While every precaution has been taken in the preparation of this document,
Schneider Electric SA assumes no liability for any omissions or errors it may contain,
nor for any damages resulting from the application or use of the information herein.
The products and options described in this document may be changed or modified at
any time, either from a technical point of view or in the way they are operated. Their
description can in no way be considered contractual.
1. Before you begin___________________________________________________________________________________________ 3
8. 6. Diagnostics in PL7 ___________________________________________________________________________________ 26
21755883 11/2009
1. Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the Installation Manual before installing or operating the Altivar drive. Installation, adjustment,
repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA and PC or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure given
in the Installation Manual to verify that the DC voltage is less than 45 VDC. The drive LEDs are not accurate indicators
of the absence of DC bus voltage.
Electric shock will result in death or serious injury.
CAUTION
DAMAGED EQUIPMENT
Do not install or operate any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
1755883 11/20093
2. Documentation structure
The following Altivar technical documents are available on the Web site www.schneider-electric.com and on the CDROM delivered with
each drive.
b Installation Manual
This manual describes:
• How to assemble the drive
• How to connect the drive
b Programming Manual
This manual describes:
• The functions
• The parameters
• How to use the drive display terminal (integrated display terminal and graphic display terminal)
b Communication Parameters Manual
This manual describes:
• The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network
• The operating modes specific to communication (state chart)
• The interaction between communication and local control
• Configuration of the communication-specific parameters via the integrated display terminal or the graphic display terminal
• Diagnostics
• Software setup
• The communication services specific to the protocol
b Altivar 58/58F Transition Manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F.
• It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.
b Altivar 38 Transition Manual
This manual describes the differences between the Altivar 61 and the Altivar 38.
It explains how to replace an Altivar 38, including how to replace drives communicating on a bus or network.
41755883 11/2009
3. Introduction
3. 1. Presentation
The standard Fipio communication card VW3 A3 311 is used to connect an Altivar 61 or Altivar 71 drive to a Fipio bus.
The data exchanges permit full drive functionality:
• Control
• Monitoring
• Adjustment
• Configuration
The profile used is FED C 32.
The periodic variables can be configured using the “Communication scanner” function.
The following assignment selections can be made:
On Fipio, address 0 is reserved for the PLC, which is the bus manager. Address 63 is reserved for the programming or operator terminal.
These two addresses must not, therefore, be used for a drive.
If address 0 has, nevertheless, been configured on the drive, its Fipio card will be deactivated.
No two devices on the Fipio bus should ever have the same address. Continued simultaneous flashing of the LEDs indicates that the drive
cannot connect to the Fipio bus because its address is already occupied by another device.
Examples:
Address 11 = 2#0000 1011
Address 34 = 2#0010 0010
1755883 11/20097
5. Connecting to the bus
Only pins 6 and 7 are used.
Pin 7
- Signal
Pin 6
+ Signal
TSX PREMIUM PLC
with integrated Fipio master
TSX FP ACC7
line terminator
TSX FP CA
ppp
Trunk cable
Drive
+ VW3 A3 311 Fipio card
Drive
+ VW3 A3 311 Fipio card
TSX FP ACC12
9-way female SUB-D connector
TSX FP ACC7
line terminator
TSX FP ACC12
9-way female SUB-D connector
5. 1. Card connector pinout
9-way male SUB-D
5. 2. Connection accessories
TSX FPACC2 female connector
The drive must be powered down when it is connected to the Fipio bus.
Connection is made via a TSX FP ACC 12 or TSX FP ACC 2 daisy chain or tap
junction connector, which is attached to the Fipio card connector.
5. 3. Wiring example
If a TSX FP ACC 2 tap junction connector is used the Fipio cables and/or the
TSX FP ACC 7 line terminator must be located on the right-hand side.
81755883 11/2009
6. Configuration
6. 1. Control - Signaling
Numerous configurations are possible. For more information, refer to the Programming Manual and the Parameters Manual.
The following configurations are just some of the possibilities available.
b Control via Fipio in I/O profile
The command and reference come from Fipio.
The command is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Reference 1 configurationNetwork card The reference comes from Fipio.
Command 1 configurationNetwork card The command comes from Fipio.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Fipio or the terminals in I/O profile
Both the command and reference come from Fipio or the terminals. Input LI5 at the terminals is used to switch between Fipio and the
terminals.
The command is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Reference 1 configurationNetwork cardReference 1 comes from Fipio.
