Always go to www.se.com for the latest update and localized versions of the manual
1/2021
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Connect the Signal Cables...................................................................... 37
Connect the Power Cables...................................................................... 40
990-5997D-0013
Important Safety Instructions — SAVE THESE
INSTRUCTIONSBattery Breaker Kit
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-5997D-0015
Battery Breaker Kit
Electromagnetic Compatibility
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category C3 according to IEC 62040-2. This is a product for
commercial and industrial applications in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances. The
second environment includes all commercial, light industry, and industrial
locations other than residential, commercial, and light industrial premises
directly connected without intermediate transformer to a public low-voltage
mains supply. The installation and cabling must follow the electromagnetic
compatibility rules, e.g.:
•the segregation of cables,
•the use of shielded or special cables when relevant,
•the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the installation manual before installing or working on
this product.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the product until all construction work has been completed and the
installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements
as defined by Schneider Electric. It concerns in particular the external and
internal protections (upstream breakers, battery breakers, cabling, etc.) and
environmental requirements. No responsibility is assumed by Schneider Electric
if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
6990-5997D-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONSBattery Breaker Kit
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
•IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
•NEC NFPA 70, or
•Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Install the product in a temperature controlled indoor environment free of
conductive contaminants and humidity.
•Install the product on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product is not designed for and must therefore not be installed in the
following unusual operating environments:
•Damaging fumes
•Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
•Moisture, abrasive dust, steam or in an excessively damp environment
•Fungus, insects, vermin
•Salt-laden air or contaminated cooling refrigerant
•Pollution degree higher than 2 according to IEC 60664-1
•Exposure to abnormal vibrations, shocks, and tilting
•Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the installation manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
990-5997D-0017
Battery Breaker Kit
Electrical Safety
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the product and do not cover the
ventilation openings when the product is in operation.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
•Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
•Turn off all power supplying the UPS system before working on or inside the
equipment.
•Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
•The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the mains supply. Before installing or
servicing the UPS system, ensure that the units are OFF and that mains and
batteries are disconnected. Wait five minutes before opening the UPS to
allow the capacitors to discharge.
•A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. The disconnection device must be easily
accessible and visible.
•The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
In systems where backfeed protection is not part of the standard design, an
automatic isolation device (backfeed protection option or other device meeting
the requirements of IEC/EN 62040–1 or UL1778 5th Edition – depending on
which of the two standards apply to your local area) must be installed to prevent
hazardous voltage or energy at the input terminals of the isolation device. The
device must open within 15 seconds after the upstream power supply fails and
must be rated according to the specifications.
Failure to follow these instructions will result in death or serious injury.
When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remote from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):
8990-5997D-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONSBattery Breaker Kit
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective
earth.
Failure to follow these instructions will result in death or serious injury.
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
•Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
•Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
•Disconnect charging source prior to connecting or disconnecting battery
terminals.
•Do not dispose of batteries in a fire as they can explode.
•Failed batteries can reach temperatures that exceed the burn thresholds for
touchable surfaces.
•Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries:
•Remove watches, rings, or other metal objects.
•Use tools with insulated handles.
•Wear protective glasses, gloves, and boots.
•Do not lay tools or metal parts on top of batteries.
•Disconnect the charging source prior to connecting or disconnecting battery
terminals.
•Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock and burns by high short-circuit current. The likelihood
of such shock can be reduced if such grounds are removed during
installation and maintenance by a skilled person (applicable to equipment
and remote battery supplies not having a grounded supply circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs. Refer to the label in the classic battery cabinet for
information on batteries in your system.
Failure to follow these instructions will result in death or serious injury.
990-5997D-0019
Battery Breaker Kit
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
CAUTION
RISK OF EQUIPMENT DAMAGE
•Wait until the system is ready to be powered up before installing batteries in
the system. The time duration from battery installation until the UPS system
is powered up must not exceed 72 hours or 3 days.
•Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period, we
recommend that you energize the UPS system for a period of 24 hours at
least once every month. This charges the batteries, thus avoiding
irreversible damage.
