schneider VW3 A3 310 User Manual

2354235 11/2008
Altivar 61/71
Modbus TCP/IP Ethernet card
User manual
VW3 A3 310
1755879
www.schneider-electric.com
Table of Contents
1. Important Information _______________________________________________________________________________________ 4
2. Before you begin___________________________________________________________________________________________ 5
3. Documentation structure_____________________________________________________________________________________ 6
4. Introduction_______________________________________________________________________________________________ 7
4. 1. Presentation _________________________________________________________________________________________ 7
4. 2. Evolutions du logiciel __________________________________________________________________________________ 7
4. 3. Notation ____________________________________________________________________________________________ 7
5. Hardware setup ___________________________________________________________________________________________ 8
5. 1. Receipt _____________________________________________________________________________________________ 8
5. 2. Hardware description __________________________________________________________________________________ 8
5. 3. Installing the card in the drive____________________________________________________________________________ 8
6. Connecting to the Ethernet network ____________________________________________________________________________ 9
6. 1. Card RJ45 connector pinout_____________________________________________________________________________ 9
6. 2. Example of connection to an Ethernet network ______________________________________________________________ 9
6. 3. Ethernet network connection elements____________________________________________________________________ 10
7. Ethernet menu ___________________________________________________________________________________________ 11
7. 1. Access to Ethernet menu via graphic display terminal________________________________________________________ 11
7. 2. Access to Ethernet menu via the integrated display terminal ___________________________________________________ 11
7. 3. Ethernet menu parameters_____________________________________________________________________________ 12
8. Configuration ____________________________________________________________________________________________ 15
8. 1. List of functions to be configured ________________________________________________________________________ 15
8. 2. Configuring IP addresses ______________________________________________________________________________ 16
8. 3. Reserving control ____________________________________________________________________________________ 18
8. 4. Configuring IO Scanning_______________________________________________________________________________ 18
8. 5. Configuring the control ________________________________________________________________________________ 19
8. 6. Configuring the fault management _______________________________________________________________________ 22
8. 7. Configuring monitored parameters _______________________________________________________________________ 24
9. Diagnostics ______________________________________________________________________________________________ 25
9. 1. Signalling LEDs _____________________________________________________________________________________ 25
9. 2. Available information _________________________________________________________________________________ 25
9. 3. Monitoring the control _________________________________________________________________________________ 26
9. 4. Troubleshooting the communication fault __________________________________________________________________ 27
9. 5. Troubleshooting the card fault __________________________________________________________________________ 28
10. Software setup __________________________________________________________________________________________ 29
10. 1. List of services supported_____________________________________________________________________________ 29
10. 2. TCP connections ___________________________________________________________________________________ 29
11. Modbus TCP server ______________________________________________________________________________________ 30
11. 1. Modbus TCP frames_________________________________________________________________________________ 30
11. 2. Drive Modbus servers________________________________________________________________________________ 30
11. 3. Ethernet card parameters_____________________________________________________________________________ 31
11. 4. List of Modbus functions supported _____________________________________________________________________ 34
11. 5. “Read Holding Registers” (3) function ___________________________________________________________________ 34
11. 6. “Write Single Register” (6) function______________________________________________________________________ 35
11. 7. “Write Multiple Registers” (16 = 16#10) function ___________________________________________________________ 36
11. 8. “Read/Write Multiple Registers” (23 = 16#17) function_______________________________________________________ 37
11. 9. “Read Device Identification” (43 = 16#2B) function _________________________________________________________ 38
12. IO Scanning service ______________________________________________________________________________________ 39
12. 1. Presentation _______________________________________________________________________________________ 39
12. 2. Periodic variables ___________________________________________________________________________________ 39
12. 3. Address table ______________________________________________________________________________________ 40
13. FDR service ____________________________________________________________________________________________ 41
13. 1. Presentation _______________________________________________________________________________________ 41
13. 2. Local configuration __________________________________________________________________________________ 42
13. 3. Downloaded configuration ____________________________________________________________________________ 43
13. 4. Periodic saving _____________________________________________________________________________________ 45
13. 5. Other commands ___________________________________________________________________________________ 45
13. 6. Configuration file____________________________________________________________________________________ 45
2 1755879 11/2009
Table of Contents
14. Standard Web server _____________________________________________________________________________________ 46
14. 1. Web server functions ________________________________________________________________________________ 46
14. 2. Applets ___________________________________________________________________________________________ 47
14. 3. Access to the Web server_____________________________________________________________________________ 48
14. 4. Web server user interface_____________________________________________________________________________ 49
14. 5. “Home” menu ______________________________________________________________________________________ 49
14. 6. “Monitoring” menu___________________________________________________________________________________ 49
14. 7. “Altivar Viewer” page ________________________________________________________________________________ 50
14. 8. “Data Viewer” page__________________________________________________________________________________ 51
14. 9. “Altivar Chart” page__________________________________________________________________________________ 52
14. 10. “Diagnostics” menu_________________________________________________________________________________ 52
14. 11. “Ethernet Statistics” page ____________________________________________________________________________ 53
14. 12. “Setup” menu _____________________________________________________________________________________ 53
14. 13. “HTTP password” and “Data write password pages” _______________________________________________________ 54
14. 14. “FDR Agent” page__________________________________________________________________________________ 55
14. 15. “IO Scanner” page _________________________________________________________________________________ 57
14. 16. "Email" page ______________________________________________________________________________________ 60
14. 17. “Documentation” menu ______________________________________________________________________________ 61
15. FTP server _____________________________________________________________________________________________ 62
16. Downloading from the Web server ___________________________________________________________________________ 64
17. SNMP agent ____________________________________________________________________________________________ 67
18. Setup using PL7 _________________________________________________________________________________________ 69
19. Setup using Concept _____________________________________________________________________________________ 75
20. Setup using ProWORX NxT ________________________________________________________________________________ 76
1755879 11/2009 3

