Schneider Electric VSE 002 User Manual

Page 1
VSE 002
RS-485 module
Publication version: VVSE2/EN M/B006
User manual
Page 2
Table of Contents
2
VVSE2/EN M/B006
Table of Contents
1. General .................................................................................... 3
2. Power supply .......................................................................... 3
3. Module interface to the VAMP relays or master device ...... 3
4. RS-485 interface ..................................................................... 4
5. Module layout ......................................................................... 5
6. Module mounting ................................................................... 5
7. Module connection to a PC ................................................... 6
8. Ordering codes ....................................................................... 6
Page 3
1 General
VSE 002 External RS-485 Module
VVSE2/EN M/B006
3
Pin number
TTL mode
RS-232 mode
1 - -
2
RXD (in)
RXD (in)
3
TXD (out)
TXD (out)
4
RTS (in)
RTS (in)
5
6
7
GND
GND
8
9
+8V (in)
+8V (in)
The active state of the RTS signal is positive voltage (> +3V) in both TTL and RS-232 modes.

1. General

External RS-485 Module VSE 002 is used to connect VAMP protection relays to a RS-485 bus.
Additionally this module can be used with any device, which has a RS-232 or TTL serial interface, when an RS-485 interface is required.

2. Power supply

The power for the module is taken from pin 9 of the D-connector or from an external power supply interface. There is a screw terminal (X1, see figure 1) for connecting an external +9...12Vdc power supply.

3. Module interface to the VAMP relays or master device

The physical interface to the device is a 9-pin D-connector. The signal levels may be either TTL or RS-232.
The TTL/RS-232 interface of the modules is:
Page 4
VSE 002 External RS-485 Module
4 RS-485 interface
4
VVSE2/EN M/B006
Termination
ON
OFF
Interface type
TTL
RS-232

4. RS-485 interface

The RS-485 interface supports 2-wire connection. The dip switch S1 is used to switch the termination and signal biasing resistors on or off.
Figure 1. Dipswitch positions of VSE 002
The direction control of the RS-485 transceiver is done with the RTS signal or automatically. The automatic direction control turns the transceiver to transmit mode after detecting the falling edge of a 0-bit. The direction is kept in transmit mode for 0,5ms. This enables the use of the automatic mode with 9,6 kb/s and 19.2 kb/s speeds. When the transceiver is changed to receive mode, the RS-485 line changes state to logic 1 state due to the biasing resistors.
Page 5
5 Module layout
VSE 002 External RS-485 Module
VVSE2/EN M/B006
5

5. Module layout

Figure 2. Component layout

6. Module mounting

Figure 3. Mounting picture of module
Page 6
VSE 002 External RS-485 Module
7 Module connection to a PC
6
VVSE2/EN M/B006
PC serial interface
VSE 002
Function
Pin
number
Pin
number
Function CD (in)
1 1
-
RXD (in)
2 2
RXD (in)
TXD (out)
3 3
TXD (out)
DTR (out)
4 4
RTS (in) GND
5 5
-
DSR (in)
6 6
-
RTS (out)
7 7
GND CTS (in)
8 8
- - 9 9
+8V (in)

7. Module connection to a PC

The module can be used with a PC, the required cable is described in figure 4. When used with a PC an external power supply is needed (e.g. type Phoenix Contact 100 – 240 AC/10-15 DC/2, Order-No. 29 83 75 6).
Figure 4. PC interface cable

8. Ordering codes

VSE 002 RS-485interfacemodule
Page 7
Page 8
Schneider Electric
35 rue Joseph Monier 92506 Rueil-Malmaison FRANCE
Phone: +33 (0) 1 41 29 70 00 Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com
Publication version: VVSE2/EN M/B006