Schneider ATV12H037M2, ATV12H055M2, ATV12HU22M2, ATV12H075M2, ATV12H018M2 User Manual

Quick Start Guide - ATV12
ENGLISH
S1A5614602
1
8B0915316127
ATV12HU15M2
1.5KW - 2HP - 200 / 240V
2
3
(a)
(a)
(a)
(a)
(a) 50 mm (2 in.)
(b) 10 mm (0.4 in.)
(b)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations
with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor shaft to prevent
rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage that can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify that the voltage is < 42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
• Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft). Check your cables before connecting the drive with motor (length, power, shielded or unshielded) In any other case, consult the ATV12 user manual (BBV28581) on www.schneider-electric.com.
• Remove ATV12 from the packaging and check that it has not been damaged.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
• Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

Check the line voltage compatibility

• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts Drive voltage range _______ Volts Drive range: ATV12pppp

Mount the drive vertically

For a surrounding air temperature up to 40 °C (104 °F) or 50°C (122°F), based on product reference number.
F1 = 100/120 V single phase / ATV12pppp M2=200/240 V single phase / ATV12ppppM3 = 200/240 V three-phase.
See user manual (BBV28581) on www.schneider-electric.com for other thermal conditions. For ATV12P baseplate product, see also the ATV12P installation manual (BBV28587)
www.schneider-electric.com 1/4 S1A56146 - 05/2013
4
ATV12F1
ATV12M2
ATV12M3
0,8...1,2 N.m
7.1...10.6 lb.in
200 / 240V
/
/
/
or
5
5.1
Do: + + +
687
9.1
LI1
+24 V
ATV 12
LIx
+24 V
ATV 12
LI2
LI1
LIx
LI1: forward LIx: reverse
LI1: stop
Control command 2-wire:
Control command 3-wire:
Parameter tCC = 2C
Parameter tCC = 3C
LI2: forward LIx: reverse
Do: + + +
687
9.1
5.2
Do: + + +
9.2
Do: + + +
9.1
6
7

Connect power wiring

• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating.
• Check that the motor voltage is compatible with the drive voltage. Motor voltage ______Volts.
• Wire the drive to the motor.
• Wire the drive to the line supply.
Connect control wiring and
Select control configuration
[REMOTE configuration]
(Control by external reference)
• Wire the speed reference:
+ 5 v
AI1
COM
2.2 KΩ
Wire the command:
[LOCAL configuration]
(control by internal reference)
.

Apply power to the drive

• Ensure that Logic Inputs are not active (see Li1, Li2, Lix ).
• Apply power to the drive.
• The drive displays bFr at first power up.
• On next start-ups, the drive displays rdY .

Set motor parameters

• Refer to the motor Nameplate for the following parameters settings.
Menu Code Description Factory setting
COnF> FULL>drC-
[Motor control menu]
COnF> FULL> FLt->
tHt-
[Motor thermal protection menu]
www.schneider-electric.com 2/4 S1A56146 - 05/2013
bFr
nPr
nCr
ItH
[Standard motor frequency]:
Standard motor frequency (Hz)
[Rated mot. power]:
Nominal motor power on motor nameplate
[Rated mot. current]:
Nominal motor current on motor nameplate (A)
[Motor thermal current]:
Nominal motor current on motor nameplate (A) drive rating
.
50
.0
drive rating
drive rating
687
687
Customer setting