Schneider Electric 3.0A, 2.0A, 5.0A, 6.0A User Manual

Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Unidades de disparo electrónico Micrologic™ 2.0A, 3.0A,
5.0A y 6.0A
MC
Déclencheurs électroniques Micrologic
2.0A, 3.0A, 5.0A et
6.0A
48049-136-05 Rev. 01, 04/2012
Retain for Future Use. / Conservar para uso futuro. / À conserver pour usage ultérieur.
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Instruction Bulletin
48049-136-05 Rev. 01, 07/2012
Retain for future use.
ENGLISH
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
DANGER
WARNING
E
IEC
ANSI
Rev. 01, 07/2012
Hazard Categories and Special
ENGLISH
Symbols
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, can result in minor or moderate injury.
NOTIC
NOTICE is used to address practices not related to physical injury. The safety alert symbol is not used with this signal word.
NOTE: Provides additional information to clarify or simplify a procedure.
Please Note Electrical equipment should be installed, operated, serviced, and
maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
FCC Notice This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. This Class A digital apparatus complies with Canadian ICES-003.
© 1999–2012 Schneider Electric All Rights Reserved2-EN
48049-136-05 Micrologic® 2.0A, 3.0A, 5.0A and 6.0A Electronic Trip Units Rev. 01, 07/2012 Table of Contents
Table of Contents
SECTION 1: GENERAL INFORMATION ...................................................................................................................... 5
Introduction ................................................................................................. 5
Communications ......................................................................................... 5
Trip Unit Settings ........................................................................................ 5
Micrologic 2.0A Trip Unit ....................................................................... 6
Micrologic 3.0A Trip Unit ....................................................................... 6
Micrologic 5.0A Trip Unit ....................................................................... 7
Micrologic 6.0A Trip Unit ....................................................................... 8
Zone-Selective Interlocking ......................................................................... 9
Trip Unit Switches ..................................................................................... 10
Long-Time Protection .......................................................................... 10
Short-Time Protection ......................................................................... 11
Instantaneous Protection ..................................................................... 12
Ground-Fault Protection ...................................................................... 13
Indicator Lights .......................................................................................... 13
Overload Indicator Light ...................................................................... 13
Trip Indicator Lights ............................................................................. 14
Ammeter ................................................................................................... 14
Trip Unit Testing ........................................................................................ 14
Micrologic Trip Unit Configuration ............................................................. 14
Control Power ...................................................................................... 14
External Power Supply ........................................................................ 15
ENGLISH
SECTION 2: AMMETER .................................................................................................................... 16
Display ...................................................................................................... 16
Ammeter Measurements ........................................................................... 16
Accessing Information ............................................................................... 16
Current Menu ...................................................................................... 17
Peak Menu .......................................................................................... 18
Switch Settings Menu .......................................................................... 19
SECTION 3: OPERATION .................................................................................................................... 20
Switch Setting Adjustment ........................................................................ 20
Examples .................................................................................................. 20
Micrologic 2.0A Trip Unit ..................................................................... 20
Micrologic 3.0A Trip Unit ..................................................................... 21
Micrologic 5.0A Trip Unit ..................................................................... 21
Micrologic 6.0A Trip Unit ..................................................................... 22
Zone-Selective Interlocking (ZSI) .............................................................. 23
Communication Module values ................................................................. 24
Trip Unit Settings Check ........................................................................... 26
Trip Unit Operation Verification ................................................................. 26
Equipment Ground-Fault Trip Functions Testing ...................................... 27
Trip Unit Resetting .................................................................................... 27
Trip Unit Status Check .............................................................................. 27
SECTION 4: TRIP UNIT REPLACEMENT .................................................................................................................... 28
Required Tools .......................................................................................... 28
Preparation ............................................................................................... 28
Record Switch Settings ....................................................................... 28
Circuit Breaker Disconnection ............................................................. 28
Circuit Breaker Accessory Cover Removal ......................................... 28
Rating Plug Removal ........................................................................... 29
Trip Unit Removal ................................................................................ 29
© 1999–2012 Schneider Electric All Rights Reserved 3-EN
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05 Table of Contents Rev. 01, 07/2012
ENGLISH
SECTION 5: ADJUSTABLE RATING PLUG REPLACEMENT .............................................................................................. 33
SECTION 6: BATTERY REPLACEMENT ....................................................................................................................34
Trip Unit Replacement ..............................................................................29
Battery Installation ...............................................................................29
Trip Unit Installation .............................................................................30
Circuit Breaker Accessory Cover Replacement ........................................ 31
Trip Unit Installation Check .......................................................................32
Secondary Injection Testing ................................................................32
Primary Injection Testing ..................................................................... 32
Check Accessory Operation ................................................................ 32
Trip Unit Setup ..........................................................................................32
Circuit Breaker Reconnection ...................................................................32
Rating Plug Removal ................................................................................ 33
New Rating Plug Installation ..................................................................... 33
Circuit Breaker Disconnection ...................................................................34
Circuit Breaker Accessory Cover Removal ...............................................34
Withstand Module Shifting ........................................................................34
Battery Replacement .................................................................................34
Withstand Module Replacement ............................................................... 35
Circuit Breaker Accessory Cover Replacement ........................................ 35
Circuit Breaker Reconnection ...................................................................35
APPENDIX A: REGISTER LIST ....................................................................................................................36
List of Registers ........................................................................................36
© 1999–2012 Schneider Electric All Rights Reserved4-EN
48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
06134858
A
B
D
E
C
A—Micrologic Trip Unit B—Product Name C—Switch Cover D—Switch Cover Opening Slot E—Adjustable Rating Plug
Rev. 01, 07/2012 Section 1—General Information
Section 1—General Information
Introduction
Micrologic™ trip units (A) provide adjustable tripping functions on electronic trip circuit breakers. The product name (B) specifies the level of protection provided by the trip unit.
