The AV-29x linkages are used to field assemble
Schneider Electric gear train hazardous location
actuators to VB-7xxx series or select VB-9xxx series
valve bodies.
Features
• Die cast aluminum mounting bracket.
• Valve position indication provided as standard.
AV-291, AV-293, AV-295, and
AV-296
Valve Linkage for
Hazardous Location Gear Train Actuators
General Instructions
Applicable Literature
• EN-56-2 Apparatus for Use in Hazardous Locations,
Verify that the fluid temperature of the media in the valve versus the ambient temperature at
the actuator does not exceed the ratings shown in Table-2.
Table-2 Restrictions on Maximum Ambient Te m pe r ature for Actuators.
Maximum Temperature of Media in the Valve
(Check Rating of Valve) °F (°C)
260 (126)136 (57)
281 (138)125 (52)
300 to 366 (149 to 185)100 (37)
Maximum Ambient for Actuator
°F (°C)
Close-off Pressure Rating
Close-off pressure ratings are listed in Table-3. Check the appropriate table to verify that the
selected valve, valve linkage,
application.
The actuator with hazardous location housing, valve, and valve linkage should be purchased
separately. See Table-3 for selections.
and actuator provide adequate close-off pressure for your
INSTALLATION
InspectionInspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements• Tools (not provided):
– Appropriate wrenches for stem extensions, lock nuts, packing nuts, and brackets
– Appropriate screwdriver for actuator mounting screws
– TOOL-37, 1-5/8" open-ended wrench with a ma
• Training: Installer must be a qualified, experienced technician
Caution:
• Install the unit in accordance with the National Electric Code Article 500 and all
applicable local codes.
• Avoid locations where excessive moisture, corrosive fumes, or vibration is present.
• Install all two-way valves so that they close against the flow. An arrow on the valve body
or a tag indicates the proper flow direction.
• Always install three-way mixing valves with two inlets and one outlet.
• Always install three-way diverting valves with one inlet and two outlets.
• The actuators can be mounted in any position above the centerline of the valve body.
For steam applications where the ambient temperature approaches the limit of the
actuator, the valve stem should be mounted 45° from vertical. When selecting a
location, allow sufficient room for accessories and for service of the product.
AV-291 and AV -293Note: Position the bracket on the valve in such a way as to make it convenient to wire the
actuator.
Valve Linkage for 1/2" to 2" VB-7xxx
1. Mount the bracket on the valve body by screwing the mounting nut into the mounting
bracket. Tighten the hex mounting nut, using a 1-5/8" open-ended wrench with a
maximum thickness of 3/16" (TOOL-37). See
Valve Linkage Common Procedure on page 6.
1. Mount the bracket onto the valve body by removing the bracket nut, placing the bracket
on the valve body, and replacing and tightening the valve bracket nut. See Figure-2.
Proceed to step 2 in AV29x Valve Linkage Common Procedure on page 6.
Indicator
ADDA-9-2
Indicator Screw
BYRF-105
Cover Screws (2)
BYRF-695
Front Cover
ADDA-880-1
Nylon Bushing
Plunger Assembly
Plunger Cam
AYRC-44-2
Connecting Pin
ADFA-20-1
Mxx-xxx Hazardous Location Actuator
1
AYRD-405
2
Mounting Bracket
NYBA-68
Stem Extension
NYBA-37
Mounting Screws (3)
BYRF-2286
Threaded VB-9xxx Valve Body
2-1/2" and 3"
Figure-2 Valve Linkages for Current 2-1/2" to 4" VB-9313 Cast Iron Flanged,
The following steps are common to all AV-29x valve linkages. Perform step 1 on page 4 or
5 before proceeding to step 2.
2. Thread the stem lock nut and stem extension down fully onto the valve stem.
3. Place the actuator onto the mounting bracket. Fasten the actuator to the mounting
bracket with the three mounting screws, BYRF-2286. Do not tighten the screws.
4. Place the nylon bushing onto the actuator shaft.
5. Position the actuator to the 3:00 (CW) or 9:00
up or down as required. Use Figure-3 and Table-4.
Table-4 Actuator Shaft and Cam Position.
Actuator
Shaft
Position
Valve PositionCam/Valve PositionValve PositionCam/Valve Position
(CCW) position so that the cam is pointing
Figure-3 Actuator Shaft Position (Front View).
CW
Short tooth on
shaft
actuator
at 9:00
CCW
Short tooth on
shaft
actuator
at 3:00
VB-7213 (closed)
VB-7313 (B closed)
VB-7323 (B to A open)
VB-921x (closed)
VB-931x (B closed)
VB-7213 (open)
VB-7313 (A closed)
VB-7323 (B to AB open)
VB-921x (open)
VB-931x (A closed)
6. Consult Table-5 for the proper cam. Place the cam in the plunger and slip the plunger
Check to assure correct plunger spring compression. The length of the stem extension
should be adjusted so that the valve disc seats before the actuator reaches the end of the
stroke. The balance of the actuator stroke is taken up in the plunger spring compression,
which should be approximately 1/16 inch (1.6 mm). This applies pressure on the disc in the
closed position(s) and compensates for disc and seat wear. Refer to Figure-5 for VB-7213
(stem down closed). For three way applica
tions (VB-73x3 or VB-9313) refer to Figure-4
andFigure-5.
VB-7213 Example1. Drive the actuator so the valve stem is fully down.
2. Observe the plunger spring compression as in Figure-5.
VB-7313 Example1. Drive the actuator so the valve stem is fully up.
2. Observe the plunger spring compression as in Figure-4.
3. Drive the actuator so the valve stem is fully down.
4. Observe the plunger spring compression as in Figure-5.
On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual i denti ty of Schn eider Elec tric,
ho wever there rem ains r eferences to TAC as a corpor a te br and in the body copy. As each document is updated, the body copy will be c han ged to reflect appropriate
4-1/2
(114)
2-15/16
(51)
2-1/8
(54)
3/4 (19) Pipe Tap
On Each Side
9
(229)
10-13/16
(275)
1/8
(3)
1-1/4 (32)
5/8 (16)
Dimensions shown
are in inches (mm).
Figure-7 Side Dimensions.
corporate brand changes.
Copyright 2010, Schneider Electric
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-27441-2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.