VTR8300 Line Voltage Fan Coil
Controller with VC3000 Relay Pack
Technical Cut Sheet
Application specific room controller with customizable
screen colors. The VTR8300 is a line-voltage fan coil terminal
equipment controller with relay pack. Suitable for both
commercial and high end hospitality markets.
VTR8300 Room Controller and VC3000 Relay Pack Features
The perfect balance between simplicity and sophistication.
An elegantly simple casing combines with configurable
screen colors to match decor. Display your own logo and
custom messages on screen to reinforce your brand and
provide a more enjoyable occupant experience.
Introduction
This two component retrot option consists of the VTR8300 room
controller and the VC3000 relay pack. Together, they provide an
easy solution for retrotting fan coil unit thermostats without requiring
other components such as relays, transformers, controllers, sensors,
and network wiring to be upgraded. Existing line voltage wiring
between the fan coil unit and room controller can be reused to further
minimize overall labor and installation costs for both retrot and new
construction control projects. Additional exibility and energy savings
can be achieved with optional wireless door and window switches.
Application specic and programmable
The VTR8300 room controllers are both application-specic AND
programmable. This enables the modication of pre-congured
control sequences, or the creation of entirely new control sequences
AT A GLANCE
Custom design
•
Touch screen with customizable user
experience
•
5 selectable screen colors out of the box
• Supports the upload of a custom standby
screen
•
Supports the display of custom messages
when integrated to a BACnet system
•
English, French, Spanish, Chinese and other
languages selectable out of the box
•
One touch changes °C / °F
Options and accessories
•
VC3000 relay pack to interface with
line-voltage fan coil
•
On-board PIR occupancy sensor (optional)
• RH sensor with dehumidification control
(optional)
•
Can be used with ZigBee Pro wireless sensors
• Free downloadable Uploader VT8000 tool
for the upload of Lua Scripts, standby screen
images, and firmware upgrades, using a USB/
Micro-USB cable
Integration
•
Multiple options for integration to Building
Management Systems (BMS)
for HVAC, lighting and other applications. The room controllers are
specically designed to provide exceptional temperature control of
multi-speed fan coil units. When compared to traditional building
automation room controllers, the VTR8300 series fan coil room
controllers provide unmatched return on investment.
Touch screen with customizable user experience
The touch screen of the VTR8300 offers a customizable user
experience with selection of languages, units, buttons, and screen
colors. It also supports the upload of an image or logo that becomes
the default standby screen of the device. Custom messages can also
be displayed on-screen using BACnet objects when the VTR8300 is
integrated to a BACnet system.
Optional passive infrared motion sensor
All models can be equipped with a discrete optional Passive Infrared
(PIR) motion sensor. With the embedded sensor, the VTR8300 uses
advanced occupancy routines to generate automatic energy savings
during occupied and unoccupied periods without sacricing occupant
comfort.
2
VTR8300 Room Controller and VC3000 Relay Pack Features
Product highlights
• Suitable for both commercial and hospitality markets
and systems
• Customizable color digital touch screen interface with
multi-language support
• Fully programmable control sequences using
scripting
• Humidity sensor with on-board dehumidication
strategy (model dependent)
• Optional occupancy sensor cover
• Advanced occupancy functions for commercial and
lodging applications
• Optional wireless door and window switches available
for wireless communicating models only
• Congurable fan sequence of operation
• On board conguration interface utility
• Congurable scheduler
• Change of value (COV) function for BMS integration
INTEGRATION
VTR8300
BACnet
MS/TP
ZigBee
Pro
ZigBee gat eway
device
3
Automation
Server
Networking between VTR8300
• ZigBee PRO wireless mesh network (P)
• BACnet MS/TP (B)
Integration to BMS systems
VTR8300 can be integrated with Building Management
Systems
• Direct wired integration to BACnet MS/TP
• ZigBee Pro integration to ZigBee gateway device
• ZigBee gateway device integration to BACnet IP,
oBIX, and EWS
VC3000
For VC3000 relay pack features
consult the VC3000 datasheet.
