While every precaution has been taken in the preparation of this document, Schneider
Electric SA assumes no liability for any omissions or errors it may contai n, nor for any
damages resulting from the application or use of the information herein.
The products described in this document may be changed or modified at any time,
either from a technical point of view or in the way they are operated. Their de scription
can in no way be considered contractual.
Before you begin_____________________________________________________________________________________________ 3
Documentation structure_______________________________________________________________________________________ 4
Introduction_________________________________________________________________________________________________ 5
Installing the card in the drive________________________________________________________________________________ 7
Coding the switches _______________________________________________________________________________________ 8
Wiring to the network ___________________________________________ _____________________________________________ 10
Wiring the DeviceNet connector_____________________________________________________________ ________________ 10
Configuring by the drive HMI __________________________________________________________________________________ 12
Configuring the control ____________________________________________________________________________________ 12
Configuring the communication scanner ______________________________________________________________________ 17
Configuring the fault management __________________________________ _________________________________________ 19
Configuring monitored parameters___________________________________________________________________________ 20
Configuring by a network tool__________________________________________________________________________________ 21
Going online with RSNetWorx ______________________________________________________________________________ 21
Creating an EDS file______________________________________________________________________________________ 21
Configuring the DeviceNet scanner __________________________________________________________________________ 22
Editing parameters of the drive______________________________________________________________________________ 27
Editing objects of the drive _________________________________________________________________________________ 32
Creating a PLC program______________________________________________________________________________________ 35
Using I/O messaging _____________________________________________________________________________________ 35
Using explicit messaging __________________________________________________________________________________ 35
Diagnostics by the drive HMI __________________________________________________________________________________ 36
Checking the node address and the data rate __________________________________________________________________ 36
Signalling LED __________________________________________________________________________________________ 37
Monitoring the control______________________________________________________________________________ _______ 38
Monitoring the communication scanner _______________________________________________________________________ 39
Troubleshooting the communication fault______________________________________________________________________ 40
Troubleshooting the card fault ______________________________________________________________________________ 41
DeviceNet objects___________________________________________________________________________________________ 42
Read and understand these instructions before performing any procedure with thi s drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand the Installation Ma nual before inst alling or op erating the Al tivar 71 drive. Installati on, adjustme nt,
repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning
protective grounding of all equipment.
• Many parts of this variable speed drive, including the printe d circuit cards, operate at the line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage prese nt.
• DO NOT short across terminals PA and PC or across the DC bus capacitors.
• Install and close all the covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive
- Disconnect all power.
- Place a “DO NOT TURN ON” label on the variable speed drive disconnect.
- Lock the disconnect in the open position.
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure given
in the Installation Manual to verif y that t he DC vol tage is l ess than 45 VDC. Th e drive LEDs are not accurate indic ators
of the absence of DC bus voltage.
Electric shock will result in death or serious injury.
CAUTION
DAMAGED EQUIPMENT
Do not install or operate any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
1755877 11/20103
2. Documentation structure
The following Altivar 61/71 technical documents are available on the Web site www.schneider-electric.com.
b Installation manual
This manual describes:
• How to assemble the drive
• How to connect the drive
b Programming manual
This manual describes:
• The functions
• The parameters
• How to use the drive HMI (integrated HMI and graphic HMI)
b Communication parameters manual
This manual describes:
• The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network
• The operating modes specific to communication (state chart)
• The interaction between communication and local control
• Configuration of the communication-specific parameters via the integrated HMI or the graphic HMI
• Diagnostics
• Software setup
• The communication services specific to the protocol
b Altivar 58/58F migration manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F.
It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.
41755877 11/2010
3. Introduction
3. 1. Presentation
The DeviceNet communication card (catalog number VW3 A3 309) is used to connect an Altivar 61/71 drive to a DeviceNet network.
The communication card has an open-style 5-pin connector for connection to the network.
Data exchanges give access to all Altivar 61/71 functions:
• Downloading configuration and adjustment parameters,
• Command,
• Monitoring,
• Diagnostics.
DeviceNet cables and connecting accessories must be ordered separately.
The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.
Note: All features regarding torque control are not available for ATV61 drives.
3. 2. Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets.
Example: [1.9 COMMUNICATION].
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (COM-).
Parameter names are displayed on the graphic display terminal in square brackets.
Example: [Fallback speed]
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
Example: (LFF).
Formats
Hexadecimal values are written as follows: 16#
Binary values are written as follows: 2#
Vocabulary
Depending on DeviceNet document and tools, equivalent wordings are used. The table below shows vocabulary used in the present
document and other corresponding definitions.
In this documentOtherComments
Node addressDeviceNet address, MAC ID
Data rateBaud rate
kbit/skBPS, kbps, k
SetpointReference, target
PathObject AddressClass, instance, attribute
The reader should avoid mixing two terms:
- DeviceNet scanner, which is the master device on the DeviceNet network.
- Communication scanner, which is a function inside the Altivar drive.
Abbreviations
Req. = Required
Opt. = Optional
1755877 11/20105
4. Quick start
This section is provided to help experienced users quickly start using the DeviceNet card. If you are unsure how to complete a step, refer
to the referenced chapter.
StepRefer to
1Review the safety precautions for the Altivar drive and DeviceNet card.Installation manual
2Verify that the Altivar drive is properly installed.Installation manual
4Install the DeviceNet card in the drive.
Verify that the Altivar drive is not powered.
Then, dismount the drive cover, mount the card in the drive. Finally mount the cover.
4Commission the DeviceNet card.
Verify that the Altivar drive is not powered.
Set a unique node address and the appropriate data rate using the switches on the card.
If desired, you can disable the switches and use parameter settings instead.
5Connect the drive to the DeviceNet network.
Verify that the Altivar drive is not powered.
Then, connect the card to the network using a DeviceNet cable.
6Apply power to the drive.
The card receives power from the drive.
Apply power to the drive.
The status indicator should be green.If it flashes red, there is a problem
(refer to 10. 2. Signalling LED
7Configure the drive for your application.
Select the functions and set the parameters as required by your application.
8Configure the drive behaviour and I/O interface for DeviceNet by the drive HMI.
Choose the suitable assemblies for your application (refer to 7. 1. Conf iguring the controlIf assemblies 100 or 101 are used, select the commands assigned to the control word (refer
the Programming manual).
).
Installation manual
5. Hardware setup
6. Wiring to the network
10. Diagnostics by the drive HMI
Programming manual
Programming manual
).
Communication parameters manual
7. Configuring by the drive HMI
Set the parameters for the following features as requiredby your application:
Control and setpoint channels (refer to 7. 1. Configuring the control
If assemblies 100 or 101 are used, input and output assignments
(refer to 7. 2. Configuring the communication scanner
Behaviour on communication fault (refer to 7. 3. Configuring the fault management
The parameters that you would like to monitor by the drive HMI for diagnostics
(refer to 7. 4. Configuring monitored parameters
9Apply power to the DeviceNet master and other devices on the network.
Verify that the master and network are instal led and fu nction ing in accordance wi th De viceNe t
standards, and then apply power to them.
10 Configure the scanner to communicate with the drive.
Use a network tool such as RSNetWorx for Devi ceNet to configure the scanne r on the network.
Make sure to:
Set up the scan list,
Map the drive data to the scan list,
Save your DeviceNet configuration to the scanner and a file.
11 Configure the drive by the network tool.
Set the parameters for the following features as required by your application:
If the data rate switches (7 and 8) are set to 1, Node address and data rate,
If you do not use default assemblies (100 or 101), select (and configure) assemblies.
12 Create a PLC program
Control the drive using I/O (assemblies).
Monitor or configure the drive using Explicit Messages.
),
).
),
),
DeviceNet master manuals
(DeviceNet cable system planning
and Installation manual ...)
8. 4. Configuring the DeviceNet
scanner
8. 5. Editing parameters of the drive
9. Creating a PLC program
DeviceNet master manuals
61755877 11/2010
5. Hardware setup
Open-style 5-pin connector
Configuration switches
(data rate and node address)
Bicolour LED
5. 1. Receipt
• Check that the card reference printed on the label is the same as that on the delivery note corresponding to the purchase order.
• Remove the option card from its packaging and check that it has not been damag ed in transit.
5. 2. Hardware description
5. 3. Installing the card in the drive
Refer to the Installation manual.
1755877 11/20107
5. Hardware setup
Data
rate
Node
address
hight = OFF = 0
low = ON = 1
5. 4. Coding the switches
b Switches description
b Overriding the switches
When switches 7 and 8 are set in position low (ON = 1), the d ata rate and the no de address of the dri ve must be set b y a network tool (refer
to 8. Configuring by a network tool). Default values are 125 kbit/s and node address 63.
b Coding the data rate
All devices connected to the DeviceNet network must communicate at the same data rate: 125, 250, or 500 kbit/s. The table below shows
the switch settings that configure the DeviceNet data rate on the drive.
Switch 7 Switch 8Data rate
00125 kbit/s
01250 kbit/s
10500 kbit/s
11The DeviceNet data rate and the node address of the drive must be set by a net work tool.
Any change to the switch setting takes effect at the next power-up.
b Coding the node address
All devices connected to the DeviceNet network must have a unique address, ranging from 0 to 63 (decimal).
If the data rate swithes (7 and 8) are both set to 1 (on), the switches 1 to 6 are i gnored an d the nod e address must be set by a network tool
(default value = 63).
The table below lists the switch setting for each valid node address.
Any change to the switch setting takes effect at the next power-up.
