed setpoint (LFrd) yes 2 Output speed (rFrd) yes
3 Not assigned yes 3 Not assigned yes
4 Not assigned yes 4 Not assigned yes
5 Not assigned yes 5 Not assigned yes
6 Not assigned yes 6 Not assigned yes
7 Not assigned yes 7 Not assigned yes
8 Not assigned yes 8 Not assigned yes
9 Not assigned yes 9 Not assigned yes
10 Not assigned yes 10 Not assigned yes
11-31 Reserved no 11-31 Reserved no
It is possible to configure the assignment of periodic variables 1 to 10.
Note: • Avoid configuring the drive configuration parameters as periodic output variables because they cannot be modified with the
40
motor running (DSP 402 state 5—"Operation Enabled”).
• Monitoring parameters must not be configured as periodic output variables, because they cannot be written.
12. IO Scanning service
The values of the periodic variables are listed in a table.
This table can be accessed in read-only mode by the Ethernet card Modbus server (Unit ID = 251).
Address Description Default value Address Description Default value
40 001 Value of output variable 1 Value of the
control word (CMd)
40 002 Value of output variable 2 Value of the speed
setpoint (LFrd)
40 003 Value of output variable 3 40 019 Value of input variable 3
40 004 Value of output variable 4 40 020 Value of input variable 4
40 005 Value of output variable 5 40 021 Value of input variable 5
40 006 Value of output variable 6 40 022 Value of input variable 6
40 007 Value of output variable 7 40 023 Value of input variable 7
40 008 Value of output variable 8 40 024 Value of input variable 8
40 009 Value of output variable 9 40 025 Value of input variable 9
40 010 Value of output variable 10 40 026 Value of input variable 10
12. 3. Address table
The periodic variables are defined in the address table. This table can be accessed in read-write mode by the Ethernet card Modbus server (Unit ID = 251).
40 017 Value of read register 1 Value of the status
word (EtA)
40 018 Value of read register 2 Value of the output
speed (rFrd)
Address Description Default value Address Description Default value
50 001 Logic address
of output variable 1
50 002 Logic address
of output variable 2
50 003 Logic address
of output variable 3
50 004 Logic address
of output variable 4
50 005 Logic address
of output variable 5
50 006 Logic address
of output variable 6
50 007 Logic address
of output variable 7
50 008 Logic address
of output variable 8
50 009 Logic address
of output variable 9
50 010 Logic address
of output variable 10
To modify the address table, IO Scanning must be disabled (only when the motor is stopped).
Address of the control word (CMd) = 8501
Address of the speed setpoint (LFrd) = 8602
0 50 019 Logic address
0 50 020 Logic address
0 50 021 Logic address
0 50 022 Logic address
0 50 023 Logic address
0 50 024 Logic address
0 50 025 Logic address
0 50 026 Logic address
50 017 Logic address
of input variable 1
50 018 Logic address
of input variable 2
of input variable 3
of input variable 4
of input variable 5
of input variable 6
of input variable 7
of input variable 8
of input variable 9
of input variable 10
Address of the status word (EtA) = 3201
Address of the output speed (rFrd) = 8604
0
0
0
0
0
0
0
0
41
13. FDR service
13. 1. Presentation
The Faulty Device Replacement (FDR) service is used to simplify the maintenance or replacement of drives connected on the Ethernet network. Not all PLCs and control system devices are able to use the FDR service. Consult the appropriate documentation for the associated controller devices.
If a drive controller is replaced, this service quickly reconfigures its replacement. The new drive (FDR client) retrieves:
• Its IP addresses and the FDR file path from a DHCP server.
• The FDR file from an FTP server, if the drive is not configured in local configuration.
In practice, the DHCP server and the FTP server are the same device (TSX Premium or Quantum PLC).
The FDR file contains:
• The Ethernet parameters (configuration of IO Scanning, FDR etc.).
• The drive parameters (drive, functions, application, etc.).
The FDR service is based on identification of the device by a “Device Name”. In the case of the Altivar 71 drive, this is represented by the [DEVICE NAME] parameter.
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section. Configuration using the standard web server is explained in the “Standard web server” section. For configuration using the PowerSuite software workshop, refer to the software online help.
Note: Check that each network device has a unique “Device Name”. The FDR server controls duplication of “Device Names” (it does not assign an IP address that has already been assigned and is active). If the same IP address is supplied on 2 devices, the 2nd should trigger an IP address duplication [External fault com.] (EPF2).
If the FDR service has been enabled, the Ethernet card attempts to restore its IP addresses on each power-up. Each time the procedure is unsuccessful, the Ethernet card reiterates its FDR requests (DHCP).
Where the configuration also needs to be downloaded by the FDR server: After assigning the Ethernet card IP addresses, if the configuration download is unsuccessful, the Ethernet card detects a network management interruption [External fault com.] (EPF2).
42
13. FDR service
13. 2. Local configuration
IP assignment
Save
If the drive parameter configuration is local, the FDR server only assigns the IP addresses:
• Card IP address.
• Subnet mask.
• Gateway IP address.
On connection to the network, the drive automatically saves its parameters in the FDR server.
To make the system operational, it is necessary to:
• Configure the FDR server.
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
M Configure the FDR server
See the PLC manual or the section on software setup using PL7.
M Configure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0)
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES)
• Select local drive configuration: [FDR Local Config.] (LCFG) = [Yes] (YES)
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu. This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
M Turn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken into account.
