Variable Speed Drives
for Synchronous and Asynchronous Motors
®
PROFINET
VW3A3627
10/2013
Communication Manual
HRB25668
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical characteristics
of the performance of the products contained herein. This documentation is not intended as a substitute for
and is not to be used for determining suitability or reliability of these products for specific user applications. It
is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and
testing of the products with respect to the relevant specific application or use thereof. Neither Schneider
Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information
contained herein. If you have any suggestions for improvements or amendments or have found errors in this
publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including
photocopying, without express written permission of Schneider Electric. All pertinent state, regional, and local
safety regulations must be observed when installing and using this product. For reasons of safety and to help
ensure compliance with documented system data, only the manufacturer should perform repairs to
components.
When devices are used for applications with technical safety requirements, the relevant instructions must be
followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
Read these instructions carefully, and look at the equipment to become familiar with the device before trying
to install, operate, or maintain it. The following special messages may appear throughout this documentation
or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
Safety Information
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard
exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious
injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious
injury or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
NOTICE
NOTICE, used without the safety alert symbol, indicates a potentially hazardous situation which, if not
avoided, can result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the controller portion of the adjustable speed drive as defined
by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product.
• show you how to install the PROFINET communication module on your Altivar,
• show you how to configure the Altivar to use PROFINET fieldbus
NOTE: Read and understand this document and all related documents (see below) before installing,
operating, or maintaining your ATV32.
This documentation is valid for the Altivar 32 PROFINET fieldbus.
User Comments
Title of DocumentationCatalog Number
ATV32 Quick Start guideS1A41715
ATV32 Quick Start AnnexS1B39941
ATV32 Installation manualS1A28686
ATV32 Programming manualS1A28692
ATV32 Atex manualS1A45605
ATV32 Safety manualS1A45606
ATV32 Modbus manualS1A28698
ATV32 CANopen manualS1A28699
ATV32 PROFIBUS DP manualS1A28700
ATV32 Modbus TCP - EtherNet/IP manualS1A28701
ATV32 DeviceNet manualS1A28702
ATV32 EtherCAT manualS1A28703
ATV32 communication parameters manualS1A44568
ATV32 Safety integrated functions manualS1A45606
ATV32 certificates and other module manuals: see www.schneider-electric.com
You can download the latest versions of these technical publications and other technical information from
www.schneider-electric.com.
We welcome your comments about this document.
You can reach us by e-mail at techpub.drives@schneider-electric.com.
6HRB25668 10/2013
About the Book
Before You Begin
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all
other pertinent product documentation and who have received safety training to recognize and avoid hazards
involved are authorized to work on and with this drive system. Installation, adjustment, repair, and maintenance
must be performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as
well as all other applicable regulations with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch.
Use only electrically insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system,
block the motor shaft to prevent rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused
conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the
absence of DC bus voltage that can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify
that the voltage is < 42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
• Install and close all covers before applying voltage.
Failture to follow these instructions will result in death or serious injury.
WARNING
DAMAGE DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for
critical control functions, provide a means to achieve a safe state during and after a path failure. Examples
of critical control functions are emergency stop, overtravel stop, power outage, and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications
of unanticipated transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines.
• Each implementation of the product must be individually and thoroughly tested for proper operation before
being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1. For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide
for Selection, Installation and Operation of Adjustable-Speed Drive Systems.”
1
HRB25668 10/20137
About the Book
8
HRB25668 10/2013
Altivar PROFINET Overview
Altivar PROFINET Overview
What Is in this Chapter?
This chapter contains the following topics:
Overview10
PROFINET Fieldbus Module Features Overview10
PROFINET11
Modbus TCP11
PROFINET and Ethernet Features11
Web server11
Notation rules in this manual11
1
TopicPage
HRB25668 10/20139
Altivar PROFINET Overview
PROFINET
Controller
I/O
Scanner
PROFINET
Explicit
Messaging
Modbus
TCP
Standard
Web
browser
Ie, Mozilla
Modbus
Messaging
(func: 3, 6, 8,
16, 43)
iPar server
DCP
MRP
Embedded
Web server,
Java applets
Modbus TCP
TCP/UDP/IP
messaging
ProfiDrive profile
CiA 402 native drive profile
Parameters
management
Drive setup
PROFINET RT
exchanges
Available
telegrams
1,100,101,102
Overview
The VW3A3627 is a dual port PROFINET fieldbus module that can be used in a PROFINET industrial fieldbus. The VW3A3627 also
offers an embedded Web server (5 languages) which offers comfortable monitoring and commissioning functions directly from a
standard web browser.