Failure to follow these instructions can result in injury or equipment
damage.
10990-5997D-001
SpecificationsBattery Breaker Kit
Specifications
NOTICE
HAZARD OF EQUIPMENT DAMAGE
Refer to the UPS installation manual for detailed specifications for the UPS
system.
Failure to follow these instructions can result in equipment damage.
Battery Breaker Kit Specifications
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This product must only be used with the Easy UPS 3M and Easy UPS 3L.
Failure to follow these instructions will result in death or serious injury.
NOTE: A maximum of four battery strings can be connected to the battery
breaker.
E3MBBK60K80HE3MBBK100K200H
Battery breakerCompact NSX250S DC (LV438990)Compact NSX630S DC (LV438274)
Maximum configuration4 hours runtime4 hours runtime for 40–50 battery blocks
Battery typeVRLA
Maximum battery short-circuit level (kA)20 kA
Minimum short-circuit current to trip the
circuit breaker (A)
12501500
1 hour runtime for 36–38 battery blocks
Battery Breaker Kit Weights and Dimensions
Weight kgHeight mmWidth mmDepth mm
Battery breaker kit
E3MBBK60K80H
Battery breaker kit
E3MBBK100K200H
7415288190
13530320230
990-5997D-00111
Battery Breaker KitSpecifications
Trip Settings
E3MBBK60K80HE3MBBK100K200H
Trip Settings for Operation with Easy UPS 3M 400 V
With One Battery Breaker Kit E3MBBK60K80H
UPS ratingMax Battery Backup
Time (minutes)
60 kVA24032-501/2/3/4200/1250
80 kVA24032-501/2/3/4250/1250
Battery BlocksBattery StringsIr/Im Setting (A)
With One Battery Breaker Kit E3MBBK100K200H
UPS ratingMax Battery Backup
Time (minutes)
100 kVA24036-501/2/3/4420/1500
120 kVA24036-501/2/3/4420/1500
160 kVA24036-501/2/3/4480/1500
200 kVA6036-381/2/3/4600/1500
24040-501/2/3/4600/1500
Battery BlocksBattery StringsIr/Im Setting (A)
With Two Battery Breaker Kits E3MBBK60K80H
UPS ratingMax Battery
Backup Time
(minutes)
60 kVA24032-5053175/12502175/1250
24032-5063175/12503175/1250
Battery
Blocks
Battery
Strings Total
Battery Breaker 1Battery Breaker 2
Battery
Strings
Ir/Im Setting
(A)
Battery
Strings
Ir/Im Setting
(A)
12990-5997D-001
SpecificationsBattery Breaker Kit
UPS ratingMax Battery
Backup Time
(minutes)
24032-5074175/12503175/1250
24032-5084175/12504175/1250
80 kVA24032-5053175/12502175/1250
24032-5063175/12503175/1250
24032-5074175/12503175/1250
24032-5084175/12504175/1250
100 kVA24036-5053200/12502175/1250
24032-5063175/12503175/1250
24032-5074175/12503175/1250
24032-5084175/12504175/1250
120 kVA24032-5053225/12502175/1250
24032-5063200/12503200/1250
24032-5074225/12503175/1250
24032-5084200/12504200/1250
160 kVA532-3653250/12502200/1250
103853250/12502200/1250
154053250/12502175/1250
24042-5053250/12502175/1250
24032-5063250/12503250/1250
1032-3674250/12503225/1250
153874250/12503200/1250
24040-5074250/12503200/1250
24032-5084250/12504250/1250
Battery
Blocks
Battery
Strings Total
Battery Breaker 1Battery Breaker 2
Battery
Strings
Ir/Im Setting
(A)
Battery
Strings
Ir/Im Setting
(A)
With Two Battery Breaker Kits E3MBBK100K200H
UPS ratingMax Battery
Backup Time
(minutes)
120 kVA24032-5053420/15002420/1500
24032-5063420/15003420/1500
24032-5074420/15003420/1500
24032-5084420/15004420/1500
160 kVA24032-5053420/15002420/1500