M Connect the drive to the network
43
13. FDR service
13. 3. Downloaded configuration
IP assignment
Save
Downloading
If the drive parameter configuration has been downloaded, the FDR server assigns:
M The IP addresses
• Card IP address.
• Subnet mask.
• Gateway IP address.
• FDR server IP address.
M Drive parameters (configuration)
b First use
Procedure:
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
• Configure the FDR server (see the PLC manual).
• Supply the FDR server with the configuration file.
• Check that the system is operational.
In the procedure described below, the configuration file is supplied to the FDR server, via the Ethernet network, using a save command performed on the drive graphic display terminal.
Note: This procedure can also be performed using a web browser, which is more user-friendly than the drive graphic display terminal (see the “Standard web server” section).
M Configure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).
Caution, before the first connection, you must select local drive configuration: [FDR Local Config.] (LCFG) = [Yes] (YES). The drive must first supply the configuration to the server.
If this option is not selected, an invalid or null configuration file may be uploaded to the FDR server. Subsequent drives would then receive incorrect configuration files, leading to unexpected behavior.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that the local configuration option [FDR Local Config.] (LCFG)=[Yes] (YES) is selected when configuring the first drive.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu. This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert]
M Turn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken into account.
(EPr).
M Connect the drive to the network
44
13. FDR service
M Download the IP addresses
• Connect the drive and the FDR server (PLC) to the Ethernet network.
• The server downloads the IP addresses to the Ethernet card.
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
You can also check, in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu whether the [IP card] (IPC1)
(IPC2) (IPC3) (IPC4), [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4) and [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4)
parameters have values other than [0.0.0.0] (0) (0) (0) (0).
M Save the drive configuration parameters in the FDR server
• Configure the drive parameters.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Specify that the drive configuration is to be downloaded from the FDR server on each power-up: [FDR Local Config.] (LCFG) = [No] (nO).
• Send a save command to the FDR server: [FDR Action] (FdrA)
After execution of the command, the [FDR Action] (FdrA) parameter reverts to the value [IDLE] (IdLE).
M Check that the system is operational
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
•The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).
If the save operation has not been successful, the card triggers a drive status [External fault com.] (EPF2).
= [SAVE] (SAUE).
b Replacing a drive
Procedure:
• Configure the drive.
• Turn off the drive.
• Connect the drive to the network.
• Check that the drive is operational.
M Configure the drive
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).
• Specify that the drive configuration is to be downloaded from the FDR server on each power-up:
[FDR Local Config.] (LCFG) = [No] (nO).
These configurations are the default values.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu. This menu can only be accessed in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).
M Turn the drive off and then back on again
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken into account.
M Connect the drive to the network
M Check that the system is operational
Check that the operation has proceeded correctly:
• The “STS” LED should be on.
•The [FDR state] (FdrE) parameter should be at the value [OPE] (OPE).
If downloading has not been possible after a period of 2 min following assignment of the IP addresses, the card triggers a drive status
[External fault com.] (EPF2).
45
13. FDR service
13. 4. Periodic saving
Periodic saving of the drive configuration can be configured on the FDR server in either local configuration or downloaded configuration mode.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Select: [FDR autosave] (FdrS) = [Yes] (YES).
• Set the [FDR t.autosave] (Fdrt) parameter.
Note: Saving too often risks overburdening the network and adversely affecting its performance (factory setting: 10 min).
13. 5. Other commands
On request, the configuration saved in the FDR server can be downloaded to the drive using the [FDR Action] (FdrA) command = [REST] (rESt).
The saved configuration can be deleted from the FDR server using the [FDR Action] (FdrA) command = [DEL] (dEL).
13. 6. Configuration file
The configuration file, XXXX.prm where XXXX is the DeviceName, is an HTML file which contains the entire drive configuration as a comment.
The HTML format is a simple way of providing the user with a summary of the configuration. An example appears below:
FDR Configuration File
File Revision: 2 ATV Revision: 1.0IE1.0 Catalog number: ATV-71HU15M3 CheckSum File: SE92
b Limitations
• The FDR configuration file XXXX.prm coming from an Ethernet V2.1 or V3.0 option board cannot be applied on a V1.1 option board. If applied, an ILF fault will appear.
• The FDR service is able to store the current configuration of the drive, but does not provide the possibility to store multi-configurations or multi-parameters configurations.
46
14. Standard web server
14. 1. Web server functions
Menu Page Function
HOME English Home page
Altivar Viewer Display of the main drive parameters (motor speed, state of drive logic and analog IO, status)
MONITORING
DIAGNOSTICS Ethernet Statistics
SETUP
DOCUMENTATION References Link to the site http://www.telemecanique.com
Data Viewer Display and modification (password-protected) of the drive parameters, arranged by category
Altivar Chart
[Security]
HTTP password
[Security]
Data write password
FDR Agent Display of the state and management of the Ethernet card FDR agent
IO Scanner
“Home” menu
Display of two drive parameters (speed, voltage, etc.) in the form of an oscilloscope type time chart
Display and resetting of the communication statistics
Drive identification
Changing the HTTP password used to access the web server
Changing the Write password that allows modification of the parameters
Display and modification (password-protected) of the assignment of the IO Scanning periodic variables
Enabling and disabling of IO Scanning (password-protected)
Setting (password-protected) of the IO Scanning and Modbus TCP messaging time outs
“Monitoring” menu
“Diagnostics” menu
“Setup” menu
“Documentation” menu
“Security” submenu
“Altivar Viewer” page
“Data Viewer” page
“Altivar Chart” page
“Ethernet Statistics” page
“Data write password” page
“HTTP password” page
“FDR Agent” page
“IO Scanner” page
A
A
A
A
A
A
Pages which contain applets are marked “A”. See page 48 for more information.
www.telemecanique.com
47
14. Standard web server
14. 2. Applets
The web server downloads Java programs called “applets” to your computer. These applets communicate with the drive using Modbus services (on port 502), thus establishing one or more connections between the computer and the drive. Until an applet has been fully transmitted from the drive to the browser, a gray rectangle appears in the place reserved for it in the page.