Basic Overview According to the Simplified TCP/IP Model
ApplicationPROFINET / IP ServicesPROFINET RT
TransportTCP/UDP–
NetworkIP–
LinkEthernetEthernet
PROFINET Fieldbus Module Features Overview
10
HRB25668 10/2013
Altivar PROFINET Overview
PROFINET
PROFINET RT extends Ethernet by an advanced industrial protocol management as an application layer for
automation applications in this way, Ethernet is excellently suited for industrial control. PROFINET relies on
TCP and UDP for non-RT information. Products from different manufacturers can be networked by using a
PROFINET-compliant switch.
Modbus TCP
The Modbus application layer is standard. Thousands of manufacturers are already implementing this
protocol. Many have already developed a Modbus TCP/IP connection and numerous products are currently
available. With the simplicity of its protocol and the fast Ethernet throughput data rate of 100 Mbit/s, Modbus
TCP/IP achieves excellent performance.
PROFINET and Ethernet Features
The product supports the following functions:
• Automatic IP address assignment via DHCP and DCP
• Support of MRP (Media Redundancy Protocol)
• Automatic configuration data via iPar-Server
• Commissioning via commissioning SoMove Lite software
• Support of LLDP (Link Layer Discovery Protocol)
• Diagnostics and configuration via integrated Web server
Web server
The standard Web server provides access to the following pages:
• Drive monitor
• Data viewer/editor
• Save and restore configuration
• Network parameters
• iPar client settings
• Administration
• TCP/UIP statistics
• Modbus statistics
Notation rules in this manual
Drive Terminal Displays
The graphic display terminal (to be ordered separately - catalog number VW3A1101) menus are shown in
square brackets.
Example: [COMMUNICATION CARD]
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (Cbd-)
Parameter names are displayed on the graphic display terminal in square brackets.
Example: [fallback spd]
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
Example: (LFF)
Formats
In this manual, hexadecimal values are written as follows: 16#
Binary values are written as follow: 2#
HRB25668 10/201311
Altivar PROFINET Overview
12
HRB25668 10/2013
Hardware Setup
Hardware Setup
What Is in this Chapter?
This chapter contains the following topics:
Hardware Presentation14
Firmware and GSDML Version Compatibility14
Installation14
Wiring17
Installation Topology18
2
TopicPage
HRB25668 10/201313
Hardware Presentation
2 RJ45 female sockets
for the PROFINET
connection
The following figure shows the dual RJ45 connector, PROFINET module:
Hardware Setup
Firmware and GSDML Version Compatibility
VW3A3627 option module is compliant with Altivar 32 V1.8 IE11 minimum versions.
Check the firmware version, on the packaging label (on the right part of the label).
The associated GSDML are named as the following example:
GSDML-V2.25-Schneider-ATV32-20130128.xml
The files are available on www.schneider-electric.com.
Installation
Check that the module catalog number marked on the label is the same as that on the delivery note
corresponding to the purchase order.
Remove the communication module from its packaging and check that it has not been damaged in transit.
RISK OF DAMAGE TO THE DRIVE
Install only communication modules designed for ATV32. See catalog numbers in the catalog.
Failure to follow these instructions can result in equipment damage.
NOTICE
14
HRB25668 10/2013
Hardware Setup
Install the PROFINET module in ATV32
Refer to the installation manual (S1A28686). Install the PROFINET module in ATV32 as follows:Install the
communication module in ATV32 as follows:
StepActionComment
1Ensure that the power is off.
Locate the option module port on the
bottom of the ATV32.
2Extract the cover.
3Insert the module
4Check that the module is correctly
inserted and locked mechanically in
the drive.
HRB25668 10/201315
Extract the communication module as follows:
StepActionComment
1Ensure that the power is off.
Press the strip.
2Extract the module while maintaining
the strip pressed,
Hardware Setup
16
HRB25668 10/2013
Hardware Setup
Wiring
Cable specifications
The VW3A3627 option module is equipped with 2 RJ45 female sockets for the PROFINET connection.
