There are 7 different schedule setting screens, one for each day of the week, titled accordingly. Each day can have different
scheduled events where the room controller is set to Occupied status or back to Unoccupied status and use the appropriate
setpoints, back and forth up to 3 times per day.
Screen title is identied by
day of the week (Sunday
through Saturday)
PARAMETER DETAILS
Conguration parameters default valueSignicance and Adjustments
Occupied
Default value: None
Unoccupied
Default value: None
Denes a time when the room controller is automatically set to
use the Occupied setpoint.
Note: There are 3 separate Occupied parameter entries
Denes a time when the room controller is automatically set to
use the Unoccupied setpoint.
Note: There are 3 separate Unoccupied parameter entries
When ZigBee wireless sensors are set up to communicate with a Room Controller, the functioning of each such sensor is
described in a separate Zone screen, up to a maximum of 10 Zones. Select the appropriate type of sensor based on the required
functioning using the up and down arrow keys.
Up to 10 separate
wireless sensors
can be congured,
each with its own
Zone screen
Identical to ZigBee
settings display
parameter, see
page 11
PARAMETER DETAILS
Conguration parameters default valueSignicance and Adjustments
Set function to
Describe function of specied wireless sensor
Default value: None
Status
Current status of information received from the sensor
Read only
Battery
Current status of sensor battery, if any.
Read only
Paired
Sensor pairing state
Read only
Only last 4 digits
in HEX shown
None: No sensor function congured for this zone
Door: Sensor is a door contact switch
Window: Sensor is a window contact switch
Motion: Sensor is a motion sensor
Status: Updates the BACnet status of the sensor, but no action
is taken by the internal logic of the controller.
Remove: Selecting this function clears the zone of the settings
for the attached sensor. However, the sensor will automatically
try to reconnect with the room controller unless it is manually
reset as well.
Close: Sensor in closed state (door/window only)
Open: Sensor in opened state (door/window only)
No motion: Sensor detects no motion (motion sensor only)
if not init theninit=truedelay=0endif ME.BV1==1 thenME.BO98=1delay=60
2/3 LUA
Debug log:
Program cmd
Program status
Program error
Run
Running
No error
LUA SETTINGS
The LUA settings screens show information about any custom LUA script uploaded to the controller. LUA scripts are not
programmable on the controllers, and so must be uploaded to the controllers.
The title of the LUA script
is shown here
The body of the LUA
script is shown here
9
PARAMETER DETAILS
Conguration parameters default valueSignicance and Adjustments
Program cmd
Default value: Run
Program status
Read only
Program error
Read only
Run: The LUA script is activated and will run continuously until
deactivated.
Stop: The LUA script is deactivated
Running: The LUA script is current active
Halted: The LUA script has been stopped and is not active.
Idle: The LUA script is running but is not currently taking any
actions
Waiting: The LUA script is running and waiting for a response.
No error: No errors in the LUA script are detected.
Syntax: A syntax error in the LUA script is detected
Runtime: A runtime error has occurred while running the LUA
script.
Memory: The device has run out of memory for the script
The LUA settings include six generic parameters that do not have predened values. These can be used to represent LUA script
variables. They are user congurable in their default state, but when they are assigned a value by a LUA script they become read
only, and the display colour of the parameter changes to red. These parameters are also modiable through BACnet as Analog Values
(AVs). These parameters can be congured to receive information from ZigBee sensors.
PARAMETER DETAILS
Conguration parameters default valueSignicance and Adjustments
Parameter A
Default value: 0
Default value can be changed by user
Parameter B
Default value: 0
Default value can be changed by user
Parameter C
Default value: 0
Default value can be changed by user
Parameter D
Default value: 0
Default value can be changed by user
Parameter E
Default value: 0
Default value can be changed by user
Parameter F
Default value: 0
Default value can be changed by user
5
A parameter dened by a LUA
script displays in red text.
The default value is normally 0,
but it can be user-congured to
use a different default value.