Reference 1B configurationAnalog input 1 on the terminals Reference 1B comes from input AI1 on the terminals.
Reference switchingInput LI5Input LI5 switches the reference (1
Command 1 configurationNetwork cardCommand 1 comes from Fipio.
Command 2 configurationTerminalsCommand 2 comes from the terminals.
Command switchingInput LI5Input LI5 switches the command.
Warning: Reference 1B is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference
(summing, PID, etc) are inhibited.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Fipio or the terminals in Drivecom profile
Both the command and reference come from Fipio or the terminals. Input LI5 at the terminals is used to switch between Fipio and the
terminals.
The command is in Drivecom profile.
The run commands are in Drivecom profile, the command and the reference
come from the same channel.
Configure the following parameters:
ParameterValueComment
ProfileDrivecom profile not separateThe run commands follow the Drivecom profile, and the command and
Reference 1 configuration Network cardReference 1 comes from Fipio.
Reference 2 configuration Analog input 1 on the terminalsReference 2 comes from input AI1 on the terminals.
Reference switchingInput LI5Input LI5 switches the reference (1
Warning: Reference 2 is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference
(summing, PID, etc) are inhibited.
Configuration via the graphic display terminal or the integrated display terminal:
b Command in Drivecom profile via Fipio and reference switching at the terminals
The command comes from Fipio.
The reference comes either from Fipio or from the terminals. Input LI5 at the terminals is used to switch the reference between Fipio and
the terminals.
The command is in Drivecom profile.
Configure the following parameters:
ParameterValueComment
ProfileSeparate Drivecom profileThe run commands follow the Drivecom profile, and the command and
Reference 1 configurationNetwork cardReference 1 comes from Fipio.
Reference 1B configuration Analog input 1 on the terminals Reference 1B comes from input AI1 on the terminals.
Reference switchingInput LI5Input LI5 switches the reference (1
Command 1 configurationNetwork cardCommand 1 comes from Fipio.
Command switchingChannel 1Channel 1 is the command channel.
Warning: Reference 1B is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference
(summing, PID, etc) are inhibited.
Configuration via the graphic display terminal or the integrated display terminal:
The response of the drive in the event of a Fipio communication fault can be configured.
RDYNET+0.00Hz0A
COM. FAULT MANAGEMENT
Configuration can be performed using the graphic display terminal or
integrated display terminal using the
parameter in the
[1.8 FAULT MANAGEMENT] (FLt-) menu,
[Network fault mgt] (CLL)
[COM. FAULT MANAGEMENT] (CLL-) submenu.
The values of the [Network fault mgt] (CLL) parameter, which trigger a drive fault [Com. network] (CnF), are:
ValueMeaning
[Freewheel] (YES)Freewheel stop (factory setting)
[Ramp stop] (rMP)Stop on ramp
[Fast stop] (FSt)Fast stop
[DC injection] (dCI)DC injection stop
Network fault mgt: Freewheel
CANopen fault mgt: Freewheel
Modbus fault mgt: Freewheel
CodeQuick
The values of the
ValueMeaning
[Ignore] (nO)Fault ignored
[Per STT] (Stt)Stop according to configuration of [Type of stop] (Stt).
[fallback spd] (LFF)Switch to fallback speed, maintained as long as the fault is present and the run command is not disabled.
[Spd maint.]
The fallback speed can be configured in the [1.8 – FAULT MANAGEMENT] (FLt-) menu using the [Fallback speed] (LFF) parameter.
[Network fault mgt] (CLL) parameter, which do not trigger a drive fault, are:
(rLS)
The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run
command has not been removed.
141755883 11/2009
6. Configuration
6. 4. Monitored parameters
It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu ([COMMUNICATION MAP]
submenu) on the graphic display terminal.
The selection is made via the
Each parameter
be used to choose the logic address of the parameter. Select an
address of zero to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCr): Logic address 3204;
signed decimal format
• Parameter 2 = Motor torque (Otr): logic address 3205; signed
The Fipio card features 4 LEDs, which are visible through the drive cover.
