The information provided in this documentation contains general descriptions and/or technical characteristics of the
performance of the products contained herein. This documentation is not intended as a substitute for and is not to
be used for determining suitability or reliability of these products for specific user applications. It is the duty of any
such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any
suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including
photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product.
For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should
perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be
followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury,
harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
Energy savings
Speed control process regulating enables significant energy savings, particulary with pump and fan applications.
Furthermore some ATV12 functions enable to enhance these savings: [Motor control type](Ctt) page
57, [Sleep/wake]
(tLS) page
74 and [PID feedback assignment](PIF) page 72.
Contents ____________________________________________________________________________________________________ 3
Important information __________________________________________________________________________________________ 4
Before you begin______________________________________________________________________________________________ 5
Documentation structure________________________________________________________________________________________ 7
Software enhancements________________________________________________________________________________________ 8
Steps for setting up (also refer to Quick Start) _______________________________________________________________________ 9
Setup - Preliminary recommendations ____________________________________________________________________________ 10
Drive ratings ________________________________________________________________________________________________ 11
Dimensions and weights_______________________________________________________________________________________ 12
Mounting___________________________________________________________________________________________________ 13
Wiring _____________________________________________________________________________________________________ 16
Power terminals _____________________________________________________________________________________________ 20
Control terminals_____________________________________________________________________________________________ 23
Check list __________________________________________________________________________________________________ 29
Factory configuration _________________________________________________________________________________________ 30
Basic functions ______________________________________________________________________________________________ 31
Programming _______________________________________________________________________________________________ 32
Structure of parameter tables___________________________________________________________________________________ 35
Function compatibility table ____________________________________________________________________________________ 36
Reference Mode rEF _________________________________________________________________________________________ 37
Monitoring mode MOn ________________________________________________________________________________________ 38
Configuration Mode ConF______________________________________________________________________________________ 44
Configuration Mode - MyMenu __________________________________________________________________________________ 45
Configuration Mode - Complete menu (FULL) ______________________________________________________________________ 47
Maintenance _______________________________________________________________________________________________ 100
Migration ATV11 - ATV12_____________________________________________________________________________________ 101
Diagnostics and Troubleshooting _______________________________________________________________________________ 108
Application notes ___________________________________________________________________________________________ 114
Short-circuit rating and branch circuit protection ___________________________________________________________________ 120
Organization tree ___________________________________________________________________________________________ 121
Parameter index ____________________________________________________________________________________________ 122
BBV28581 05/20133
Page 4
Important information
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow
this symbol to avoid possible injury or death.
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain
it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call
attention to information that clarifies or simplifies a procedure.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
NOTICE
NOTICE, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can
result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this product.
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product
documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with
this drive system. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other
applicable regulations with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically
insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Before performing any type of work on the drive system, block the motor shaft
to prevent rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage
that can exceed 800Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify that the voltage is <
42Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
• Install and close all covers before applying voltage.
Failture to follow these instructions will result in death or seìrious injury.
DANGER
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the Altivar 12 drive.
• Any changes made to the parameter settings must be performed by qualified personnel.
Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
BBV28581 05/20135
Page 6
Before you begin
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for critical control functions,
provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop,
overtravel stop, power outage, and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated
transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines.
• Each implementation of the product must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
a. For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control”
and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems.”
a
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the line voltage is compatible with the supply voltage range shown on the drive
nameplate. The drive may be damaged if the line voltage is not compatible.
Failure to follow these instructions can result in injury or equipment damage.
Using motors in parallel
Set Motor control type Ctt page 57to Std.
NOTICE
RISK OF DAMAGE TO THE MOTOR
Motor thermal protection is no longer provided by the drive. Provide an alternative means of thermal protection on every motor
Failure to follow these instructions can result in equipment damage
6BBV28581 05/2013
Page 7
Documentation structure
The following Altivar 12 technical documents are available on the Schneider Electric website (www.schneider-electric.com).
ATV12 Quick Start Guide (S1A56146)
The Quick Start describes how to wire and configure the drive to start motor quickly and simply for simple applications.
This document is delivered with the drive with an Annex (S1A58684) for Short Circuit Current Ratings (SCCR) and branch circuit protection.
ATV12 User manual (BBV28581)
This manual describes how to install, program and operate the drive.
ATV12 Modbus Communication manual (BBV28590)
This manual describes the assembly, connection to the bus or network, signaling, diagnostics, and configuration of the communicationspecific parameters via the 7 segment LED display.
