Important Information _________________________________________________________________________________________ 5
Before you begin_____________________________________________________________________________________________ 6
Documentation structure_______________________________________________________________________________________ 7
Introduction_________________________________________________________________________________________________ 8
Receipt _________________________________________________________________________________________________ 9
Hardware description ______________________________________________________________________________________ 9
Installing the card in the drive________________________________________________________________________________ 9
Connecting to the Ethernet network_____________________________________________________________________________ 10
Card RJ45 connector pinout________________________________________________________________________________ 10
Example of connection to an Ethernet network _________________________________________________________________ 10
Ethernet network connection elements________________________________________________________________________ 11
Ethernet menu _____________________________________________________________________________________________ 12
Access to Ethernet menu via graphic display terminal____________________________________________________________ 12
Access to Ethernet menu via the integrated display terminal_______________________________________________________ 12
Ethernet menu parameters_________________________________________________________________________________ 13
List of functions to be configured ____________________________________________________________________________ 16
Configuring IP addresses__________________________________________________________________________________ 17
Reserving control _____________________________________________________________________________________ ___ 19
Configuring IO Scanning___________________________________________________________________________________ 19
Configuring the control ____________________________________________________________________________________ 20
Configuring the fault management ___________________________________________________________________________ 23
Configuring monitored parameters___________________________________________________________________________ 25
Signalling LEDs _________________________________________________________________________________________ 26
Available information _____________________________________________________________________________________ 27
Monitoring the control______________________________________________________________________________ _______ 27
Troubleshooting the communication fault______________________________________________________________________ 28
Troubleshooting the card fault ______________________________________________________________________________ 29
List of services supported__________________________________________________________________________________ 30
TCP connections ________________________________________________________________________________________ 30
Modbus TCP server _________________________________________________________________________________________ 31
Modbus TCP frames______________________________________________________________________________________ 31
Drive Modbus servers_____________________________________________________________________________________ 31
Ethernet card parameters__________________________________________________________________________________ 32
List of Modbus functions supported __________________________________________________ ________________________ 35
“Read Holding Registers” (3) function ________________________________________________________________________ 35
“Write Single Register” (6) function___________________________________________________________________________ 36
“Write Multiple Registers” (16 = 16#10) function ________________________________________________________________ 37
“Read/Write Multiple Registers” (23 = 16#17) function____________________________________________________________ 38
“Read Device Identification” (43 = 16#2B) function ______________________________________________________________ 39
IO Scanning service _________________________________________________________________________________________ 40
Standard Web server ________________________________________________________________________________________ 47
Web server functions _________________________________________________________ ____________________________ 47
Applets ________________________________________________________________________________________________ 48
Access to the Web server__________________________________________________________________________________ 49
Web server user interface__________________________________________________________________________________ 50
“Home” menu ___________________________________________________________________________________________ 50
“Monitoring” menu________________________________________________________________________________________ 50
“Altivar Viewer” page _____________________________________________________________________________________ 51
“Data Viewer” page_______________________________________________________________________________________ 52
“Altivar Chart” page_______________________________________________________________________________________ 53
“Diagnostics” menu_______________________________________________________________________________________ 53
“Ethernet Statistics” page________________ __________________________________________________________________ 54
“Setup” menu ___________________________________________________________________________________________ 54
“HTTP password” and “Data write password pages” _____________________________________________________________ 55
“FDR Agent” page________________________________________________________________________________________ 56
“IO Scanner” page _______________________________________________________________________________________ 58
"Email" page____________________________________________________________________________________________ 61
“Documentation” menu____________________________________________________________________________________ 62
FTP server ________________________________________________________________________________________________ 63
Downloading from the Web server______________________________________________________________________________ 65
SNMP agent _______________________________________________________________________________________________ 68
Setup using PL7____________________________________________________________________________________________ 70
Setup using Concept ________________________________________________________________________________________ 76
Setup using ProWORX NxT___________________________________________________________________________________ 77
4AAV69931 01/2011
1. Important Information
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personnal injury if the instruction are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
NOTICE
Read these instructions carefully, and look at th e equip ment to bec ome fami liar with t he devi ce before t rying to insta ll, operat e, or maintain
it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifie s a procedure.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or
equipment damage.