I/O
COM
ERR
RUN
LED no.ColorMeaningOnFlashing slowly or quickly
2.1RedI/OMinor internal fault
2.2YellowCOM
2.3RedERRSerious faultCommunication fault
2.4GreenRUNNormal operation
Exchanges on the Fipio bus
Self-test on
initialization
161755883 11/2009
7. Diagnostics
RUNNET+50.00Hz80A
COMMUNICATION MAP
Command Channel: COM. CARD
Cmd value: 000F
Hex
Active ref. channel: COM. CARD
Frequency ref.: 500.0
Hz
Status word: 8627
Hex
CodeQuick
W3204: 53
W3205: 725
W7132: 0000
Hex
W0: -----
Hex
COM. SCANNER INPUT MAP
COM SCAN OUTPUT MAP
CMD. WORD IMAGE
FREQ. REF. WORD MAP
MODBUS NETWORK DIAG
MODBUS HMI DIAG
CANopen MAP
PROG. CARD SCANNER
Active command channel
Value of control word
used to control the drive
(hexadecimal format)
Active reference channel
Value of frequency reference (unit 0.1 Hz)
used to control the drive
Value of status word
(hexadecimal format)
Values of the four monitored words selected by the user.
The address and display format of these parameters can be
configured in the
[6 - MONITORING CONFIG.] menu,
[6.3 - COM. MAP CONFIG.] submenu (see
"Configuration" section on page 15
).
The value of a monitored word is equal to "
-----" if:
- Monitoring is not activated
(address equal to W0)
- The parameter is protected
- The parameter is not known (e.g., W3200)
Value of periodic input variables
Value of periodic output variables
Control word from Fipio
[COM. card cmd.] (CMd3)
Frequency reference from Fipio
[Com. card ref.] (LFr3)
7. 3. Control - Signaling
On the graphic display terminal only, the [1.2 - MONITORING] menu ([COMMUNICATION MAP] submenu) can be used to display
control-signal diagnostic information between the drive and the Fipio PLC:
1755883 11/200917
7. Diagnostics
7. 4. Communication scanner
On the graphic display terminal, in the [1.2 - MONITORING](SUP-) menu ([COMMUNICATION MAP] (CMM-) submenu):
- The [COM. SCANNER INPUT MAP](ISA-) submenu is used to display the value of the 8 communication scanner input variables
[Com Scan In
- The [COM SCAN OUTPUT MAP](OSA-) submenu is used to display the value of the 8 communication scanner output variables
Fipio faults are indicated by the red LED 2.2 (Err) on the Fipio card.
In the factory configuration, if Fipio is involved in the command or reference, a Fipio fault will trigger a resettable drive fault
network]
The Parameters Manual contains a detailed description of how to manage communication faults (see the "Communication monitoring"
section).
· Following initialization (power-up), the drive checks that at least one command or reference parameter has been written for the first time
by Fipio.
· Then, if a communication fault occurs on Fipio, the drive will react according to the configuration (fault, maintain, fallback, etc.).
The response of the drive in the event of a Fipio communication fault can be changed (see the Configuration section).
- Drive fault
- No drive fault (stop, maintain, fallback)
The
(CnF) fault. It can be accessed on the graphic display terminal only, in the [1.10 DIAGNOSTICS](dGt-) menu, [MORE FAULT
INFO]
(AFI-) submenu.
(CnF) and initiate a freewheel stop.
[Com. network] (CnF) (freewheel stop, stop on ramp, fast stop or DC injection braking stop)
[Network fault] (CnF) parameter can be used to obtain more detailed information about the origin of the last [Com. network]
ValueDescription of the values of the [Network fault] (CnF ) parameter
0No fault
1Loss of communication with the master
2PLC in STOP
3Fipio card fault (FIPCO initialization error)
4Fipio card fault (STATE_UF update error)
5Fipio card fault (CHANNEL_STATE update error)
[Com.
7. 6. Card fault
The [internal com. link](ILF) fault appears when the following serious problems occur:
- Hardware fault on the Fipio card
- Dialog fault between the Fipio card and the drive
The response of the drive in the event of an [internal com. link](ILF) fault cannot be configured, and the drive trips with a freewheel stop.
This fault cannot be reset.
Two diagnostic parameters can be used to obtain more detailed information about the origin of the [internal com. link] (ILF) fault:
- [Internal link fault 1](ILF1) if the fault has occurred on option card no. 1 (installed directly on the drive)
- [Internal link fault 2](ILF2) if the fault has occurred on option card no. 2 (installed on option card no. 1)
The Fipio card can be in position 1 or 2.