AV25
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV26
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV27
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV28
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV29
The value(s) of this parameter depends on what is assigned to it
using the LUA script function
AV30
The value(s) of this parameter depends on what is assigned to it
ZigBee Pro set-up screen shows when a ZigBee wireless adapter module is detected in the model. Select the
desired parameter and use the up or down arrow to set the parameter to the desired value.
1/3 Zigbee network
COM address254
Node typeRouter
ZigBee PAN ID25
ZigBee® Pro short
ZigBee channel15
ZigBee short0x0000
address. The address is
generated once the device
joins a ZigBee® network.
11
Note: To change the value of
a parameter, simply press on
the parameter name or value
and then use the arrow keys
to change the value.
Previous
Page
ZigBee statusNo NWK
Next
Page
Back to
Setup Page
Change Value
( see note )
Status of controller
detecting a ZigBee®
network. Will display
Online when connected
successfully to network.
PARAMETER DETAILS
Conguration parameters default valueSignicance and adjustments
COM address
Terminal Equipment
Controller networking address
Default value = 254
Range is: 0 to 254
ZigBee® Pan IDPersonal Area Network Identication
Default value = 0
Range is: 1 to 1000
For wireless models, the use of the COM address is not
mandatory. The COM address is an optional way to identify a
device on the network and is recommended if used with a MPM.
It is Mandatory for BACnet.
This parameter (PAN ID) links specic Terminal Equipment
Controllers to specic ZigBee® coordinators. For every Terminal
Equipment Controller reporting to a coordinator, make sure you
set the SAME channel value both on the coordinator and the
Terminal Equipment Controller(s).
The default value of 0 is NOT a valid PAN ID.
The valid range of available PAN ID is from 1 to 1000.
Range 1 to 500 for centralized networked applications using a
ZigBee® Coordinator.
Range 501 to 1000 is for stand-alone applications where each
controller is its own coordinator for stand alone installation of
wireless door and window switches.
These parameters are only displayed
on models with built in humidity sensor
VTR8300 SeriesUser Interface Guide
PARAMETER DETAILS SCREEN 3/7
Conguration parameters default valueSignicance and adjustments
Standby time
Default 0.5 hours
Unocc. time
Default 0.0 hours
Temp. occ. time
Default value = 2 hours
Standby Time
Time delay between the moment where the PIR cover detects
last movement in the area, and the time which the Terminal
Equipment Controller stand-by setpoints become active.
Range: 0.5 to 24.0 hours in 0.5 hours increments.
Unoccupied Time
Time delay between the moment where the Terminal Equipment
Controller toggles to stand-by mode, and the time which the
Terminal Equipment Controller unoccupied mode and setpoints
become active.
Factory value 0.0 hours: Setting this parameter to its default
value of 0.0 hours disables the unoccupied timer. This prevents
the Terminal Equipment Controller to drift from stand-by mode to
unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours in 0.5 hours increments.
Temporary Occupancy Time
Temporary occupancy time with occupied mode setpoints when
override function is enabled.
When Terminal Equipment Controller is in unoccupied mode,
function is enabled with either the menu or BI2 congured as
Conguration parameters default valueSignicance and adjustments
Cool CPH
Default value = 4 C.P.H.
Heat CPH
Default value = 4 C.P.H.
Cooling valve
Default value = NC
Heating valve
Default value = NC
Cooling output cycles per hour
Will set the maximum number cycles per hour under normal control operation.
It represents the maximum number of cycles that the equipment will turn ON
and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the
expense of wearing mechanical components faster.
Range is: 3, 4, 5, 6,7 & 8 C.P.H.
Heating output cycles per hour
Sets the maximum number cycles per hour under normal control operation. It
represents the maximum number of cycles that the equipment will turn ON and
OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the
expense of wearing mechanical components faster.
Range is: 3, 4, 5, 6,7 & 8 C.P.H.
Sets the type of valve used for cooling
NC = Valve is normally closed when no power is present.