WARNING
Warning indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
Read and understand these instructions before performing any procedure with thi s drive.
* For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for
Selection, Installation and Operation of Adjustabl e-Speed Drive Systems".
DANGER
HAZARDOUS VOLTAGE
• Read and understand this bulletin in its entirety before ins talling or operating Altivar 61 / 71 drive.
This equipment must only be installed, adjusted, repaired, and maintained by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit board s, operate at the line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage prese nt.
• DO NOT short across terminals PA and PC or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive.
WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement
procedure given in the Installation Manual to verify that the DC voltage is less than 45 VDC. The drive LEDs are not
accurate indicators of the absence of DC bus voltage.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not install or operate any drive or drive accessory that appears damaged.The relays, inputs, or outputs of a damaged
drive may not operate in a normal manner, leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical
control functions, provide a means to achieve a safe state during and af ter a path failure. Examples of critical control
functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Considerat ion must be given to the implications of unanticipated
transmission delays or failures of the link.*
• Each implementation of an Altivar 71 Modbus TCP/IP Ethernet card must be indi viduall y and thoroughl y tested for proper
operation before being placed into service.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
AAV69931 01/20116
3. Documentation structure
The following Altivar 61 / 71 technical documents are available on the Web site www.schneider-electric.com and on the CDROM.
b Installation Manual
This manual describes:
• How to assemble the drive.
• How to connect the drive.
b Programming Manual
This manual describes:
• The functions.
• The parameters.
• How to use the drive display terminal (integrated display terminal and graphi c display terminal).
b Communication Parameters Manual
This manual describes:
• The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network.
• The operating modes specific to communication (state chart).
• The interaction between communication and local control.
• Configuration of the communication-specific parameters via the integrated display terminal or the graphic display terminal.
• Diagnostics.
• Software setup.
• The communication services specific to the protocol .
b Altivar 58/58F Migration Manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F.
It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.
7AAV69931 01/2011
4. Introduction
4. 1. Presentation
The Ethernet card (catalog number VW3 A3 310d) is used to connect an Altivar 61 / 71 drive to an Ethernet network using the Modbus
TCP/IP protocol and Transparent Ready services.
The VW3 A3 310d card is equipped with two shielded RJ45 Ethernet connector.
The accessories for connection to the Ethernet network must be ordered separately.
The data exchanges permit full drive functionality:
• Configuration
• Adjustment
• Control
• Monitoring
• Diagnostics
The standard Web server (English only) provides access to the following pages:
• Altivar Viewer
• Data Viewer
• Ethernet
• Security
Etc.
The standard Web server can be adapted or replaced by a customized server depending on the requirements of the application.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.
4. 2. Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets.
Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (COM-).
The parameter names displayed on the graphic display terminal are shown in square brackets.
Example: [Fallback speed].
The parameter codes displayed on the integrated 7-segment display terminal are shown in round brackets.
Example: (LFF).
Formats
Hexadecimal values are written as follows: 16#
Binary values are written as follows: 2#
AAV69931 01/20118
5. Hardware setup
LEDs
Shielded female RJ45
Ethernet connector
(Port 1)
MAC address label
on the Ethernet card
Shielded female RJ45
Ethernet connector
(Port 2)
5. 1. Receipt
• Check that the card catalog number marked on the label is the same as that on t he delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damag ed in transit.
CAUTION
STATIC SENSITIVE COMPONENTS
The Modbus TCP/IP Ethernet card can be damaged by static electricity. Observe electrostatic preca utions when handling and
installing the card.
Failure to follow this instruction can result in equipment dama ge .
5. 2. Hardware description
5. 3. Installing the card in the drive
See the Installation Manual.
9AAV69931 01/2011
6. Connecting to the Ethernet network
8........................1
PLC
ATV61/71 ATV61/71 ATV61/71 ATV61/71 ATV61/71
Daisy chain and/or star topology
Ethernet switch
6. 1. Card RJ45 connector pinout
The Ethernet card is equipped with a shielded RJ45 connector. The shielding is connected to the drive ground.
Use an STP (shielded twisted pair) Ethernet cable.
PinSignal
1TD+
2TD3RD+
4
5
6RD7
8
The transmission speed is detected automatically by the card (10 Mbps or 100 Mbps).