Architects and designers can match their decor
• Five screen colors are selectable through the interface
• Customizable standby screens and messages
> 5 configurable
screen colors
CUSTOM STANDBY SCREEN & MESSAGES
> Custom
standbyscreen
> Custom
BACnet MS/TP
messages
VTR8300 Room Controller and VC3000 Relay Pack Features
4
Programming the VTR8300 with Lua
The VTR8300 room controllers are programmable
using the open programming language Lua.
Although building management systems often
use open protocols and standards, their program
BACnet objects and scripting features remain
proprietary and incompatible with third party
devices. The VTR8300 use of an open language
enables interopreability with all systems.
Programming with BMS integration
When integrated into a BACnet MS/TP building
management system, the VTR8300 offers 10
Program BACnet objects, each able to contain 480
characters. No special software, license or tool is
required.
• BACnet MS/TP integration into BMS
• 10 Program BACnet objects (Lua scripts)
• Each object can contain 480 characters max
Programming without integration
When there is no BACnet MS/TP integration, a Lua
script can be uploaded directly to the VTR8300 using
the Uploader VT8000 tool. Unlike the 10 PG objects
used when the unit is integrated via BACnet MS/TP,
there is only one script, which can contain up to 16KB.
• No BACnet MS/TP integration
• 1 Lua script of 16KB max
• Uploader VT8000 to upload scripts using PC
software tool and a USB/Micro-USB cable
HVAC applications and beyond
Programming can be used to go beyond the
pre-congured control sequences of the VTR8300 to
create customized HVAC applications. It can also be
used to comply with specic project requirements and
manage other applications, such as lighting and other
equipment.
Using Lua scripts enables you to take advantage
of the extra inputs and outputs of the VTR8300 to
manage other devices, such as sensors and relays.
Uploader VT8000
Lua scripts, standby screen images and rmware
upgrades can be loaded to the VTR8300 using the
Uploader VT8000 tool and a USB/Micro-USB cable.
> PG objects of the
VTR8300 viewed
through a BMS
> PG objects of the
VTR8300 viewed
through its touchscreen display
VTR8300 Room Controller and VC3000 Relay Pack Features
Return air
3 Speed fan Cooling coil Heating coil
Supply air
Line Voltage Fan Control Units
The VTR8300 is congured to manage up to 10 different VC3000 relay packs, each controlling a line voltage
fan coil installation. The diagram below shows an example of a typical line voltage fan coil application and how it
would be wired to the relay pack controlled by the VTR8300.
EMC Directive 2004/108/EC
IEC 61326-1:2005
FCC 15 Subpart B
ICES-003
Radio Standards (Wireless Models)
R&TTE Directive 1999/5/EC
IEC 61326-1:2005
EN 301 489-1 V1.9.2
EN 301 328 V1.8.1
FCC 15 Subpart C
RSS 210
THIS DEVICE COMPLIES WITH PART 15 OF
THE FCC RULES. OPERATION IS SUBJECT TO
THE FOLLOWING TWO CONDITIONS: (1) THIS
DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT
ANY INTERFERENCE RECEIVED, INCLUDING
INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
Check with your local government for instruction on disposal
of these products.
5
Dimensions
120mm (4.72”)
86mm (3.39”)
27mm (1.06”)
VTR8300 Room Controller and VC3000 Relay Pack
Ordering information
B
VTR835 050
RH sensor and control
-00 = No RH sensor or control
-50 = RH sensor with
dehumidification control
A
PIR:
-0 = No PIR
-5 = PIR on board
05
Network
-B = BACnet
(ZigBee
module available separately)
®
MS/TP
Pro communication
6
Part numbers
VTR8300
Part numbers
VTR8300A5000B
VTR8350A5000Bx
VTR8300A5500Bx
VTR8350A5500Bxx
VTR8300A5000BLTD
RH sensor &
control
PIR motion
ZigBee® Pro communication module
(ordered separately)
VCM8000V5000P
Part numbers
sensor
ZigBee Wireless Communication Modules
VC3000 Relays
Consult their respective datasheets for the latest