NO = Valve is normally opened when no power is present.
Sets the type of valve used for heating.
NC = Valve is normally closed when no power is present.
NO = Valve is normally opened when no power is present.
Conguration parameters default valueSignicance and adjustments
Prop. band
Default value= 3
Proportional Band Setting
Adjusts proportional band used by the Terminal Equipment Controller PI
control loop.
Note: default value of 3.0 gives satisfactory operation in most normal
installation cases. The use of a superior proportional band different than the
factory one is normally warranted in applications where Terminal Equipment
Controller location is problematic and leads to unwanted cycling of the unit. A
typical example is a wall mounted unit where Terminal Equipment Controller
is installed between return and supply air feeds and is directly inuenced by
Conguration parameters default valueSignicance and adjustments
Pulsed heating
Default value = Off
No. of pipes
Default is: 2 Pipes
Operation seq.
Default is: Heating only
Cool
HeatHeating onlyHeating only
Ht-Cl
VDC output conguration. VC3000 series model dependent.
Off = Regular On-Off control for VC350xE models only.
Can be used with 2 & 4 pipes applications.
On = VDC SSR electric heat 10 second pulsed time base modulation for
VC340xE models only.
Can only be used with 2 pipes system only.
Occ Out = VDC Occupancy output follows local device occupancy for
VC3514E model only.
• Occupied & Temporary Occupied = Contact closed
• Stand-By & Unoccupied = Contact opened
Number of pipes
Denes the type of system installed.
Operation sequence
Selects the initial sequence of operation required by the installation type and
the application.
2 Pipes4 Pipes
Cooling onlyCooling only
Cooling with electric reheatHeating / Cooling
25
Ht-RhtHeating with electric reheat---
ReheatElectric reheat only---
For 2 Pipe output applications, the system access is limited if RUI 1 is
congured for local changeover COS, COC/NC or COC/NC. The current
water temperature detected by the RUI 1 then limits the system mode
available for the local conguration or network write.
For sequence “electric reheat”, set PulsedHt to "On" to enable pulsed electric
reheat applications with VC3400E & VC3404E.
Purge sample
Default is: 2 hrs
Time interval between valve samples. Will open valve for a short period
adjusted by “Purge open” parameter in order to sample pipe temperature to
decide between heating or cooling mode.
Adjustable from 0 to 4 hrs.
(0 = disable this function).
Purge open
Default is: 2 min
Time the valve will open to sample pipe temperature (to decide between
This parameter is only displayed on
models with built in humidity sensor
VTR8300 SeriesUser Interface Guide
6/7 Configuration
Main password0
User password0
Schedule menuEnable
Calib. temp.0.0 °C
Calib. humid.0.0 %RH
PARAMETER DETAILS
Conguration parameters default valueSignicance and adjustments
Main password
Default value = 0
User password
Default value = 0
Calib. temp.
Default value = 0.0 °C or °F
Calib. humid.
Default value = 0 %RH
Installer password
This parameter sets a protective access password to prevent unauthorized
access to the conguration menu parameters. A default value of “0” will not
prompt a password or lock the access to the conguration menu.
Range is: 0 to 9999.
User password
This parameter sets a protective access password to prevent user unauthorized
access to main screen adjustments. A default value of “0” will not prompt for a
password.
Range is: 0 to 9999.
Room temperature sensor calibration
Offset that can be added/subtracted to actual displayed room temperature.
Range is: ± 2.5 °C, 0.1 °C increments ( ± 5.0 °F, 0.1 °F increments ).
Humidity sensor calibration
Offset that can be added/subtracted to actual displayed humidity.