Micrologic 3.0A
Type of protection
2—Basic IEC protection (LS0) 3—Basic UL protection (LI) 5—Selective protection (LSI) 6—Selective protection plus ground fault
protection for equipment (LSIG)
Trip unit series
0—Indicates the first version
Type of measurement
None—Provides protection only
A—Provides protection plus ammeter measurements
Micrologic trip units are field replaceable to allow for upgrading of the trip unit in the field. For complete information on available circuit breaker models, frame sizes, interrupting ratings, sensor plugs, rating plugs and trip units, see the product catalog.
Figure 1: Micrologic Trip Unit
rolo
ic
M
06133249
%
0
0
1
%
0
4
u
n
e
m
ENGLISH
A
7.0
ic
g
m
ar l a
e m i
8
t
r
12
t
ng o l
)
4
6
s (
1 8
.
r
9
I
.
2
20
7
.
5
9
.
1
24
6
8
.
9
.
5
.
r I
6
@
5
.
1
n
.4
I
x
Communications Micrologic trip units can communicate with other devices if the optional
Circuit Breaker Communication Module (BCM) is installed. For information on the communication module, see the product catalog and Modbus™ Communications System, Data Bulletin 0613IB1201.
Trip Unit Settings On the face of the trip unit are adjustable switches to allow changing of trip
characteristics. Trip units are shipped with the long-time pickup switch set at
1.0 and all other trip unit adjustments set at their lowest settings.
© 1999–2012 Schneider Electric All Rights Reserved
5-EN
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
0 Ir Isd I
t
06134245
06134246
Micrologic 2.0 A
menu
long time
alarm
instantaneous
.4
.5
.6
.7.8.9
.95 .98
1
Ir
x In
.5
1
2
4
8
12
16 20
tr
(s)
@
6 Ir
24
setting
Isd
2.5
5
6
1.5
2
3
4
8
10
x Ir
G
F
A
H
J
I
F
G
H
K
B
C
E
D
N
M
L
06133243
Micrologic 3.0 A
menu
long time
alarm
instantaneous
.4
.5
.6
.7.8.9
.95 .98
1
Ir
x In
.5
1
2
4
8
12
16 20
tr
(s)
@
6 Ir
24
3
6
8
setting
Ii
1.5
2
4
5
10
12
x In
0 Ir Ii I
t
06133201
G
F
A
H
J
I
F
G
H
K
B
C
E
D
N
M
L
Section 1—General Information Rev. 01, 07/2012
ENGLISH
Micrologic 2.0A Trip Unit
The Micrologic 2.0A trip unit provides basic IEC (LS0) protection and a built-in ammeter.
A. Trip unit name B. Alphanumeric display C. Three-phase bar graph D. Scroll button E. Menu button F. Long-time pickup (Ir) switch G. Long-time delay (tr) switch H. Short-time pickup (Isd) switch* I. Test plug receptacle J. Overload indicator light K. Reset button for battery status check and trip
L. Self-protection indicator light M. Short-time or instantaneous trip indicator
N. Long-time trip indicator light
NOTE: For use with IEC circuit breakers only. Figure 2: 2.0A Trip Unit
indicator LED
light
Micrologic 3.0A Trip Unit
The Micrologic 3.0A trip unit provides basic UL (LI) protection and a built-in ammeter.
A. Trip unit name B. Alphanumeric display C. Three-phase bar graph D. Scroll button E. Menu button F. Long-time pickup (Ir) switch G. Long-time delay (tr) switch H. Instantaneous pickup (Ii) switch I. Test plug receptacle J. Overload indicator light K. Reset button for battery status check and trip
L. Self-protection indicator light M. Short-time or instantaneous trip indicator
N. Long-time trip indicator light
*Short-time delay is factory set at 0 (no delay), thus short-time pickup provides instantaneous protection.
indicator LED
light
Figure 3: 3.0A Trip Unit
© 1999–2012 Schneider Electric All Rights Reserved6-EN
48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Micrologic 5.0 A
menu
d
elay
sh
o
r
t
ti
me
lon
g
ti
me
a
l
a
rm
tr
(s)
se
tting
.4
.5
.