It also describes the communication services of the Modbus protocol.
This manual includes all Modbus addresses. It explains the operating mode specific to communication (state chart).
ATV12P Installation manual (BBV28587)
This manual describes how to install the drive ATV12 baseplate following the conditions of acceptability.
ATV12 Parameters description file
All the parameters are grouped together in an Excel file with the following data:
• Code
•Name
• Modbus Addresses
• Category
• Read/write access
• Type: signed numerical, unsigned numerical, etc.
•Unit
• Factory setting
• Minimum value
• Maximum value
• Display on the 7-segment integrated display terminal
• Relevant menu
This file offers the option of sorting and arranging the data according to any criterion chosen by the user.
BBV28581 05/20137
Page 8
Software enhancements
Since it was first marketed, the Altivar ATV 12 has been equipped with additional functions. Software version V1.2 has now been updated
to V1.4. This documentation relates to version V1.4.
The software version appears on the rating plate attached to the side of the drive.
Enhancements made to version V1.2 in comparison to V1.1
• New parameters:
- Sleep threshold OffsetSLE. See page 75
- PI feedback supervision thresholdLPI. See page 76
- PI feedback supervision function time delaytPI. See page 76
- Maximum frequency detection hysteresisAP0. See page 76
- PI feedback supervisionMPI. See page 76
- Fallback speedLFF. See page 76
- Time delay before automatic start for the overload faultFtO. See page 77
- Time delay before automatic start for the underload faultFtU. See page 78
- Selecting the operating modeMdE. See page 78
- Starting frequency of the auxiliary pumpFOn. See page 78
- Time delay before starting the auxiliary pumptOn. See page 78
- Ramp for reaching the auxiliary pump nominal speedrOn. See page 78
- Auxiliary pump stopping frequencyFOF. See page 78
- Time delay before the auxiliary pump stop commandtOF. See page 79
- Ramp for auxiliary pump stoppingrOF. See page 79
- Zero flow detection periodnFd. See page 79
- Zero flow detection activation thresholdFFd. See page 79
- Zero flow detection offsetLFd. See page 79
•New menu Pump sub-menuPMP-. See page 77
• New quick REMOTE/LOCAL configuration switching using the embedded buttons. See page 34
• New wiring labels, LO+ and LO- instead of LO and CLO, see pages 18
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. For pumping applications.
.
and 19.
Enhancements made to version V1.4 in comparison to V1.2
•New menu:
- External faultEtF-. See page 97
• New parameters:
- External fault assignmentEtF. See page 97
- Stop type - external faultEPL. See page 97
• New detected fault:
- External detected fault by logic inputEPF1. See page 111
These parameters are added to the standard ATV12 product offer.
. For External fault management by logic input.
.
.
.
8BBV28581 05/2013
Page 9
Steps for setting up (also refer to Quick Start)
1. Receive and inspect the drive
v Check that the part number printed on the label is the same as that on the
purchase order.
v Remove the Altivar from its packaging and check that it has not been damaged
in transit.
2. Check the line voltage
v Check that the line voltage is compatible with the voltage
range of the drive (page 11
).
3. Mount the drive
v Mount the drive in accordance with the instructions
in this document (page 13
).
v Install any options required.
Steps 2 to 4 must
be performed with
the power off.
4. Wire the drive
(page 20)
v Connect the motor, ensuring that its
connections correspond to the voltage.
v Connect the line supply, after making
sure that the power is off.
v Connect the control part.
5. Configure the drive(page 32)
v Apply input power to the drive but
do not give a run command.
v Set the motor parameters
(in Conf mode) only if the factory
configuration of the drive is not
suitable.
v Perform auto-tuning.
6. Start
BBV28581 05/20139
Page 10
Setup - Preliminary recommendations
Before switching-on the drive
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that all logic inputs are inactive to help prevent an accidental startup.
Failure to follow these instructions will result in death or serious injury.
Before configuring the drive
DANGER
UNINTENDED EQUIPMENT OPERATION
• Read and understand this manual before installing or operating the Altivar 12 drive.
• Any changes made to the parameter settings must be performed by qualified personnel.
• Ensure that all logic inputs are inactive to help prevent an accidental startup when modifying parameters.
Failure to follow these instructions will result in death or serious injury.
Using the drive with motor having a different size
The motor could have different rating than drive. In case of smaller motor, there is no specific calculation. The motor current has to be set
on Motor thermal current ItH parameter page 94
on a 2.2 kW (3 HP) drive) it is necessary to ensure motor current and actual motor power will not pass over nominal power of drive.
