Schneider Electric VT2212G13A020 Catalog Page

Page 1
PopTop™ 2-Position Zone Valves
Erie’s line of motorized hydronic valves, the PopTop, provides convenient, reliable, and easy installation for a variety of heating and cooling applications. The PopTop makes installation a snap with easy, one-handed removal or engagement of the actuator to the valve body.
Features:
• Brass forged 300 psig rated body
• Meets or exceeds ANSI IV standard for close off
• Wide variety of Cv’s for better control
• 2-way and 3-way
POPTOP VALVE BODIES
PopTop valves are designed for two position (on/off) control of fl uid fl ow in a wide variety of heating and cooling applications.
2-way
Model Connection Cv
VT2211 1/2” Sweat 1.0 VT2212 2.5 VT2213 3.5
VT2221 1/2” NPT 1.0 VT2222 2.5 VT2223 3.5
VT2312 3/4” Sweat 2.5 VT2313 3.5 VT2315 5.0 VT2317 7.5
VT2322 3/4” NPT 2.5 VT2323 3.5 VT2325 5.0 VT2327 7.5
VT2413 1” Sweat 3.5 VT2415 5.0
VT2417 7.5 VT2427 1” NPT 8.0 VT2517 1-1/4” Sweat 8.0 VT2341 3/4” Inverted fl are 1.0 VT2342 2.5 VT2343 3.5
3-way
Model Connection Cv
VT3211 1/2” Sweat 1.5 VT3212 3.0 VT3213 4.0
VT3221 1/2” NPT 1.5 VT3222 3.0 VT3223 4.0
VT3312 3/4” Sweat 3.0 VT3313 4.0 VT3315 5.0 VT3317 7.5
VT3322 3/4” NPT 3.0 VT3323 4.0 VT3325 5.0 VT3327 7.5
VT3413 1” Sweat 4.0 VT3415 5.0
VT3417 7.5 VT3427 1” NPT 8.0 VT3517 1-1/4” Sweat 8.0 VT3341 3/4” Inverted fl are 1.5 VT3342 3.0 VT3343 4.0
Options Steam - High Temperature VSxxxx Must be used with High Temperature Actuator
3
Page 2
PopTop™ 2-Position Actuators
The following tables contain a complete listing of Erie 2-Position actuator combinations for 24 and 120 Vac. The same combinations are available for 208 Vac (D designator) and 230 Vac (U designator). The end switch option, (designated by the A at the end of the part #) is not available in the combination of 277 Vac with high temperature.
Features:
• Sized to fi t most baseboard applications.
• Terminal block option.
• UL Listed
GENERAL CLOSE-OFF (GCO) ACTUATORS
2-way
Model Action Voltage Options
AG13A020 On/Off 24 Vac 18” leads AG13A01A On/Off 24 Vac Terminal block, end switch AG13A02A On/Off 24 Vac 18” leads, end switch AG14A020 On/Off 24 Vac Steam, 18” leads AG14A00A On/Off 24 Vac Steam, end switch AG14A02A On/Off 24 Vac Steam, 18” leads, end switch AG13B020 On/Off 120 Vac 18” leads AG13B02A On/Off 120 Vac 18” leads, end switch AG14B020 On/Off 120 Vac Steam, end switch AG14B02A On/Off 120 Vac Steam, 18” leads, end switch
Normally Open Actuators 2-way only
Model Action Voltage Options
AG23A020 On/Off 24 Vac 18” leads AG23A01A On/Off 24 Vac Terminal block, end switch AG23A02A On/Off 24 Vac 18” leads, end switch AG24A020 On/Off 24 Vac Steam, 18” leads AG24A02A On/Off 24 Vac Steam, 18” leads, end switch AG23B020 On/Off 120 Vac 18” leads AG23B02A On/Off 120 Vac 18” leads, end switch AG24B020 On/Off 120 Vac Steam, end switch AG24B00A On/Off 120 Vac AG24B02A On/Off 120 Vac Steam, 18” leads, end switch
Steam, terminal block, end switch
Features:
• Offers same great features of the General Close-off actuator plus up to 25% more close-off pressure rating.
• Close-off up to 75 psi.
