The Andover ContinuumTM b3810 series controllers are designed
for control of Air Handling Units, Roof Top Units, and other
mechanical plant equipment.
Page 2
BACnet b3810 Series Local Connectors
Features
PRODUCT AT A GLANCE
• Nati ve BACnet MS/TP Commun ication s for
Inter operabi lity to Third- Party S ystems
• Supports 18 BACnet Object Types including
Trends, Schedules, Calendars, and Loops
• Powerful , Flexi ble Loca l Contr oller fo r the
Most Demanding Applications
• Expa ndable I/O Mee ts Addi tional Point
Count Needs
• Non-Volatile Flash Memory Provides Utmost
Reli ability — Stor es Both Applic ation P rogram
and Operating System
• Opti onal Di splay/Ke ypad Pr ovides E asy
Operator Interface (Mounted Separately)
• Local, Extended Storage of Log Data
• View and Modify Information with Optional
Smart Sensor Display
• Local, On-Board Service Port
• BTL Listed B-AAC Controller with Local Trends
02
Choose the b3810 model with the
confi guration that matches your
application:
• The b3810, designed for stand-alone equipment
control of Roof Top Units, Air Handling Units, or
other packaged mechanical equipment, features
eight universal inputs, one Smart Sensor/Room
Sensor input, plus eight program-controlled
digital outputs.
• The b3814, designed for stand-alone equipment
control of Roof Top Units, Air Handling Units, or
other packaged mechanical equipment, features
eight universal inputs, one Smart Sensor/Room
Sensor input, plus four program-controlled digital
outputs and four analog outputs for direct control
of devices requiring 0-10 volt control signals.
Both models feature an additional room sensor
input, which supports Andover Continuum Smart
Sensor, or any standard room temperature sensor.
The b3810 series also features universal inputs, a
real-time clock, override switches on all outputs,
two-piece removable connectors, and the ability to
expand the I/O for additional points.
The b3810 Series also features Flash memory,
increased user memory, and a fast (32-bit) processor
for faster scan times, with plenty of memory available
for data logging of your critical data.
As native BACnet controllers, the b3810 Series
can communicate with other BACnet devices on
the MS/TP network, in strict accordance with
ANSI/ASHRAE standard 135-2004, and are listed
with the BACnet Testing Labs (BTL) as BACnet
Advanced Application Controllers (B-AAC). By
connecting to an Andover Continuum b4920
device or bCX1 network controller, the b3810
series and other MS/TP devices can share data
from the wider Ethernet/IP network of controllers.
Schneider Electric
SDS-B3810-A4.BU.N.EN.7.2009.0.00.CC
Page 3
BACnet b3810 Series Local Connectors
B
3
2
1
AC P OWER
24 VAC
30 VA
50/ 60 HZ
L
N
+
DC P OWER
12-28 V DC
20W
REV:
4
5
6
SHLD
+
-
RS-4 85
TD
3
2
1
ACPOWER
24VAC30VA50/60HZ
L
N
+
DCPOWER
12-28VDC20W
03
Features
(continued)
Increased Reliability with Flash Memory
The b3810’s non-volatile Flash memory stores your
operating system and application programs, so
that in the event of a power loss, your application
will be restored when power is returned. In
addition, the Flash memory allows for easy
upgrades of your
downloads, eliminating
proms. The b3810 controllers include an onboard battery to safeguard your runtime data —
protecting all point data and log data from being
lost if power is removed.
operating system via software
the need to swap out
Inputs
The input conguration on the b3810 series
consists of eight full range, 12-bit Universal inputs
that accept voltage (0-10VDC), digital (on/off),
counter signals (up to 4Hz), temperature signals, or
supervised alarm circuits for security applications
or broken wire detection. The b3810 Series
offers an additional input to support the Andover
Continuum Smart Sensor, or any standard room
temperature sensor.
Dimensional Drawings
1
2
4
3
Outputs
The b3810 contains eight Form C relay outputs,
each rated for 24 VAC/30VDC, 3 amp, while the
b3814 contains four Form C relay outputs and four
analog outputs (0-10V). Both the relay and analog
outputs have manual override switches, with
software feedback of the switch position.