1. Important Information

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personnal injury if the instruction are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.
WARNING
Warning indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
PLEASE NOTE
Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons. © 2009 Schneider Electric. All Rights Reserved.
4 1755879 11/2009

2. Before you begin

Read and understand these instructions before performing any procedure with this drive.
* For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems".
DANGER
HAZARDOUS VOLTAGE
• Read and understand this bulletin in its entirety before installing or operating Altivar 71 drive. This equipment must only be installed, adjusted, repaired, and maintained by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning protective grounding of all equipment.
• Many parts of this variable speed drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA and PC or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure given in the Installation Manual to verify that the DC voltage is less than 45 VDC. The drive LEDs are not accurate indicators of the absence of DC bus voltage.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED EQUIPMENT
Do not install or operate any drive or drive accessory that appears damaged.The relays, inputs, or outputs of a damaged drive may not operate in a normal manner, leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.*
• € Each implementation of an Altivar 71 Modbus TCP/IP Ethernet card must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
1755879 11/2009 5

3. Documentation structure

The following Altivar 71 technical documents are available on the Web site www.schneider-electric.com and on the CDROM delivered with each drive.
b Installation Manual
This manual describes:
• How to assemble the drive.
• How to connect the drive.
b Programming Manual
This manual describes:
• The functions.
• The parameters.
• How to use the drive display terminal (integrated display terminal and graphic display terminal).
b Communication Parameters Manual
This manual describes:
• The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network.
• The operating modes specific to communication (state chart).
• The interaction between communication and local control.
b Modbus, CANopen, Ethernet, Profibus, INTERBUS, Uni-Telway, DeviceNet, Modbus Plus, Fipio, etc., manuals.
These manuals describe:
• Connection to the bus or network.
• Configuration of the communication-specific parameters via the integrated display terminal or the graphic display terminal.
• Diagnostics.
• Software setup.
• The communication services specific to the protocol.
b Altivar 58/58F Migration Manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F. It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.
6 1755879 11/2009

4. Introduction

4. 1. Presentation

The Ethernet card (catalog number VW3 A3 310) is used to connect an Altivar 71 drive to an Ethernet network using the Modbus TCP/IP protocol and Transparent Ready services.
The VW3 A3 310 card is equipped with a shielded RJ45 Ethernet connector.
The accessories for connection to the Ethernet network must be ordered separately.
The data exchanges permit full drive functionality:
• Configuration
• Adjustment
• Control
• Monitoring
• Diagnostics
The standard Web server (English only) provides access to the following pages:
• Altivar Viewer
• Data Viewer
• Ethernet
• Security Etc.
The standard Web server can be adapted or replaced by a customized server depending on the requirements of the application.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.

4. 2. Software evolution

The Ethernet option board now provides new functionnalities. The Ethernet option board is now in V2.1 version. This new version can replace the previous one without modifications. This documentation deals with the V2.1 version but still usable for the V1.1 since the evolutions don't modify or remove functions previously available but add new ones.
b Evolution coming with the V2.1 Ethernet version

1 New Email function (see page 60). 2 Names of web pages have been modified:

- Altivar (Eth V1.1) becomes Altivar Viewer (Eth V2.1)
- Data Editor (Eth V1.1) becomes Data Viewer (Eth V2.1)
3 The graphic interface of the Data Viewer page (Eth V2.1) provides the same functionnalities than the Data Editor (Eth V1.1) but offer the
new possibiilty : to write the command word.