Data rate = 250 kbit/s (switches 7 and 8 = 2#01)
Node address = 25 (switches 1 to 6 = 2#01 1001)
Data rate = 500 kbit/s (switches 7 and 8 = 2#10)
Node address = 52 (switches 1 to 6 = 2#11 0100)
b Examples
1755877 11/20109
6. Wiring to the network
1
2
3
4
5
6. 1. Cable routing practices
When wiring Altivar 61/71 drives to a DeviceNet network, follow all wiring practices required by national and local electrical codes. Also
observe the following guidelines:
• Avoid areas of high temperature, moisture, vibration, or other mechanical stress.
• Secure the cable where necessary to prevent its weight and the weight of other cables from pulling or twisting the cable.
• Use cable ducts, raceways, or other structures to protect th e cable. Use these structures for signal wiring paths. They must not contain
power wiring.
• Avoid sources of electrical interference th at can induce noise into the cabl e. Use the maximum practicable separat ion from such sources.
When planning cable routing within a building, follow these guidelines:
• Maintain a minimum separation of 1 m from the following equipment :
- air conditioners and large blowers,
- elevators and escalators,
- radios and televisions,
- intercom and security systems,
- fluorescent, incandescent, and neon lighting fixtures.
• Maintain a minimum separation of 3 m from the following equipment :
- line and motor power wiring,
- transformers,
- generators,
- alternators.
When wiring in electrical equipment rooms or large electrical equipment line-ups, observe the following guidelines for cable segregation
and separation of circuits:
• Use metallic conduit for drive wiring. Do not run control network and power wiring in the same conduit.
• Separate non-metallic conduits or cable trays used to carry power wiring from metallic conduit carrying low-level control network wiring
by at least 300 mm.
• Separate metallic conduits carrying power wiring or low-level control network wiring by at least 80 mm.
• Cross the metallic conduits and non-metallic conduits at right angles whenever power and control network wiring cross.
• Attenuate conducted emissions from the dri ve to the line in some installations to p revent interf erence with telecommunicat ion, radio, and
sensitive electronic equipment. Such inst ances may require attenua ting filters. Consu lt the Altivar catalog for selection and appli cation of
these filters.
6. 2. Wiring the DeviceNet connector
The figures and the table below show the pin-outs of the card connectors. The removable DeviceNet female connector attaches to the
network cable.
1234
DeviceNet card male connectorRemovable DeviceNet female connector
Line termination: If the drive is the first or the last device on the DeviceNet net wo rk, a li ne termi nat or (1 21
removable DeviceNet female connector, between pins 2 and 4 (CAN_L and CAN_H).
101755877 11/2010
Ω resistor) must be wired on the
6. Wiring to the network
The ODVA standards (Release 2.0) specify 7 types of cables for use in DeviceNet networks:
• Thick cable
• Thin cable
• Flat cable
• Cable I
• Cable II
• Cable IV
• Cable V
The table below lists main specifications of cables. For more information, refer to the ODVA specifications.
Type of cableData conductor pair sizePower conductor pair sizeData impedance
The maximum permissible length of the network cable depends an the data rate and the type of cable.
Type of cableData rate
125 kbit/s250 kbit/s500 kbit/s
Thick cable500 m (1640 ft)250 m (820 ft)100 m (328 ft)
Thin cable100 m (328 ft)100 m (328 ft)100 m (328 ft)
Flat cable420 m (1378 ft)200 m (656 ft)75 m (246 ft)
Cable I100 m (328 ft)100 m (328 ft)100 m (328 ft)
Cable II500 m (1640 ft)250 m (820 ft)100 m (328 ft)
Cable IV--Cable V420 m (1378 ft)200 m (656 ft)75 m (246 ft)
For maximum length of the drops refer to table, whatever type of cable:
Data rateCu m ulat ive dr opMaximum drop
125 kbit/s156 m (516 ft)6 m (20 ft)
250 kbit/s78 m (256 ft)6 m (20 ft)
500 kbit/s39 m (128 ft)6 m (20 ft)
1755877 11/201011
7. Configuring by the drive HMI
7. 1. Configuring the control
b Principle
By the configuration of the control, it is possible to decide from what channel the drive receives its commands and setpoint, either
permanently or depending on a switching command.
Numerous configurations are possible. For more information, refer to the Programming manual and Communication parameters manual.
The following configurations are some of the possibilities available.
M Control with communication scanner
If the default assemblies (100, 101) are selected, all possibilities of Altivar 61/71 drive are available.
It is possible to use all profiles and modes of the drive:
- I/O profile,
- Drivecom profiles with separate or non separate mode.
By the configuration of the communication scanner, it is possible to assign any relevant parameter of the drive to the 4 input and 4 output
variables of the assemblies.
See the input / output interface with the PLC can be fully customised depending on the application.
The use of the communication scanner is als the best way to interface with a "Controller Inside" card.
M Control according to ODVA AC drive profile
The ODVA AC drive profile is activated when one of the following assembl ies is selected:
• 20: Basic speed control output
• 21: Extended speed control output
• 22: Speed and torque control output
• 23: Extended speed and torque control output
• 70: Basic speed control input
• 71: Extended speed control input
• 72: Speed and torque control input
• 73: Extended speed and torque control input
The advantage of using the ODVA drive profile standard is the interchangeability with other brands.
The drive must be configured in the Drivecom profile with separate mode.
The DeviceNet card translates the commands, behaviour and monitoring information from of ODVA profi le (on the network) to the Drivecom
profile (in the drive).
M Control according to Allen-Bradley® drive profi le
The Allen-Bradley® Drive profile is activated when one of the following assemblies is selected:
• 103: Allen-Bradley® drive output
• 104: Allen-Bradley® drive input
• 105: Allen-Bradley® drive input with parameters
If you need to replace Allen-Bradley® drives, in an existing application, this profile is a good way to minimise the modifications.
The drive must be configured in the Drivecom profile with separate mode.
The DeviceNet card translates the commands, behaviour and monitoring information from of Allen-Bradley® drive profile (on the network)
to the Drivecom profile (in the drive).
Note 1: If the DeviceNet communication is active while changing a configuration parameter, it will generate an EPF2 fault.
Note 2: When changing (CHCF) [Profile], assemblies are set to their default values.
121755877 11/2010
7. Configuring by the drive HMI
b Available configurations
M If you use the communication scanner:
• 100: Communication scanner output
• 101: Communication scanner input there is no limitation in the configuration of the control.
The examples below are only possible if you use the communication scanner.
M If you use the ODVA AC drive profile or Allen-Bradley® Drive profile, that is, the assemblies:
• 20: Basic speed control output
• 21: Extended speed control output
• 22: Speed and torque control output
• 23: Extended speed and torque control output
• 70: Basic speed control input
• 71: Extended speed control input
• 72: Speed and torque control input
• 73: Extended speed and torque control input
• 103: Allen-Bradley® drive output
• 104: Allen-Bradley® drive input
• 105: Allen-Bradley® drive input with parameters only some configurations are permitted, they are listed in the table below.
ParameterPermitted valueComment
ProfileDrivecom profile separateThe run commands are in Drivecom profile,
Setpoint 1 configurationNetwork cardSetpoint 1 comes from DeviceNet.
Setpoint 1B configurationTerminalsSetpoint 2 comes from terminals (AI1 or AI2).
Setpoint 2 configurationTerminalsSetpoint 2 comes from terminals (AI1 or AI2).
Command 1 configurationNetwork cardCommand 1 comes from DeviceNet.
Command 2 configurationTerminalsCommand 2 comes from terminals.
Setpoint switchingNetwork card bit 13Bit 13 of the control word switches the setpoint (1 <-> 1B or 1 <-> 2).
Command switchingNetwork card bit 12Bit 12 of the control word switches the command.
the command and the reference can come from different channels.
Configuration via the graphic display terminal or the integrated display terminal:
Case 1: Setpoint 1B is connected to the functions (Summing, PID, etc) which remain active even after switching.
Case 2: Setpoint 2 is directly connected to the drive reference limit. If switching is performed, the functions that affect the reference
(summing, PID, etc.) are inhibited.
Note: It is not possible to configure the display terminal as a channel.
To switch to the display terminal, use the function force local and assign the parameter [Forced local Ref.] to [HMI](LCC).
Note: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.
The command and the setpoint come from DeviceNet.
Control is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the command word.
Setpoint 1 configurationNetwork card The setpoint comes from DeviceNet.
Command 1 configurationNetwork card The command comes from DeviceNet.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via DeviceNet or via the terminals in I/O profile
Note: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.
The command and the setpoint both come from DeviceNet or the terminals. Input LI5 at the terminals is used to switch between
DeviceNet and the terminals.
Control is in I/O profile.
Configure the following parameters:
ParameterValueComment
ProfileI/O profileThe run command is simply obtained by bit 0 of the control word.
Setpoint 1 configurationNetwork cardSetpoint 1 comes from DeviceNet.
Setpoint 1B configurationAnalog input 1 on the terminals Setpoint 1B comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from DeviceNet.
Command 2 configurationTerminalsCommand 2 comes from the terminals.
Command switchingInput LI5Input LI5 switches the command.
Note: Setpoint 1B is connected to the functions (Summing, PID, etc) which remain active even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
b Control via DeviceNet or the terminals in Drivecom profile
Note: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.
The command and the setpoint both come from DeviceNet or the terminals. Input LI5 at the terminals is used to switch between
DeviceNet and the terminals.