The [Internal link fault 1](ILF1) and [Internal link fault 2](ILF2) parameters can only be accessed on the graphic display terminal in
the [1.10 DIAGNOSTICS](dGt-) menu, [MORE FAULT INFO](AFI-) submenu.
ValueDescription of the values of the [Internal link fault 1] (ILF1)and [Internal link fault 2](ILF2) parameters
0No fault
1Loss of internal communication with the drive
2Hardware fault detected
3Error in the EEPROM checksum
4Faulty EEPROM
5Faulty Flash memory
6Faulty RAM memory
7Faulty NVRAM memory
8Faulty analog input
9Faulty analog output
10Faulty logic input
11Faulty logic output
101Unknown card
102Exchange problem on the drive internal bus
103Time out on the drive internal bus (500 ms)
1755883 11/200919
8. Software setup
2 In this window, you can add a Fipio device by
double-clicking on a connection point located between
addresses 0 and 62.
The "Add/Modify Device" window will appear.
3 Enter the Fipio address of the drive in the "Connection point
number" field (see the section on coding the drive address
on page 7
) and add a description (if required) in the
"Comment" field.
Next, select the "STD_P" (standard profiles) family and the
"FED C32" base module in this family (extended profile of a compact device with 32 periodic input and output words).
Click "OK" to confirm your selections.
1
2
3
8. 1. Configuration in PL7
1 In PL7, open the "Hardware Configuration" window for the TSX Premium PLC, followed by the "Fipio Configuration" window.
When you return to the "Hardware Configuration"
window, the new device will appear in the list of
Fipio logic addresses used.
Note: No configuration or adjustment settings
can be made in PL7 for this type of base module.
These settings must, therefore, be made either
via the integrated display terminal or the graphic
display terminal (see "Programming Manual").
Alternatively, the indexed periodic variables
service (PKW) described in this manual can be
used.
201755883 11/2009
8. Software setup
8. 2. Available objects
OBJECTDESCRIPTIONACCESSFORMAT
%QW\p.2.c\0.0.iPeriodic output variables
(drive control and adjustment)
%IW\p.2.c\0.0.iPeriodic input variables
(drive monitoring)
%I\p.2.c\0.0.ERRChannel faultImplicit read
%MW\p.2.c\0.0.2Channel status
(drive and communication diagnostics)
The Fipio card on the drive does not provide PL7 configuration (%KW\...), adjustment (%MW\...), or Fipio message handling services.
Configuration and adjustments can be accessed via the PKW service (indexed periodic values).
Syntax:
Word access
Output: %QW\p.2.c\0.0.i
Input: %IW\p.2.c\0.0.i
Implicit write
operation
Implicit read
operation
operation
Explicit read
operation
32 words
32 words
1 bit
1 word
p: Processor slot (0 or 1)
c: Number of the connection point on the Fipio bus (device address: 1 to 62)
Number of the periodic output or input variable (0 to 31)
i:
Note: If i = 0, it is not displayed: %QW\p.2.c\0.0
See "Configuration - Communication scanner" for information about how periodic variables are assigned.
See "Diagnostics - Communication scanner" for information about how periodic variables are displayed.
Not used
Input
PKWs
PKEin: Parameter logic address-
-
221755883 11/2009
8. Software setup
8. 4. PKW service
The PKW service provides read and write access to the drive parameters.
b Output PKWs
• PKEout
Parameter logic address
• RWout
= 0: PKW service not active
= 1: Read
= 2: Write
If PKEout and RWout (not 0) remain unchanged, the drive will execute the function permanently. Therefore, if you wish a service to be
confirmed, you must reset Rwout to zero between each transaction.
• PWEout
Write operation: Value of parameter to be written
b Input PKWs
• PKEin
The availability of the result of the PKW transaction is indicated by the value of PKEin changing to the same as that of PKEout.
• RWin
= 0: PKW service not active
= 1: Read operation correct
= 2: Write operation correct
= 7: Read or write error
•PWEin
- If the write operation is completed without errors: Parameter value. During a write operation, this value may differ from the value of
PKWout if PKWout is not within the permissible limits (the write operation is accepted but an upper or lower limit is applied).
- If there is an error:
= 0: Incorrect address
= 1: Write operation not accepted (read-only parameter or local forcing preventing a configuration or adjustment parameter being
written)
Note: The parameters configured in the periodic output variables should not be changed by the PKW indexed variable.