4 WEB DESIGNER complian.

Note : A FDR configuration file XXXX.prm coming from an Ethernet V2.1 option board can not be applied on a V1.1 option board.

4. 3. Notation

Drive terminal displays
The graphic display terminal menus are shown in square brackets. Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in round brackets. Example: (COM-).
The parameter names displayed on the graphic display terminal are shown in square brackets. Example: [Fallback speed].
The parameter codes displayed on the integrated 7-segment display terminal are shown in round brackets. Example: (LFF).
Formats
Hexadecimal values are written as follows: 16# Binary values are written as follows: 2#
1755879 11/2009 7

5. Hardware setup

LEDs
Shielded female RJ45 Ethernet connector
MAC address label
on the Ethernet card
00-80-F4-80-xx-yy

5. 1. Receipt

• Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damaged in transit.
CAUTION
STATIC SENSITIVE COMPONENTS
The Modbus TCP/IP Ethernet card can be damaged by static electricity. Observe electrostatic precautions when handling and installing the card.
Failure to follow this instruction can result in equipment damage.

5. 2. Hardware description

5. 3. Installing the card in the drive

See the Installation Manual.
8 1755879 11/2009

6. Connecting to the Ethernet network

8........................1

6. 1. Card RJ45 connector pinout

The Ethernet card is equipped with a shielded RJ45 connector. The shielding is connected to the drive ground. Use an STP (shielded twisted pair) Ethernet cable.
Pin Signal
1TD+
2TD-
3 RD+
4
5
6 RD-
7
8
The transmission speed is detected automatically by the card (10 Mbps or 100 Mbps).
The card can operate in half duplex or full duplex mode, whether connected to a hub or a switch and regardless of the transmission speed (10 Mbps or 100 Mbps).
The card supports the ETHERNET 2 frame format (IEEE 802-3 not supported).

6. 2. Example of connection to an Ethernet network

1 TSX PREMIUM PLC with TSX ETY 4101 or 5101 module

2 490 NTW 000 02 cable

3 499 NEH 104 10 hub

1755879 11/2009 9

6. Connecting to the Ethernet network

6. 3. Ethernet network connection elements

Please consult our catalog “Ethernet TCP/IP and the Web” (available on the Web site www.schneider-electric.com).
Connecting cables
Description Use Length Catalog number
From To m
Straight shielded twisted pair cables
2 RJ45 connectors
ATV71 (+ VW3 A3 310 card)
Hubs
pH 1pp 10
499 N Switches
pS 171 00
499 N
Hubs and switches
Description Characteristics Catalog number
Hubs 4 × 10BASE-T ports 499 NEH 104 10
4 × 100BASE-TX ports 499 NEH 141 10
3 × 10BASE-T ports 2 × 10BASE-FL ports, multimode fiber, ST (BFOC) connectors
Switches 5 × 10BASE-T/100BASE-TX ports
Unmanageable basic
4 × 10BASE-T/100BASE-TX ports 1 × 100BASE-FX port, multimode fiber, SC connectors Unmanageable
3 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, multimode fiber, SC connectors Unmanageable
4 × 10BASE-T/100BASE-TX ports 1 × 100BASE-FX port, monomode fiber, SC connectors Unmanageable
3 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, monomode fiber, SC connectors Unmanageable
8 × 10BASE-T/100BASE-TX ports Unmanageable
7 × 10BASE-T/100BASE-TX ports Manageable
5 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, multimode fiber, SC connectors Manageable
5 × 10BASE-T/100BASE-TX ports 2 × 100BASE-FX port, monomode fiber, SC connectors Manageable
2 490 NTW 000 02
5 490 NTW 000 05
12 490 NTW 000 12
40 490 NTW 000 40
80 490 NTW 000 80
499 NOH 105 10
499 NES 251 00
499 NMS 251 01
499 NMS 251 02
499 NSS 251 01
499 NSS 251 02
499 NES 181 00
499 NES 271 00
499 NOS 271 00
499 NSS 271 00
10 1755879 11/2009