The b3810 contains an I/O expansion port for
the addition of up to two Andover Continuum xP
expansion modules directly on the bottom of the
controller. The xP family of modules includes the
xPDI8, xPUI4, xPDO2, xPDO4, xPAO2, xPAO4.
In addition to two input/output modules, the I/O
bus supports the xP Local Display Module, which
allows the user to view and change point values.
Schneider Electric
SDS-B3810-A4.BU.N.EN.7.2009.0.00.CC
1
Power Drawing
2
Communi cations
Drawing
Page 4
BACnet b3810 Series Local Connectors
1
2
3
4
5
6
7
8
40
36
45
44
43
42
41
39
38
37
35
34
40
36
45
44
43
42
41
39
38
37
35
34
1
2
28
24
33
32
31
30
29
27
26
25
23
22
28
24
33
32
31
30
29
27
26
25
23
22
3
4
I
V
GND
5
I
V
GND
6
I
V
GND
7
I
V
GND
8
PLACARD, INPUT,
I2814 / I2810
05-1001-223
TITLE:
P/N:
REV:
DATE:
1OF1
DRAWNBY:
B
11/3/04M.ROGERS
SHEET:
FULL
ECO#11244
SCALE:
SOFTWARE:ECONUMBER:
ADOBEILLUSTRATOR10.0
21
19
20
7 RE T
8 IN 1
9 IN 2
10
RET
11 IN 3
12 IN 4
13 RET
14 IN 5
15 IN 6
16 RET
17 IN 7
18 IN 8
RET
IN 9
SPWR
SMART
SENSOR
UNIVERSAL
INPUTS
1
2
3
6
5
4
8
7
OFF
ON
SERVICEPORT
4
5
6
SHLD
+
-
RS-485
R
D
TD
RESTART
CPU
3
2
1
ACPOWER
24VAC30VA50/60HZ
L
N
+
DCPOWER
12-28VDC20W
04
Features
Software Capabilities
The dynamic memory of the b3810 can be
allocated for any combination of programs,
scheduling, alarming, and data logging using the
powerful Andover Plain English programming
language. Our object-oriented Plain English
language with intuitive keywords provides an easy
method to tailor the controller to meet your exact
requirements. Programs are entered into the b3810
using the Andover Continuum CyberStation
Programs are then stored and executed by the
b3810 controllers.
Programming multiple b3810 Series controllers is
inherently easy with Plain English. A complete copy
of one b3810’s programs can be loaded directly
into other b3810s without changing any point
names or programs.
Smart Sensor Interface
The b3810 provides a built-in connection for
Andover Continuum Smart Sensor. The Smart
Sensor provides a 2-character LED display and
a 6-button programmable keypad that enables
operators and occupants to change setpoints,
balance VAV boxes, monitor occupancy status, and
turn equipment on and off. An enhanced version
of the Smart Sensor is also available with a 4-digit
custom LCD that provides the following icons: PM,
%, °, Setpoint, Cool, Heat, CFM, Fan, OA, and SP.
Local Display
The local display with keypad (xP Display) allows for
the addition of a fully programmable local display
module that can be mounted within 10 feet (3
meters) of the controller. Connected via a ribbon
cable, the xP-Display easily allows the Operator
Interface to be mounted on the door of an enclosure
or on a wall below or next to the controller.
Optional Wireless Internet
The b3810 Series BACnet controllers can also
communicate using a wireless mesh network. Simply
plug Andover Continuum Wireless Adapters into
the service ports of these controllers with wireless
compatible firmware to create a wireless mesh
network that sends and receives BACnet messages.
Schneider Electric
SDS-B3810-A4.BU.N.EN.7.2009.0.00.CC
(continued)
Input/Output Drawings
TM
.
3
Smart S ensor
and Input s Drawing
b3810b3814
Outputs D rawing
4
Page 5
BACnet b3810 Series Local Connectors
Specifications
b3810 Series Local Connectors
05
Electrical
Power
24VAC, 12-24VDC - auto sensing,
+10% -15%, 50/60 Hz
Power Consumption
30 VA
Overload Protection
Fused with 3 amp fuse.