Configure the following parameters:
ParameterValueComment
ProfileSeparate Drivecom profileThe run commands are in Drivecom profile, the command and the
Setpoint 1 configurationNetwork cardSetpoint 1 comes from DeviceNet.
Setpoint 2 configurationAnalog input 1 on the terminalsSetpoint 2 comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from DeviceNet.
Command 2 configurationTerminalsCommand 2 comes from the terminals.
Command switchingInput LI5Input LI5 switches the command.
Note: Setpoint 2 is directly connected to the drive ref erence limit. If switching is performed, the functions that af fect the reference (summing,
PID, etc) are inhibited.
Configuration via the graphic display terminal or the integrated display terminal:
b Control in Drivecom profile via DeviceNet and setpoint switching at the terminals
Note: This configuration can only be used if the communication scanner assemblies (100 and 101) are selected.
The command comes from DeviceNet.
The setpoint comes either from DeviceNet or from the terminals. I nput LI5 at the terminals is used to switch the setpoint between DeviceNet
and the terminals.
Control is in Drivecom profile.
Configure the following parameters:
ParameterValueComment
ProfileSeparate Drivecom profileThe run commands are in Drivecom profile, the command and the
Setpoint 1 configurationNetwork cardSetpoint 1 comes from DeviceNet.
Setpoint 1B configurationAnalog input 1 on the terminalsSetpoint 1B comes from input AI1 on the terminals.
Setpoint switchingInput LI5Input LI5 switches the setpoint (1
Command 1 configurationNetwork cardCommand 1 comes from DeviceNet.
Command switchingChannel 1Channel 1 is the command channel.
Note: Setpoint 1B is connected to the functions (summing, PID, etc) that remain active, even after switching.
setpoint can come from different channels.
↔1B).
Configuration via the graphic display terminal or the integrated display terminal:
You need to read this chapter only if you use the assemblies 100 or 101 that use the drive communication scanner.
The variables exchanged by the output assembly 100 and input assembly 101 are selected by configuring the communication scanner.
The 4 output variables are assigned by means of the 4 parameters [Scan. Outp address](nCAp). They are configured using the graphic
display terminal via the [1.9 - COMMUNICATION](COM-) menu, [COM. SCANNER OUTPUT](OCS-) submenu.
The 4 input variables of the assembly 101 are assigned by means of the 4 parameters [Scan. Inp address](nMAp). They are configured
using the graphic display terminal via the [1.9 - COMMUNICATION](COM-) menu, [COM. SCANNER INPUT](ICS-) submenu.
Enter the logic address of the parameter (see the Communication parameters manual).
If a parameter [Scan. Outp address](nCAp) or [S can. Inp address](nMAp) is equal to zero, the corresponding period variable is not
used by the drive.
These 8 assignment parameters are described in the tables below:
[Scan. Out1 address](nCA1)Bytes 0 and 1Control word (CMd)
[Scan. Out2 address](nCA2)Bytes 2 and 3Speed reference (LFrd)
[Scan. Out3 address] (nCA3)Bytes 4 and 5Not used
[Scan. Out4 address] (nCA4)Bytes 6 and 7Not used
[Scan. Out5 address](nCA5) to [Scan. Out8 address](nCA8) are not useful for the DeviceNet card.
[Scan. In1 address](nMA1)Bytes 0 and 1Status word (EtA)
[Scan. In2 address](nMA2)Bytes 2 and 3Output speed (rFrd)
[Scan. In3 address](nMA3)Bytes 4 and 5Not used
[Scan. In4 address](nMA4)Bytes 6 and 7Not used
[Scan. In5 address](nCA5) to [Scan. In8 address](nCA8) are not useful for the DeviceNet card.
Example of configuration via the graphic display terminal:
All modifications to parameters [Scan. Outp address](nCAp) or [Scan. Inp address](nMAp) must be made with the motor stopp ed. The
master PLC program should be updated to take account of this modification.
1755877 11/201017
7. Configuring by the drive HMI
Example of configuration of communication scanner assemblies 100 and 101
The following output and input variables are to be configured:
Bytes 0 and 1Control word (CMd)Bytes 0 and 1Status word (EtA)
Bytes 2 and 3Speed reference (LFrd)Bytes 2 and 3Output speed (rFrd)
Bytes 4 and 5Acceleration (ACC)Bytes 4 and 5Speed reference before ramp (FrHd)
Bytes 6 and 7Deceleration (dEC)Bytes 6 and 7Logic input map (IL1r)
The communication fault occurs when there is a time out on control traffi c: COS, cycl ic, polli ng or explic it messaging. In fact ory setting, the
communication fault triggers a [Com. network](CnF) fault.
The configuration fault occurs when:
- ODVA AC drive profile or Allen-Bradley® Drive profile are used (assemblies 20, 21, 22, 23, 70, 71, 72, 73, 103, 104, 105),
- the configuration of the drive control parameters is not correct (refer to 7. 1. Configuring the control),
- a DeviceNet connection is active between the drive and the PLC.
In factory setting, the communication fault triggers a [External fault com.](EPF2) fault.
The response of the drive in the event of a DeviceNet communicati on fault can also be configured.
Configuration can be performed using the graphic display terminal or int egrated
display terminal in the [1.8 - FAULT MANAGEMENT](FLt-) menu:
- For the communication fault, in the [COM. FAULT MANAGEMENT](CLL-)
submenu, via the [Network fault mgt](CLL) parameter.
- For the configuration fault, in the [EXTERNAL FAULT](EtF-) submenu, via
the [External fault ass.](EPL) parameter.
The values of the [Network fault mgt](CLL) or [External fault ass.](EPL) parameters, which t rigger a drive fault [Com. network] (CnF),
are:
ValueMeaning
[Freewheel](YES)Freewheel stop (factory setting)
[Ramp stop](rMP)Stop on ramp
[Fast stop](FSt)Fast stop
[DC injection] (dCI )DC injection sto p
The values of the [Network fault mgt](CLL) or [External fault ass.](EPL) parameters, which do not trigger a drive fault, are:
ValueMeaning
[Ignore](nO)Fault ignored
[Per STT](Stt)Stop according to configuration of [Type of stop] (Stt).
[fallback spd](LFF)Switch to fallback speed, maintained as long as the fault is present and the run command is not dis abled.
[Spd maint.]
(rLS)
The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run
command has not been removed.
The fallback speed can be configured in t he [1.8 – FAULT MANAGEMENT](FLt-) menu using the [Fallbac k speed] (LFF) parameter.
1755877 11/201019
7. Configuring by the drive HMI
7. 4. Configuring monitored parameters
It is possible to select up to 4 parameters to display their values in the [1.2 - MONITORING] menu ([COMMUNICATION MAP] submenu)
on the graphic display terminal.
The selection is made via the [6 – MONITOR CONFIG.] menu ([6.3 - CONFIG. COMM. MAP] submenu).
Each parameter [Address 1 select] ... [Address 4 selec t] can be used to
choose the logic address of the parameter. Select an address of zero
to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCr): Logic address 3204;
signed decimal format
• Parameter 2 = Motor torque (Otr): logic address 3205; signed
decimal format
• Parameter 3 = Last fault occurred (LFt): logic address 7121;
hexadecimal format
• Disabled parameter: Address W0; default format: hexadecimal
format
RDYNET+0.00Hz0A
6.3 CONFIG. COMM. MAP.
Address 1 select: 3204
FORMAT 1: Signed
Address 2 select: 3205
FORMAT 2: Signed
Address 3 select: 7121
CodeQuick
FORMAT 3: Hex
Address 4 select: 0
FORMAT 4: Hex
One of the three display formats below can be assigned to each monitored word:
RSNetWorx for DeviceNet is a Rockwell® software application that can be used to set up DeviceNet networks and configure connected
devices.
RSNetWorx for DeviceNet (version 2.22.18) is used for examples in this manual. Different versions of software may differ in appearance
and procedures.
Proper EDS file (A71vp_E.eds) and icone (Altivar_71.ico) for Altivar drives are distrib ute d on the CD-ROM del ive red wi th each dri ve. Th ey
are also available on the Internet : www.schneider-electric.com
8. 2. Going online with RSNetWorx
You can view the devices on a DeviceNet network by going online. A device may appear as an unrecognised device if RSNetWorx does
not have an EDS file for it.
1 After setting up a driver in RSLinx, start RSNetWorx for DeviceNet.
2 Select Network > Online. If the Browse for Network dialog box appears, RSLi nx has multiple drivers configured.
Select your DeviceNet network, and click OK. A prompt appears.
3 Click OK to go online. The devic es on the network appear in the Configur ation View. You can select Graph, Spreadshee t, or Master/Slave
views. The figure below shows an example network in a Graph view.
8. 3. Creating an EDS file
If the adapter and drive appear as an unrecognized device, create an EDS file for it.
1 Right-click the "Unrecognized Device" icon, and select Register Device in the menu. The EDS Wizard appears.
2 Click Next to display the next step.
3 Select Upload EDS, and then click Next.
4 Type a description (if desired), and then click Next.
5 Under Polled, select Enabled, type 4 in the Input Size and Output Size boxes, and then click Next. RSNetWorx will upload the EDS file
from the deviceNet card.
6 Click Next to display the icon options for the node. We recommend that you use the icon for your product. You can chan ge icons by
clicking Change icon.
Proper icon (Altivar_71.ico) is distributed on the CD-ROM delivered with each dri ve. They are also available on the Internet :
www.schneider-electric.com
7 Click Next to view a summary, and then click Next again to accept it.
8 Click Finish to finish the EDS creation. A new icon represents the Altivar drive in the Configuration View.
1755877 11/201021
8. Configuring by a network tool
8. 4. Configuring the DeviceNet scanner
b Setting up the scan list
For the scanner to communicate with a drive, the scanner must be configured and the drive's node number must be added to its scan list.