The applet connects when the page is opened and remains connected until the page is closed.
Display problems can appear with the SUN “Java virtual machine” (JVM). Use the Internet Explorer default JVM. Consult your internet browser’s Help files for assistance with configuring your browser’s Java settings.
The applets associated with the web pages monitor communication with the drive. When the drive no longer responds to requests to update the data, the message “Link down” is displayed in one field and the other field contents are emptied.
Subsequently, the description of each page indicates the data refresh period requested by the applet loaded on the computer. The refresh period actually observed depends on:
• The performance of the computer on which the web browser is running.
• The communication system response time.
• The amount of data to be refreshed on the page.
48
14. Standard web server
14. 3. Access to the web server
Number of Modbus TCP connections 0
To connect to the web server of a drive located, for example, at IP address 139.160.69.241 enter the URL “http://139.160.69.241/” in the address bar of a web browser.
When the browser first connects to the drive web server, it requests entry of a username and a password (HTTP password).
14. 4. Username and password
By default, the username and the password (HTTP password) are both “USER” (upper case).
If authentication is accepted, the home page is displayed. If not, after three attempts, access to this page is denied as illustrated below:
To attempt a new connection to the drive server home page, simply refresh the web browser display (F5 key or “Refresh” button, for example).
49
14. Standard web server
14. 5. Web server user interface
The drive web server pages have the same appearance:
1 A bar at the top containing links to HTML pages for the main menus: “Home”, “Documentation”, “Monitoring”, “Control”, etc.
This bar is the same regardless of which HTML page is being viewed.
Note: The “Control” and “Maintenance” menus are disabled. They only appear because of the “Transparent Ready” common interface.
2 A menu down the left-hand side which displays links to the HTML pages available in the selected menu.
3 The center part of the window displays the information for the selected page.
1
2
14. 6. “Home” menu
Number of Modbus TCP connections used 0
The home page or “Home” menu contain the following items:
• A “Languages” submenu containing:
- A link to the “English” page
1
3
The only link in the “Languages” submenu sends the user to the home page in English and configures the web browser to open the HTML pages located in the corresponding directory (e.g., the “http://139.160.69.241/html/english/” directory becomes the standard directory in the case of English).
14. 7. “Monitoring” menu
Number of Modbus TCP connections used 0
The “Monitoring” menu contains the following items:
• A link to the “Altivar Viewer” page.
• A link to the “Data Viewer” page.
• A link to the “Altivar Chart” page.
50
14. Standard web server
14. 8. “Altivar Viewer” page
Number of Modbus TCP connections used 2 Refresh period 0.5 s
This page gives an overview of the drive state.
The state indicated in the “Altivar State” field corresponds to the display on the drive integrated display terminal. A delay may sometimes be noticed between the displays on the web server and the display terminal, depending on the performance of the computer used to display the pages using a web browser and the communication system performance.
The motor speed displayed on the “Motor Speed” gauge is calibrated according to the maximum frequency [Max frequency] (tFr) and the number of pairs of poles [Pr] (PPn).
The LI… area gives the state of the drive terminals (logic inputs LI1 to LI14, logic outputs LO1 to LO4, relay outputs R1 to R4, analog inputs AI1 to AI4 and analog outputs AO1 to AO3). When a logic input is active, the LED is green. When a logic output is active, the LED is red.
51
14. Standard web server
14. 9. “Data Viewer” page
This page is used to display the drive parameters and modify their values. The parameters are arranged in groups, and consistent with the keypad and user manuals The display mode for each value depends on the nature of the parameter.
• The unit for the physical values is displayed in the “Unit” column.
• The registers (bit fields) are displayed in hexadecimal format (16#xxxx).
• Signed values are displayed as such.
To begin monitoring, click the “Start animation” button:
To modify the parameter value, click the “Write value of selected row” button then select the parameter to modify
It is only possible to modify the parameter values after entering the “Write password” (see “HTTP password” and “Data write password pages” section on page 55 also a “Cancel” button, for canceling the password entry. After entering the password, press the Enter key so that it is taken into account by the web browser.
When the value of a parameter cannot be modified, a message box appears: “This parameter can't be written!” This is the case for any parameter until you have correctly entered the Password. If IO Scanning has been enabled, modifying the value of a parameter assigned to periodic output variables will have no effect since this value is updated cyclically by the PLC. The same applies if a parameter is written periodically by a Modbus service.
). Click on the “Password” button to enter this password. An entry field then appears in the parameter table, and
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that an IP Master has been configured before modifying values with the Data Viewer.
Failure to follow this instruction will result in death, serious injury, or equipment damage.
It is possible to write the command word using the Data Viewer. It is mandatory to configure an IP master in order to avoid undesired action.