. In case of higher size of motor, possible up to 2 sizes (example is using a 4 kW (5.5 HP)
Line contactor
NOTICE
RISK OF DAMAGE TO THE DRIVE
• Avoid operating the contactor frequently to avoid premature aging of the filter capacitors.
• Power cycling must be MORE than 60 seconds.
Failure to follow these instructions can result in equipment damage.
Use with a smaller rated motor or without a motor
• In factory settings mode, Output Phase loss OPL page 94is active (OPL set to YES). To check the drive in a test or maintenance
environment without having to switch to a motor with the same rating as the drive (useful in the case of high power drives), deactivate
Output Phase loss OPL(OPL set to nO).
•Set Motor control type Ctt page 57
to Stdin Motor control menudrC-.
NOTICE
RISK OF DAMAGE TO THE MOTOR
Motor thermal protection will not be provided by the drive if the motor rating current is less than 20% of the rated drive current. Provide
an alternative means of thermal protection.
Failure to follow these instructions can result in equipment damage.
(1)These power ratings are for a switching frequency of 4 kHz, in continuous operation. The
switching frequency is adjustable from 2 to 16 kHz.
Above 4 kHz, the drive will reduce the switching frequency if an excessive temperature rise
occurs. The temperature rise is detected by a probe in the power module. Nonetheless,
derating should be applied to the nominal drive current if continuous operation above 4 kHz
is required:
• 10% derating for 8 kHz
• 20% derating for 12 kHz
• 30% derating for 16 kHz
(3)Size description
Maximum line current Apparent
power
at 200 Vat 240 V
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient
current for
60 s2 s
(2)Reference description,
(2)
example: ATV12HU15M3
ATV12: Altivar 12;
H: product on heatsink;
U15: drive power rating,
see nCU parameter page 41M3: drive voltage rating,
see UCAL parameter page 41
Free space ≥ 50 mm (2 in.) on each side, with vent cover fitted. Mounting type A is
suitable for drive operation at surrounding air temperature less than or equal to 50°C
(122°F) and 40°C (104°F) for UL.
≥ 50 mm
(2 in.)
≥ 50 mm
(2 in.)
Type B mounting
Drives mounted side-by-side, vent cover should be removed.
Type C mounting
Free space ≥ 50 mm (2 in.) on each side. Vent cover should be removed for operation at
surrounding air temperature above 50°C (122°F).
With these types of mounting, the drive can be used up to an ambient temperature of 50°C (122°F), with a switching frequency of 4 kHz.
Fanless drives need derating.
≥ 50 mm
(2 in.)
≥ 50 mm
(2 in.)
Mounting and temperature conditions
Install the unit vertically, at ± 10°.
Do not place it close to heating elements.
Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the
top of the unit.
Free space in front of unit: 10 mm (0.4 in.) minimum.
It is recommended that the drive is installed on a dissipative surface.
Removing the vent cover(s)
Mounting types
BBV28581 05/201313
Page 14
Mounting
40°C (104°F) mounting types A and C
50°C (122°F) mounting type C mounted on metal plate (1)
Switching frequency in kHz
40°C (104°F) mounting type B
60°C (140°F) mounting types A, B and C (1)
Switching frequency in kHz
ATV12HU
ppM2, ATV12H075F1, ATV12HU15M3 to ATV12HU40M3
50°C (122°F) mounting types A, B and C
60°C (140°F) mounting type C mounted on metal plate (1)
Derating curves
Derating curves for the nominal drive current (In) as a function of temperature, switching frequency and mounting type.
ATV12H0
ppM2, ATV12H0ppM3, ATV12H018F1 to ATV12H037F1
For intermediate temperatures (for example 55°C (131°F)), interpolate between 2 curves.
(1) Not UL recognized.
Bus voltage measurement procedure
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand the precautions in “Before you begin” on page 5 before performing this procedure.
Failure to follow these instructions will result in death or serious injury.
EMC mounting plate: size 1 VW3A9523, size 2 VW3A9524 or size 3 VW3A9525 to be ordered
separately
Mount the EMC mounting plate to the holes in the ATV12 using the 2 screws supplied, as shown in the drawings below.
BBV28581 05/201315
Page 16
Wiring
Recommendations
Keep the power cables separate from control circuits with low-level signals (detectors, PLCs, measuring apparatus, video, telephone).
Always cross control and power cables at 90° if possible.
Power and circuit protection
Follow wire size recommendations according to local codes and standards.