The card can operate in half duplex or full duplex mode, wh eth er conn ected t o a hub or a swi t ch and regardl ess of the t ra nsmission spe ed
(10 Mbps or 100 Mbps).
The card supports the ETHERNET 2 frame format (IEEE 802-3 not supported).
6. 2. Example of connection to an Ethernet network
Note: When the topology is a daisy chain, if one drive is turned off, the drive(s) next the drive powered off trip in CNF fault. To keep the
integrity of the Ethernet daisy chain network even if one or several drives are powered off, it is mandatory to add an external permanent
24VDc supply for the drives control bloc.
AAV69931 01/201110
6. Connecting to the Ethernet network
6. 3. Ethernet network connection elements
Please consult our catalog “Ethernet TCP/IP and the Web” (available on the Web site www.schneider-electric.com).
Connecting cables
DescriptionUseLengthCatalog number
FromTom
Straight shielded twisted pair cables
2 RJ45 connectors
ATV71
(+ VW3 A3 310d card)
Hubs
pH 1pp 10
499 N
Switches
pS 171 00
499 N
Hubs and switches
DescriptionCharacteristicsCatalog number
Hubs4 × 10BASE-T ports499 NEH 104 10
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
CodeQuick
ENT
RDYNET +0.00 Hz0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS/OUTPUTS CFG
Code<<>>Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
ENT
RUNNET+50.00 Hz 80A
1.9 COMMUNICATION
COM. SCANNER OUTPUT
MODBUS HMI
MODBUS NETWORK
CANopen
ETHERNET
Code<<>>Quick
XXX
SIM-
ESC
ESC
ENT
FCS-
LAC-
CON-
FLt-
ESC
ESC
ESC
ENT
ESC
Displays the drive state
EtH-
Power-up
7. 1. Access to Ethernet menu via graphic display terminal
The [ETHERNET] submenu is used to configure and display the Ethernet card parameters and can be accessed via the
[1.9 - COMMUNICATION] menu.
If you are using the FDR (Faulty Device Replacement) function, you must also configure the device name in the [7. DISPLAY CONFIG.]
menu, [7.1 USER PARAMETERS] submenu, [DEVICE NAME] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert](EPr).
7. 2. Access to Ethernet menu via the integrated display terminal
The (EtH-) submenu is used to configure and display the Ethernet card parameters. It can be accessed via the (COM-) menu.
Note: The device name required for the FDR (Faulty Device Replacement) function cannot be con figured via the integrated display terminal.
AAV69931 01/201112
7. Ethernet menu
7. 3. Ethernet menu parameters
CodeDescription
(bdr)M [Bit rate]
(PAn-)
(IPC-)
(IPC1)
(IPC2)
(IPC3)
(IPC4)
Transmission speed detected on the network by the Ethernet card
Type:Display (read-only)
Possible
values:
Default value:[0 Mbps](0M)
b [DEVICE NAME]
Device name used by FDR service. Accessible with an ATV71 from V1.2 and a ATV61 from V1.3 version.
Use the navigation selector button to increment the charac ter (a lph abetic al order) and << a nd > > (F2 and F3) t o switch
to the next or previous character respectively. Use F1 to change to ABC, abc, 123, *[-.
Type:Configuration (read and write)
Possible values:16 characters on 1 or 2 lines.
Default value:[0]
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPC1, IPC2, IPC3 and IPC4.
• If the value is [0.0.0.0](0) (0) (0) (0), the Ethernet card waits for an address from a BOOTP
or DHCP server.
Note: If you enter a value other than [0.0.0.0](0) (0) (0) (0), dynamic addressing by a BOOTP
or DHCP server is disabled.
Note: After dynamic addressing by a BOOTP or DHCP server, the value [0.0.0.0](0)(0)(0)(0)
is replaced by the address supplied.
(IPM-)
(IPM1)
(IPM2)
(IPM3)
(IPM4)
(IPG-)
(IPG1)
(IPG2)
(IPG3)
(IPG4)
b [IP Mask]
M [255.255.254.0] (255)(255)(254)(0)
Subnet mask
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPM1, IPM2, IPM3 and IPM4.
• If the value of the IP address [IP card] is [0.0.0.0](0) (0) (0) (0), the Ethernet card waits for
a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the
address supplied.
b [IP Gate]
M [0.0.0.0] (0) (0) (0) (0)
Gateway IP address
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPG1, IPG2, IPG3 and IPG4.