1 Go online with RSNetWorx for DeviceNet. The devices on the network are displayed in the configuration view.
2 Right-click the DeviceNet scanner (node 00) and sel ect Properties. The Scanner Module dialog box appears.
Important: If your scanner is an unrecognized device, you must create an EDS file for it and then configure the scanner. Configure the
scanner using the General and Module tabs. If you need more information, click Help or refer to your scanner documentation.
3 Click the Scanlist tab. A message box prompts you to upload.
4 Click Upload. Data is uploaded from the scanner, and then the Scanlist page appears.
5 Select the Automap on Add box (a check mark will appear).
6 Under Available Devices, select the drive, and then click > (Right Arrow) to add it to the scanlist.
221755877 11/2010
8. Configuring by a network tool
7 Under Scanlist, select the drive, and then click Edit I/O Parameters.
The Edit I/O Parameters dialog box appears.
8 Select the type(s) of data exchange (Polled, Change of State, and /or Cyclic). In our example, we selected Polled.
The type supported by the DeviceNet card for Altivar are:
9 Type the number of bytes tha t are required for your I/O in the Rx Size and Tx Size bo xes. The size will depend on t he assembly you have
selected for your application:
Assembly attributeAssembly nameRx size
70ODVA Basic speed control input4 bytes
71ODVA Extended speed control input4 bytes
72ODVA Speed and torque control input6 bytes
73ODVA Extended speed and torque control input6 bytes
101Communication scanner input8 bytes
104Allen-Bradley® drive input4 bytes
105Allen-Bradley® drive input with parameters8 bytes
Assembly attributeAssembly nameTx size
20ODVA Basic speed control output4 bytes
21ODVA Extended speed control output4 bytes
22ODVA Speed and torque control output6 bytes
23ODVA Extended speed and torque control output6 bytes
100Communication scanner output8 bytes
103Allen-Bradley® drive output4 bytes
10 Set the scan rate. (Click Help for more information.)
Data ExchangeRate to set
PolledPolled Rate
Change of StateHeartbeat Rate
CyclicSend Rate
11 Click OK.
If you changed any settings, a Scanner Applet asks if it is OK to unmap the I/O. Click Yes to continue. The Edit I/O Parameters dialog
box closes and then the Scanner Module dialog box reappears.
You will map the I/O in the next section in this chapter.
1755877 11/201023
8. Configuring by a network tool
b Mapping the drive data in the scanner
Data from I/O messages must be mapped in the scanner. This mapping determines where a PLC program can find data that is passed over
the network. You must map both the Input I/O and the Out put I/O.
M Mapping the inputs
1 In the Scanner Module dialog bo x, click the Input tab. (If necessary , right-click t he scanner in the conf iguration view to di splay this dial og
box.)
The figure below is an example for assembly 73 (ODVA Extended speed and torque control input).
If you selected the Automap on Add box in the Scanlist page, RSNetWorx has already mapped the I/O. If it is not mapped, click Automap
to map it. If you need to change the mapping, click Advanced and change the settings. Click Help for assistance.
2 In the Memory box, select a location in scanner memory.
ScannerMemory Locations
1747-SDNDiscrete or M-File
1756-DNBAssembly Data
1771-SDNBlock Xfer 62 - 57
In our example, we are using a 1747-SDN and selected Discrete.
3 In the Start Word box, select the word in memory at which the data should start.
In our example, we selected 3. The drive parameters will be mapped:
InputParameter of the drive
I:1.3Status word
I:1.4Actual speed
I:1.5Actual torque
241755877 11/2010
8. Configuring by a network tool
M Mapping the outputs
1 In the Scanner Module dialog box, click the Output tab. To display this di alog box, right-click the scanner in the configuration view.
The figure below is an example for assembly 23 (ODVA Extended speed and torque control output).
If you selected the Automap on Add box in the Scanlist page, RSNetWorx has already mapped the I/O. If it is not mapped, click Automap
to map it. If you need to change the mapping, click Advanced and change the settings. Click Help for assistance.
2 In the Memory box, select a location in scanner memory.
ScannerMemory Locations
1747-SDNDiscrete or M-File
1756-DNBAssembly Data
1771-SDNBlock Xfer 62 - 57
In our example, we are using a 1747-SDN and selected Discrete.
3 In the Start Word box, select the word in memory at which the data should start.
In our example, we selected 3. The drive parameters will be mapped:
InputParameter of the drive
O:1.3Control word
O:1.4Speed setpoint
O:1.5Torque setpoint
1755877 11/201025
8. Configuring by a network tool
b Saving the Configuration
After configuring a scanner, you must download the configuration to the scanner. You should also save it to a file on your computer.
1 In the Scanner Module dialog box, click Apply to save the configuration to the scan ner. A Scanner Configuration Applet appears and
asks if it is OK to download the changes.
2 Click Yes to download the changes. The changes are downloaded and then the Scanner Module dialog box reappears.
3 Click OK to close the Scanner Module dialog box.
4 Select File > Save. If this is the first time that you saved the project, the Save As dialog box appears. Navigate to a folder, type a file
name, and click Save to save the configuration to a file.
b Auto Device Replacement
Do not activate ADR (Auto Device Replacement).
Parameters download of the Altivar drive needs a specific process:
1 Upload the drive parameters:
- Read drive parameters using explicit messages.
- Store the parameters in a data table of the PLC.
2 Dowload the drive parameters:
- Disable consistency check (Set bit 15 of the parameter Extended control word (CMI)).
- Write parameters from the data table of the PLC to the drive using explicit messages.
- Enable consistency check (Reset bit 15 of the parameter parameter Extended control word (CMI)).
3 Read and compare the parameters between the drive and the save table.
Extended control word (CMI)
It is necessary to disable the consistency check before writing parameters.
If the consistency check is not disabled, the drive ve rifies, at each Set acce ss, if the parameter matches with the o thers. If it does not match,
the drive modifies or rejects the parameter.
261755877 11/2010
8. Configuring by a network tool
8. 5. Editing parameters of the drive
b Using the Device Parameters editor
Parameters in the drive and in the DeviceNet card can be e di ted with Devi ce Parame ters edi to r of RSNetWorx, i f the y are descri bed in the
eds file.
1 After creating an EDS file, right-click on the icon for the Altivar drive and select Properties. The Altivar drive dialog box appears.
2 Click the Device Parameters tab. If an EDS Editor message appears, click Upload to load the parameter values in the drive to the
computer.
Parameters are displayed in numerical order under Parameter. You can either scroll through the list or sel ect a specific group of
parameters in the Groups box. The available groups and the numbers of parameters will vary based on the type of drive.
3 In the Current Value column, double-click a value to edit it.
4 Click Apply to save changes to the drive.
1755877 11/201027
8. Configuring by a network tool
b Limitations of the Device Parameters editor
If you use the feature Download To Device / All, you may encounter unexpected events:
• If you first Upload From Device / All and then Download To Device / All, the actual configura tion of the dr ive may be different from the
one that you initially saved.
• A fault [External fault com.](EPF2) may occur.
We do not recommended to used the feature Download To Device / All.
You assume full responsibility for all cons equences related to the use of this feature.
M Additional information for Download To Device / All
The Download To Device / All function use s s equential explicit messaging to the parameters described in the eds file.
Each time it receives Set access to a parameter, the drive checks th e consistency of thi s parameter with the others (values already existing
in the drive).
If there is an inconsistency, the drive rejects the parameter or modifies it according to internal rules (parameter management).
Example:
A rule of the parameter management is:
[Low speed](LSP) must be lower or equal to [High speed](HSP).
Initially [Low speed](LSP) = 20Hz and [High speed](HSP) = 30Hz.
The Download To Device / All function writes sequentially : [Low speed](LSP) = 35Hz and then [High speed](HSP) = 50Hz.
The result in the drive will be [Low speed](LSP) = 30Hz and [High speed](HSP) = 50Hz and so the configuration served will be di fferent
from the one saved in an Upload From Device / All.
M Additional information for fault [External fault com.] (EPF2)
When the drive uses assemblies 20, 21, 22, 23, 70, 71, 72, 73, 1 03, 104 or 105, there are cond itions on the values of the parameters (refer
to 7.1 Configuring the control):
• [Profile](CHCF
• [Ref.1 channel](Fr1),
• [Ref.1B channel](Fr1b),
• [Ref.2 channel](Fr2),
• [Cmd channel 1](Cd1),
• [Cmd channel 2](Cd2),
• [Ref 1B switching](rCb),
• [Ref. 2 switching](rFC),
• [Cmd switching](CCS).
If during the Download To Device / All operation, the conditions are not fulfilled the fault [External fault com.] (EPF2) occurs.
It may occur also if the problem appears only once during operation, even though at the end the configuration is valid.
If you use them, you do not need reading this section.
If you use another assembly, you must configure it in the drive.