Before wiring power terminals, connect the ground terminal to the grounding screws located below the output terminals (see Access to the
motor terminals if you use ring terminals, page 21
.
The drive must be grounded in accordance with the applicable safety standards. ATV12
such the leakage current is over 3.5 mA.
When upstream protection by means of a "residual current device" is required by the installation standards, a type A circuit breaker should
be used for 1-phase drives and type B for 3-phase drives. Choose a suitable model incorporating:
• HF current filtering
• A time delay which prevents tripping caused by the load from stray capacitance on power-up. The time delay is not possible for 30 mA
devices. In this case, choose devices with immunity against accidental tripping, for example RCDs with SI type leakage current
protection.
If the installation includes several drives, provide one "residual current device" per drive.
ppppM2 drives have an internal EMC filter, and as
Control
For control and speed reference circuits, it is recommended to use shielded twisted cables with a pitch of between 25 and 50 mm (1 and
2 in.), connecting the shield to ground as outlined on page 26
.
Length of motor cables
For motor cable lengths longer than 50 m (164 ft) for shielded cables and longer than 100 m (328 ft) for unshielded cables, please use motor
chokes.
For accessory part numbers, refer to the catalog.
Equipment grounding
Ground the drive according to local and national code requirements. A minimum wire size of 10 mm² (6 AWG) may be required to meet
standards limiting leakage current.
.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The drive panel must be properly grounded before power is applied.
• Use the provided ground connecting point as shown in the figure below.
Failure to follow these instructions will result in death or serious injury.
DANGER
ATV12H075F1, ATV12H075M2 AND ATV12H075M3 - GROUND CONTINUITY HAZARD
An anodized heatsink can create an insulation barrier to the mounting surface. Ensure that you follow the recommended grounding
connections.
Failure to follow these instructions will result in death or serious injury.
• Ensure that the resistance of the ground is one ohm or less.
• When grounding several drives, you must connect each one
directly, as shown in the figure to the left.
• Do not loop the ground cables or connect them in series.
16BBV28581 05/2013
Page 17
Wiring
WARNING
RISK OF DRIVE DESTRUCTION
• The drive will be damaged if input line voltage is applied to the output terminals (U/T1,V/T2,W/T3).
• Check the power connections before energizing the drive.
• If replacing another drive, verify that all wiring connections to the drive comply with wiring instructions in this manual.
Failure to follow these instructions can result in death, serious injury or equipment damage.
WARNING
INADEQUATE OVERCURRENT PROTECTION
• Overcurrent protective devices must be properly coordinated.
• The Canadian Electrical Code and the National Electrical Code require branch circuit protection. Use the fuses recommended in the
Quick Start Annex (S1A58684) delivered with the drive.
• Do not connect the drive to a power feeder whose short-circuit capacity exceeds the drive short-circuit current rating listed in the
Quick Start Annex (S1A58684) delivered with the drive.
Failure to follow these instructions can result in death, serious injury or equipment damage.
BBV28581 05/201317
Page 18
Wiring
1-phase supply 100...120 V
3-phase supply 200...240 V
ATV12ppppF1
1-phase supply 200...240 V
ATV12
ppppM2
ATV12
ppppM3
Source
3-phase
motor
General wiring diagram
(1)R1 relay contacts, for remote indication of the drive status, see page 52
(2) Internal + 24 V c. If an external source is used (+ 30 V c maximum), connect the 0 V of the source to the COM terminal, and do not
use the + 24 V
(3) Reference potentiometer SZ1RV1202 (2.2 k
(4) Optional braking module VW3A7005
(5) Optional braking resistor VW3A7
Note:
If intermittent OSF code appear, set Relay R1 to FLt and it can be connected to upstream protection to avoid overvoltage in the
drive. In this case LO1 can be used for others drive status see page 53
c terminal on the drive.
ppp or other acceptable resistor. See the possible resistor values in the catalog.
• Use transient voltage surge suppressors for all inductive circuits near the drive or coupled to the same circuit (relays, contactors,
solenoid valves, etc.).
• The ground terminal (green screw) is located on the opposite side in comparison with its position on the ATV11 (see wiring trap label).
Ω) or similar (10 kΩ maximum).
18BBV28581 05/2013
Page 19
Wiring
Input 120 V
Output 240 V
Input 240 V
Output 240 V
Input 240 V
Output 240 V
Wiring labels
ATV12HpppF1
ATV12H
ATV12H
pppM2
pppM3
BBV28581 05/201319
Page 20
Power terminals
Wiring trap
Line supply is at the top of the drive, the motor power supply is at the bottom of the drive. The power terminals can be accessed without
opening the wiring trap if you use stripped wire cables.