• If the value of the IP address [IP card] is [0.0.0.0](0) (0) (0) (0), the Ethernet card waits for
a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the
address supplied.
13AAV69931 01/2011
7. Ethernet menu
CodeDescription
(IPP-)
(IPP1)
(IPP2)
(IPP3)
(IPP4)
(IPF-)
(IPF1)
(IPF2)
(IPF3)
(IPF4)
(ISA)M [IO Scan.activ.]
(tOUt)M [time out]
b [IP Master]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the device that retains control
Type:Configuration (read and write)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
b [IP FDR]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the FDR server
Type:Display (read-only)
Possible
values:
Default value:[0.0.0.0](0) (0) (0) (0)
Enable IO Scanner
Type:Configuration (read and write)
Possible
values:
Default value:[Yes](YES)
Display (read-only) if the address is supplied by a DHCP server
• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.
• If the value is [0.0.0.0](0) (0) (0) (0), writing of the control word (CMd) is accepted
by the Ethernet card regardless of which device has sent it.
• If the value is other than [0.0.0.0](0) (0) (0) (0) only the device which has the IP address
[IP Master] is authorized to write the control word (CMd).
Note: This configuration also affects the type of communication monitoring.
• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.
• If the value is [0.0.0.0](0) (0) (0) (0), there is no server.
• [No](nO): IO Scanner disabled.
• [Yes](YES): IO Scanner enabled.
Ethernet communication monitoring time out
Type:Configuration (read and write)
Possible
values:
Default value:[2.0 s](2.0)
(FdrU)M [FDR validation]
Enable FDR service
Type:Configuration (read and write)
Possible
values:
Default value:[Yes](YES)
(LCFG)M [FDR Local Config.]
Selection of local or server configuration
Type:Configuration (read and write)
Possible
values:
Default value:[No](nO)
(FdrF)M [FDR Error Mgt.]
Enable FDR fault management process
Type:Configuration (read and write)
Possible
values:
Default value:[Yes](YES)
• [0](0): Monitoring disabled.
• [0.5 s](0.5) to [60.0 s](60.0): Time out value (unit: 0.1 s).
• [No](nO): FDR service disabled.
• [Yes](YES): FDR service enabled.
• [No](nO): The drive configuration is downloaded from an FDR server.
• [Yes](YES): The drive configuration is local and saved in a FDR server.
In the event of a problem with the FDR file (missing or invalid):
• [No](nO): The Ethernet card does not trigger an Ethernet fault (network management).
• [Yes](YES): The Ethernet card triggers a network management fault.
AAV69931 01/201114
7. Ethernet menu
CodeDescription
(FdrA)M [FDR Action]
FDR service command
Type:Command (read and write)
Possible
values:
Default value:[IDLE](IdLE)
(FdrS)M [FDR autosave]
Enable periodic saving of the FDR service
Type:Configuration (read and write)
Possible
values:
Default value:[No](nO)
(Fdrt)M [FDR t.autosave]
Interval for periodic saving of the FDR service
Type:Configuration (read and write)
Possible
values:
Default value:[10] (10)
(FdrE)M [FDR state]
• [IDLE](IdLE):No command.
• [SAVE](SAUE): Command: save.
• [REST](rESt): Command: download.
• [DEL](dEL): Command: delete.
The command remains displayed during the action then reverts to the value [IDLE](IdLE).
• [No](nO): Automatic saving disabled.
• [Yes](YES): Automatic saving enabled.
• [2](2) to[9999](9999): 2 min to 9999 min.
FDR service state
Type:Display (read-only)
Possible
values:
Default value:[IDLE](IdLE)
(Fdrd)M [FDR Error Code]
FDR service error code
Type:Display (read-only)
Possible
values:
Default value:[0](0)
• [IDLE](IdLE): “Idle”.
• [INIT](INIt): Initializatio n .
• [CONF](CONF): Configuration.
• [RDY](rdY): Ready.
• [GET](GEt): Download the current configuration.
• [SET](SEt): Save the current configuration.
• [APP](APP): Write the FDR server configuration to the drive.
• [OPE](OPE): Operational.
• [UCFG](UCFG): Not configured.
• [0](0): No fault.
• [2](2): The FDR configuration file is not compatible with the drive type
(example: the drive is not the same rating as that defined in the FDR file).
• [3](3): Error reading the FDR configuration file on the server.
• [4](4): Error writing the FDR configuration file to the server.
• [7](7): Time-out for receipt of the FDR configuration file from the server.
• [9](9): Duplication of IP address.
• [12](12): The FDR configuration file is missing.
15AAV69931 01/2011
8. Configuration
8. 1. List of functions to be configured
The table below gives the list of configuration functions and how they can be accessed:
Functions
Entering the IP addressesppp
FDR
(Faulty Device Replacement)
IO Scanning
Reserving control (IP master)pppp
Communication monitoringpppp
Security of access
to the standard Web server
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section.
Configuration using the standard Web server is explained in the “Standard Web server” section.
For configuration using the PC-Software workshop, refer to the online help.
Note: The Ethernet card saves its configuration (IP address, mask, gateway, etc.) t o the EEPROM each time the config uration is modi fied.
Note: For performance reasons, we do not re commend using the drive communicat ion scanner. It is better to use the Ethernet I O Scanner.
Note: Configuration must be performed with the motor stopped.
Entering the device namepp
Configuration (time delay, etc.)pppp
Commands (save, etc.)ppp
Enable IO Scannerpppp
Configuring the IO Scanner variablespp
Changing the “username”p
Changing the “HTTP password”p
Changing the “Write password”pp
Graphic
display
terminal
Integrated
display
terminal
PC-Software
software
workshop
Standard
Web
server
AAV69931 01/201116
8. Configuration
Static
addressing
DHCP
FDR
BOOTP
Initialization
Power-up
An address has been entered
[IP card] <> 0.0.0.0
No address has been entered
[IP card] = 0.0.0.0
Dynamic
addressing
[FDR validation] = [No]
[FDR validation] = [Yes]
[DEVICE NAME] blank
[DEVICE NAME] has been
entered
8. 2. Configuring IP addresses
b Assigning IP addresses
The drive needs 3 IP addresses:
• The drive IP address.
• The subnet mask.
• The gateway IP address.
These IP addresses can be entered directly:
• Using the integrated display terminal.
• Using the graphic display terminal.
• Or using the PC-Software workshop.
They can be provided by:
• A BOOTP server (correspondence between the MAC address and the IP addresses).
• Or a DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).
If an IP address other than 0.0.0.0 has been entered using the display terminal or the PC-Software workshop, assignment using a server
is disabled.
The BOOTP service is enabled:
• When no IP address other than 0.0.0.0 has been entered.
• And the FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).
The DHCP service is enabled:
• When no IP address other than 0.0.0.0 has been entered.
• And the FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).
17AAV69931 01/2011
8. Configuration
b Entering IP addresses in the terminal
In the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu, enter the following IP addresses:
- [IP card](IPC1) (IPC2) (IPC3) (IPC4).
- [IP Mask](IPM1) (IPM2) (IPM3) (IPM4).
- [IP Gate](IPG1) (IPG2) (IPG3) (IPG4).
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the IP addresses are not
taken into account.
Note: Before entry begins, the IP address displayed is the active IP address.
If this address is modified, the new IP address entered is displayed. This IP address will be effective the next time the drive is turned on.
b Configuring BOOTP
The BOOTP service is used to assign IP addresses from the MAC address. The MAC address consisting of 6 hexadecimal digits
(00-80-F4-80-xx-yy) must be entered in the BOOTP server. The MAC address appears on the label attached to the Ethernet card.
In the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu:
• Leave the IP address [IP card](IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0](0) (0) (0) (0).
• Do not enable the FDR service: [FDR validation](FdrU) = [No](nO).
b Configuring FDR
The FDR service (based on DHCP) is used to assign the IP addresses from the device name that must be entered in the drive and in the
FDR server (DHCP).
In the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu:
• Leave the IP address [IP card](IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0](0) (0) (0) (0).
• Enable the FDR service: [FDR validation](FdrU) = [Yes](YES).
For the FDR function, select the drive configuration as either:
•Local: [FDR Local Config.](LCFG) = [Yes](YES).
• Downloaded. In this case, it is essential to consult the “FDR Service” section.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert](EPr).