6
.7
.8
.9
.9
5
.
9
8
1
Ir
x
In
.5
1
2
4
8
1
2
1
6
2
0
@
6 I
r
2
4
06133244
e
4
I i
x In
3
6
8
10
12 15
off
2
tsd
(s)
on I2t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
x Ir
2
2.5
3
4
5
6 8
10
Isd
1.5
i
n
stantan
eo
u
s
G
F
A
H
L
K
F
G
J
M
B
C
E
D
P
O
N
I
J
I
H
Rev. 01, 07/2012 Section 1—General Information
Micrologic 5.0A Trip Unit
The Micrologic 5.0A trip unit provides selective (LSI) protection and a built-in ammeter.
A. Trip unit name B. Alphanumeric display C. Three-phase bar graph D. Scroll button E. Menu button F. Long-time pickup (Ir) switch G. Long-time delay (tr) switch H. Short-time pickup (Isd) switch I. Short-time delay (tsd) switch J. Instantaneous pickup (Ii) switch K. Test plug receptacle L. Overload indicator light M. Reset button for battery status check and trip
indicator LED N. Self-protection indicator light O. Short-time or instantaneous trip indicator
light P. Long-time trip indicator light
Figure 4: 5.0A Trip Unit
t
06133202
0 Ir Isd I
Ii
ENGLISH
© 1999–2012 Schneider Electric All Rights Reserved
7-EN
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
Micrologic 6.0 A
menu
delay
short tim
e
long time
alarm
ground fault
setting
test
.4
.5
.6
.7.8.9
.95 .98
1
Ir
x In
.5
1
2
4
8
12
16 20
tr
(s)
@
6 Ir
24
tsd
tg
06133245
4
I i
x In
3
5
6
10
12 15
off
2
tsd
(s)
on I2t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
x Ir
2
2.5
3
4
5
6 8
10
Isd
1.5
on
I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
B
C
D
E
F
G H
J
Ig
A
(s)
instantaneous
40
100
%
%
0 Ir Isd I
t
Ii
06133202
0 I
t
I2t off
I2t on
Ig
06133247
G
F
A
H
O
M
F
G
J
P
B
C
E
D
T
S
Q
I
J
I
H
K
L
N
R
K
L
Section 1—General Information Rev. 01, 07/2012
ENGLISH
Micrologic 6.0A Trip Unit
The Micrologic 6.0A trip unit provides selective and ground-fault protection for equipment (d1200 A) (LSIG) and a built-in ammeter.
A. Trip unit name B. Alphanumeric display C. Three-phase bar graph D. Scroll button E. Menu button F. Long-time pickup (Ir) switch G. Long-time delay (tr) switch H. Short-time pickup (Isd) switch I. Short-time delay (tsd) switch J. Instantaneous pickup (Ii) switch K. Ground-fault pickup (Ig) switch L. Ground-fault delay (tg) switch M. Test plug receptacle N. Ground fault push-to-trip button O. Overload indicator light P. Reset button for battery status check and trip
Q. Self-protection indicator light R. Ground-fault trip indicator light S. Short-time or instantaneous trip indicator
T. Long-time trip indicator light
Figure 5: 6.0A Trip Unit
indicator LED
light
© 1999–2012 Schneider Electric All Rights Reserved8-EN
48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units Rev. 01, 07/2012 Section 1—General Information
Zone-Selective Interlocking
Short-time and ground-fault protection can be interlocked to provide zone-selective interlocking.
Control wiring links several trip units in the distribution network and in the event of a fault, a trip unit will obey the set delay time only if receiving a signal from a downstream trip unit.
If the trip unit does not receive a signal, tripping will be instantaneous (with no intentional delay).
The fault is cleared instantaneously by the
nearest upstream circuit breaker.
Thermal stresses (I
2
t) in the network are minimized without any effect on the correct time delay coordination of the installation.
Figure 6 shows circuit breakers 1 and 2 zone­selective interlocked.
A fault at A is seen by circuit breakers 1 and
2. Circuit breaker 2 trips instantaneously and also informs circuit breaker 1 to obey set delay times. Thus, circuit breaker 2 trips and clears the fault. Circuit breaker 1 does not trip.
A fault at B is seen by circuit breaker 1.
Circuit breaker 1 trips instantaneously since it did not receive a signal from the downstream circuit breaker 2. Circuit breaker 1 trips and clears the fault. Circuit breaker 2 does not trip.