• UL Listed
HIGH CLOSE-OFF (HCO) ACTUATORS
2-way
Model Action Voltage Options
AH13A020 On/Off 24 Vac 18” leads AH13A01A On/Off 24 Vac Terminal block, end switch AH13A02A On/Off 24 Vac 18” leads, end switch AH14A020 On/Off 24 Vac Steam, 18” leads AH14A00A On/Off 24 Vac Steam, end switch AH14A02A On/Off 24 Vac Steam, 18” leads, end switch AH13B020 On/Off 120 Vac 18” leads AH13B02A On/Off 120 Vac 18” leads, end switch AH14B020 On/Off 120 Vac Steam, end switch AH14B02A On/Off 120 Vac Steam, 18” leads, end switch
Normally Open Actuators 2-way only
Model Action Voltage Options
AH23A020 On/Off 24 Vac 18” leads AH23A01A On/Off 24 Vac Terminal block, end switch AH23A02A On/Off 24 Vac 18” leads, end switch AH24A020 On/Off 24 Vac Steam, 18” leads AH24A02A On/Off 24 Vac Steam, 18” leads, end switch AH23B020 On/Off 120 Vac 18” leads AH23B02A On/Off 120 Vac 18” leads, end switch AH24B020 On/Off 120 Vac Steam, end switch AH24B00A On/Off 120 Vac AH24B02A On/Off 120 Vac Steam, 18” leads, end switch
Steam, terminal block, end switch
4
Page 3
PopTop™ 2-Position Zone Valve Assemblies
Options VTxxxxxx3_020 200°F Max Hot Water Application
Select AC Voltage A-24, B-120, D-208, U-230, T-277 VSxxxxxx4_020 250°F Max Hot Water Application or 15 PSI Max Steam Application A High Temperature Actuator Must Be Used with VSXXXX
a — Normally closed to B-port
Options
• Normally Closed Option is available with 2- or 3-way assemblies
• Normally Open option is available with 2-way assemblies only
2-way normally open and additional combinations are also available, see bulletin F-26496.
Features:
• Factory assembled valve and actuator combinations.
• Quicker installation time and easier maintenance
• UL Listed
Features:
• Offers the same great features as the General Close-Off assemblies, plus up to 25% more close-off psi.
• UL Listed
GENERAL CLOSE-OFF (GCO) ASSEMBLIES
2-way Normally Closed GCO
Model Action Cv Close-off psig p
VT2211G13_020 1/2” Sweat 1.0 60 VT2212G13_020 2.5 40 VT2213G13_020 3.5 25
VT2221G13_020 1/2” NPT 1.0 60 VT2222G13_020 2.5 40 VT2223G13_020 3.5 25
VT2312G13_020 3/4” Sweat 2.5 40 VT2313G13_020 3.5 25 VT2315G13_020 5.0 20 VT2317G13_020 7.5 17
VT2322G13_020 3/4” NPT 2.5 40 VT2323G13_020 3.5 25 VT2325G13_020 5.0 20 VT2327G13_020 7.5 17
VT2415G13_020 1” Sweat 5.0 20 VT2417G13_020 7.5 17
VT2427G13_020 1” NPT 8.0 17 VT2517G13_020 1-1/4” Sweat 8.0 17 VT2343G13_020
3/4” Inverted Flare
3.5 25
3-way Valve Assembliesa GCO
Model Action Cv Close-off psig p
VT3211G13_020 1/2” Sweat 1.5 60 VT3212G13_020 3.0 40 VT3213G13_020 4.0 25
VT3221G13_020 1/2” NPT 1.5 60 VT3222G13_020 3.0 40 VT3223G13_020 4.0 25
VT3312G13_020 3/4” Sweat 3.0 40 VT3313G13_020 4.0 25 VT3315G13_020 5.0 20 VT3317G13_020 7.5 17
VT3322G13_020 3/4” NPT 3.0 40 VT3323G13_020 4.0 25 VT3325G13_020 5.0 20 VT3327G13_020 7.5 17
VT3415G13_020 1” Sweat 5.0 20 VT3417G13_020 7.5 17
VT3427G13_020 1” NPT 8.0 17 VT3517G13_020 1-1/4” Sweat 8.0 17 VT3343G13_020
Options VTxxxxxx3_020 200°F Max Hot Water Application
Select AC Voltage A-24, B-120, D-208, U-230, T-277 VSxxxxxx4_020 250°F Max Hot Water Application or 15 PSI Max Steam Application A High Temperature Actuator Must Be Used with VSXXXX
3/4” Inverted Flare
4.0 25
HIGH CLOSE-OFF (HCO) ASSEMBLIES
2-way Normally Closed HCO
Model Action Cv Close-off psig p
VT2211H13_020 1/2” Sweat 1.0 75 VT2212H13_020 2.5 50 VT2213H13_020 3.5 30
VT2221H13_020 1/2” NPT 1.0 75 VT2222H13_020 2.5 50 VT2223H13_020 3.5 30