Turn the drive off and then back on again (contro l voltage if a separate power supply is being used), ot herwise the device name is not taken
into account.
Note: The FDR function cannot be fully configured using the integrated display terminal as it does not provide access to the device name.
AAV69931 01/201118
8. Configuration
8. 3. Reserving control
It is strongly recommended that control should be reserved for a single master device.
If control were not to be reserved for a master device (for example a PLC):
• Any other Modbus TCP Ethernet client could send unwanted commands.
• Other clients could use the 8 available TCP connections and prevent the master from having control.
WARNING
IP MASTER NOT SPECIFIED
Use the [IP MASTER](IPP) menu option to configure a network maste r device. If a vali d IP address for a master devi ce is not specified
using this option, other Ethernet cli ents c an sat urate t he TCP c onne ctions or sen d i ncorrec t comma nds le ading to un int ended equ ipment
operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
To configure this reservation, enter an IP address other than [0.0.0.0](0) (0) (0) (0) in th e [1.9 COMMUNICATION](COM-) menu,
[ETHERNET](EtH-) submenu, [IP Master] submenu.
• If control has been reserved:
Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging.
2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections
(8 maximum) and the control master therefore no longer being able to access the drive Modbus TCP server.
Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint).
When control has been reserved and another device attempts to write the control word (CMd):
- via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.
- via Modbus TCP messaging: Control is denied.
• If control has not been reserved ([IP Master] = [0.0.0.0](0) (0) (0) (0)), control can come from any IP address.
8. 4. Configuring IO Scanning
Refer to the “IO Scanning Service” section.
The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION](COM-) menu, [ETHERNET] (EtH-)
submenu via parameter [IO Scan.activ.](IOSA).
It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).
To configure IO Scanning, use the standard Web server or the PC-Software workshop.
19AAV69931 01/2011
8. Configuration
8. 5. Configuring the control
Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters
Manual.
The following configurations are just some of the possibili ties available.
b Control via Ethernet in I/O profile
The command and setpoint come from Ethernet.
The command is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Setpoint 1 configurationNetwork card The setpoint comes from Ethernet.
Command 1 configurationNetwork card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Ethernet or the terminals in I/O profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet
and the terminals.
The command is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Setpoint 1 configurationNetwork cardSetpoint 1 comes from Ethernet.
Setpoint 1B configurationAnalog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from Ethernet.
Command 2 configurationTerminalsCommand 2 comes from the terminals.
Command switchingInput LI5Input LI5 switches the command.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain act ive, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via Ethernet or the terminals in Drivecom profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet
and the terminals.
The command is in Drivecom profile.
The run commands are in Drivecom profile, the command and the setpoint
come from the same channel.
Configure the following parameters:
ParameterValueComment
ProfileDrivecom profile not separateThe run commands are in Drivecom profile, the command and the
Setpoint 1 configurationNetwork cardSetpoint 1 comes from Ethernet.
Setpoint 2 configurationAnalog input 1 on the terminalsSetpoint 2 comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Note: Setpoint 2 is directly connected to the drive setpoint limit. If switching is performed, the functions that affect the setpoint (summing,
PID, etc.) are disabled.
Configuration via the graphic display terminal or the integrated display terminal:
b Command in Drivecom profile via Ethernet and setpoint switching at the terminals
The command comes from Ethernet.
The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet
and the terminals.
The command is in Drivecom profile.
Configure the following parameters:
ParameterValueComment
ProfileDrivecom profile separateThe run commands are in Drivecom profile, the command and the
Setpoint 1 configurationNetwork cardSetpoint 1 comes from Ethernet.
Setpoint 1B configurationAnalog input 1 on the terminalsSetpoint 1B comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from Ethernet.
Command switchingChannel 1Channel 1 is the command channel.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain act ive, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
- Network management faults (server missing, duplication of IP address, etc.).
- Communication faults (time out on the master traffic, etc.).
