Schneider Electric VTR8300 Data Sheet

Room Controllers
VTR8300 Line Voltage Fan Coil Controller with VC3000 Relay Pack
Technical Cut Sheet
Application specific room controller with customizable screen colors. The VTR8300 is a line-voltage fan coil terminal equipment controller with relay pack. Suitable for both commercial and high end hospitality markets.
The perfect balance between simplicity and sophistication. An elegantly simple casing combines with configurable screen colors to match decor. Display your own logo and custom messages on screen to reinforce your brand and provide a more enjoyable occupant experience.
Introduction
This two component retrot option consists of the VTR8300 room controller and the VC3000 relay pack. Together, they provide an easy solution for retrotting fan coil unit thermostats without requiring other components such as relays, transformers, controllers, sensors, and network wiring to be upgraded. Existing line voltage wiring between the fan coil unit and room controller can be reused to further minimize overall labor and installation costs for both retrot and new construction control projects. Additional exibility and energy savings can be achieved with optional wireless door and window switches.
Application specic and programmable
The VTR8300 room controllers are both application-specic AND programmable. This enables the modication of pre-congured control sequences, or the creation of entirely new control sequences
AT A GLANCE
Custom design
Touch screen with customizable user
experience
5 selectable screen colors out of the box
Supports the upload of a custom standby
screen
Supports the display of custom messages
when integrated to a BACnet system
English, French, Spanish, Chinese and other
languages selectable out of the box
One touch changes °C / °F
Options and accessories
VC3000 relay pack to interface with
line-voltage fan coil
On-board PIR occupancy sensor (optional)
RH sensor with dehumidification control
(optional)
Can be used with ZigBee Pro wireless sensors
Free downloadable Uploader VT8000 tool
for the upload of Lua Scripts, standby screen
images, and firmware upgrades, using a USB/
Micro-USB cable
Integration
Multiple options for integration to Building
Management Systems (BMS)
for HVAC, lighting and other applications. The room controllers are specically designed to provide exceptional temperature control of multi-speed fan coil units. When compared to traditional building automation room controllers, the VTR8300 series fan coil room controllers provide unmatched return on investment.
Touch screen with customizable user experience
The touch screen of the VTR8300 offers a customizable user experience with selection of languages, units, buttons, and screen colors. It also supports the upload of an image or logo that becomes the default standby screen of the device. Custom messages can also be displayed on-screen using BACnet objects when the VTR8300 is integrated to a BACnet system.
Optional passive infrared motion sensor
All models can be equipped with a discrete optional Passive Infrared (PIR) motion sensor. With the embedded sensor, the VTR8300 uses advanced occupancy routines to generate automatic energy savings during occupied and unoccupied periods without sacricing occupant comfort.
2
Product highlights
• Suitable for both commercial and hospitality markets
and systems
• Customizable color digital touch screen interface with
multi-language support
• Fully programmable control sequences using
scripting
• Humidity sensor with on-board dehumidication
strategy (model dependent)
• Optional occupancy sensor cover
• Advanced occupancy functions for commercial and
lodging applications
• Optional wireless door and window switches available
for wireless communicating models only
• Congurable fan sequence of operation
• On board conguration interface utility
• Congurable scheduler
• Change of value (COV) function for BMS integration
INTEGRATION
VTR8300
BACnet
MS/TP
ZigBee
Pro
ZigBee gat eway
device
3
Automation
Server
Networking between VTR8300
• ZigBee PRO wireless mesh network (P)
• BACnet MS/TP (B)
Integration to BMS systems
VTR8300 can be integrated with Building Management Systems
• Direct wired integration to BACnet MS/TP
• ZigBee Pro integration to ZigBee gateway device
• ZigBee gateway device integration to BACnet IP,
oBIX, and EWS
VC3000
For VC3000 relay pack features consult the VC3000 datasheet.
Architects and designers can match their decor
• Five screen colors are selectable through the interface
• Customizable standby screens and messages
> 5 configurable
screen colors
CUSTOM STANDBY SCREEN & MESSAGES
> Custom
standby screen
> Custom
BACnet MS/TP messages
4
Programming the VTR8300 with Lua
The VTR8300 room controllers are programmable using the open programming language Lua. Although building management systems often use open protocols and standards, their program BACnet objects and scripting features remain proprietary and incompatible with third party devices. The VTR8300 use of an open language enables interopreability with all systems.
Programming with BMS integration
When integrated into a BACnet MS/TP building management system, the VTR8300 offers 10 Program BACnet objects, each able to contain 480 characters. No special software, license or tool is required.
• BACnet MS/TP integration into BMS
• 10 Program BACnet objects (Lua scripts)
• Each object can contain 480 characters max
Programming without integration
When there is no BACnet MS/TP integration, a Lua script can be uploaded directly to the VTR8300 using the Uploader VT8000 tool. Unlike the 10 PG objects
used when the unit is integrated via BACnet MS/TP, there is only one script, which can contain up to 16KB.
• No BACnet MS/TP integration
• 1 Lua script of 16KB max
• Uploader VT8000 to upload scripts using PC
software tool and a USB/Micro-USB cable
HVAC applications and beyond
Programming can be used to go beyond the pre-congured control sequences of the VTR8300 to create customized HVAC applications. It can also be used to comply with specic project requirements and manage other applications, such as lighting and other equipment.