2
NOTE: Use I
t off with ZSI for proper coordination. Using I2t on with ZSI is not recommended as the delay in the upstream device receiving a restraint signal could result in the trip unit tripping in a time shorter than the published trip curve.
NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0 setting will eliminate selectivity for that circuit breaker.
Figure 6: Zone-Selective Interlocking
06133376
1
B
2
A
ENGLISH
© 1999–2012 Schneider Electric All Rights Reserved
9-EN
Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units 48049-136-05
x Ir
2
2.5
3
4
5
6 8
10
1.
5
setting
Isd
instantaneous
long time
alarm
tr
(s)
.4
.5
.6
.7.8.9
.95 .98
1
Ir
x In
.5
1
2
4
8
12
16 20
@ 6 Ir
24
06134243
x In
2
3
4
5
6
8
10
12
1.
5
setting
Ii
instantaneous
long time
alarm
tr
(s)
.4
.5
.6
.7.8.9
.95 .98
1
Ir
x In
.5
1
2
4
8
12
16 20
@ 6 Ir
24
06133203
.4
.5
.6
.7.8.9
.95 .98
1
delay
short tim
e
I itsd
(s)
on I2t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
long time
alarm
Ir
x In
.5
1
2
4
8
12
16 20
tr
(s)
@
6 Ir
24
setting
x Ir
2
2.5
3
4
5
6 8
10
Isd
1.
5
x In
3
4
6
8
10
12 15
off
2
06133204
.4
.5
.6
.7.8.9
.95 .98
1
delay
short tim
e
I itsd
(s)
on I2t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
instantaneous
long time
alarm
Ir
x In
ground fault
B
C
D
E
F
G H
J
Ig tg
(s)
on I2t
.
2
.
3
.
4
.
4
.
1
.
2
.
3
.
1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
@
6 Ir
24
setting
x Ir
2
2.5
3
4
5
6 8
10
Isd
1.
5
x In
3
4
5
8
10
12 15
off
2
test
06133351
Section 1—General Information Rev. 01, 07/2012
Trip Unit Switches
ENGLISH
Long-Time Protection
Long-time protection protects equipment against overloads.
Long-time protection is standard on all trip
units.
The long-time pickup (Ir) (A) sets the
maximum current level (based on sensor plug rating In) which the circuit breaker can continuously carry. If current exceeds this value, circuit breaker will trip after the preset time delay. The long-time pickup (Ir) is adjustable from 0.4–1.0 times the sensor plug rating (In).
The long-time delay (tr) (B) sets the length of
the time that the circuit breaker will carry an overcurrent (below the short-time or instantaneous pickup current level) before tripping. See Table 1 for delay settings.
Both long-time pickup and long-time delay
are on the field-replaceable adjustable rating plug. To change settings to more precisely match the application, various rating plugs are available. For instructions on replacing the rating plug, see Section
5 —Adjustable
Rating Plug Replacement.
For Masterpact™ NT and NW circuit
breakers, the In value can be changed by replacing the sensor plug below the trip unit. For further information, see the instructions packed with the sensor plug replacement kit.
The overload indicator light (C) indicates that
the Ir long-time pickup threshold has been exceeded.
Long-time protection uses true RMS
measurement.
Thermal imaging provides continuous temperature rise status of the wiring, both before and after the device trips. This allows the circuit breaker to respond to a series of overload conditions which could cause conductor overheating, but would go undetected if the long-time circuit was cleared every time the load dropped below the pickup setting or after every tripping event.
NOTE: Micrologic trip units are powered from the circuit to always provide fault protection. All other functions (display, metering, communications, etc.) require external power. See 15 for more information.
Figure 7: Long-Time Protection Switches
Micrologic 2.0A Trip Unit
B
A
Micrologic 5.0A Trip Unit
B
A
C
C
Micrologic 3.0A Trip Unit
B
A
Micrologic 6.0A Trip Unit
B
A
C
C
Table 1: Micrologic Trip Unit Long-Time Delay Values
1
Setting
Long-Time Delay in Seconds
tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600
tr at 6 x Ir 0.51 2 4 8 12162024
3
tr at 7.2 x Ir 0.34
1
Ir = In x long-time pickup. In = sensor rating. Trip threshold between 1.05 and 1.20 Ir.
2
Time-delay accuracy +0/-20%
3
For Micrologic 5.0A and 6.0A trip units, when tsd is set to 0.4 on or 4.0 off, then tr = 0.5 instead of 0.34.
0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
2
NOTE: If checking trip times, wait a minimum of 15 minutes after circuit
breaker trips before resetting to allow the thermal imaging to reset completely to zero or use a full-function test kit to defeat the thermal imaging.
© 1999–2012 Schneider Electric All Rights Reserved10-EN
Loading...
+ 28 hidden pages