VT2312H13_020 3/4” Sweat 2.5 50 VT2313H13_020 3.5 30 VT2315H13_020 5.0 25 VT2317H13_020 7.5 20
VT2322H13_020 3/4” NPT 2.5 50 VT2323H13_020 3.5 30 VT2325H13_020 5.0 25 VT2327H13_020 7.5 20
VT2415H13_020 1” Sweat 5.0 25 VT2417H13_020 7.5 20
VT2427H13_020 1” NPT 8.0 20 VT2517H13_020 1-1/4” Sweat 8.0 20 VT2343H13_020
3/4” Inverted Flare
3.5 30
3-way Valve Assembliesa HCO
Model Action Cv Close-off psig p
VT3211H13_020 1/2” Sweat 1.5 75 VT3212H13_020 3.0 50 VT3213H13_020 4.0 30
VT3221H13_020 1/2” NPT 1.5 75 VT3222H13_020 3.0 50 VT3223H13_020 4.0 30
VT3312H13_020 3/4” Sweat 3.0 50 VT3313H13_020 4.0 30 VT3315H13_020 5.0 25 VT3317H13_020 7.5 20
VT3322H13_020 3/4” NPT 3.0 50 VT3323H13_020 4.0 30 VT3325H13_020 5.0 25 VT3327H13_020 7.5 20
VT3415H13_020 1” Sweat 5.0 25 VT3417H13_020 7.5 20
VT3427H13_020 1” NPT 8.0 20 VT3517H13_020 1-1/4” Sweat 8.0 20 VT3343H13_020
a — Normally closed to B-port
Options
• Normally Closed Option is available with 2- or 3-way assemblies
• Normally Open option is available with 2-way assemblies only
3/4” Inverted Flare
4.0 30
5
Page 4
Part Numbering System
TWO POSITION ZONE VALVES, SPRING RETURN ACTUATORS
V X X X X X X X X X XX X
Body Type
T = On/Off General S = On/Off Steam* * High temperature actuator must be used.
Confi guration
2 = 2-way 3 = 3-way
Valve Size
2 = 1/2” 3 = 3/4” 4 = 1” 5 = 1-1/4”
Connection Type (Availability)
1 = Sweat (1/2”, 3/4”, 1”, 1-1/4”) 2 = Threaded NPT (1/2”, 3/4”, 1”) 3 = Threaded Rp, Metric (1/2”, 3/4”, 1”) 4 = Inverted fl are (1/2”) 5 = SAE fl are (1/2”)
Cv Size
2-way 3-way Size Connection
1 = 1.0 1.5 1/2” (1, 2, 3) 3/4” (4) 2 = 2.5 3.0 1/2” (1, 2, 3, 5) 3/4” (1, 2, 3, 4) 3 = 3.5 4.0 1/2” (1, 2, 3, 5) 3/4” (1, 2, 3, 4) 1” (1) 5 = 5.0 5.0 3/4” (1, 2, 3) 1” (1) 7 = 7.5 7.5 3/4” (1, 2, 3) 1” (1)
8.0 8.0 1” (2, 3) 1-1/4” (1)
Actuator Type
G = On/off, General Close-off (GCO) H = On/off, High Close-off (HCO)
Options
0 = No options
A = End switch
Electrical Leads
00 = 6” Motor wires 01 = Terminal block with End switch (24 Vac only) 02 = 18” (Standard) Wire leads
Voltage
A = 24 Vac, 50/60 Hz B = 110 Vac, 50 Hz and 120 Vac, 60 Hz D = 208 Vac, 50/60 Hz T = 277 Vac, 50/60 Hz U = 230 Vac, 50 Hz and 240 Vac, 60 Hz
Temperature Ratings
3 = General temperature
4 = High temperature
Action
1 = Spring Return Normally Closed (2- or 3-way)
2 = Spring Return Normally Opened (2-way only)
Cautions
When ordering valve body only: Use the fi rst six positions to confi gure the valve.
When ordering actuator only: Use the last seven positions to confi gure the actuator. Prefi x with the letter A.
Inverted fl are fi ttings must be ordered separately. See actuator accessories, bulletin F-26496, for fi tting part numbers.
End switch is not available for 277 Vac models if actuator temperature rating is high temperature.
Actuators with Terminal blocks require end switch and the end switch is 24 Vac at 101 mA min. to 5A max.
End switch is 24 - 240 Vac at 101 mA min to 5A max. and 9 to 30- Vdc at 100 mA max. for actuators rated 240 V or less. End switch is 277 Vac at 101 mA min. to 5A max. for actuators rated 277V.
Body and Actuator Combination: Temperature Confi gurations
Body Confi guration Actuator Spring Return Mode
VTXXXX AXX3XXXX T = General 3 = General temperature S = Steam 4 = High temperature If body confi guration is T, actuator temp rating can be 3 or 4. If actuator temp rating is 3, body style must be T. If body confi guration is S, actuator temp rating must be 4. If actuator temp rating is 4, body style can be S or T.
6
Loading...