MOV protected
Real-Time Clock
Battery-backed real-time clock
Mechanical
Operating Environment
32°–120°F (0–49°C),
10–95% RH (non-condensing)
Size
9.51˝ H x 7.26˝ W x 2.14˝ D
(241H x 184W x 54D) mm
Weight
1.65 lbs. (0.75 kg)
Enclosure Type
UL Open class, IP 10.
Flammability rating of UL94-5V
Mounting
Panel mount
Battery
Battery Backup
Replaceable, non-rechargeable,
lithium battery. Provides 5 years
typical accumulated power failure
backup of RAM memory
Communications
Communications Interface
RS-485 BACnet,
MS/TP 127 devices maximum
Communications Speed
9600, 19.2K, 38.4K, 76.8K baud
Bus Length
4,000 ft. (1,220m) standard;
BACnet repeater allows extension
to longer distances.
Bus Media
Twisted, shielded pair,
low capacitance cable
Inputs/Outputs
Inputs
8 Universal inputs: Voltage (0-10 VDC);
Temperature -30°F to 230°F (-34°C to
110°C), Digital (on/off), Counter
(up to 4Hz at 50% duty cycle,
125 ms min. pulse width). Supervised
Alarm (single or double resistor).
Current input (0 - 20 mA) using
external 500 ohm resistor
1 Smart Sensor Temperature Input
(32°F to 105°F) (0°C to 41°C)
Input Voltage Range
0-10 volts DC
Input Impedance
30.1K ohm to 10V or 5M ohm with
pull-up resistor disabled
Input Resolution
2.5 mV
Input Accuracy
±7.5mV (±0.25°C from -23°C to +54°C)
or (±0.46°F from -10°F to +130°F)
Digital Outputs
8 single pole single throw (SPST)
Form C relays (4 Form C on b3814)
(Any two consecutive Form C outputs
can be congured as one Form K Tristate)
Output Rating
Maximum 3A, 24VAC/30VDC,
±1500V transients
(Tested according to EN61000-4-4)
Output Accuracy
0.1 sec. for pulse width modulation
Analog Outputs
4 analog outputs (b3814 only)
Output Rating
For 0-10V: 5mA maximum,
2K ohm minimum impedance,
±1000V transients
(Tested according to EN61000-4-4).
Fuse-protected only on the b3814
Output Resolution
0.1V for 0-10V
Output Overrides
Each output is equipped with a manual
override switch. Software feedback
of the switch position is provided,
for display and alarming
Expansion Bus
Interfaces to optional xP I/O
Expansion Modules
Sc
hneider Electric
SDS-B3810-A4.BU.N.EN.7.2009.0.00.CC
Page 6
BACnet b3810 Series Local Connectors
04
Specifications
(continued)
b3810 Series Local Connectors
Connections
Power
3-position xed screw terminal connector
Inputs
Removable two-piece terminal strip
Outputs
Removable two-piece terminal strip
Smart Sensor
Removable two-piece terminal strip
Communications
Removable 3-position terminal connector
Expansion Port
6-position shrouded connector
Service Port
4-position shrouded connector
User LEDs/Switches
Status Indicator LEDs
CPU CPU Active
TD Transmit Data
RD Receive Data
Output Output Status (per
EXPANSION
PORT PWR Power Status
Switches
RESET
Input Pull-up Resistor Switch (per input)
Individual Output Override Switches
General
Memory
256K SRAM, 1MB FLASH
Processor
Motorola 32-bit Coldre
output) (Digital only)
Agency Listings
UL/CUL 916, FCC CFR 47 Part 15,
ICES-003, EN55022, ASIN2S 3548,
Class A, CE
Models
b3810
BACnet b3810 Local Controller
b3810-WL
Wireless BACnet b3810 Local Controller
b3814
BACnet b3814 Local Controller
b3814-WL
Wireless BACnet b3814 Local Controller
All brand names, trademarks and registered trademar ks are the proper ty of their respective owners. Information contained within this document is subje ct to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.