• Minimum Cat 5e,
• Use equipotential bonding conductors (100 BASE-TX, Category 5e or Industrial Ethernet fast connect)
• Connector RJ45, no crossover cable
• Shield: both ends grounded
• Twisted-pair cable
• Verify that wiring, cables, and connected interfaces meet the PELV requirements.
• Maximum cable length per segment = 100 m (328 ft) / 6 plugs
The following table describes the pin out of each RJ45:
PinSignalMeaning
1Tx+Ethernet transmit line +
2Tx–Ethernet transmit line –
3Rx+Ethernet receive line +
4––
5––
6Rx–Ethernet receive line –
7––
8––
HRB25668 10/201317
Installation Topology
MRP
manager
The VW3A3627 option module, with its 2 RJ45 connector, enables several wiring solutions:
Daisy Chain and/or Star topology
Ring topology
Hardware Setup
PROFINET
SWITCH
The ring topology can only be used with a Media Redundancy Protocol (MRP) capable managed device.
The bus watchdog shall be increased when using MRP function in order to avoid untimely [Com. network]
(CnF) trip.
18
HRB25668 10/2013
Configuration and Parameters
Configuration and Parameters
Overview
This chapter describes the parameters of the VW3A3627module. These parameters are described here
according to the local HMI or the Graphic keypad. These settings are also possible from SoMove or from the
embedded Web server.
What Is in this Chapter?
This chapter contains the following topics:
Network Settings20
iPar Settings22
Modbus TCP Settings23
3
TopicPage
HRB25668 10/201319
Network Settings
Configuration and Parameters
The parameters are accessible in the [CONFIGURATION](COnF), [FULL](FULL),
[COMMUNICATION] (COM-) menu and [COMMUNICATION CARD](Cbd-) submenu.
Use this parameter to select the IP
address assignment method.
[IP card] (IPC- )
(IPC1) (IPC2) (IPC3) (IPC4)
These fields are editable when IP
mode is set to Fixed address
[IP Mask] (IPM-)
(IPM1) (IPM2) (IPM3) (IPM4)
These fields are editable when IP
mode is set to Fixed address
[IP Gate](IPG-)
(IPG1) (IPG2) (IPG3) (IPG4)
These fields are editable when IP
mode is set to Fixed address
[Network error] (Err)
Ethernet Error Code
[SERVICES](EWE-)
Enable web services
[PPO profile used] (PrFL)
Actual profile
[MAC @] (MAC)
MAC ad
Displays MAC addresses of the
device.
dress d
isplay
Range or Listed ValuesDefaultLong
Name
0: Man
2: DHCP
3: DCP
0 to 255 for each of the 4 fields0.0.0.0[0.0.0.0]0
0 to 255 for each of the 4 fields0.0.0.0[255.255.254.0] 255
0 to 255 for each of the 4 fields0.0.0.0[0.0.0.0]0
0: No error
1: PROFINET I/O timeout
2: Network overload
3: Loss of Ethernet Carrier
9: Duplicated IP address.
10: No valid IP.
12: IPAR unconfigured state
13: IPAR unrecoverable error
17: Application I/O configuration error
0: No web services
1: Web server enabled
0: UNCFG
1: Profidrive
100: Device specif
[xx-xx-xx-XX-XX-XX]–[xx-xx-xx-XX-
Man[fixed]
[DHCP]
[DCP]
0––R64270
1––R/W–
0[0]0R/W6665
XX-XX]
Short
Name
MAnU
dHCP
dCP
0
0
0
255
254
0
0
0
0
–––
AccessParameter
Number
to
3347
R/W64250
R/W64212
64213
64214
64215
R/W64216
64217
64218
64219
R/W64220
64221
64222
64223
Left port MAC address is +1.
Right port MAC address is + 2.
If the IP address is not set to a valid value at first power-on, the drive will trip in EPF2.
Assigning IP parameters
The drive needs 3 IP parameters:
• The drive IP address.
• The subnet mask.
• The gateway IP address.
These IP addresses can be entered directly:
If [IP mode](IpM) is set to [fixed] (MAnU). Using the integrated display terminal, using the graphic display
terminal, or using the SoMove software.
They can be provided by either:
• A DHCP server (correspondence between the Device name and the IP addresses).
• A DCP (Discovery Control Protocol) protocol to discover PROFINET devices.