M Selecting the input assembly
1 In the Groups box, select DeviceNet Interface.
2 For the parameter PollProdPath, in the Current Value column, select the input asse mbly that fits to your application.
3 For the parameter PollConsPath, in the Current Value column, select the input assembly that fits to your application.
Assembly attributeAssembly name
70ODVA Basic speed control input
71ODVA Extended speed control input
72ODVA Speed and torque control input
73ODVA Extended speed and torque control input
101Communication scanner input
104Allen-Bradley® drive input
105Allen-Bradley® drive input with parameters
1755877 11/201029
8. Configuring by a network tool
M Selecting the output assembly
1 In the Groups box, select DeviceNet Interface.
2 For the parameter CCProdPath, in the Current Value column, select the assembly that fits to your application.
Assembly attributeAssembly nameTx size
20ODVA Basic speed control output4 bytes
21ODVA Extended speed control output4 bytes
22ODVA Speed and torque control output6 bytes
23ODVA Extended speed and torque control output6 bytes
100Communication scanner output8 bytes
103Allen-Bradley® drive output4 bytes
M Selecting additional parameters of assembly 105
If you use assembly 105, apply the procedure below, otherwise skip this section and read below: Saving changes in the drive.
1 Select the additional parameters that you need for your application.
Example : [Motor current](LCr) and [Motor torque](Otr).
2 Refer to the Communication para meters manual. Write down the class Id a nd the attribute id of the paramet ers. Convert the hexadecimal
values to decimal values.
Example :
Parameter namePathClass IdAttribute id
HexadécimalDécimalHexadécimalDécimal
[Motor current]
(LCr)
[Motor torque]
(Otr)
3 In the Groups box, select DeviceNet Interface.
4 For the parameter FirstParamClass, in the Current Value column, type the class value in decimal.
Example : 113.
5 For the parameter FirstParamAttr, in the Current Value column, type the attribute value in decimal.
Example : 5.
6 If you need a second additiona l para meter, for the parameter SecondParamCla ss, in the Current Value column, type the class value in
decimal.
Example : 113.
If you do not need skip to step Saving changes in the drive.
7 For the parameter SecondParamAttr, in the Current Value column, type the attribute value in decimal.
Example : 6.
M Saving changes in the drive
1 Click Applyto save changes to the device.
2 Cycle power off / on the drive.
71/01/0516#7111316#055
71/01/0616#7111316#066
301755877 11/2010
8. Configuring by a network tool
b Configuring node address and data rate
If the data rate switches (7 and 8) are set to 1, it is possible to configure node address and data rate by the Device Parameters editor of
RSNetWorx.
M Configuring the node address
1 Connect the drive on the network. The default value of the node address is 63. So you must no connect simultaneously several drives
with software configured node address. You must connect and set the address of drives one by one.
2 Go on line with the drive and launch the Device Parameters editor of RSNetWorx.
3 In the Groups box, select DeviceNet.
4 For the parameter MAC ID, in the Current Value column, type the address value. The new value is immediately applie d to the drive and
stored in EEPROM (so used at each power-up of the drive).
M Configuring the data rate
1 Connect the drive on the network. The default value of the data rate is 125kbit/s. If it does not match the data rate of the DeviceNet
network, you must temporarily set the data rate of the network tool 125kbit/s in order to access the drive and modify its data rate.
2 Go on line with the drive and launch the Device Parameters editor of RSNetWorx.
3 In the Groups box, select DeviceNet.
4 For the parameter Baud rat e, i n the Current Value col umn, select t he data rate val ue. The new val ue will be appl ied to t he drive at next
power-up. It is stored in EEPROM (so used at each power-up of the drive).
1755877 11/201031
8. Configuring by a network tool
8. 6. Editing objects of the drive
b Using the Class Instance Editor
DeviceNet objects of the drive and the DeviceNet card can be edited with the Class Instance Editor of RSNetWorx.
This editor provides direct access to the device using native DeviceNet object addressing.
Using this editor requires a detailed und erstanding of t he capabi liti es and limit ations of the devic e bein g config ured, a s well as t he possible
impacts that these changes may have on the operation of your system. You assume full responsibility for all consequences related to the
use of this editor.
1 Go online with RSNetWorx for DeviceNet. The devices on the network are displayed in the configuration view.
321755877 11/2010
8. Configuring by a network tool
2 Right-click on the icon for the Altivar drive and select Class Instance Editor. The Altivar drive dialog box appears.
3 In the Object Address field, type the path of the parameter in the boxes Class, Instance, Attribute.
4 In the Service Code field, select the action in the Description box.
5 In the boxes Transmit data size, Data sent to the device, Va lues i n decimal t ype the desc ript ion of t he data tha t y ou want to sen d t o
the drive.
6 Click Execute to exchange the dat a with the drive. Click Help for assistance.
1755877 11/201033
8. Configuring by a network tool
b Configuring NetRef parameter
Configure NetRef by the Class Instance Editor for testing.
BaseClassInstanceAttribute
Hexadecimal16# 2A16#0116#04
Decimal4214
It is possible to provide the speed setpoint with output assembly 20, if the parameter NetRef is set to.
The default value is 0, output assembly 20 controls the drive but the speed target is given by the terminals (AI1).
The default setting applies each time the connection is cl osed (Power on of the drive, DeviceNet disconnected from the card).
If assembly 20 must be used, the PLC program must set this parameter by explicit messaging.
It may be easier to use another assembly (21).
b Configuring node address and data rate
If the data rate switches (7 and 8) are set to 1, configure node address and data rate by the Class Instance Editor.
Node address
BaseClassInstanceAttribute
Hexadecimal16# 0316#0116#01
Decimal311
Data rate
BaseClassInstanceAttribute
Hexadecimal16# 0316#0116#02
Decimal312
341755877 11/2010
9. Creating a PLC program
9. 1. Using I/O messaging
I/O messaging is used to transfer real time data between the PLC and the drive :
• Commands,
•Setpoints,
• Settings,
•States,
• Measurements,
•...
Depending on your application needs and other constraints, select the right assemblies:
• communication scanner assemblies and configure the parameters of the assembly (refer to 8. 4. Configuring the DeviceNet scanner),
• or ODVA AC drive profile,
• or Allen-Bradley® Drive profile (you can select 2 monitoring parameters in assembly 105).
To obtain the best response time in the application choose t he adequate exchange method:
• Change of State (COS),
• Cyclic,
• or Polled.
The exchange method is downloaded in the drive by the DeviceNet scanner and must be configured by network tool (refer to 8. 4.
Configuring the DeviceNet scanner).
9. 2. Using explicit messaging
I/O messaging is used to transfer data that does not require continuous updates between the PLC and the drive :
• Configuration,
• Settings,
• Fault parameters,
• Log parameters;
•...
If the PLC program configures the drive using explicit messaging.
The new value of the parameters are not stored in EEPROM and they will be lost at next power off.
To store the values of parameters (whole configuration) in EEPROM, it is necessary to set to 1 the bit 1 of Extended control word (CMI),
refer to the Communication parameters manual.
1755877 11/201035
10. Diagnostics by the drive HMI
10. 1. Checking the node address and the data rate
On the graphic or integrated HMI, you can check the node address and the data rate through the menu [1.9 - COMMUNICATION](COM-)
sub-menu [DeviceNet](dnt-).
These parameters are both "read only" (i.e. their value cannot be changed with the HMI):
Keypad DisplayRangeRemarks
[Address] (AdrC)[0] (0) ... [63] (63)If data rate switches (7 and 8) are both set to 1 (ON), t he default node address
of the drive is 63, until it is set by network tool.
[Data rate] (bdr)[125 kbd] (125)
[250 kbd] (250)
[500 kbd] (500)
If data rate switches (7 and 8) are both set to 1 (ON), the default data rate of
the drive is 125 kbit/s, until it is set by network tool.
361755877 11/2010
10. Diagnostics by the drive HMI
1.1
1.2
1.3
1.4
1.5
2.1
2.2
2.3
2.4
2.5
MNS
10. 2. Signalling LED
The DeviceNet card features one combined Module/Network Status LED (MNS) in position 2.1, which is visible through the drive cover:
LED status indication
LED stateDrive controller stateIndication
OffDevice is not on line• The device is not powered.
Flasching greenDevice is operational and on line,
but not connected
OR
Device is on line but needs
commissioning
Speady greenDevice is operational, online, and
connected
Flasching redMajor fault and/or connection
time-out
Speady redCritical fault or
critical link failure
Flashing green / redCommunication faultThe device has detected a Network Access error and is in the
• The device has not completed the duplicate node address test yet.
The device is on line and operating in a normal condition, but network
connections are not established.
• The device has passed the duplicate node address test and is on line, but
has not established connections to other nodes.
• The device is not allocated to a master.
• Configuration is missing, incomplete, or incorrect.
The device is operating in a normal condition.
It is allocated to a master.
• The device has experienced a major recoverable fault.
• One or more I/O connections timed out.
• The card has a major unrecoverable fault and may need replacing.
• The device has detected an error that has rendered it incapable of
communicating on the network (duplicate node address or bus turned off).
Communication Faulted state. The device has subsequently received and
accepted an Identify Communication Faulted Request—Long Protocol
message.
Note: After power on, the MNS LED quickly glows green then red and finally turns off.
1755877 11/201037
10. Diagnostics by the drive HMI
RUNNET+50.00Hz80A
COMMUNICATION MAP
Command Channel: COM. CARD
Cmd value: 000F
Hex
Active ref. channel: COM. CARD
Frequency ref.: 500.0
Hz
Status word: 8627
Hex
CodeQuick
W3204: 53
W3205: 725
W7132: 0000
Hex
W0: -----
Hex
COM. SCANNER INPUT MAP
COM SCAN OUTPUT MAP
CMD. WORD IMAGE
FREQ. REF. WORD MAP
MODBUS NETWORK DIAG
MODBUS HMI DIAG
CANopen MAP
PROG. CARD SCANNER
Active command channel
Value of control word
used to control the drive
(hexadecimal format)
Active reference channel
Value of frequency reference (unit 0.1 Hz)
used to control the drive
Value of status word
(hexadecimal format)
Values of the four monitored words selected by the user.