Using Lua scripts enables you to take advantage of the extra inputs and outputs of the VTR8300 to manage other devices, such as sensors and relays.
Uploader VT8000
Lua scripts, standby screen images and rmware upgrades can be loaded to the VTR8300 using the Uploader VT8000 tool and a USB/Micro-USB cable.
> PG objects of the
VTR8300 viewed through a BMS
> PG objects of the
VTR8300 viewed through its touch­screen display
Return air
3 Speed fan Cooling coil Heating coil
Supply air
Line Voltage Fan Control Units
The VTR8300 is congured to manage up to 10 different VC3000 relay packs, each controlling a line voltage fan coil installation. The diagram below shows an example of a typical line voltage fan coil application and how it would be wired to the relay pack controlled by the VTR8300.
TYPICAL APPLICATION
Filter status switch Fan status switch
Existing field wires
5
Optional Wireless
ZigBee® Communication
Bacnet® Communication
or
Optional Wired
VTR8300
FanCoil Terminal Equipment Controller
VC3504E5000
Optional Wireless Accessories
ZigBee® Pro
Optional wireless communication
SED-WDS Door & Window Swi tch
SED-CMS Ceiling Mounted Motion Sensor
SED-WMS Wall Mo unted Motion Sensor
VTR8300 Room Controller and VC3000 Relay Pack
Specifications
VTR8300 and VC3000
Dimensions
Height: 12cm/4.72in Width: 8.6cm/3.39in Depth: 2.7cm/1.06in
VC3000 Power Requirements
90 - 277 Vac universal, 50/60Hz
VTR8300 Power Requirements (supplied by VC3000)
7 Vdc
2.4 watts minimum
Operating Conditions
0 °C - 50 °C ( 32 °F - 122 °F ) 0% - 95% R.H. non-condensing
Storage Conditions
-30 °C - 50 °C ( -22 °F - 122 °F ) 0% - 95% R.H. non-condensing
Temperature Sensor
Local 10 K NTC type 2 thermistor
Temperature Sensor Resolution
± 0.1 °C ( ± 0.2 °F )
Temperature Control Accuracy
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
Humidity Sensor and Calibration
Single point calibrated bulk polymer type
sensor
Humidity Sensor Precision
Reading range from 10-90 % R.H. non­condensing 10 to 20% precision: 10% 20% to 80% precision: 5% 80% to 90% precision: 10%
Humidity Sensor Stability
Less than 1.0 % yearly (typical drift)
Dehumidication Setpoint Range
30% - 95% R.H.
Occ, Stand-By and Unocc Cooling Setpoint Range
12.0 - 37.5 °C ( 54 - 100 °F )
Occ, Stand-By and Unocc Heating Setpoint Range
4.5 °C - 32 °C ( 40 °F - 90 °F )
Room and Outdoor Air Temperature Display Range
-40 °C - 50 °C ( -40 °F - 122 °F )
Proportional Band for Room Temperature
control
Cooling & Heating: Default: 1.8°C ( 3.2°F )
Binary Inputs
Dry contact across terminal BI1, BI2 and UI3 to Scom
Wire Gauge
Power supply: 18 gauge or larger, Communications: 24 gauge or larger
Fan Line Voltage Contact Electrical Ratings
Brown, Blue, Red wires 1/2 HP or 13A maximum.
Approximate Shipping Weight
0.34 kg (0.75 lb)
Main Heat Voltage Electrical Ratings
Orange wire, 10A maximum
Cool Line Voltage Electrical Ratings
Yellow wire, 5A maximum
Output Ratings
Fan: Brown, Blue, Red wires 1/2 HP or 13A at 277Vac maximum.
Safety Standards All Models
UL 61010 - 1 (3rd edition) CSC 61010 - 1 (3rd edition) IEC 61010 - 1 (3rd edition)
EMC Standards All Models
EMC Directive 2004/108/EC IEC 61326-1:2005 FCC 15 Subpart B ICES-003
Radio Standards (Wireless Models)
R&TTE Directive 1999/5/EC IEC 61326-1:2005 EN 301 489-1 V1.9.2 EN 301 328 V1.8.1 FCC 15 Subpart C
RSS 210
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFER­ENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Check with your local govern­ment for instruction on disposal of these products.
5
Dimensions
120mm (4.72”)
86mm (3.39”)
27mm (1.06”)
VTR8300 Room Controller and VC3000 Relay Pack
Ordering information
B
VTR83 5 05 0
RH sensor and control
-00 = No RH sensor or control
-50 = RH sensor with dehumidification control
A
PIR:
-0 = No PIR
-5 = PIR on board
05
Network
-B = BACnet
(ZigBee module available separately)
®
MS/TP
Pro communication
6
Part numbers
VTR8300
Part numbers
VTR8300A5000B
VTR8350A5000B x
VTR8300A5500B x
VTR8350A5500B x x
VTR8300A5000BLTD
RH sensor &
control
PIR motion
ZigBee® Pro communication module (ordered separately) VCM8000V5000P
Part numbers
sensor
ZigBee Wireless Communication Modules
VC3000 Relays
Consult their respective datasheets for the latest available part numbers and features
Vicon ics Techno logie s Inc.
028-0453 -02 April 2 015
© 2015 Viconics Technologies Inc. All rights reserved.