20
HRB25668 10/2013
Configuration and Parameters
Entering IP parameters in the Terminal
In the [CONFIGURATION](COnF), [FULL](FULL), [COMMUNICATION](COM-) menu and
[COMMUNICATION CARD](Cbd-) submenu, enter the following IP parameters:
• [IP card](IPC1) (IPC2) (IPC3) (IPC4),
• [IP Mask](IPM1) (IPM2) (IPM3) (IPM4),
• [IP Gate](IPG1) (IPG2) (IPG3) (IPG4).
Turn off the drive and then back on again (control voltage if a separate power supply is being used), otherwise
the IP parameters are not taken into account.
If this address is modified, the new IP address entered is displayed. This IP address will be effective the next
time the drive is turned on.
Case of manual switching of [IP mode](IPMode)
1. When switching [IP mode](IPMode) to [DCP] (dCP)
- IP Settings are no longer editable
- Turn off the drive supply and then back on again, including control voltage if a separate power supply
is being used
- The new configuration is applied, the device is waiting for IP settings from PROFINET controller
2. When switching [IP mode] (IPMode) to [Manual] (Manu)
- IP Settings becomes editable
- Set IP settings with valid values
- Turn off the drive and then back on again, including control voltage if a separate power supply is being
used
- The new configuration is applied
Note: If IP settings are not valid, the drive will trip in EPF2 after next power-on.
3. When switching [IP mode] (IPMode) to [DHCP] (dHCP)
- IP Settings are no longer editable.
- Set the Device Name with a valid value.
- Turn off the drive and then back on again, including control voltage if a separate power supply is being
used.
- The new configuration is applied, the device is waiting for IP settings from DHCP Server.
Note: If the Device Name is not valid, the drive will trip in EPF2 after next power-on.
Case of automatic switching of [IP mode](IPMode) to [DCP](dCP)
Needed conditions:
- The device has a Station Name configured and validated
- The device is connected to a PROFINET controller
- The PROFINET controller has the Station Name in its own configuration
- The settings are in local configuration of the PROFINET controller
If all of these conditions are fulfilled:
- [IP mode](IPMode) is automatically set to [DCP] (dCP)
- IP settings are replaced by the one set in local PROFINET controller
- The new configuration is applied immediately
HRB25668 10/201321
iPar Settings
Configuration and Parameters
These parameters are accessible in the [CONFIGURATION](COnF), [FULL](FULL),
[COMMUNICATION] (COM-) menu and [COMMUNICATION CARD](Cbd-) submenu.
The following table describes the parameters related to the iPar settings server function
Parameter Description
(HMI mnemonic)
[iPar Validation] (IPAU)
Enable iPar service
[iPar Autosave] (IPAS)
Enable iPar autosave service
[iPar timer] (IPAt)
Interval for periodic saving of the
iPar service
[iPar Error Mgt] (IPAF)
Enable iPar detected error
management
[iPar Local Conf] (ICFG)
Selection of local or server
configuration
[iPar Status] (IPAE)
iPar service status
[iPar Error Cod] (IPAd)
Detected error code
Range or Listed ValuesDefaultLong
Name
0: no
1: yes
0: no
1: yes
0: no autosave
1 to 9999 (minutes)
0: no
1: yes
0: The drive configuration is downloaded
from the iPar server at Power-onof the drive.
1: The drive configuration is local.
0: idle state
1: initialization
2: configuration
3: ready
4: operational
5: not configured
6: Unrecoverable detected fault state
0: No detected error
1: Stored configuration is not ok
2: No configuration file on the IPAR server or
configuration is not compatible. (Served
configuration is not ok)
3: Detected error connection to the IPAR
configuration file on the server.
4: Detected error writing the configuration file
to the server.
0[No]
[Yes]
0[No]
[Yes]
10––R/W64278
1[No]
[Yes]
0[No]
[Yes]
[IDLE]
[INIT]
[CONF]
[RDY]
[OPE]
[UCF
[UNR
0[0]
[1]
[2]
[3]
[4]
G]
EC]
Short
Name
(nO)
(YES)
(nO)
(YES)
(nO)
(YES)
(nO)
(YES)
(IdLE)
(INIt)
(CONF)
(rdY)
(OPE)
(UCFG)
(UrEC)
(0)
(1)
(2)
(3)
(4)
AccessParameter
Number
R/W64274
R/W64275
R/W64277
R/W64276
R64279
R64280
22
HRB25668 10/2013
Configuration and Parameters
Modbus TCP Settings
The Modbus channel is only used for commissioning tools and for embedded Web server
(UnitID 251: Fieldbus module, Unit ID 248: Variable Speed Drive).