The address and display format of these parameters can be
configured in the [6 - MONITORING CONFIG.] menu,
[6.3 - COM. MAP CONFIG.] submenu
(see the "Configuration" section on page 20
).
The value of a monitored word is equal to "-----" if:
- Monitoring is not activated
(address equal to W0)
- The parameter is protected
- The parameter is not known (e.g., W3200)
Input assembly 101 variables values
Output assembly 100 variables values
Control word from DeviceNet
[COM. card cmd.](CMd3)
Frequency reference from DeviceNet
[Com. card ref.](LFr3)
10. 3. Monitoring the control
On the graphic display terminal only, the [1.2 - MONITORING] menu ([COMMUNICATION MAP] submenu) can be used to display
control-signal diagnostic information between the drive and the DeviceNet PLC:
Note:
The DeviceNet card receives from the network a control word and sends a status word.
The drive has its own drive control word and status word.
The network information and the drive information can match or not:
- If the output assembly 100 and the input assembly 101 are selected
and
if drive control word and drive status word are assigned to the assemblies
then the values displayed in the [COMMUNICATION MAP] submenu represent the values on the DeviceNet network.
The drive can be in I/O profile or DSP402 / Drivecom profile.
- In the other cases (assemblies 21, 71, 103 ...), the DeviceNet card processes the commands coming from the network
(in Allen Bradley ® drive profile or ODVA profile). It calculat es a drive control word according to DSP402 / Drivecom profile.
This DSP402 / Drivecom control word of drive if displayed and not the network one.
381755877 11/2010
10. Diagnostics by the drive HMI
10. 4. Monitoring the communication scanner
You only need to read this chapter if you use the assemblies 100 or 101. These assemblies use the drive communication scanner.
On the graphic display terminal, in the [1.2 - MONITORING](SUP-) menu ([COMMUNICATION MAP] (CMM-) submenu):
- The [COM. SCANNER INPUT MAP](ISA-) submenu is used to display the value of the variables of the input assembly 101:
4 communication scanner input parameters [Com Scan Inp val.](NMp).
- The [COM SCAN OUTPUT MAP](OSA-) submenu is used to display the value of the variables of the output assembly 100:
4 communication scanner output parameters [Com Scan Outp val.](NCp).
DeviceNet faults are indicated by the LED on the DeviceNet card.
In the factory configuration, if DeviceNet is involved in the command or reference, a DeviceNet fault will trigger a resettable drive fault
[Com. network.](CnF) or [External fault com.](EPF2) and initiate a freewheel stop.
The Communication parameters manual contains a detailed description of how to manage communication faults
(see the "Communication monitoring" section).
• Following initialization (power-up), the drive checks that at least one command or reference parameter has been written for the first time
by DeviceNet.
• Then, if a communication fault occurs on DeviceNet, the drive will react according to the configuration (fault, maintain, fallback, etc.).
The response of the drive in the event of a DeviceNet communication fault can be changed (see the Configuration section).
- Drive fault [Com. network] (CnF) or [External fault com.](EPF2) (freewheel stop, stop on ramp, fast stop or DC injection braking
stop)
- No drive fault (stop, maintain, fallback)
The [Network fault](CnF) parameter can be used to obtain more detailed information about the origin of the last [Com. network](CnF)
fault. It can be accessed on the graphic display terminal only, in the [1.10 DIAGNOSTICS](DGt-) menu, [MORE FAULT INFO]
(AFI-) submenu.
This parameter is available in the DeviceNet Interface object (16#64 = 100), attribute 4.
ValueDescription of the values of the [Network fault](CnF) parameter
0No fault
1Fault triggere d by the user
2Duplicate node address (MAC ID )
3CAN FIFO RX errorThese events may be caused by loose or broken cables or by noise.
4CAN FIFO TX error
5CAN overrun
6CAN transmit errorThese events may be caused by loose or broken cables or by noise.
7CAN bus off
8Control time out.
9Acknowledge error, for COS or cyclic only.
10
This type of fault can be triggered by the parameter "ForceFault/trip" of the Control Supervisor object (16#28 = 41),
attribute 17.
COS, cyclic, polling or explicit messaging restart the timer.
The time out can be configured in the parameter "Expected_packet_rate" of the Connection object (5), attribute 9.
The error can be configured in the parameters "Acknowledge Timer" and "Retry Limi t" of t he Acknowl edge Ha ndl er obj ect,
attributes 1 and 2.
The DeviceNet master has been disconnected and reconnected in a shorter time than the time out.
401755877 11/2010
10. Diagnostics by the drive HMI
10. 6. Troubleshooting the card fault
The [internal com. link](ILF) fault appears when the following serious problems occur:
- Hardware fault on the DeviceNet card
- Dialog fault between the DeviceNet card and the drive
The response of the drive in the event of an [internal com. link](ILF) fault cannot be configured, and the drive trips with a freewhee l stop.
This fault cannot be reset.
Two diagnostic parameters can be used to obtain more detailed information about the origin of the [internal com. link](ILF) fault:
- [Internal link fault 1](ILF1) if the fault has occurred on option card no. 1 (installed directly on the drive)
- [Internal link fault 2](ILF2) if the fault has occurred on option card no. 2 (installed on option card no. 1)
The DeviceNet card can be in position 1 or 2.
The [Internal link fault 1](ILF1) and [Internal link fault 2](ILF2) parameters can only be accessed on the graphic display terminal in
the [1.10 DIAGNOSTICS](dGt-) menu, [MORE FAULT INFO](AFI-) submenu.
ValueDescription of the values of the [Internal link fault 1] (ILF1) and [Internal link fault 2](ILF2) parameters
0No fault
1Loss of internal communication with the drive
2Hardware fault detected
3Error in the EEPROM checksum
4Faulty EEPROM
5Faulty Flash memory
6Faulty RAM memory
7Faulty NVRAM memory
8Faulty analog input
9Faulty analog output
10Faulty logic input
11Faulty logic output
101Unknown card
102Exchange problem on the drive internal bus
103Time out on the drive internal bus (500 ms)
1755877 11/201041
11. DeviceNet objects
11. 1. Supported classes
Object classClass IDNeed for
Hex.Dec.
Identity16#011Required1Supports the reset serviceMessage router
Message
router
DeviceNet16#033Required1Configures node attributesMessage router
Assembly16#044Required13Defines I/O data formatMessage router, assembly, or
DeviceNet
connection
Motor data16#2840Required1Defines motor data for the motor
Control
supervisor
AC/DC drive16#2A42Required1Provides drive configurationMessage router, assembly, or
Acknowledge
handler
Application 16#70
DeviceNet
interface
16#022Optional 1Explicit message connection
16#055Required3Logical ports into or out of the
16#2941Required1Manages drive functions,
16#2B43Optional1I/O connection or message router
- A8
16#64100Optional1
ODVA
conformance
112-
OptionalVendor specific objectMessage router or parameter
424
No. of
instances
Effect on behaviorInterface
parameter object
device
connected to this device
operational states, and control
I/O connection or message router
Message router or parameter
object
Message router, assembly, or
parameter object
parameter object
object
421755877 11/2010
11. DeviceNet objects
11. 2. Identity object
The Identity object provides identificatio n and status information about the drive.
Class code
HexadecimalDecimal
16#011
Class attributes
Attribute IDAccessNameNeedData typeValueDetails
1GetRevision Opt.UINT1—
2GetMax InstancesOpt.UINT1 1 defined instance
Instance attributes
Attribute ID Access NameNeed Data typeValue Details
16#0EGet_Attribute_SingleReq.Read an attribute
16#10Set_Attribute_Single(1)Write an attribute
16#05ResetReq.Reset DeviceNet module
(1)Required if the heartbeat interval must be defined.
441755877 11/2010
11. DeviceNet objects
Key
Name of the state
NMS LED STATUS
Major
unrecoverable
fault
Major
recoverable
fault
Major
recoverable
fault
Flashing red
Operational
Solid green
Standby
Flashing green
Device self testing
Flashing red/green
Nonexistent
Off
Major
unrecoverable
fault
Solid red
Desactivated
Activated
Minor
fault
Failed
tests
Passed
tests
Power
Applied
Power loss
(from any state)
Identity object reset service
(from any state except Major
unrecoverable fault)
Fault corrected
State diagram for the Identity object
1755877 11/201045
11. DeviceNet objects
11. 3. Message router object
The Message router object is the element throu gh which all the "Explici t messages" objects pass in order to be directed t owards the objects
they are truly destined to.
Class code
HexadecimalDecimal
16#022
Class attributes
Attribute IDAccessNameNeedData typeValueDetails
1GetRevisionOpt.UINT12GetMax instancesOpt.UNT11 Defined instance
Instance attributes
Attribute ID Access NameNeed Data typeValueDetails
1GetObject list:
Number classes
2GetNumber availableOpt.UINT1Maximum number of simultaneous connections
3GetNumber activeOpt.UINT1Number of active connections
4GetActive connections Opt.UINT [ ]1List of active connections (referred to with their respective
Opt.Struct of:
UINT
UINT [ ]
20
(codes)
List of supported objects; the first UINT is the number of
supported classes; the remaining UINTs are the codes of
these classes.
Connection instance ID)
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instance service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
461755877 11/2010
11. DeviceNet objects
11. 4. DeviceNet object
The DeviceNet object provides the status and configuration of a DeviceNet node.