24032-5063420/15003420/1500
24032-5074420/15003420/1500
24032-5084420/15004420/1500
200 kVA24036-5053420/15002420/1500
24032-5063420/15003420/1500
24032-5074420/15003420/1500
24032-5084420/15004420/1500
Battery
Blocks
Battery
Strings Total
Battery Breaker 1Battery Breaker 2
Battery
Strings
Ir/Im Setting
(A)
Battery
Strings
Ir/Im Setting
(A)
990-5997D-00113
Battery Breaker KitSpecifications
Trip Settings for Operation with Easy UPS 3M 208 V
With One Battery Breaker Kit E3MBBK60K80H
UPS ratingMax Battery Backup
Time (minutes)
50 kVA24032-401/2/3/4200/1250
60 kVA24032-401/2/3/4220/1250
Battery BlocksBattery StringsIr/Im Setting (A)
With One Battery Breaker Kit E3MBBK100K200H
UPS ratingMax Battery Backup
Time (minutes)
80 kVA24032-401/2/3/4420/1500
100 kVA24032-401/2/3/4420/1500
Battery BlocksBattery StringsIr/Im Setting (A)
With Two Battery Breaker Kits E3MBBK60K80H
UPS ratingMax Battery
Backup Time
(minutes)
50 kVA24032-4053175/12502175/1250
24032-4063175/12503175/1250
24032-4074175/12503175/1250
24032-4084175/12504175/1250
60 kVA24032-4053175/12502175/1250
24032-4063175/12503175/1250
24032-4074175/12503175/1250
24032-4084175/12504175/1250
80 kVA24032-4053175/12502175/1250
24032-4063175/12503175/1250
24032-4074175/12503175/1250
24032-4084175/12504175/1250
100 kVA24032-4053200/12502200/1250
24032-4063200/12503200/1250
24032-4074200/12503200/1250
24032-4084200/12504200/1250
Battery
Blocks
Battery
Strings Total
Battery Breaker 1Battery Breaker 2
Battery
Strings
Ir/Im Setting
(A)
Battery
Strings
Ir/Im Setting
(A)
14990-5997D-001
SpecificationsBattery Breaker Kit
Trip Settings for Operation with Easy UPS 3L at Power Factor 1.0
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection is to be provided by others.
Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
following assertions:
•90 °C conductors
•An ambient temperature of 30 °C
•Use of copper conductors
•Installation method C
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC.
Cable Size for Cables Between UPS and Battery Breaker for Easy UPS 3M
Battery breaker kitsConnection60 kVA80 kVA100 kVA120 kVA160 kVA200 kVA
1 x E3MBBK60K80HDC+, N, DC- (mm²)5070
PE (mm²)2535
2 x E3MBBK60K80HDC+, N, DC- (mm²)5050505070
PE (mm²)2525252535
1 x
E3MBBK100K200H
2 x
E3MBBK100K200H
DC+, N, DC- (mm²)
PE (mm²)
DC+, N, DC- (mm²)
PE (mm²)
––
––
–––
–––
––––
––––
–
–
2 x 702 x 702 x 952 x 120
707095120
150150150
959595
Cable Size per String for Cables Between Battery Breaker and Battery Bank For Easy UPS 3M
Number of battery
strings
1 battery stringBatt+, N, Batt-
2 battery stringsBatt+, N, Batt-
Connection60 kVA80 kVA100 kVA120 kVA160 kVA200 kVA
50702 x 702 x 702 x 952 x 120
(mm²)
PE (mm²)2535707095120
2535707095120
(mm²)
PE (mm²)161635355070
3 battery stringsBatt+, N, Batt-
(mm²)
PE (mm²)161625252535
4 battery stringsBatt+, N, Batt-
(mm²)
PE (mm²)161616161625
161650505070
161635353550
Cable Size for Cables Between UPS and Battery Breaker for Easy UPS 3L
Battery breaker kitsConnection250 kVA300 kVA400 kVA500 kVA600 kVA
1 x
E3MBBK100K200H
DC+, DC- (mm²)2 x 1202 x 1202 x 120
PE, N (mm²)120120120
990-5997D-00129
––
––
Battery Breaker KitSpecifications
Cable Size for Cables Between UPS and Battery Breaker for Easy UPS 3L (Continued)