52
14. Standard web server
14. 10. “Altivar Chart” page
Number of Modbus TCP connections used 1 Refresh period 1 s
This page is used to monitor two drive parameters simultaneously.
Two parameters can be selected and displayed simultaneously. To do this, select them in the Trace1 and Trace2 list. To change the display range, you can modify the curve minimum and maximum points by entering the values directly in fields Min and Max for each trace. To speed up sampling, enter a value of 0 in the interval Intv(s) field. Note: Entering a value of 0 in the Intv(s) field increases the traffic on the Ethernet network and can cause collision problems if there is too much traffic, thereby reducing the overall network performance. If this problem occurs, increase the sampling period.
To start the oscilloscope function, press the Run/Stop button. Pressing the button again stops the sampling and updates the screen.
Reset: clears the active traces.
14. 11. “Diagnostics” menu
Number of Modbus TCP connections used 0
The “Diagnostics” menu contains the following item:
• A link to the “Ethernet Statistics” page.
53
14. Standard web server
14. 12. “Ethernet Statistics” page
Number of Modbus TCP connections used 1 Refresh period 0.5 s
This page provides the Ethernet statistics and the drive identification data.
14. 13. “Setup” menu
Number of Modbus TCP connections used 0
The “Setup” menu contains the following items:
• A “Security” submenu containing:
- A link to the ”HTTP password” page.
- A link to the ”Data write password” page.
• A link to the ”FDR Agent” page.
• A link to the ”IO Scanner” page.
• A link to the ”E-mail” page.
54
14. Standard web server
14. 14. “HTTP password” and “Data write password pages”
Number of Modbus TCP connections used (for each page) 0
These two pages are used to modify the two web server passwords.
By default, the username and both passwords are: “USER” (upper case).
The username can only be modified using the PowerSuite software workshop.
The username and the “HTTP password” are used to access the web server in display mode.
The “Write password” is used to access the web server in modification mode.
When the value of a parameter cannot be modified, the background of the corresponding cell appears grayed-out. This is the case for any parameter until you have correctly entered the “Write password”.
Note: Do not lose the username or the passwords. If they are lost, the card must be rest. Contact you Schneider Electric representative for instructions.
55
14. Standard web server
14. 15. “FDR Agent” page
Number of Modbus TCP connections 1 Refresh period 1s
This page displays the main parameters used by the VW3A3310d Ethernet card FDR function and is used to configure these parameters. See the “FDR Service” section.
Information on the FDR Agent page
IP Address [IP card]
NetMask [IP Mask]
Gateway [IP Gate]
FTP Server [IP FDR]
DeviceName [DEVICE NAME] Used by the DHCP server to assign the Ethernet card IP addresses dynamically
Device File Not accessible Name of FDR configuration file.
Device Reference - Drive catalog number.
Checksum File Not accessible Drive configuration Checksum value. Whenever a drive parameter is modified, this value
56
Corresponding terminal display
(IPC-)
(IPM-)
(IPG-)
(IPF-)
Description/Possible values
Ethernet card IP address
Subnet mask
Gateway IP address
Indicates the IP address of the FDR server that has supplied the Ethernet card configuration, in particular its IP addresses. This is the server which also supplies the drive configuration file, if [FDR Local Config.]
(LCFG) = [No] (nO).
(example: Machine 157).
The file name is consistent with the DeviceName (in our example: Machine 157.prm). If the FDR server file has not been downloaded to the drive, “Local” is displayed in this field.
changes.
14. Standard web server
Information on the FDR Agent page
Validation [FDR validation]
Local Config [FDR Local Config.]
File Error [FDR Error Mgt.]
AutoSave [FDR autosave]
Period [FDR t.autosave]
FDR State [FDR state]
Error Code [FDR fault]
Save Counter Not accessible Number of times the configuration has been saved to the FDR server.
Restore Counter Not accessible Number of times the configuration has been downloaded from the FDR server.
Delete Counter Not accessible Number of times the configuration file has been deleted in the FDR server.
Save File [FDR Action]
Restore File [FDR Action]
Delete File [FDR Action]
Reset counter Not accessible Command to reset the “Save counter”, “Restore counter” and “Delete counter” counters.
Corresponding terminal display
(FdrU)
(LCFG)
(FdrF)
(FdrS)
(Fdrt)
(FdrE)
(Fdrd)
(FdrA)
(FdrA)
(FdrA)
Description/Possible values
Enables the FDR function
• Off = [No] (nO): FDR service disabled.
•On = [Yes] (YES): FDR service enabled.
Selection of local or server configuration
• Off = [No] (nO): The drive configuration is downloaded from an FDR server.
•On = [Yes] (YES): The drive configuration is local.
Enables the FDR file error detection.
• Off = [No] (nO): In the event of a problem with the FDR file (missing or invalid), the Ethernet card does not trigger an Ethernet [FDR fault] (Fdrd).
•On = [Yes] (YES): In the event of a problem with the FDR file (missing or invalid), the Ethernet card triggers an [FDR fault] (Fdrd).
Enables periodic saving of the FDR service.
• Off = [No] (nO): Automatic saving disabled.
•On = [Yes]
Interval for periodic saving of the FDR service. 2 min to 9999 min
FDR service state.
• Idle = [IDLE] (IdLE): FDR service inactive.
• Initialization = [INIT] (InIt): Initialization of the current Ethernet card.
• Configuration = [CONF] (COnF): Configuration of the current Ethernet card.
• Ready = [RDY] (rdY): Ethernet card ready.
• Get Conf = [GET] (GEt): Downloads the current configuration from the FDR server.
• Store Conf = [SET] (SEt): Saves the current configuration to the FDR server.
• Apply Conf = [APP] (APP): Writes the FDR server configuration to the drive.
• Operational = [OPE] (OPE): Operational.
• Unconfigured = [UCFG] (UCFG): FDR service interruption.
Ethernet error code.
•= [0]: No communication interruption
• Service Unavailable = The FDR server is not available.
•= [2]: The FDR configuration file is not compatible with the drive type (example: the drive is not the same rating as that defined in the FDR file).
•= [3]: Error reading the FDR configuration file on the server.
[4]: Error writing the FDR configuration file to the server.
•=
•= [7]: Time out for receipt of the FDR configuration file from the server.
•= [9]: Duplication of IP address.
• File Not Found = [12]: The FDR configuration file is missing.
•= [203]: Inconsistent hardware configuration.
This counter is incremented even if the drive configuration is identical to that of the server.
This counter is not incremented if the drive configuration is identical to that of the server (comparison of checksums).
Command to save the configuration to the FDR server. Corresponds to the display terminal command: [SAVE] (SAUE).
Command to download the configuration from the FDR server. Corresponds to the display terminal command: [REST] (rESt).
Command to delete the configuration file in the FDR server. Corresponds to the display terminal command: [DEL] (dEL).
(YES): Automatic saving enabled.
57
14. Standard web server
14. 16. “IO Scanner” page
Number of Modbus TCP connections 1 Refresh period 1s
This page is used to:
• Enable or disable IO Scanning.
• Display and modify assignment of the IO Scanning periodic variables.
• Set the communication monitoring time out.
The default configuration is described in the screen below:
Modifications are protected by the “Write password” modification password. Click on the “PassWord” button to enter the “Write password”. After correctly entering the password, you can access “IoScanner”, “Time Out (s)”, “Master”, “Output parameters”, “Input parameters” and the “Save” and “Abort” buttons. By default, the password is “USER”. It can be modified in the “Data write password” page.
58
14. Standard web server
b Enabling IO Scanning
Control by the IO Scanner is enabled if the “IoScanner” field is set to “Yes” and disabled if the “IoScanner” field is set to “No”.
The “IoScanner” field corresponds to the parameter [IO Scan.activ.] (IOSA).
DANGER
UNINTENDED EQUIPMENT OPERATION
• Do not disable a drive's IO scanning support when the PLC is using the IO scanner to monitor/control client devices.
• Do not modify the assignment of the periodic variables if the PLC is using IO scanning to monitor/control client devices. Disabling a drive's IO Scanning or modifying the assignment of periodic variables can result in a loss of control via the network, and could result in unintended equipment operation.
Failure to follow these instructions will result in death, serious injury, or equipment damage.
Disabling a drive's IO Scanning or modifying the assignment of periodic variables can result in a loss of control via the network, and could result in unintended equipment operation.
Note: Disabling IO Scanning results in loss of control if a PLC is using the IO Scanner.
Before disabling IO Scanning, you must disable the time out (set the value to 0). However, communication monitoring remains active and the card will detect a communication interruption at the end of the period defined by the time out. In factory settings mode, a communication interruption will trigger a resettable stop condition [Com. network] (CnF) and initiate a freewheel stop.
Once the value in the “IoScanner” field has been modified, it may take a while to update the page, depending on the capacity of your computer and network.
The “IoScanner” field corresponds to the parameter [IO Scan.activ.] (IOSA).
b Assigning the IO Scanning periodic variables
Note: Modifying the assignment of the periodic variables can result in loss of control if a PLC is using the IO Scanner.
To modify the IO Scanning periodic variables, proceed as follows:
1 Enter “No” in the “Io Scanner” field. 2 Modify the assignment of periodic variables. 3 Apply these modifications using the “Save” button. 4 Enter “Yes” in the “Io Scanner” field.
Once the value in the “IoScanner” field has been set to “No”, it may take a while to update the page, depending on the capacity of your computer.
A drop down menu is used to modify the assignment of each of the periodic variables.
Click on the periodic variable whose assignment you wish to modify, then choose the code corresponding to the drive parameter to be assigned.
Modifications to “Output parameters” and/or “Input parameters” can be confirmed by clicking the “Save” button or canceled by clicking the “Abort” button.
Each time the “Save” button is pressed the address table will be saved to an EEPROM on the Ethernet card. The assignments are now saved, even if the power is turned off.
59
14. Standard web server
b Time out
This page can also be used to modify the communication monitoring “time out”. Entries must be confirmed by pressing “Enter”. The accepted values are as follows: 0: No communication check.
0.5 to 60.0 s: Time out value.
See the “Configuration - Communication faults” section.
The default time out value is 2 s (display: “2.0”).
The “Time Out” field corresponds to the [time out] (tOUt) parameter.
b Master
See the “Reserving control” section.
To configure reservation, enter an IP address other than [0.0.0.0] in the “Master” field. This field is equivalent to the [IP Master] (IPP-) parameter.
60
14. Standard web server
14. 17. “E-mail” page
The configuration page of the E-mail service is available in the setup menu V E-mail of the option board web page, only for V2.1 version and above.
This service is able to generate and send e-mails to a predefined address in case of alarms or drive detected faults. The controller inside option board can also initiate the sending of an e-mail.