Access to the power terminals
Access to the terminals if you use stripped wire cables
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Replace the wiring trap before applying power.
Failure to follow these instructions will result in death or serious injury.
CAUTION
RISK OF BODY INJURY
Use pliers to remove snap-off of the wiring trap.
Failure to follow these instructions can result in injury or equipment damage.
Access to the line supply terminals to connect ring terminals
A) IT jumper on ATV12ppppM2
B) Grounding screws located below the output terminals.
20BBV28581 05/2013
Page 21
Power terminals
Access to the motor terminals if you use ring terminals
Characteristics and functions of power terminals
TerminalFunctionFor ATV12
t
R/L1 - S/L2/NPower supply1-phase 100…120 V
R/L1 - S/L2/N1-phase 200…240 V
R/L1 - S/L2 - T/L33-phase 200…240 V
PA/++ output (dc) to the braking module DC Bus (visible part on wiring trap) All ratings
PC/–– output (dc) to the braking module DC Bus (visible part on wiring trap) All ratings
PONot used
U/T1 - V/T2 - W/T3Outputs to the motorAll ratings
Ground terminalAll ratings
BBV28581 05/201321
Page 22
Power terminals
ATV12H
Applicable wire
size (1)
Recommended
wire size (2)
Tightening
torque (3)
mm² (AWG)mm² (AWG)N·m (lb.in)
018F1
037F1
0
ppM2
0
ppM3
2 to 3.5
(14 to 12)
2
(14)
0.8 to 1
(7.1 to 8.9)
ATV12H 018F1, 037F1, 0ppM2, 0ppM3
ATV12H 075F1, U
ppM2, U15M3, U22M3
ATV12H U30M3, U40M3
(1)The value in bold corresponds to the minimum wire gauge to permit secureness.
(2)75°C (167 °F) copper cable (minimum wire size for rated use)
(3)Recommended to maximum value.
ATV12H
Applicable
wire size (1)
Recommended
wire size (2)
Tightening
torque (3)
mm² (AWG)mm² (AWG)N·m (lb.in)
075F1
U
ppM2
3.5 to 5.5
(12 to 10)
5.5
(10)
1.2 to 1.4
(10.6 to 12.4)
U15M3
U22M3
2 to 5.5
(14 to 10)
2 (14) for U15M3
3.5 (12) for U22M3
ATV12H
Applicable
wire size (1)
Recommended
wire size (2)
Tightening
torque (3)
mm² (AWG)mm² (AWG)N·m (lb.in)
U30M3
U40M3
5.5 (10)5.5 (10)
1.2 to 1.4
(10.6 to 12.4)
Arrangement of the power terminals
22BBV28581 05/2013
Page 23
Control terminals
It is possible to lock the
cover with a lead seal.
Note: To connect cables, use a
slotted screwdriver 0.6 x 3.5.
(1)The value in bold corresponds to the minimum wire gauge to permit secureness.
(2)Recommended to maximum value.
ATV12 Control terminalsApplicable wire size (1)Tightening torque (2)
mm² (AWG)N·m (lb.in)
R1A, R1B, R1C0.75 to 1.5 (18 to 16)
0.5 to 0.6 (4.4 to 5.3)
Other terminals0.14 to 1.5 (26 to 16)
Normally open (NO) contact of the relay
Normally closed (NC) contact of the relay
Common pin of the relay
COMmon of analog and logic I/Os
Analog Input
+5VDC supply provided by the drive
Analog Output
Logic Output (collector)
Common of the Logic Output (emitter)
COMmon of analog and logic I/Os
Logic Input
Logic Input
Logic Input
Logic Input
+24 VDC supply provided by the drive
Connection for SoMove software, Modbus network or remote display.
Keep the control circuits away from the power cables. For control and speed reference circuits, it is recommended to use shielded twisted
cables with a pitch of between 25 and 50 mm (1 and 2 in.), connecting the shielding as outlined on page 26
Access to the control terminals
To access the control terminals, open the cover.
Note: For information regarding HMI button functions, see "HMI description" on page 32.
.
Arrangement of the control terminals
BBV28581 05/201323
Page 24
Control terminals
Characteristics and functions of the control terminals
TerminalFunctionElectrical characteristics
R1ANO contact of the relayMin. switching capacity:
• 5 mA for 24 V
R1BNC contact of the relay
R1CCommon pin of the relay
COMCommon of analog and logic I/Os
AI1Voltage or current analog input• resolution: 10 bits
5V+5 VDC power supply for reference potentiometer• precision: ± 5%
AO1Voltage or current analog output (collector)• resolution: 8 bits
LO+Logic output• voltage: 24 V (maximum 30 V)
LO-Common of the logic output (emitter)
LI1
LI2
LI3
LI4
+24V+ 24 VDC supply provided by the drive+ 24 VDC –15% +20% protected against short-circuits and
Logic inputsProgrammable logic inputs
Maximum switching capacity:
• 2 A for 250 V
(cos ϕ = 0.4 and L/R = 7 ms)
• 3 A for 250 V
(cos ϕ = 1 and L/R = 0)
• response time: 30 ms maximum.
• precision: ± 1% at 25°C (77°F)
• linearity: ± 0.3% (of full scale)
• sampling time: 20 ms ± 1 ms
Analog voltage input 0 to +5 V or 0 to +10 V
(maximum voltage 30 V) impedance: 30 kΩ
Analog current input x to y mA, impedance: 250 Ω
• maximum current: 10 mA
• precision: ± 1% at 25°C (77°F)
• linearity: ± 0.3% (of full scale)
• refresh time: 4 ms (maximum 7 ms)
Analog voltage output: 0 to +10 V (maximum voltage +1%)
• minimum output impedance: 470 Ω
Analog current output: x to 20 mA
• maximum output impedance: 800 Ω
• impedance: 1 kΩ, maximum 10 mA (100 mA in open collector)
• linearity: ± 1%
• refresh time: 20 ms ± 1 ms.
• +24 VDC power supply (maximum 30 V)
• impedance: 3.5 kΩ minimum
• state: 0 if < 5 V, state 1 if > 11 V in positive logic
• state: 1 if < 10 V, state 0 if > 16 V or switched off (not connected)
in negative logic
• sampling time: < 20 ms ± 1 ms.
overloads.
Maximum customer current available 100 mA
c
a and for 30 V c on inductive load
a and 4 A for 30 V c on resistive load
24BBV28581 05/2013
Page 25
Control terminals
Source - using external supplySink - using external supply
Source - using internal supplySink - using internal supply
Control connection diagrams
The Logic inputs typenPL parameter page 51 is used to adapt the operation of the logic inputs to the technology of the programmable
controller outputs.
• Set the parameter to POS for Source operation.
• Set the parameter to nEG for internal Sink operation.
• Set the parameter to EnEG for external Sink operation.
Note: The modification will be taken into account only at the next control power-on.
DANGER
UNINTENDED EQUIPMENT OPERATION
• The accidental grounding of logic inputs configured for Sink Logic can result in unintended activation of drive functions.
• Protect the signal conductors against damage that could result in unintentional conductor grounding.
• Follow NFPA 79 and EN 60204 guidelines for proper control circuit grounding practices.
Failure to follow these instructions will result in death or serious injury.
BBV28581 05/201325
Page 26
Wiring
Electromagnetic Compatibility (EMC), wiring
Principle and precautions
IMPORTANT: The high frequency equipotential ground connection between the drive, motor, and cable shielding does not eliminate the
need to connect the ground (PE) conductors (green-yellow) to the appropriate terminals on each unit. To help accomplish this, the user
must follow the following points:
• Grounds between the drive, motor, and cable shielding must have high frequency equipotentiality.
• When using shielded cable for the motor, use a 4-conductor cable so that one wire will be the ground connection between the motor
and the drive. Size of the ground conductor must be selected in compliance with local and national codes. The shield can then be
grounded at both ends. Metal ducting or conduit can be used for part or all of the shielding length, provided there is no break in
continuity.
• When using shielded cable for the Dynamic Brake (DB) resistors, use a 3-conductor cable so that one wire will be the ground
connection between the DB resistor assembly and the drive. Size of the ground conductor must be selected in compliance with local
and national codes. The shield can then be grounded at both ends. Metal ducting or conduit can be used for part or all of the shielding
length, provided there is no break in continuity.
• When using shielded cable for control signals, if the cable is connecting equipment that is close together and the grounds are bonded
together, then both ends of the shield can be grounded. If the cable is connected to equipment that may have a different ground
potential, then ground the shield at one end only to prevent large currents from flowing in the shield. The shield on the ungrounded
end may be tied to ground with a capacitor (for example: 10 nF, 100V or higher) in order to provide a path for the higher frequency
noise.
• Keep the control circuits away from the power circuits. For control and speed reference circuits, use of shielded twisted cables with
a pitch of between 25...50 mm (1 and 2 in.) is recommended.
• Ensure maximum separation between the power supply cable (line supply) and the motor cable and also ensure maximum separation
between the control cables and any power cables.
• The motor cables must be at least 0.5 m (20 in.) long.
• Do not use surge arresters or power factor correction capacitors on the variable speed drive output.
• If using an additional input filter, it should be mounted as closed as possible to the drive and connected directly to the line supply via
an unshielded cable. Link 1 on the drive is via the filter output cable.
• For installation of the optional EMC plate and instructions for meeting IEC 61800-3 standard, refer to the section entitled “Installing
the EMC plates” and the instructions provided with the EMC plates.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Do not expose cable shielding except where connected to ground at the metal cable glands and underneath the grounding clamps.
• Ensure that there is no risk of the shielding coming into contact with live components.
Failure to follow these instructions will result in death or serious injury.
26BBV28581 05/2013
Page 27
Wiring
1. Non-shielded wires for the output of the status relay contacts.
2. Sheet steel grounded casing not supplied with the drive, to be mounted as indicated on the diagram.
3. PA and PC terminals, to the braking module DC bus
4. Shielded cable for connecting the control/signalling wiring.
For applications requiring several conductors, use small cross-sections (0.5 mm
2
, 20 AWG).
The shielding must be connected to ground at both ends. The shielding must be continuous and intermediate terminals must be in EMC
shielded metal boxes.
5. Shielded cable for motor connection with shielding connected to ground at both ends.
This shielding must be continuous, and if there are any intermediate terminals, they must be in an EMC shielded metal box. The motor
cable PE grounding conductor (green-yellow) must be connected to the grounded casing.
6. Grounding conductor, cross-section 10 mm²
(6 AWG) according to IEC 61800-5-1 standard.
7. Power input (non-shielded cable)
Attach and ground the shielding of cables 4 and 5 as close as possible to the drive:
• Expose the shielding.
• Use cable clamps of an appropriate size on the parts from which the shielding has been exposed, to attach them to the casing.
The shielding must be clamped tightly enough to the metal plate to ensure correct contact.
• Types of clamp: stainless steel (delivered with the optional EMC plate).
Installation diagram (example)
BBV28581 05/201327
Page 28
Wiring
Normal
(filter connected)
IT system
(filter disconnected)
EMC conditions for ATV12ppppM2
C1 EMC category is reached if length of shielded cable is 5 m (16.4 ft) maximum and Switching frequencySFr page 59 is 4, 8 or 12 kHz.
C2 EMC category is reached if length of shielded cable is 10 m (32.8 ft) maximum and Switching frequencySFr is 4, 8 or 12 kHz and if
length of shielded cable is 5 m (16.4 ft) maximum for all other values of Switching frequencySFr.
Internal EMC filter on ATV12ppppM2
All ATV12ppppM2 drives have a built-in EMC filter. As a result they exhibit leakage current to ground. If the leakage current creates
compatibility problems with your installation (residual current device or other), then you can reduce the leakage current by opening the IT
jumper as shown below. In this configuration EMC compliance is not guaranteed.
NOTICE
DRIVE LIFETIME REDUCTION
On ATV12ppppM2 ratings, if the filters are disconnected, the drive’s switching frequency must not exceed 4 kHz. Refer to Switching
frequencySFr page 59
Failure to follow these instructions can result in equipment damage.
for adjustment,
28BBV28581 05/2013
Page 29
Check list
Read carefully the safety information in the user manual and the catalog. Before starting up the drive, please check the following points
regarding mechanical and electrical installations, then use and run the drive.
For complete documentation, refer to www.schneider-electric.com.
1. Mechanical installation
• Refer to the Mounting and temperature conditions instructions on page 13 for drive mounting types and recommendations on the
ambient temperature.
• Mount the drive vertically as specified, see Mounting and temperature conditions instructions on page 13
• The use of the drive must be in agreement with the environments defined by the standard 60721-3-3 and according to the levels
defined in the catalog.
• Mount the options required for your application, refer to the catalog.
.
2. Electrical installation
• Connect the drive to the ground, see Equipment grounding on page 16.
• Ensure that the input power voltage corresponds to the drive nominal voltage and connect the line supply as shown in General wiring
diagram on page 18
• Ensure you use appropriate input power fuses and circuit breaker, see in the Annex (S1A58684) delivered with the drive.