Battery breaker kitsConnection250 kVA300 kVA400 kVA500 kVA600 kVA
2 x
E3MBBK100K200H
3 x
E3MBBK100K200H
DC+, DC- (mm²)2 x 702 x 952 x 1202 x 1202 x 120
PE (mm²)7095120120120
N (mm²)120120120120120
DC+, DC- (mm²)
PE, N (mm²)
–––
–––
2 x 1202 x 120
120120
Cable Size per String for Cables Between Battery Breaker and Battery Bank for Easy UPS 3L
Number of battery
1
strings
1 battery stringBatt+, N, Batt-
2 battery stringsBatt+, N, Batt-
3 battery stringsBatt+, N, Batt-
4 battery stringsBatt+, N, Batt-
Connection250 kVA300 kVA400 kVA500 kVA600 kVA
2 x 1202 x 1202 x 1202 x 1202 x 120
(mm²)
PE (mm²)120120120120120
120120120120120
(mm²)
PE (mm²)7070707070
7070707070
(mm²)
PE (mm²)3535353535
5050505050
(mm²)
PE (mm²)2525252525
1.Cable sizes are based on same number of battery strings for all battery breaker kits
30990-5997D-001
SpecificationsBattery Breaker Kit
Recommended Cable Sizes for 208 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection is to be provided by others.
Cable sizes in this manual are based on table B.52.5 of IEC 60364-5-52 with the
following assertions:
•90 °C conductors
•An ambient temperature of 30 °C
•Use of copper conductors
•Installation method C
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC.
Cable Size for Cables Between UPS and Battery Breaker for Easy UPS 3M
Battery breaker kitsConnection50 kVA60 kVA80 kVA100 kVA
1 x E3MBBK60K80HDC+, N, DC- (mm²)7070
PE (mm²)3535
2 x E3MBBK60K80HDC+, N, DC- (mm²)50505070
PE (mm²)25252535
1 x
E3MBBK100K200H
DC+, N, DC- (mm²)
PE (mm²)
––
––
––
––
2X702X70
7070
Cable Size per String for Cables Between Battery Breaker and Battery Bank For Easy UPS 3M
Number of battery
strings
1 battery stringBatt+, N, Batt-
2 battery stringsBatt+, N, Batt-
3 battery stringsBatt+, N, Batt-
Connection50 kVA60 kVA80 kVA100 kVA
70702X702X70
(mm²)
PE (mm²)35357070
35357070
(mm²)
PE (mm²)16163535
16165050
(mm²)
PE (mm²)16162525
4 battery stringsBatt+, N, Batt-
(mm²)
PE (mm²)16161616
16163535
990-5997D-00131
Battery Breaker KitSpecifications
Torque Specifications
Bolt SizeTorque
M820 Nm
M1030 Nm
Environment
OperationStorage
Temperature0 °C to 40 °C-25 °C to 55 °C
32990-5997D-001
Installation ProcedureBattery Breaker Kit
Installation Procedure
NOTE: The illustrations in this manuals shows the installation in a 700 mm
empty battery cabinet. The battery breaker kit can also be installed in a 1100
mm empty battery cabinet or in a grounded metal box.
1. Mount the battery breaker kit. Follow one of the procedures:
– Mount the Battery Breaker Kit in a Grounded Metal Box, page 34, or
– Mount the Battery Breaker in the Empty Battery Cabinet – Bottom Cable
Entry, page 35, or
– Mount the Battery Breaker in the Empty Battery Cabinet – Top Cable
Entry, page 36.
2. Connect the Signal Cables, page 37.
3. Connect the Power Cables, page 40.
990-5997D-00133
Battery Breaker KitMount the Battery Breaker Kit in a Grounded Metal Box
Mount the Battery Breaker Kit in a Grounded Metal
Box
CAUTION
RISK OF EQUIPMENT DAMAGE
Mount the battery breaker kit in a grounded metal box with enough cable
bending space and clearance. The mounting surface should be flat and able to
support the weight of the battery breaker kit.