It is possible to configure the E-mail service after entering the “Write password” (see “HTTP password” and “Data write password pages” section on page 55
Enter the following information to configure the E-mail service:
E-mail IP Server: IP address of the E-mail server that will process the message (SMTP server) E-mail Dest @: E-mail address of the E-mail recipient E-mail From @: E-mail address of the Ethernet option board which will send the e-mail (this is a virtual address since the option board
does not provide any incoming e-mail box)
Configure the triggering mode for sending E-mail:
Drive Fault: an E-mail is sent when a drive detects a fault (triggered by ETA status word bit 3) Drive alarm: an E-mail is sent when a drive generates an alarm (triggered by ETA status word bit 7) Eth. Board fault: an E-mail is sent if an ethernet board becomes inoperative PLC Board status: an E-mail is sent on demand from the application of the Controller Inside Card.
E-mail example sent on CNF fault of the Ethernet board:
From: ALTIVAR@pascal.fr
Subject: Error CNF on Altivar Drive
Date: Wed, 14 Dec 2005 14:55:32 +0100
Fault occurred on Ethernet Board's Drive:
DeviceName: ATV
IP Address: 139.160.69.241
Reference: ATV71H037M3
Description: TimeOut TCP/Modbus (CNF)
IMPORTANT NOTICE
This E-mail has been automatically generated. Please do not reply.
Copyright © 2005, Schneider Automation. All rights reserved
).
Service diagnostic:
• E-mail Status
-0 V Idle
-1 V Operational
-2 V Stopped
• SentCount: number of e-mails successfully sent
• ErrorCount: number of errors occurred
• LastError: last error code
61
14. Standard web server
14. 18. “Documentation” menu
Number of Modbus TCP connections used 0
The “Documentation” menu contains a link to the “References” page. This page displays a link to the site: http://www.telemecanique.com/.
62
15. FTP server
x
b Access
The Ethernet card has a structured FTP server which is used to:
• Access the embedded web server resource files.
• Store the FDR (Faulty Device Replacement) service configuration files.
Access to the FTP server is restricted. To access it, the user has to enter a username and a password:
• The username is USER.
• The default HTTP password is USER. It can be changed by the standard web server.
Address format in lnternet Explorer: .
To obtain this display in Internet Explorer, first activate the “Enable folder view for FTP sites” option (located in Tools, Internet Options …, Advanced, Browsing).
ftp://USER:USER@xxx.xxx.xxx.x
Username
HTTP password
IP address
The FTP server accepts up to 2 FTP clients connected at the same time.
The FTP server content cannot be modified if the motor is running.
63
15. FTP server
b Functions
The table below describes the functions available:
FTP functionality Comment
Username check. Accepts or rejects connection Handled
HTTP password check. Accepts or rejects Handled
User output Handled
Type of file system Handled. “DOS”.
Create a volume or disk Not handled
Change file name Handled
Delete a file Handled
Open a file Handled in read/write mode
Read a file Handled
Write a file Handled
Close a file Handled
Open a directory Handled
Close a directory Handled
Change directory Handled
Current directory = parent directory Handled
Delete a directory Handled
Create a directory Handled
Restore current directory Handled
Read next directory input Handled
b File system
The FTP server “fdr” directory is fixed. The RD (remove directory) command therefore has no effect on this directory. However, the whole “html” directory can be modified using the MD (make directory) and RD commands.
Note: Before modifying the content of this directory, remember to save it to the hard disk of your PC. Do not modify this saved directory because in the event of a problem, you can use it to restore the original content of the FTP server “html” directory.
The file system is DOS type. The response to DIR or LS commands is as follows:
08-28-01 08:07AM <DIR> Java
08-28-01 08:07AM 57346 AtvSys.jar
The Ethernet card manages the time and date of web server file save operations.
But there is a specific procedure for starting the Ethernet card date/time function:
• Connect a browser to the standard web server.
• Open one of the pages containing a Java applet (Altivar Viewer, Data Viewer, Altivar chart, Ethernet Statistics, FDR agent, IO Scanner).
• On each connection, the applet sends the date and time present on the PC, from which it is executed.
The date/time function remains active until midnight. After midnight, it is automatically deactivated.
Note: If the date/time function has not been activated, the date and time used to date-stamp the web server files are those supplied by the Ethernet card software.
64
16. Downloading from the web server
b Principle
VW3A3310d Ethernet card
File system
Write to
Flash memory
Read
Read
The Ethernet card has an embedded FTP server which authorizes access to the various URLs available for the HTTP server. A browser such as Internet Explorer can be used to display the URLs like a disk in the Windows explorer. This “disk” consists of various directories containing the URL files. It is therefore possible to use the different commands managed by Windows explorer such as deletion, renaming or writing (downloading) files (check that card IO Scanning has been disabled).
FTP server
HTTP server
PC
Internet
Explorer
b File management
The memory zone assigned to the web server URLs consists of 24 blocks:
• 23 sectors of 64 Kb for file storage.
• 1 sector of 64 Kb for the file table.
The web server storage capacity is 1.5 Mb, i.e. 1536 Kb.
The file table is used to make the link between the HTTP server, the FTP server and the various “URL” files. This table is dynamic and is cleared and reprogrammed each time there is a change.
The maximum number of URL files is limited to 150.
The information relating to each file is as follows:
• File name (32 characters max.).
• Location address in the card memory.
• File size in bytes.
• “FTP” storage directory (html, html/lib/js etc.).
• URL processing function. (Access management, etc.). The URLs have a default function which requires a password (“HTTP password”) in order to access them via HTTP, apart from a few exceptions (see below).
65
16. Downloading from the web server
Each URL in the HTTP server is stored in the file table. As a result, the user can easily change the standard web server by adding, deleting or modifying the URL files.
However, some URLs are required and/or cannot be modified.
• The “index.htm”, “html/english/home/index.htm” and “html/english/home/home.htm” pages, which form the entry page to the web server, are compulsory.
• The WebServer.htm page (see later), and the various HTML requests, such as password modification, are fixed and are not visible via the FTP server.
The maximum file size is limited to 64 Kb. The size of the AtvSys.jar java archive file, containing the java applets, is almost 64 Kb. If additional java applets are required, two archive files must be created.
b Web server
The web server has a masked page, which cannot be accessed directly via a hyperlink, providing access to a summary of the memory resources, sector by sector, used by the web server.
Example of access: http://192.168.1.23/WebServer.htm
Memory Sector Free (bytes) Max (bytes) FastFree (bytes) # File
Sector 12 1,429 65,536 1,429 44
Sector 13 237 65,536 237 01
Sector 14 18,516 65,536 18,516 02
Sector 15 65,536 65,536 65,536 00
Sector 16 65,536 65,536 65,536 00
Sector 17 65,536 65,536 65,536 00
Sector 18 65,536 65,536 65,536 00
Sector 19 65,536 65,536 65,536 00
Sector 20 65,536 65,536 65,536 00
Sector 21 65,536 65,536 65,536 00
Sector 22 65,536 65,536 65,536 00
Sector 23 65,536 65,536 65,536 00
Sector 24 65,536 65,536 65,536 00
Sector 25 65,536 65,536 65,536 00
Sector 26 65,536 65,536 65,536 00
Sector 27 65,536 65,536 65,536 00
Sector 28 65,536 65,536 65,536 00
Sector 29 65,536 65,536 65,536 00
Sector 30 65,536 65,536 65,536 00
Sector 31 65,536 65,536 65,536 00
Sector 32 65,536 65,536 65,536 00
Sector 33 65,536 65,536 65,536 00
Sector 34 65,536 65,536 65,536 00
TOTAL 1,330,902 1,507,328 1,330,902 47
66
16. Downloading from the web server
b Standard web server resources
The web server is version HTTP 1.1 and also supports HTTP 1.0.
The HTTP server provides access to the resources (URLs) in the Ethernet card:
• HTML pages
• Images
• Java applets
• Text file (Description of the drive parameters)
Type
HTML pages
File name (Complete URL)
AtvChart.htm 651
AtvConf.htm 630 Access not permitted -
AtvFdr.htm 628 Pwd change OK -
AtvView.htm 880 Pwd change NOK -
DataEditor.htm 633 Parameter file fdr/Current.prm Variable
DocReferences.htm 660
index.htm 591 images/Telemecanique.gif 3,582
SecurityData.htm 1,570
SecurityHttp.htm 1,523 lib/images/left.gif 870
Statistic.htm 648 lib/images/moins.gif 866
html/english/header.htm 968 lib/images/plus.gif 883
html/english/index.htm 560 lib/images/right.gif 882
html/english/control/index.htm 575
html/english/control/menu.htm 760 AtvSys.jar 64,736
html/english/diagnostic/index.htm 575 Text file DataFile.txt 42,196
html/english/diagnostic/menu.htm 856
html/english/documentation/index .htm
html/english/documentation/men u.htm
html/english/home/home.htm 698 lib/js/index.js 895
html/english/home/index.htm 575 lib/js/menu.js 4,824
html/english/home/menu.htm 830 lib/js/tools.js 261
html/english/maintenance/index.h tm
html/english/maintenance/menu. htm
html/english/monitoring/index.ht m
html/english/monitoring/menu.ht m
html/english/setup/index.htm 575
html/english/setup/menu.htm 1,056
Size
(bytes)
575 lib/js/header.js 5,629
839 lib/js/home.js 536
575
64 lib/css/header.css 988
575 lib/css/main.css 341
960 lib/css/menu.css 655
Type
Special
HMTL pages
Images
Java
applets
JavaScript
scripts
Cascaded
Style
Sheets
File name (Complete URL)
WebServer.htm -
altivar71.jpg 14,982
images/TelemecaniquePocketPC .gif
AtvChart.jar 15,479
html/config.js 418
main.css 314
Size
(bytes)
3,216
The total size is 176,426 bytes for a total of 47 files (excluding special HTML pages and parameters file).
The standard web server HTML pages have been designed for a 1024 × 768 minimum screen resolution.
67
17. SNMP agent
b Presentation
The SNMP protocol (Simple Network Management Protocol) is used to provide the data and services required for managing a network.
The data is stored in an MIB (Management Information Base). The SNMP protocol is used to read or write MIB data.
Implementation of the Ethernet card SNMP services is minimal, as only the required objects are handled.