Conguration parameters default valueSignicance and adjustments
Unocc. cool
Default value = 26.5 °C (80 °F)
Standby cool
Default value = 25.5 °C (78 °F)
Occ. cool
Default value = 24.0 °C (74 °F)
Occ. heat
Default value = 22.0 °C (72 °F)
Standby heat
Default value = 20.5 °C (69 °F)
Unocc. heat
Default value = 16.5 °C (62 °F)
Unoccupied cooling setpoint
Range is: 12.0 to 37.5 °C (54 to 100 °F)
Standby cooling setpoint
The value of this parameter should be set between the occupied
and unoccupied cooling setpoints. Make sure that the difference
between the stand-by and occupied value can be recovered in a
timely fashion when movement is detected in the zone.
Stand-by cooling setpoint range is: 12.0 to 37.5 °C ( 54 to 100 °F
).
Occupied cooling setpoint
Range is: 12.0 to 37.5 °C (54 to 100 °F).
Occupied heatling setpoint
Range is: 12.0 to 37.5 °C (54 to 100 °F).
Stand-by heating setpoint
The value of this parameter should be set between the occupied
and unoccupied heating setpoints. Make sure that the difference
between the stand-by and occupied value can be recovered in a
timely fashion when movement is detected in the zone.
Stand-by heating setpoint range is: 4.5 to 32.0 °C ( 40 to 90 °F ).
Cooling mode or cooling only
sequence of operation
In Cooling mode, the setpoint displayed in the bar is the
current occupied cooling setpoint.
During occupied setpoint adjustment, the large digits are
temporarily used to display the occupied cooling setpoint
while it is adjusted.
Normal temperature display resumes after the setpoint
is adjusted and the actual occupied cooling setpoint is
displayed in the setpoint bar.
Heating mode or heating only
sequence of operation
In Heating mode, the setpoint displayed in the bar is the
current occupied heating setpoint.
During occupied setpoint adjustment, the large digits are
temporarily used to display the occupied heating setpoint.
Normal temperature display resumes after the setpoint
is adjusted and the actual occupied heating setpoint is
displayed in the setpoint bar.
Automatic Heating / Cooling mode
In automatic mode, the setpoint displayed at the top
of the set point bar located directly under the blue line
represent the actual occupied cooling setpoint.
During occupied setpoints adjustment, the large digits
are temporarily used to display the occupied “Cooling
Setpoint” or occupied “Heating Setpoint”. The actual
setpoint is dependent on the last effective demand
(heating or cooling).
Normal temperature display resumes after the
setpoints are adjusted and the actual occupied heating
and cooling setpoints are displayed in the setpoint bar.
Conguration parameters default valueSignicance and adjustments
Night backlight
Default value = 5%
RH display
Default value = Disabled
Night Backlight Display
Set display backlight intensity after 2 minutes of keyboard inactivity.
Adjustable: 0 to 100%.
Parameter only available for models with motion/light detectors.
The screen backlight progressively decreases down to this setting when room is dark. This feature is used mostly in hospitality
applications when a darker non obtrusive lighting level is desired
when room is dark.
Relative Humidity Display
Enables display of humidity below room temperature on the
display
Note: This represents the
BACnet® device name
automatically assigned
using the current
BACnet® MAC address.
The network can
update and change the
device BACnet® name.
If changed, the new
updated BACnet® device
name will be shown
VTR8300 SeriesUser Interface Guide
39
TEST OUTPUTS SCREEN
1/1 Test outputs
Cooling output
(see note 1)
High speed
fan output
Low speed
fan output
Note 1: Cooling output can also be used for heating on two pipes systems.
See note 2
Heating output
Medium speed
output
Pulsed heating demand
Note 2: The test output screen allows manual override of specied outputs. When any BACnet® network
priority array includes a value, the status background is shown in red. After any output state is overridden,
the command is cancelled after 1 min of screen inactivity (auto exit to main screen) or when page is exited.
Please refer to the BACnet® integration guide for more details.
Only English, French, Spanish, Chinese and Russian are enabled by default, which means that they will be accessible to users cycling
through languages on the display settings menu screen. To change the language selection settings, touch a language on the screen
and then use the arrow buttons to disable or enable it. The English language is always enabled.