Failure to follow these instructions can result in injury or equipment
damage.
1. Measure and mark the holes for mounting the battery breaker kit in the metal
box.
2. Drill holes in each of the marked locations.
3. Mount the battery breaker kit in the metal box.
34990-5997D-001
Mount the Battery Breaker in the Empty Battery Cabinet –
Bottom Cable EntryBattery Breaker Kit
Mount the Battery Breaker in the Empty Battery
Cabinet – Bottom Cable Entry
1. Install the battery breaker kit in the bottom of the empty battery cabinet.
Front View of the Empty Battery Cabinet
990-5997D-00135
Battery Breaker Kit
Mount the Battery Breaker in the Empty Battery Cabinet –
Top Cable Entry
Mount the Battery Breaker in the Empty Battery
Cabinet – Top Cable Entry
1. Install the battery breaker kit in the top of the empty battery cabinet.
Front View of the Empty Battery Cabinet
36990-5997D-001
Connect the Signal CablesBattery Breaker Kit
Connect the Signal Cables
NOTE: Route the signal cables separately from the power cables.
NOTE: The illustrations in this procedure show a bottom cable entry system.
The procedure is the same for a top cable entry system.
1. Install the temperature sensor provided with the UPS.
WARNING
HAZARD OF FIRE
Position the temperature sensor as described to ensure correct
temperature measurements.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
Front View of the Empty Battery Cabinet
2. Route the battery temperature sensor cables through the top or the bottom of
the empty battery cabinet to the UPS dry contact terminals BAT_T for Easy
UPS 3M and J12 for Easy UPS 3L.
990-5997D-00137
Battery Breaker KitConnect the Signal Cables
3. Route the signal cables through the top or bottom of the empty battery
cabinet to the battery breaker.
4. Remove the cover from the battery breaker.
5. Connect the signal cables according to one of the diagrams below for Easy
UPS 3M:
Signal Cables in Installations with One Battery Breaker
Signal Cables in Installations with Two Battery Breakers
a. Connect the AUX switch signal cables from the battery breaker(s) and
fuse(s) to J5–1 and J5–2 in the UPS.
b. Connect the undervoltage trip coil signal cables from the battery breaker
(s) to J6–1 and J6–4 in the UPS.
38990-5997D-001
Connect the Signal CablesBattery Breaker Kit
6. Connect the signal cables according to the diagram below for Easy UPS 3L.
a. Connect the AUX switch signal cables from the battery breakers and fuse
(s) to J4-3 and J4-4, J5-1 and J5-2, and J5-3 and J5-4 in the UPS.
b. Connect the undervoltage trip coil signal cables from the battery breaker
s to J3-1 and J3-2, J3-3 and J3-4, and J4-1 and J4-2 in the UPS.
7. Fasten the signal cables with cable ties (provided) to the cable relief.
8. Reinstall the breaker cover on the battery breaker.
990-5997D-00139
Battery Breaker KitConnect the Power Cables
Connect the Power Cables
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Perform a total power off of the UPS system before connecting the battery
cables to the battery breaker.
Failure to follow these instructions will result in death or serious injury.
1. Lockout/Tagout the battery breaker in the OFF position.
Empty Battery Cabinet – Bottom Cable Entry
2. Connect the PE cable.
Empty Battery Cabinet – Top Cable Entry
3. Connect the DC cables (DC+, N, DC-) from the UPS.
4. Install the protection cover over the terminals on the left side of the battery
breaker.
5. Install the batteries as described in the installation manual supplied with the
empty battery cabinet.
40990-5997D-001
Connect the Power CablesBattery Breaker Kit
6. Connect the battery cables (Batt+, N, Batt-) from the batteries in the empty
battery cabinet to the battery breaker.
Empty Battery Cabinet – Bottom Cable Entry
7. Install the protection cover over the terminals on the right side of the battery
breaker.
Empty Battery Cabinet – Top Cable Entry
990-5997D-00141
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison