Quick Start Guide - ATV32
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product
documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive
system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable
regulations with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically
insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor shaft to
prevent rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage that
can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify that the voltage is < 42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
• Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single asynchronous motor with a motor cable length less than 50 meters (164
ft). Check your cables before connecting the drive with motor (length, power, shielded or unshielded).
In any other case, consult the ATV32 installation manual (S1A28686) and programming manual (S1A28692) on www.schneider-electric.com.
Check the delivery of the drive
• Remove ATV32 from the packaging and check that it has not been damaged.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
• Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.
ATV32H037M2
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________
•For ATV32H0ppM2, H0ppN4, HU1pN4 , ATV32HUppM2, ATV32HU22N4, U30N4, U40N4,
remove the output connector from the packaging and check that it has not been damaged.
0,37KW - 1/2HP - 220/ 240V
8B0917121134
Check the line voltage compatibility
• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts Drive voltage range _______ Volts
Drive range: ATV32ppppM2 = 200/240 V single phase - ATV32ppppN4 = 380/500V three-phase
www.schneider-electric.com 1/4 S1A41715 - 01/2014

u 50 mm
2 in.
u 50 mm
2 in.
u 10 mm
0.39 in.
( 1 )
(1) Minimum value corresponding to thermal contrainst.
On ATV32H0ppM2, H0ppN4, HU1pN4, ATV32HUppM2, ATV32HU22N4,
U30N4, U40N4 , a 150 mm (5.9 in) clearance may help to connect the
ground.
OR
OR OR
Asynchronous motor
ATV32H0ppM2, H0ppN4, HU1pN4
ATV32HUppM2
ATV32HU22N4, U30N4, U40N4
ATV32HU55N4, U75N4
ATV32HD11N4, D15N4
Mount the drive vertically
For a surrounding air temperature up to 50 °C (122°F). See installation manual (S1 A28686) on www.schneider-electric.com for other mounting and
thermal conditions.
Connect the drive: Power
• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating. (See SCCR annex)
• Check that the motor voltage is compatible with the drive voltage. Motor voltage ______Volts.
• Wire the drive to the motor.
• Wire the drive to the line supply.
200/240 V
380/500 V
0,6 ... 0,8 N.m
5.3 ... 7.1 lb.in
1,2 ... 1,5 N.m
10.6 ... 13.3 lb.in
1 ... 1,5 Nm
8.9 ... 13.3 lb.in
HAZARD OF FIRE OR ELECTRIC SHOCK
• To avoid overheating or loss of contact, connections must be carried out according to the cable sizes and tightening torques visible on
the label stuck on the ATV32.
• The use of multi-wire cable without a lug is forbidden for the mains connection.
•For ATV32H0ppM2, H0ppN4, HU1pN4 , ATV32HUppM2, ATV32HU22N4, U30N4, U40N4, the stripping length of the output power and braking
resistor cables must be shorter than 10 mm (0.39 in.)
•
Carry-out a pull out test to check that terminal screws are correctly tighten.
DANGER
Failure to follow these instructions will result in death or serious injury.
www.schneider-electric.com 2/4 S1A41715 - 01/2014

LI1: forward
LI2: reverse
Control command 2-wire: Parameter tCC = 2C
• Wire the speed reference: • Wire the command:
Connect the drive: Control by external reference
(Fr1 = Al1 )
0,5 N.m
4.4 lb.in
Apply power to the drive
• Ensure that used Logic Inputs are not active (LI1, LI2 see drawing ).
• Apply power to the drive.
• At first power up, the drive displays bFr, in the menu SIM- [SIMPLY START]
Set motor parameters for asynchronous motor
• Refer to the motor Nameplate for the following parameters settings .
Menu Code Description Factory setting
[Standard mot. freq]:
Standard motor frequency (Hz)
[Rated motor power]:
Nominal motor power on motor nameplate (KW)
[Rated motor volt.]:
Nominal motor voltage on motor nameplate (V)
[Rated motor current.]:
Nominal motor current on motor nameplate (A)
[Rated motor freq.]:
Nominal motor frequency on motor nameplate (Hz)
[Rated motor speed]:
Nominal motor speed on motor nameplate (rpm)
[Mot. therm. current]:
Nominal motor current on motor nameplate (A)
ConF> FULL>
SIM-
[SIMPLY START]
bFr
nPr
UnS
nCr
FrS
nSP
ItH
5
SW1
Source
Sink
Ext
Int
(2)
.
A1
50.0
drive rating
drive rating
drive rating
50.0
drive rating
drive rating
+24
ATV32
LI2
LI1
0V
Customer
setting
(2)for synchronous motor, consult the ATV32 programming manual (S1A28692) on www.schneider-electric.com.
Set basic parameters
Menu Code Description Factory setting
ACC
ConF> FULL>
SIM-
[SIMPLY START]
9
Start the motor
• Switch on LI1
dEC
LSP
HSP
[Acceleration]:
Acceleration time (s)
[Deceleration]:
Deceleration time (s)
[Low speed]:
Motor frequency at minimum reference (Hz)
[High speed]:
Motor frequency at maximum reference (Hz)
3.0
3.0
0.0
50.0
Customer
setting
www.schneider-electric.com 3/4 S1A41715 - 01/2014

Menus structure
ESC
COnFMOn
rdY
rEF
ESC
ESC
= ENT
ESC
A dash appears after menu codes to differentiate them from parameter codes. Example: [SIMPLY START]SIM-, tCC parameter.
[SPEED REFERENCE] [MONITORING]
[CONFIGURATION]
«LED ConF” and «LED
Value” illuminated
Refer to the programming manual (S1A28692) for
comprehensive menu descriptions.
ESC
COnF FULL
ENT
ESC
ENT
SIM-
ESC
tCC
ENT
bFr
ESC
HSP
ESC
3C
ENT
2C
ENT
2C
www.schneider-electric.com 4/4 S1A41715 - 01/2014