Note: An SNMP agent can be configured to generate TRAPS to the SNMP Manager. TRAPS are used to signal a specific agent state (status, reset, etc.). The VW3A3310d Ethernet card does not handle TRAPS.
b Tree structure
68
17. SNMP agent
b Objects handled
Objects Description Access Default value
SysDescr Text description of the device R SCHNEIDER ATV Altivar Fast
SysObjectID Pointer to the product reference
in the private MIB
SysUpTime Time elapsed since the
Ethernet card was last turned on
SysContact Data item used to contact
the manager of this node
SysName Node administrative name R/W ATV
SysLocation Physical location of the product R/W -
SysService Indicates the type of service
offered by this product
The SysContact, SysName and SysLocation objects can be modified by the user. The values written are saved to the Ethernet card via an SNMP client not supplied with the VW3A3310d Ethernet card.
The size of these character strings is limited to 50 characters.
Using the “public” character string as a “community string” allows the user to access objects in “read only” mode, whereas the “schneider” character string enables read access to “read only” objects and write access to “R/W” objects.
R entreprises.3833.1.7.255.6
R-
R/W -
R72
Ethernet TCP/IP Module
69
18. Setup using PL7
b Defining the hardware configuration
Configure an Ethernet module, then configure the module so that it can communicate with the drive. The example shows a TSX Premium PLC equipped with a TSX ETY5103 module.
70
18. Setup using PL7
b BOOTP configuration
The BOOTP server function consists of allocating BOOTP clients their IP addresses.
The activation conditions for the drive BOOTP client are described in the “Configuration - IP Addresses” section.
This window is used to configure the BOOTP server.
The drive MAC address is given on a label attached to its VW3A3310d Ethernet card. The IP address assigned to the drive must be entered in the table against the MAC address.
In this example, the Ethernet card MAC address is 00.80.F4.7D.00.A3, and its IP address is 139.160.69.242.
Each line in the “Table of supplied addresses” can accept both the MAC and IP addresses of a BOOTP client.
71
18. Setup using PL7
b Configuring Modbus messaging
To use Modbus messaging in PL7, the “IP address”, “Subnet mask” and “Gateway address” parameters must be configured in the “Messaging” tab in the PLC Ethernet module configuration screen.
Data entered in the “Connection configuration” box is used to manage the PLC Modbus messaging service, but has no effect on IO Scanning which is an independent service.
Example:
PLC IP address 139.160.69.245
Subnet mask 255.255.254.0
Gateway address 139.160.68.1
Drive IP address 139.160.69.242
Xway address IP address Protocol Access Mode
1 1.101 139.160.69.242 MODBUS MULTI
72
18. Setup using PL7
b Configuring periodic variables
This window is used to configure the IO Scanning function, described in the IO Scanning Service section on page 40. In this example:
• The periodic variables of the drive at IP address 139.160.69.242 are associated with PLC data words.
• The drive periodic output variables (control) are associated with the 32 words (WR count) starting at PLC address %MW550 (Write Ref.).
• The drive periodic input variables (monitoring) are associated with the 32 words (RD count) starting at PLC address %MW500 (Read Ref.).
73
18. Setup using PL7
The addresses for the PLC %MW words correspond to the configuration in the previous example.
PLC address
%MW 550 Reserved no %MW 500 Reserved no
%MW 551 Control word (CMd) yes %MW 501 Status word (EtA) yes
%MW 552 Speed setpoint (LFrd) yes %MW 502 Output speed (rFrd) yes
%MW 553 Not assigned yes %MW 503 Not assigned yes
%MW 554 Not assigned yes %MW 504 Not assigned yes
%MW 555 Not assigned yes %MW 505 Not assigned yes
%MW 556 Not assigned yes %MW 506 Not assigned yes
%MW 557 Not assigned yes %MW 507 Not assigned yes
%MW 558 Not assigned yes %MW 508 Not assigned yes
%MW 559 Not assigned yes %MW 509 Not assigned yes
%MW 560 Not assigned yes %MW 510 Not assigned yes
%MW 561 to %MW 581
Periodic output variable (default assignment)
Reserved no
Configurable
PLC address
%MW 511 to %MW 531
Periodic input variable (default assignment)
Reserved no
Configurable
74
18. Setup using PL7
b Configuring the DHCP address server (FDR)
The DHCP server function consists of allocating BOOTP clients an IP address.
The activation conditions for the drive DHCP (FDR) client are described in the “Configuration - IP Addresses” section.
This window is used to configure the DHCP server.
The user must enter the following fields:
• “Name” to indicate the device name. In our example the ATV name is “ATV_0004”. This “name” corresponds to the FDR function DeviceName and the drive parameter [DEVICE NAME].
• “IP address” to indicate the device IP address. In our example the ATV IP address is “139.160.69.242”.
• “Netmask” to indicate the subnet mask. In our example the subnet mask is “255.255.254.0”.
• “Gateway” to indicate the gateway IP address. In our example the gateway IP address is “139.160.68.1”.
Each line in the “Table of supplied addresses” can accept both the names and IP addresses of a DHCP client.
75
19. Setup using Concept
b Hardware configuration
b Ethernet and I/O Scanner configuration
The screen illustrated below does not apply to the 140-NOE-771-10 master module. Note that the unit ID must be set to 251 for I/O scanner. The screen capture illustrated below incorrectly shows a Unit ID of 1.
76
20. Setup using ProWORX NxT
b Hardware configuration (Traffic Cop)
b Network configuration
77
20. Setup using ProWORX NxT
b TCP/IP configuration
b I/O Scanner configuration
Note that the unit ID must be set to 251 for I/O scanner. The screen capture illustrated below incorrectly shows a Unit ID of 1.
78
30072-452-37
2008-02
Loading...