Class code
HexadecimalDecimal
16#033
Class attributes
Attribute IDAccessNameNeedData typeValueDetails
1GetRevision Opt.UINT2—
2GetMax InstancesOpt.UINT1 1 Defined instance
4Get/SetBusOff counterOpt.USINT0–255Number of occurrences of BusOff state. Set access
5GetAllocation
information
(1) Use Set access only if data rate switches (7 and 8) are both set to 1 (ON).
Opt.BOOL—Upon BusOff event:
Opt.BYTE
USINT
—
0–63
See below
0: CAN component remains in BusOff
1: Component is reset and communication resumes
is used to reset this counter.
Allocation choice
Master address (255 not allocated)
1755877 11/201047
11. DeviceNet objects
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instance service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleOpt.Read an attribute
16#10Set_Attribute_SingleOpt.Write an attribute
16#4BAllocate Master/Slave Connection SetOpt.Allocation connection master/slave
16#4CRelease Master/Slave Connection SetOpt.Release connection master/slave
481755877 11/2010
11. DeviceNet objects
11. 5. Assembly object
The Assembly object binds together the att ribu te s of mu lt ip le object s so that inf ormatio n t o or fr om each obj ect can be co mmuni cat ed over
a single connection.
Assembly objects ar e s tatic.
The assemblies in use can be modified through the parameter access of the network configuration tool (RSNetWorx).
The drive needs a power off to take into account a new assembly assignment.
Class code
HexadecimalDecimal
16#044
Class attribute
Attribute IDAccessNameNeedData typeValueDetails
1GetRevision Opt.UINT2—
2GetMax instanceOpt.UINT10513 defined instances
Instances supported
InstanceNameData size
20ODVA Basic speed control output4 bytes
21ODVA Extended speed control output4 bytes
22ODVA Speed and torque control output6 bytes
23ODVA Extended speed and torque control output6 bytes
100Communication scanner output8 bytes
103Allen-Bradley® drive output4 bytes
70ODVA Basic speed control input4 bytes
71ODVA Extended speed control input4 bytes
72ODVA Speed and torque control input6 bytes
73ODVA Extended speed and torque control input6 bytes
101Communication scanner input8 bytes
104Allen-Bradley® drive input4 bytes
105Allen-Bradley® drive input with parameters8 bytes
Instance attributes
Attribute IDAccessNameNeed Data typeValueDetails
3Get/Set (1)DataReq.
(1)Set access is restricted to output instances only (instances 20, 21, 22, 23, 100 and 103).
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instance service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
16#10Set_Attribute_SingleOpt.Write an attribute
1755877 11/201049
11. DeviceNet objects
b Output assembly 100
Bytes 0 and 1
1st Scanner out parameter [Val Com Scan Out1](NC1)
Bytes 2 and 3
2nd Scanner out parameter [Val Com Scan Out2](NC2)
Bytes 4 and 5
3rd Scanner out parameter [Val Com Scan Out3](NC3)
Bytes 6 and 7
4th Scanner out parameter [Val Com Scan Out4](NC4)
b Input assembly 101
Bytes 0 and 1
1st Scanner in parameter [Val Com Scan In1](NM1)
Bytes 2 and 3
2nd Scanner in parameter [Val Com Scan In2](NM2)
Bytes 4 and 5
3rd Scanner in parameter [Val Com Scan In3](NM3)
Bytes 6 and 7
4th Scanner in parameter [Val Com Scan In4](NM4)
Note:
• For the assignment of the scanner parameters by the drive HMI, refer to chapter 7. Configuring by the drive HMI.
• For monitoring of the scanner parameters by the drive HMI, refer to chapter 10. Diagnostics by the drive HMI.
• For the assignment and monitoring of the scanner parameters by the network configuration software (RSNetWorx ...) , refer to chapter
8. Configuring by a network tool
.
501755877 11/2010
11. DeviceNet objects
b Output assembly 20
Byte 0
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
not usednot usednot usednot usednot usedFault reset
• Output assembly 20 controls the drive if the parameter NetCtrl is set to 1 (attribute 5 of Control Supervisor object ; path 16# 29/01/05, t he
default setting is 1).
• Output assembly 20 gives the speed setpoint to drive if the parameter NetRef is set to 1 ( attribute 4 of AC/DC Drive obje ct, pat h 16#2A/
01/04, the default setting is 0).
In default setting, output assembly 20 controls the drive but the speed setpoint is via terminals (AI1 or AI2).
The default setting applies each time the connection is cl osed (Power on of the drive, DeviceNet disconnected from the card).
• Output assembly 22 controls the drive if the parameter NetCtrl is set to 1 (attribute 5 of Control Supervisor object ; path 16# 29/01/05, t he
default setting is 1).
• Output assembly 22 gives the speed setpoint to drive if the parameter NetRef is set to 1 ( attribute 4 of AC/DC Drive obje ct, pat h 16#2A/
01/04, the default setting is 0).
In default setting, output assembly 22 controls the drive but the speed setpoint is via terminals (AI1 or AI2).
The default setting applies each time the connection is cl osed (Power on of the drive, DeviceNet disconnected from the card).
• Output assembly 22 controls the drive if the parameter NetCtrl is set to 1 (attribute 5 of Control Supervisor object ; path 16# 29/01/05, t he
default setting is 1).
• Output assembly 22 gives the speed setpoint to drive if the parameter NetRef is set to 1 ( attribute 4 of AC/DC Drive obje ct, pat h 16#2A/
01/04, the default setting is 0).
In default setting, output assembly 22 controls the drive but the speed setpoint is via terminals (AI1 or AI2).
The default setting applies each time the connection is cl osed (Power on of the drive, DeviceNet disconnected from the card).
1755877 11/201057
11. DeviceNet objects
b Input assembly 104
Byte 0
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Actual
Faultnot usedDeceleratingAccelerating
Byte 1
Bit 15Bit 14Bit 13Bit 12Bit 11Bit 10Bit 9Bit 8
Reference sourceControl sourceAt speed
0000000
0001001
0010010
not used011
0011100
Preset speed 3 (SP3)101
0100110
Preset speed 4 (SP4)111
0101not used
Preset speed 5 (SP5)
0110
Preset speed 6 (SP6)
0111
Preset speed 7 (SP7)
1000
Reference from terminals (AI1 or AI2)
1001
Reference from network (DeviceNet)
1010
1011
1100
1101
1110
not used
1111
No reference source defined
direction
1=Forward
0=Reverse
Command
direction
1=Forward
0=Reverse
Control from terminals
Control from network
RunningEnabled
Bytes 2 and 3
Actual speed scaled
Unsigned, 0 to 32 767. 32 767= parameter [High speed](HSP), path 16#70/01/69
Note: When the value of Reference source (bits 12, 13, 14 and 1 5) is Preset s peed p (SPp) it means t hat t he co rre sponding comma nds i s
given by the assembly 103 via Reference select (bits 12,13 and 14) (not by the terminals).
581755877 11/2010
11. DeviceNet objects
b Input assembly 105
Byte 0
Bit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
Actual
Faultnot usedDeceleratingAccelerating
Byte 1
Bit 15Bit 14Bit 13Bit 12Bit 11Bit 10Bit 9Bit 8
Reference sourceControl sourceAt speed
0000000
not usedControl from terminals
0001001
Preset speed 1 (SP1)Control from network
0010010
Preset speed 2 (SP2)011
0011100
Preset speed 3 (SP3)101
0100110
Preset speed 4 (SP4)111
0101not used
Preset speed 5 (SP5)
0110
Preset speed 6 (SP6)
0111
Preset speed 7 (SP7)
1000
Reference from terminals (AI1 or AI2)
1001
Reference from network (DeviceNet)
direction
1=Forward
0=Reverse
Command
direction
1=Forward
0=Reverse
RunningEnabled
1
1
1
1
1
1111
Bytes 2 and 3
Actual speed scaled
Unsigned, 0 to 32 767. 32 767= parameter [High speed](HSP), path 16#70/01/69
Bytes 4 and 5
First extended monitoring parameter (see DeviceNet interface object page 70
Bytes 6 and 7
Second extended monitoring parameter (see DeviceNet interface object page 70
1755877 11/201059
0
0
1
1
1
not used
No reference source defined
1
1
0
0
1
0
1
0
1
0
)
)
11. DeviceNet objects
11. 6. Connection object
Class code
HexadecimalDecimal
16#055
Class attributes
Attribute IDAccessNameNeed Data typeValueDetails
1GetRevision Opt.UINT1—
2GetMax instancesOpt.UINT4 3 defined instances (1)
(1)Only instances 1 (explicit message), 2 (polled I/O message), and 4 (change of state/cyclic message) are supported. Instance 3 (bit
strobe) is not supported.
Attributes of instance 1—Explicit message instance
Attribute IDAccess NameNeed Data typeValueDetails
1GetStateReq.USINT—0 : Non-existent
2GetInstance_typeReq.USINT0Explicit Message
3GetTransportClass_triggerReq.BYTE16#83Class 3 server
4GetProduced_connection_idReq.UINT10xxxxxx011xxxxxx = Node address
5GetConsumed_connection_idReq.UINT10xxxxxx100xxxxxx = Node address
6GetInitial_comm_characteristicsReq.BYTE16#21Explicit messaging via Group 2
7GetProduced_connection_sizeReq.UINT36Produced data maximum size
8GetConsumed_connection_sizeReq.UINT36Consumed data maximum size
9Get/Set Expected_packet_rateReq.UINT25002.5 sec. (TimeOut)
12Get/SetWatchdog_timeout_actionReq.USINT1 or 3 1 : Auto-Delete
13GetProduced connection path lengthReq. UINT0Length of attribute 14 data
14GetProduced connection pathReq.Array of UINTNullEmpty
15GetConsumed connection path lengthReq.UINT0Length of attribute 16 data
16GetConsumed connection pathReq.Array of UINT NullEmpty
3 : Established
5 : Deferred Delete
(in bytes)
(in bytes)
3 : Deferred Delete (Default)
Refer to DeviceNet specification for more information.