1755883 11/200923
8. Software setup
8. 5. Examples
b Example 1: Cyclic reading of HSP (3104)
Result of 500 read (50 Hz)
Output PKWsInput PKWs
PKEout3104PKEin3104
RWout1RWin1
PWEout_PWEin_
b Example 2: Cyclic writing of LSP (3105) to the value 100 (10 Hz)
Output PKWsInput PKWs
PKEout3105PKEin3105
RWout2RWin2
PWEout100PWEin100
b Example 3: Incorrect write operation: RFR parameter (3202) is read-only
Output PKWsInput PKWs
PKEout3202PKEin3202
RWout2RWin7
PWEout500PWEin1
b Example 4: Writing the value 1000 (100 Hz) to HSP, limited to 600 (60 Hz) by the drive
1Write
Output PKWsInput PKWs
PKEout3104PKEin3104
RWout2RWin2
PWEout1000PWEin1000
The input PKW responds in the bus scan cycle. The request is subsequently transmitted to the drive. The parameter is limited several
milliseconds later. It will be taken note of during the next cycle.
2 followed by a read operation
Output PKWsInput PKWs
PKEout3104PKEin3104
RWout1RWin1
PWEout_PWEin600
241755883 11/2009
8. Software setup
b Example 5: Display of I/O in debug mode
Example of an animation table in PL7 containing the periodic data exchanged with a drive at address 11 on the Fipio bus:
The periodic variables shown here are the same as those described in the example on page 13
Their values are described below (see the Parameters Manual):
• Periodic control of drive (%QW\0.2.11\0.0 to %QW\0.2.11\0.0.7):
- Control word (CMd) = 16#000F = "Enable operation": Command to switch to or maintain the "Operation enabled" state of the drive
(ATV running) in the DSP402 state graph
- Speed reference (LFrd) = 1000: Motor controlled at 1000 rpm
- Ramp increment (Inr) = 1: Unit of 0.1 s applied to ACC and DEC (among others)
- Acceleration (ACC) = 50: Acceleration 5.0 s (50 x 0.1 s)
- Deceleration (dEC) = 100: Deceleration 10.0 s (100 x 0.1 s)
• Periodic monitoring of drive (%IW\0.2.11\0.0 to %IW\0.2.11\0.0.7):
- Status word (EtA) = 16#0627: Drive in "Operation enabled" state (ATV running) in the DSP402 state graph with reference reached/in
steady state (bit 10 = 1)
- Output speed (FrHd) and Speed reference before ramp (rFrd) = 1000: 1000 rpm
- Logic input map (IL1r) = 16#0005: Logic inputs LI1 and LI3 active
- Physical image of analog input AI1 (AI1r) = 3925: 3.925 V (or mA) on AI1
- Physical image of analog input AI2 (AI2r) = 2513: 2.513 V (or mA) on AI2
• Use of PKW service for indexed periodic variables (request = %QW\0.2.11\0.0.28 to %QW\0.2.11\0.0.30 and
response = %IW\0.2.11\0.0.28 to %IW\0.2.11\0.0.30):
- Request for cyclic writing (RWout = 2) of the LSP variable (PKEout = 3105) at 10 Hz (PWEout = 100)
- Positive response: Write operation performed successfully (RWin = 2)
In this state, the motor runs forward at the reference speed (1000 rpm).
.
1755883 11/200925
8. Software setup
8. 6. Diagnostics in PL7
1 Monitoring system words %SW128 to %SW131.
Each bit in this group of words is indicative of the state of a device connected to the Fipio bus.
2 Monitoring the implicit word "Module fault" %I\p.2.c\0.MOD.ERR, which checks the connection point.
Normally at 0. A value of 1 indicates a fault.
3 For more information, read the "Channel status" %MW\p.2.c\0.0.2.
This information is updated by the explicit command READ_STS %CH\p.2.c\0.0.
p: Processor slot (0 or 1)
c: Connection point number
Definition of "Channel status"
BitDescription
0Reserved
1Reserved
2Reserved
3Supply fault
4Reserved
5Hardware configuration fault (CFI)
6PLC communication fault
7Reserved
8Configuration fault
9Module missing
10Module inoperative
11Module faulty
12Internal fault, TSX hardware fault
13Internal fault, TSX system fault
14Dialog fault, Fipio communication fault
15Dialog fault, drive parameterization fault
261755883 11/2009
ATV61/71_fipio_EN_1755883_03
1755883 11/2009
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.