Schneider Electric Smart-UPS On-Line SRT1000, Smart-UPS On-LineSRT1500 Installation Guide

Installation Guide Smart-UPS™On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

Important Safety Messages

Read the instructions carefully to become familiar with the equipment before attempting to install, operate, service or maintain the UPS. The following special messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Warning or Caution product safety label indicates that a hazard exists that can result in injury and product damage if the instructions are not followed.
Information
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.

Safety and General Information

• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC could void the warranty.
• This UPS is intended for indoor use only.
• Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
• Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
• For a UPS with a factory installed power cord, connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• The batteries are heavy. Remove the batteries before installing the UPS and external battery packs (XLBPs), in a rack.
• Always install XLBPs at the bottom in rack-mount configurations. The UPS must be installed above the XLBPs.
• Always install peripheral equipment above the UPS in rack-mount configurations.
• Additional safety information can be found in the Safety Guide supplied with this unit.
Deenergizing safety
The UPS contains internal batteries and may present a shock hazard even when disconnected from the branch circuit (mains).
• input circuit breaker is in the OFF position.
• internal UPS batteries are removed.
• XLBP battery modules are disconnected.
Before installing or servicing the equipment check that the:
Electrical safety
• For models with a hardwired input, the connection to the branch circuit (mains) must be performed by a qualified electrician.
• The protective earth conductor for the UPS carries the leakage current from the load devices (computer equipment). An insulated ground conductor is to be installed as part of the branch circuit that supplies the UPS. The conductor must have the same size and insulation material as the grounded and ungrounded branch circuit supply conductors. The conductor will typically be green and with or without a yellow stripe.
• The UPS input ground conductor must be properly bonded to protective earth at the service panel.
• If the UPS input power is supplied by a separately derived system, the ground conductor must be properly bonded at the supply transformer or motor generator set.
Smart-UPS On-Line SRT1000/SRT1500 Tower/Rack-Mount 2U2
Battery safety
• When replacing batteries, replace with the same number and type of batteries as originally installed in the equipment.
• Batteries typically last for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short duration discharges will shorten battery life. Batteries should be replaced before end of life.
• Replace batteries immediately when the unit indicates battery replacement is necessary.
• Schneider Electric uses Maintenance-Free sealed Lead Acid batteries. Under normal use and handling, there is no contact with the internal components of the battery. Over charging, over heating or other misuse of batteries can result in a discharge of battery electrolyte. Released electrolyte is toxic and may be harmful to the skin and eyes.
• CAUTION: Before installing or replacing the batteries, remove jewelry such as wristwatches and rings. High short circuit current through conductive materials could cause severe burns.
• CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
• CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes and may be toxic.
General information
• The UPS will recognize as many as 10 external battery packs connected to the UPS.
Note: For each XLBP added, increased recharge time will be required.
• The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.
• Always recycle used batteries.
• Recycle the package materials or save them for reuse.
FCC Class A radio frequency warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are intended to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
3Smart-UPS On-Line SRT1000/SRT1500 Tower/Rack-Mount 2U

Package Contents

x4
su04
x4
x6
Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
Included with all models NC models only
Front bezel RJ45 to DB9 cable
User Documentation CD.
USB cable
PCBE Software CD
EPO Terminal block
Included with Tower models only
• 2 pairs stabilizer brackets
• 4 flat head screws to secure tower stabilizer brackets to the UPS
Temperature sensor probe
User Do cumen tati on
Serial configuration cable
Network Management Utility CD
Included with Rack-Mount models only
Rail Kit with instructions and hardware for installing rails in a rack.
34a
Smart-UPS On-Line SRT1000/SRT1500 Tower/Rack-Mount 2U4
• 1 pair rack-mount brackets
• 6 flat head screws to secure rack-mount brackets to the UPS
• 4 ornamental screws to secure rack-mount brackets to the rails

Specifications

For additional specifications refer to the APC by Schneider Electric web site, www.apc.com.
Environmental
Temperature Operating 0º to 40º C (32º to 104º F)
Storage -15º to 45º C (5º to 113º F)
Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
Protection Class IP 20 rating
Note: Charge the battery modules every six months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power, and frequent short duration discharges will shorten battery life.
Physical
SRT1000XLA/SRT1000RMXLA/SRT1000RMXLA-NC SRT1500XLA/SRT1500RMXLA/SRT1500RMXLA-NC model
The UPS is heavy. Follow all lifting guidelines.
Lifting guidelines 18 - 32 kg (40 - 70 lb) 32 - 55 kg (70 - 120 lb)
Unit weight batteries included, without packaging 22 kg (48.5 lb)
Unit weight batteries included, with packaging Rack-Mount models: 29.6 kg (65.26 lb)
Tower models: 26.9 kg (59.3 lb)
Unit dimensions without packaging Height x Width x Depth
Unit dimensions with packaging Height x Width x Depth
The model and serial numbers are on a small label located on the rear panel.
85 (2U) mm x 432 mm x 505 mm
3.35 (2U) in x 17 in x 20 in
245 mm x 595 mm x 750 mm
9.7 in x 23.4 in x 29.5 in
5Smart-UPS On-Line SRT1000/SRT1500 Tower/Rack-Mount 2U