601755877 11/2010
11. DeviceNet objects
Attributes of instance 2—Polled I/O message instance
Attribute ID AccessNameNeedData typeValueDetails
1GetStateReq.USINT—0: Non-existent
2GetInstance_typeReq.USINT1I/O Message
3GetTransportClass_triggerReq.BYTE16# 83Class 3 server
4GetProduced_connection_idReq.UINT01111xxxxxxxxxxxx = Node address
5GetConsumed_connection_idReq.UINT10xxxxxx101xxxxxx = Node address
6GetInitial_comm_characteristicsReq.BYTE16# 01Group 1 / Group 2
7GetProduced_connection_sizeReq.UINT4, 6, or 8Size of data produced
8GetConsumed_connection_sizeReq.UINT4, 6, or 8Size of data consumed
9Get/SetExpected_packet_rateReq.UINT—Exchange frequency (ms)
12Get/SetWatchdog_timeout_actionReq.USINT0, 1, or 2 (2)0: Transition to TimeOut
(1)Assembly assignment should not be modified in a running application.
If you Set any one of the values displayed in the "Value" column, it will be saved in EEPROM and then used at each power-up.
Any other value will not be saved.
(2)0 and 1: when the drive is disconnected from the network a DeviceNet fault occurs. In factoring set tings the DeviceNet fault triggers a
fault [Com. network](CnF) and a free wheel stop.
2: The DeviceNet fault is automatically reset (drive immediately restarts when RUN command is applied).
1755877 11/201061
11. DeviceNet objects
Attributes of instance 4—Change of st at e /cy c lic mes sa ge in st an c e
4GetProduced_connection_idReq.UINT01101xxxxxxxxxxxx = Node address
5GetConsumed_connection_idReq.UINT10xxxxxx101xxxxxx = Node address
6GetInitial_comm_characteristicsReq.BYTE16# 01Group 1 / Group 2
7GetProduced_connection_sizeReq.UINT4, 6, or 8Size of data produced
8GetConsumed_connection_sizeReq.UINT0Size of data consumed
9Get/SetExpected_packet_rateReq.UINT—Exchange frequency (ms)
12Get/Set Watchdog_timeout_actionReq.USINT 0, 1, or 2 (2)0: Transition to TimeOut
The first and only one instance
of the Acknowledge
handler object
(Class ID 16#2B)
2 data productions.
Undefined
(1)Assembly assignment should not be modified in a running application.
If you Set any one of the values displayed in the "Value" column, it will be saved in EEPROM and then used at each power-up.
Any other value will not be saved.
(2)To ensure a DeviceNet fault (and by default [Network fault](CnF)) in case of time out, configure "Polled I/O".
621755877 11/2010
11. DeviceNet objects
Class service
Service codeService nameNeedDescription
16#08CreateOpt.Instantiation of a connection
16#0EGet_Attribute_Single Req.Read an attribute
Instance service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
16#10Set_Attribute_SingleOpt.Write an attribute
16#05ResetOpt.Reset Inactivity/Watchdog timer
1755877 11/201063
11. DeviceNet objects
11. 7. Motor data object
The Motor data object acts as a motor parameter database.
Class code
HexadecimalDecimal
16#2840
Class attributes
Attribute IDAccessNameNeedData typeValueDetails
1GetRevision Opt.UINT2—
2GetMax instanceOpt.UINT1—
6GetMax ID number of class attributeOpt.UINT7—
7GetMax ID number of instance attributeOpt.UINT15—
Instance attributes
Attribute IDAccessNameNeedData typeValueDetails
3Get/SetMotorTypeReq.USINT76 = Wound rotor induction motor
6Get/SetRatedCurrentReq.UINTDepends on the
drive rating
7Get/SetRatedVoltageReq.UINTDepends on the
drive rating
9Get/SetRatedFreqOpt.UINT50/60[Rated motor freq.](FrS)
15Get/SetBaseSpeedOpt.UINTDepends on the
drive rating
7 = Squirrel cage induction motor
[Rated mot. current](nCr)
[Rated mot. volt.](UnS)
[Nom motor speed](nSP)
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instance service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
16#10Set_Attribute_SingleOpt.Write an attribute
641755877 11/2010
11. DeviceNet objects
11. 8. Control supervisor object
The Control supervisor object models the functions for managing all devices within the hierarchy of motor control devices.
Class code
HexadecimalDecimal
16#2941
Class attributes
Attribute IDAccessNameNeedData typeValueDetails
1GetRevision Opt.UINT2—
2GetMax instanceOpt.UINT1—
6GetMax ID number of class attributeOpt.UINT7—
7GetMax ID number of instance attributeOpt.UINT17—
Instance attributes
Attribute IDAccessNameNeedData typeDetails
3Get/SetRun FwdReq.BOOLOn an edge (0 V1)
4Get/SetRun RevOpt.BOOLOn an edge (0 V1)
5Get/SetNetCtrlOpt.BOOL0: Local Control (Channel 1)
6GetStateOpt.USINT0 = Vendor Specific,
7GetRunning FwdReq.BOOL
8GetRunning RevOpt.BOOL
9GetReadyOpt.BOOL
10GetFaultedReq.BOOL
12Get/SetFaultRstReq.BOOLFault reset (0 V1)
13GetFaultCodeOpt.UINTRefer to the Communication parameters manual:
15GetCtrlFromNetOpt.BOOL0 = Local Control; 1 = Network Control
16Get/SetDNFaultModeOpt.USINTAction on loss of DeviceNet command:
17Get/SetForceFault/TripOpt.BOOLForce a DeviceNet fault (0 V1)
1Get/SetAcknowledge timerReq.UINT16Default: 16 ms
2Get/SetRetry li mitReq.USINT1—
3Get/SetCOS producing connection instanceReq.UINT4Assembly
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instance service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
16#10Set_Attribute_SingleReq.Write an attribute
681755877 11/2010
11. DeviceNet objects
11. 11. Application objects
Class code
HexadecimalDecimal
16#70 to 16#A8112 to 424
Altivar parameters path
The Altivar parameters are grouped in classes.
Each application class has only 1 instance.
Each instance groups 200 parameters.
Each attribute in an instance relates to a parameter.
The first parameter registered in the first applicati on class (class code: 16#70 = 112) has the logical address 3000.
Examples:
1GetRevision Opt.UINT1
2GetMax instanceOpt.UINT1
6GetMax ID number of class attributeOpt.UINT7
7GetMax ID number of instance attributeOpt.UINTX
Instance attributes
Attribute IDAccessNameData typeValue
1Get/SetFirst parameter of the class UINT / USINTValue returned by the drive
...............
XGet/SetLast parameter of the classUINT / USINTValue returned by the drive
Note: Depending on the parameter, writ e access may be prohib ited. Ref er to the Communi catio n parameters manual for more informa tion.
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instances service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
116#0Set_Attribute_SingleOpt.Write an attribute
1755877 11/201069
11. DeviceNet objects
11. 12. DeviceNet interface object
Class code
HexadecimalDecimal
16#64100
Class attributes
Attribute IDAccessNameNeedData typeValue
1GetRevisionOpt.UINT1
2GetMax instanceOpt.UINT1
6GetMax ID number of class attributeOpt.UINT7
7GetMax ID number of instance attributeOpt.UINT9
Instances attributes
AttribueIDAccess NameData type Details
1Get/Set
(1)
2Get/Set
(1)
3Get/Set
(1)
4Get[Network fault](CnF)USINT0 : no fault
5GetSoftware revision of the DeviceNet cardUINTEx : 16# 1109 = V1.1ie09
6Get/Set Attribute of first extended monitoring parameter (input assembly 105)USINT0 : not configured
7Get/Set Attibute of second extended monitoring parameter (input assembly 105) USINT
8Get/Set Class of first extended monitoring parameter (input assembly 105)USINT0 : not configured
9Get/Set Class of second extended monitoring parameter (input assembly 105)USINT
Polling production instance assemblyUSINT0 : instance 70
1 : user forced fault
2 : duplicate Node Address
3 : CAN FIFO RX Error
4 : CAN FIFO TX Error
5 : CAN OverRun
6 : CAN send Error
7 : CAN Bus Off
8 : Control Time Out
9 : Acknowledge Error
10 : see page 40
(1)Any Set access to one of these parameters triggers the save in EEPROM for future use. In addition, the new va lue is immediately applied
to the drive if the corresponding Connection Object (Polled I/O Message or Change of State/Cyclic Message, i.e. Class ID 16#80
Instance #2 or #4) is not in "Established" state. Otherwise, the drive must be restarted to apply the new value.
701755877 11/2010
11. DeviceNet objects
Class service
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
Instance services
Service codeService nameNeedDescription
16#0EGet_Attribute_SingleReq.Read an attribute
16#10Set_Attribute_SingleOpt.Write an attribute
1755877 11/201071
AT V61_71_devicenet_EN_1755877_03
1755877 11/2010
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.