7. Ethernet menu

RDY NET +0.00 Hz 0A
MAIN MENU
1 DRIVE MENU
2 ACCESS LEVEL
3 OPEN / SAVE AS
4 PASSWORD
5 LANGUAGE
Code Quick
ENT
RDY NET +0.00 Hz 0A
1 DRIVE MENU
1.1 SIMPLY START
1.2 MONITORING
1.3 SETTINGS
1.4 MOTOR CONTROL
1.5 INPUTS/OUTPUTS CFG
Code << >> Quick
1.6 COMMAND
1.7 APPLICATION FUNCT.
1.8 FAULT MANAGEMENT
1.9 COMMUNICATION
1.10 DIAGNOSTICS
1.11 IDENTIFICATION
1.12 FACTORY SETTINGS
1.13 USER MENU
1.14 PROGRAMMABLE CARD
ENT
RUN NET +50.00 Hz 80A
1.9 COMMUNICATION
COM. SCANNER OUTPUT
MODBUS HMI
MODBUS NETWORK
CANopen
ETHERNET
Code << >> Quick
XXX
SIM-
ESC
ESC
ENT
FCS-
LAC-
CON-
FLt-
ESC
ESC
ESC
ENT
ESC
Displays the drive state
COMMUNICATION
Power-up

7. 1. Access to Ethernet menu via graphic display terminal

The [ETHERNET] submenu is used to configure and display the Ethernet card parameters and can be accessed via the
[1.9 - COMMUNICATION] menu.
If you are using the FDR (Faulty Device Replacement) function, you must also configure the device name in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu, [DEVICE NAME] submenu.
This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).

7. 2. Access to Ethernet menu via the integrated display terminal

The (EtH-) submenu is used to configure and display the Ethernet card parameters. It can be accessed via the (COM-) menu.
Note: The device name required for the FDR (Faulty Device Replacement) function cannot be configured via the integrated display terminal.
1755879 11/2009 11

7. Ethernet menu

7. 3. Ethernet menu parameters

Code Description
(bdr) M [Bit rate]
(PAn-)
(IPC-)
(IPC1) (IPC2) (IPC3) (IPC4)
Transmission speed detected on the network by the Ethernet card
Type: Display (read-only)
Possible values:
Default value: [0 Mbps] (0M)
b [DEVICE NAME]
Device name used by FDR service. Accessible with an ATV71 from V1.2 and a ATV61 from V1.3 version. Use the navigation selector button to increment the character (alphabetical order) and << and >> (F2 and F3) to switch to the next or previous character respectively. Use F1 to change to ABC, abc, 123, *[-.
Type: Configuration (read and write)
Possible values: 16 characters on 1 or 2 lines.
Default value: [0]
b [IP card]
M [139.160.069.241] (139) (160) (069) (241)
Ethernet card IP address
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
[0 Mbps] (0M): Indeterminate speed (before automatic detection of the Ethernet network speed) [10 Mbps] (10M): 10 Mbps [100 Mbps] (100M): 100 Mbps
Display (read-only)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPC1, IPC2, IPC3 and IPC4.
• If the value is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for an address from a BOOTP or DHCP server.
Note: If you enter a value other than [0.0.0.0] (0) (0) (0) (0), dynamic addressing by a BOOTP or DHCP server is disabled. Note: After dynamic addressing by a BOOTP or DHCP server, the value [0.0.0.0] (0)(0)(0)(0) is replaced by the address supplied.
(IPM-)
(IPM1) (IPM2) (IPM3) (IPM4)
(IPG-)
(IPG1) (IPG2) (IPG3) (IPG4)
b [IP Mask]
M [255.255.254.0] (255) (255) (254) (0)
Subnet mask
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPM1, IPM2, IPM3 and IPM4.
• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the address supplied.
b [IP Gate]
M [0.0.0.0] (0) (0) (0) (0)
Gateway IP address
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
Display (read-only) if the address has been supplied by a BOOTP or DHCP server
• 0 to 255 for each of fields IPG1, IPG2, IPG3 and IPG4.
• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for a mask from a BOOTP or DHCP server.
Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the address supplied.
12 1755879 11/2009

7. Ethernet menu

Code Description
(IPP-)
(IPP1) (IPP2) (IPP3) (IPP4)
(IPF-)
(IPF1) (IPF2) (IPF3) (IPF4)
(ISA) M [IO Scan.activ.]
(tOUt) M [time out]
b [IP Master]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the device that retains control
Type: Configuration (read and write)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
b [IP FDR]
M [0.0.0.0] (0) (0) (0) (0)
IP address of the FDR server
Type: Display (read-only)
Possible values:
Default value: [0.0.0.0] (0) (0) (0) (0)
Enable IO Scanner
Type: Configuration (read and write)
Possible values:
Default value: [Yes] (YES)
Display (read-only) if the address is supplied by a DHCP server
• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.
• If the value is [0.0.0.0] (0) (0) (0) (0), writing of the control word (CMd) is accepted by the Ethernet card regardless of which device has sent it.
• If the value is other than [0.0.0.0] (0) (0) (0) (0) only the device which has the IP address
[IP Master] is authorized to write the control word (CMd).
Note: This configuration also affects the type of communication monitoring.
• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.
• If the value is [0.0.0.0] (0) (0) (0) (0), there is no server.
[No] (nO): IO Scanner disabled.
[Yes] (YES): IO Scanner enabled.
Ethernet communication monitoring time out
Type: Configuration (read and write)
Possible values:
Default value: [2.0 s] (2.0)
(FdrU) M [FDR validation]
Enable FDR service
Type: Configuration (read and write)
Possible values:
Default value: [Yes] (YES)
(LCFG) M [FDR Local Config.]
Selection of local or server configuration
Type: Configuration (read and write)
Possible values:
Default value: [No] (nO)
(FdrF) M [FDR Error Mgt.]
Enable FDR fault management process
Type: Configuration (read and write)
Possible values:
Default value: [Yes] (YES)
[0] (0): Monitoring disabled.
[0.5 s] (0.5) to [60.0 s] (60.0): Time out value (unit: 0.1 s).
[No] (nO): FDR service disabled.
[Yes] (YES): FDR service enabled.
[No] (nO): The drive configuration is downloaded from an FDR server.
[Yes] (YES): The drive configuration is local and saved in a FDR server.
In the event of a problem with the FDR file (missing or invalid):
[No] (nO): The Ethernet card does not trigger an Ethernet fault (network management).
[Yes] (YES): The Ethernet card triggers a network management fault.
1755879 11/2009 13

7. Ethernet menu

Code Description
(FdrA) M [FDR Action]
FDR service command
Type: Command (read and write)
Possible values:
Default value: [IDLE] (IdLE)
(FdrS) M [FDR autosave]
Enable periodic saving of the FDR service
Type: Configuration (read and write)
Possible values:
Default value: [No] (nO)
(Fdrt) M [FDR t.autosave]
Interval for periodic saving of the FDR service
Type: Configuration (read and write)
Possible values:
Default value: [10] (10)
(FdrE) M [FDR state]
[IDLE] (IdLE): No command.
[SAVE] (SAUE): Command: save.
[REST] (rESt): Command: download.
[DEL] (dEL): Command: delete. The command remains displayed during the action then reverts to the value [IDLE] (IdLE).
[No] (nO): Automatic saving disabled.
[Yes] (YES): Automatic saving enabled.
[2] (2) to [9999] (9999): 2 min to 9999 min.
FDR service state
Type: Display (read-only)
Possible values:
Default value: [IDLE] (IdLE)
(Fdrd) M [FDR Error Code]
FDR service error code
Type: Display (read-only)
Possible values:
Default value: [0] (0)
[IDLE] (IdLE): “Idle”.
[INIT] (INIt): Initialization.
[CONF] (CONF): Configuration.
[RDY] (rdY): Ready.
[GET] (GEt): Download the current configuration.
[SET] (SEt): Save the current configuration.
[APP] (APP): Write the FDR server configuration to the drive.
[OPE] (OPE): Operational.
[UCFG] (UCFG): Not configured.
[0] (0): No fault.
[2] (2): The FDR configuration file is not compatible with the drive type (example: the drive is not the same rating as that defined in the FDR file).
[3] (3): Error reading the FDR configuration file on the server.
[4] (4): Error writing the FDR configuration file to the server.
[7] (7): Time-out for receipt of the FDR configuration file from the server.
[9] (9): Duplication of IP address.
[12] (12): The FDR configuration file is missing.
14 1755879 11/2009

8. Configuration

8. 1. List of functions to be configured

The table below gives the list of configuration functions and how they can be accessed:
Functions
Entering the IP addresses ppp
FDR (Faulty Device Replacement)
IO Scanning
Reserving control (IP master) pppp Communication monitoring pppp
Security of access to the standard Web server
Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section.
Configuration using the standard Web server is explained in the “Standard Web server” section.
For configuration using the PowerSuite software workshop, refer to the online help.
Note: The Ethernet card saves its configuration (IP address, mask, gateway, etc.) to the EEPROM each time the configuration is modified.
Note: For performance reasons, we do not recommend using the drive communication scanner. It is better to use the Ethernet IO Scanner.
Note: Configuration must be performed with the motor stopped.
Entering the device name pp Configuration (time delay, etc.) pppp Commands (save, etc.) pp p Enable IO Scanner pppp Configuring the IO Scanner variables pp
Changing the “username” p Changing the “HTTP password” p Changing the “Write password” pp
Graphic
display
terminal
Integrated
display
terminal
PowerSuite
software
workshop
Standard
Web
server
1755879 11/2009 15

8. Configuration

Static
addressing
DHCP
FDR
BOOTP
Initialization
Power-up
An address has been entered
[IP card] <> 0.0.0.0
No address has been entered
[IP card] = 0.0.0.0
Dynamic
addressing
[FDR validation] = [No]
[FDR validation] = [Yes]
[DEVICE NAME] blank
[DEVICE NAME] has been
entered

8. 2. Configuring IP addresses

b Assigning IP addresses
The drive needs 3 IP addresses:
• The drive IP address.
• The subnet mask.
• The gateway IP address.
These IP addresses can be entered directly:
• Using the integrated display terminal.
• Using the graphic display terminal.
• Or using the PowerSuite software workshop.
They can be provided by:
• A BOOTP server (correspondence between the MAC address and the IP addresses).
• Or a DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).
If an IP address other than 0.0.0.0 has been entered using the display terminal or the PowerSuite software workshop, assignment using a server is disabled.
The BOOTP service is enabled:
• When no IP address other than 0.0.0.0 has been entered.
• And the FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).
The DHCP service is enabled:
• When no IP address other than 0.0.0.0 has been entered.
• And the FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).
16 1755879 11/2009

8. Configuration

b Entering IP addresses in the terminal
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu, enter the following IP addresses:
- [IP card] (IPC1) (IPC2) (IPC3) (IPC4).
- [IP Mask] (IPM1) (IPM2) (IPM3) (IPM4).
- [IP Gate] (IPG1) (IPG2) (IPG3) (IPG4).
Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the IP addresses are not taken into account.
Note: Before entry begins, the IP address displayed is the active IP address. If this address is modified, the new IP address entered is displayed. This IP address will be effective the next time the drive is turned on.
b Configuring BOOTP
The BOOTP service is used to assign IP addresses from the MAC address. The MAC address consisting of 6 hexadecimal digits (00-80-F4-80-xx-yy) must be entered in the BOOTP server. The MAC address appears on the label attached to the Ethernet card.
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Do not enable the FDR service: [FDR validation] (FdrU) = [No] (nO).
b Configuring FDR
The FDR service (based on DHCP) is used to assign the IP addresses from the device name that must be entered in the drive and in the FDR server (DHCP).
In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:
• Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).
• Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES). For the FDR function, select the drive configuration as either:
•Local: [FDR Local Config.] (LCFG) = [Yes] (YES).
• Downloaded. In this case, it is essential to consult the “FDR Service” section.
Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu. This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr). Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken
into account.
Note: The FDR function cannot be fully configured using the integrated display terminal as it does not provide access to the device name.
1755879 11/2009 17

8. Configuration

8. 3. Reserving control

It is strongly recommended that control should be reserved for a single master device.
If control were not to be reserved for a master device (for example a PLC):
• Any other Modbus TCP Ethernet client could send unwanted commands.
• Other clients could use the 8 available TCP connections and prevent the master from having control.
WARNING
IP MASTER NOT SPECIFIED
Use the [IP MASTER] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
To configure this reservation, enter an IP address other than [0.0.0.0] (0) (0) (0) (0) in the [1.9 COMMUNICATION] (COM-) menu,
[ETHERNET] (EtH-) submenu, [IP Master] submenu.
• If control has been reserved: Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging. 2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections (8 maximum) and the control master therefore no longer being able to access the drive Modbus TCP server.
Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint). When control has been reserved and another device attempts to write the control word (CMd):
- via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.
- via Modbus TCP messaging: Control is denied.
• If control has not been reserved ([IP Master] = [0.0.0.0] (0) (0) (0) (0)), control can come from any IP address.

8. 4. Configuring IO Scanning

Refer to the “IO Scanning Service” section.
The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via parameter [IO Scan.activ.] (IOSA).
It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).
To configure IO Scanning, use the standard Web server or the PowerSuite software workshop.
18 1755879 11/2009

8. Configuration

8. 5. Configuring the control

Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters Manual. The following configurations are just some of the possibilities available.
b Control via Ethernet in I/O profile
The command and setpoint come from Ethernet. The command is in I/O profile.
Configure the following parameters:
Parameter Value Comment
Profile I/O profile The run command is simply obtained by bit 0 of the control word.
Setpoint 1 configuration Network card The setpoint comes from Ethernet.
Command 1 configuration Network card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [I/O profile] (IO)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Cmd channel 1] (Cd1) [Com. opt card] (nEt)
b Control via Ethernet or the terminals in I/O profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals. The command is in I/O profile.
Configure the following parameters:
Parameter Value Comment
Profile I/O profile The run command is simply obtained by bit 0 of the control word.
Setpoint 1 configuration Network card Setpoint 1 comes from Ethernet.
Setpoint 1B configuration Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
Command 1 configuration Network card Command 1 comes from Ethernet.
Command 2 configuration Terminals Command 2 comes from the terminals.
Command switching Input LI5 Input LI5 switches the command.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [I/O profile] (IO)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Cmd channel 1] (Cd1) [Com. card] (nEt)
[Cmd channel 2] (Cd2) [Terminals] (tEr)
[Cmd switching] (CCS) [LI5] (LI5)
[1.7 APPLICATION FUNCT.] (FUn-) [REFERENCE SWITCH.]
[Ref.1B channel] (Fr1b) [Ref. AI1] (AI1)
[Ref 1B switching] (rCb) [LI5] (LI5)
1B).
1755879 11/2009 19

8. Configuration

b Control via Ethernet in Drivecom profile
The command and setpoint come from Ethernet. The command is in Drivecom profile.
Configure the following parameters:
Parameter Value Comment
Profile Drivecom profile not
separate
Setpoint 1 configuration Network card The command comes from Ethernet.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Not separ.] (SIM) (factory setting)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
b Control via Ethernet or the terminals in Drivecom profile
Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals. The command is in Drivecom profile.
The run commands are in Drivecom profile, the command and the setpoint come from the same channel.
Configure the following parameters:
Parameter Value Comment
Profile Drivecom profile not separate The run commands are in Drivecom profile, the command and the
Setpoint 1 configuration Network card Setpoint 1 comes from Ethernet.
Setpoint 2 configuration Analog input 1 on the terminals Setpoint 2 comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
Note: Setpoint 2 is directly connected to the drive setpoint limit. If switching is performed, the functions that affect the setpoint (summing, PID, etc.) are disabled.
Configuration via the graphic display terminal or the integrated display terminal:
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Not separ.] (SIM)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Ref.2 chan] (Fr2) [Ref. AI1] (AI1)
[Ref. 2 switching] (rFC) [LI5] (LI5)
setpoint come from the same channel.
2) and the command.
20 1755879 11/2009

8. Configuration

b Command in Drivecom profile via Ethernet and setpoint switching at the terminals
The command comes from Ethernet. The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet and the terminals. The command is in Drivecom profile.
Configure the following parameters:
Parameter Value Comment
Profile Drivecom profile separate The run commands are in Drivecom profile, the command and the
Setpoint 1 configuration Network card Setpoint 1 comes from Ethernet.
Setpoint 1B configuration Analog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switching Input LI5 Input LI5 switches the setpoint (1
Command 1 configuration Network card Command 1 comes from Ethernet.
Command switching Channel 1 Channel 1 is the command channel.
Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
setpoint can come from different channels.
1B).
Menu Parameter Value
[1.6 - COMMAND] (CtL-) [Profile] (CHCF) [Separate] (SEP)
[Ref.1 channel] (Fr1) [Com. card] (nEt)
[Cmd channel 1] (Cd1) [Com. card] (nEt)
[Cmd switching] (CCS) [Ch1 active] (Cd1)
[1.7 APPLICATION FUNCT.] (FUn-) [REFERENCE SWITCH.]
[Ref.1B channel] (Fr1b) [Ref. AI1] (AI1)
[Ref 1B switching] (rCb) [LI5] (LI5)
1755879 11/2009 21