Function NameCodeDescriptionRemarks
Read Multiple Register03
Write Single Register06
Diagnostic08
Write multiple register16
Read device Identification43
Identification
Byte(s)MeaningWith the VW3 A3627 PROFINET module
24…23+BValue of object 2 (B ASCII characters) (1)Example: “ATV32HU15M3”
26+B…29+BValue of object 3 (C ASCII characters)Example: “0201” for version 2.1
32+B…31+B+D Value of object 4 (D ASCII characters) (1)Example: “MACHINE 4”
Read Multiple RegisterMaximum PDU length: 63 words
16#03
Write Single Register–
16#06
Diagnostic–
16#08
Write Multiple Register Maximum PDU length: 63 words
16#10
Schneider Identification(subfunction 14/16#0E)
16#2B
See the table below
0Function code = 16#2B16#2B
1Type of MEI16#0E
2ReadDeviceId code16#01
3Degree of conformity16#02
4Number of additional frames16#00 (a single frame)
5Next object ID16#00
6Number of objects
3 for Basic
4 for Regular or Extended
7Object 1 ID16#00 = Vendor Name
8Length of object 1 (A)13
9…21Value of object 1 (A ASCII characters)“SchneiderElectric”
22Object 2 ID16#01 = Product Code
23Length of object 2 (B)11 (for the following example only)
24+BObject 3 ID16#02 = Major.Minor Revision
25+BLength of object 3 (C)4
30+BObject 4 ID16#06 = Application Name (2)
31+BLength of object 4 (D)8 (for the following example only)
For Regular
And
Extended
(1)The length of this field is variable. Use the “Length of object X” field associated with it to determine the length.
(2)In the case of the drive, this data item corresponds to [DEVICE NAME].
The response to a “drive identification” request does not cause an exception response.
HRB25668 10/201323
Configuration and Parameters
24
HRB25668 10/2013
Configuration
Configuration
What Is in this Chapter?
This chapter contains the following topics:
Configuring the Control Channel26
Configuring Monitor Parameters29
Configuring Communication Interruption Management30
4
TopicPage
HRB25668 10/201325
Configuring the Control Channel
Reset
Run reverse
Run forward
[INPUTS / OUTPUTS CFG] /
[Forward] is assigned to CMd bit 0
[INPUTS / OUTPUTS CFG] /
[Reverse assign.] is assigned to
CMd bit 1
[FAULT MANAGEMENT] /
[FAULT RESET] / [Fault reset] is
assigned to CMd bit 7
This chapter explains through 3 examples how to configure the drive for operation from communication
network. Several other combinations are possible. The whole coverage of these possibilities is not in the scope
of this document. For more information, refer to the programming manual.
• I/O Mode - a simple command word (based on forward, reverse, and reset binary commands).
• Combined Mode (with native profile CiA 402) - Both reference and command word come from the
communication network.
• Separate (with native profile CiA 402) - reference and command come from separate sources: for example,
the command (in CiA 402) comes from the communication network and the reference from the HMI.
Configuration of the Drive for Operation in I/O Profile
To illustrate the I/O Profile, here is a simple example, which can be extended with additional features. The
command word is made of Run forward (bit 0 of CMd), run reverse (bit 1 of CMd), and a detected fault reset
(bit 7 of CMd).
Configuration
NOTE: This operating mode is not applicable when the drive is configured from the controller to operate with
the telegram 1 (PROFIdrive).
The settings will be the following:
[Ref.1 channel] (Fr1)[Com. card] (nEt)
[Profile] (CHCF)[I/O profile] (IO)
[Cmd switching] (CCS)Default value
[Cmd channel 1] (Cd1)[Com. card] (nEt)
The bits of the command word can now be configured.
In the [INPUTS / OUTPUTS CFG] menu, configure:
[Forward](Frd)[Cd00] (Cd00)
[Reverse assign.] (rrS)[Cd01] (Cd01)
In the [FAULT MANAGEMENT] menu, [FAULT RESET] submenu, configure:
[Fault reset] (rSF)[Cd07] (Cd07)
26
HRB25668 10/2013
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.