The associated information is:
Network managementCommunication
Associated drive faultCode:
Configuring the
communication fault
Configuring the drive’s
response
[External fault com.](EPF2)
Parameter:
[FDR Error Mgt.](FdrF)
Menu:
[1.9 COMMUNICATION](COM-)
Submenu:
[ETHERNET](EtH-)
Parameter:
[External fault mgt](EPL)
Menu:
[1.8 FAULT MANAGEMENT](FLt-)
Submenu:
[EXTERNAL FAULT](EtF-)
Ethernet fault type
Code:
[Com. network](CnF)
Parameter:
[time Out](tOUt)
Menu:
[1.9 COMMUNICATION](COM-)
Submenu:
[ETHERNET](EtH-)
Parameter:
[COM. fault mgt](CLL)
Menu:
[1.8 FAULT MANAGEMENT](FLt-)
Submenu:
[COM. FAULT MANAGEMENT](CLL-)
b Network management fault
The IP address duplication management fault cannot be configured.
If the FDR (Faulty Device Replacement) service has been configured, the FDR fault can be disabled via the [FDR Error Mgt.](FdrF)
parameter, which can be accessed via the [1.9 COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu.
In factory settings mode, a network management fault will trigger a resettable drive fault [External fault com.](EPF2) and initiate
a freewheel stop.
b Communication fault
It is strongly recommended that control should be reserved for a single master device.
Monitoring begins when the first control word is received.
Even if the command channel is not the network, a write access on the CMD word is necessary to activate the monitoring of the network.
WARNING
IP MASTER NOT SPECIFIED
Use the [IP MASTER](IPP) menu option to configure a network maste r device. If a vali d IP address for a master devi ce is not specified
using this option, other Ethernet cli ents c an sat urate t he TCP c onne ctions or sen d i ncorrec t comma nds le ading to un int ended equ ipment
operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
• If control has been reserved:
A communication fault is triggered if the Ethernet card does not receive a Modbus TCP requ est within a predefined period
of time (time out).
Any type of Modbus request from the master device [IP Master] is taken into account (write operation, read operation, etc.).
• If control has not been reserved:
A communication fault is triggered if the Ethernet card does not receive a control word write request (CMd) within a predefined
period of time (time out).
Receipt of the command (CMd) is taken into account regardless of the sender’s IP address.
The “time out” can be set to between 0.5 and 60 s via the graphic display terminal or integrated display terminal in the
[1.9 COMMUNICATION](COM-) menu, [ETHERNET](EtH-) submenu via the [time Out](tOUt) parameter. The default value is 2 s.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication fault will trigger a resettable drive fault
[Com. network](CnF) and initiate a freewheel stop.
For communication faults
in the [COM. FAULT MANAGEMENT](CLL-) submenu
via parameter [COM. fault mgt](CLL)
For network management faults
in the [EXTERNAL FAULT](EtF-) submenu
via the [External fault mgt](EPL) parameter
b Drive response
The drive response to an Ethernet fault can be configured via the graphic display terminal or the integrated display terminal,
from the [1.8 FAULT MANAGEMENT](FLt-) menu:
The values of parameters: [COM. fault mgt](CLL) that will trigger a drive fault [Com. network](CnF)
and [External fault mgt](EPL) that will trigger a driv e fault [External fault com.](EPF2) are:
[Freewheel](YES): Freewheel stop (factory setting).
[Ramp stop](rMP): Stop on ramp.
[Fast stop](FSt): Fast stop.
[DC injection](dCI): DC injection stop.
The values of parameters [COM. fault mgt](CLL) and [External fault management](EPL) which will not trigger a drive fault are:
[Ignore](nO): Fault ignored.
[Per STT](Stt): Stop according to configuration of [Stop type] (Stt).
[fallback spd](LFF): Change to fallback speed, maintained as long as the fault persists and the run command has not been removed.
[Spd maint.](rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run command has
not been removed.
The fallback speed can be configured in the
[1.8 - FAULT MANAGEMENT](FLt-) menu via the [Fallback speed](LLF) parameter.
AAV69931 01/201124
8. Configuration
8. 7. Configuring monitored parameters
It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu on the graphic display terminal.
The selection is made via the [6 - MONITORING CONFIG.] menu, [6.3 - COM. MAP CONFIG.] submenu.
Each parameter in the range [Address 1 select.] … [Address 4 select.]
is used to select the parameter logic address. Sel ect an address of zero
to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCR): logic address 3204;
signed decimal format.
• Parameter 2 = Motor torque (OTR): logic address 3205;
signed decimal format.