8. Configuration

8. 6. Configuring the fault management

b Communication monitoring
The Ethernet card can detect 2 types of fault:
- Network management faults (server missing, duplication of IP address, etc.).
- Communication faults (time out on the master traffic, etc.).
The associated information is:
Network management Communication
Associated drive fault Code:
Configuring the communication fault
Configuring the drive’s response
[External fault com.] (EPF2)
Parameter:
[FDR Error Mgt.] (FdrF)
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[ETHERNET] (EtH-)
Parameter:
[External fault mgt] (EPL)
Menu:
[1.8 FAULT MANAGEMENT] (FLt-)
Submenu:
[EXTERNAL FAULT] (EtF-)
Ethernet fault type
Code:
[Com. network] (CnF)
Parameter:
[time Out] (tOUt)
Menu:
[1.9 COMMUNICATION] (COM-)
Submenu:
[ETHERNET] (EtH-)
Parameter:
[COM. fault mgt] (CLL)
Menu:
[1.8 FAULT MANAGEMENT] (FLt-)
Submenu:
[COM. FAULT MANAGEMENT] (CLL-)
b Network management fault
The IP address duplication management fault cannot be configured.
If the FDR (Faulty Device Replacement) service has been configured, the FDR fault can be disabled via the [FDR Error Mgt.] (FdrF) parameter, which can be accessed via the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu.
In factory settings mode, a network management fault will trigger a resettable drive fault [External fault com.] (EPF2) and initiate a freewheel stop.
b Communication fault
It is strongly recommended that control should be reserved for a single master device. Monitoring begins when the first control word is received.
WARNING
IP MASTER NOT SPECIFIED
Use the [IP MASTER] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended equipment operation.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
• If control has been reserved: A communication fault is triggered if the Ethernet card does not receive a Modbus TCP request within a predefined period of time (time out). Any type of Modbus request from the master device [IP Master] is taken into account (write operation, read operation, etc.).
• If control has not been reserved: A communication fault is triggered if the Ethernet card does not receive a control word write request (CMd) within a predefined period of time (time out). Receipt of the command (CMd) is taken into account regardless of the sender’s IP address.
The “time out” can be set to between 0.5 and 60 s via the graphic display terminal or integrated display terminal in the
[1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via the [time Out] (tOUt) parameter. The default value is 2 s.
In factory settings mode, if Ethernet is involved in the command or setpoint, a communication fault will trigger a resettable drive fault
[Com. network] (CnF) and initiate a freewheel stop.
22 1755879 11/2009

8. Configuration

RDY NET +0.00Hz 0A
COM. FAULT MANAGEMENT
Network fault mgt : Freewheel
CANopen fault mgt : Freewheel
Modbus fault mgt : Freewheel
Code Quick
RDY NET +0.00Hz 0A
EXTERNAL FAULT
External fault mgt : Freewheel
Code Quick
For communication faults in the [COM. FAULT MANAGEMENT] (CLL-) submenu via parameter [COM. fault mgt] (CLL)
For network management faults in the [EXTERNAL FAULT] (EtF-) submenu via the [External fault mgt] (EPL) parameter
b Drive response
The drive response to an Ethernet fault can be configured via the graphic display terminal or the integrated display terminal, from the [1.8 FAULT MANAGEMENT] (FLt-) menu:
The values of parameters: [COM. fault mgt] (CLL) that will trigger a drive fault [Com. network] (CnF) and [External fault mgt] (EPL) that will trigger a drive fault [External fault com.] (EPF2) are:
[Freewheel] (YES): Freewheel stop (factory setting). [Ramp stop] (rMP): Stop on ramp. [Fast stop] (FSt): Fast stop. [DC injection] (dCI): DC injection stop.
The values of parameters [COM. fault mgt] (CLL) and [External fault management] (EPL) which will not trigger a drive fault are:
[Ignore] (nO): Fault ignored. [Per STT] (Stt): Stop according to configuration of [Stop type] (Stt). [fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command has not been removed. [Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run command has
not been removed.
The fallback speed can be configured in the
[1.8 - FAULT MANAGEMENT] (FLt-) menu via the [Fallback speed] (LLF) parameter.
1755879 11/2009 23

8. Configuration

8. 7. Configuring monitored parameters

It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu on the graphic display terminal.
The selection is made via the [6 - MONITORING CONFIG.] menu, [6.3 - COM. MAP CONFIG.] submenu.
Each parameter in the range [Address 1 select.] … [Address 4 select.] is used to select the parameter logic address. Select an address of zero to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCR): logic address 3204; signed decimal format.
• Parameter 2 = Motor torque (OTR): logic address 3205; signed decimal format.
• Parameter 3 = Last fault occurred (LFT): logic address 7121; hexadecimal format.
• Disabled parameter: address 0; default format: hexadecimal format.
One of the three display formats below can be assigned to each monitored word:
Format Range Terminal display
Hexadecimal 0000 … FFFF [Hex]
Signed decimal -32,767 … 32,767 [Signed]
Unsigned decimal 0 … 65,535 [Unsigned]
RDY NET +0.00Hz 0A
6.3 COM. MAP CONFIG.
Word 1 add. select. : 3204
Format word 1 : Signed
Word 2 add. select. : 3205
Format word 2 : Signed
Word 3 add. select. : 7121
Code Quick
Format word 33 : Hex
Word 4 add. select. : 0
Format word 4 : Hex
24 1755879 11/2009
Loading...
+ 54 hidden pages