• Wire the control terminals as required, see Control terminals on page 23
to the EMC compatibility rules on page 26
• The ATV12ppppM2 range integrates an EMC filter. The leakage current can be reduced using the IT jumper as explained in the
paragraph Internal EMC filter on ATV12ppppM2 on page 28
• Ensure that motor connections correspond to the voltage (star, delta).
.
. Separate the power cable and the control cable according
.
.
3. Use and run the drive
• Start the drive and you will see Standard motor frequencybFr page 45 at the first power-on. Check that the frequency defined by
the frequency bFr (the factory setting is 50 Hz) is in accordance with the frequency of the motor, see First power-up on page 34
For the following power-on, you will see rdY on the HMI.
.
• MyMenu (upper part of CONF mode) allows you to configure the drive for most applications (see page 45
• Factory / recall customer parameter setFCS function page 46
allows you to reset the drive with factory settings.
).
BBV28581 05/201329
Page 30
Factory configuration
ATV12ppppM3
3-phase
motor
Source
Drive factory settings
The Altivar 12 is factory-set for the most common operating conditions (motor rating according to drive rating):
• Display: drive ready (rdY) motor stopped or motor frequency reference while running
• Automatic adaptation of the deceleration ramp in the event of overvoltage on braking.
• No automatic restarting after a detected fault is cleared
• Logic inputs:
- LI1: forward (2-wire transitional control)
- LI2, LI3, LI4: no assignment
• Logic output: LO1: no assignment
• Analog input: AI1 (0 to + 5 V) speed reference
• Relay R1: the contact opens in the event of a detected fault (or drive off)
• Analog output AO1: no assignment
CodeDescriptionValue
bFrStandard motor frequency50 Hz
UnSRated motor voltage230 V
ACCAcceleration3 seconds
dECDeceleration3 seconds
LSPLow speed0 Hz
HSPHigh speed50 Hz
CttMotor control typeStandard U/F law
UFrIR compensation (law U/F)100%
IthMotor thermal currentequal to nominal motor current (value determined by drive rating)
SdC1Automatic DC injection current0.7 x nominal drive current, for 0.5 seconds.
SFrSwitching frequency4 kHz
If the above values are compatible with the application, the drive can be used without changing the settings.
Drive factory wiring diagram
R/L1
S/L2
(1)(3)
R1A
T/L3
R1B
ac
R1C
COM
b
AI1
+5V
AO1
page
45
57
64
64
45
89
90
57
58
94
67
59
(1) R1 relay contacts, for remote indication of the drive status.
(2) Internal + 24 V
use the + 24 V
(3) Reference potentiometer SZ1RV1202 (2.2 k
(4) Forward
30BBV28581 05/2013
LI3
LI4
(2)
+24 V
(4)
LO-
COM
LI1
LI2
U/T1
V/T2
PA / +
PC / -
U1
c. If an external source is used (+ 30 V c maximum), connect the 0 V of the source to the COM terminal, and do not
c terminal on the drive.
W/T3
V1
W1
M
3 a
Ω) or similar (10 kΩ maximum).
LO+
Page 31
Basic functions
Status relay, unlocking
The R1 status relay is energized when the drive power is applied with no fault detected. It de-energizes in the event of a detected fault or
when the drive power is removed.
The drive is reset after a detected fault:
• by switching off the drive until the display disappears completely, then switching on again
• automatically in the cases described in the "automatic restart" function, FLt- menu, Automatic restart Atr page 91
• via a logic input when this input is assigned to the "drive reset" function, FLt- menu, Detected fault reset assignmentrSF page
91
set to LpH.
Drive thermal detection
Thermal detection is provided by a built-in PTC probe in the power module.
Drive ventilation
Ratings up to 0.75 kW (1 HP) do not include a fan. The fan runs only when the drive thermal state requires ventilation.
Motor thermal detection
Function:
Thermal detection by calculating the I2t.
set to YES
Note: The motor thermal state memory returns to zero when the drive power is cycled if Motor thermal state memoMtM page 94
is not set to YES.
NOTICE
RISK OF DAMAGE TO THE MOTOR
The use of external overload protection is required under the following conditions:
• Repowering up the product since there is no motor thermal state memory.
• Running multiple motors
• Running motors rated at less than 20% of the nominal drive current
• Using motor switching
Failure to follow these instructions can result in equipment damage.
NOTICE
MOTOR OVERHEATING
• This drive does not provide direct thermal protection for the motor.
• Use of a thermal sensor in the motor may be required for protection at all speeds or loading conditions.
• Consult the motor manufacturer for the thermal capability of the motor when operated over the desired speed range
Failure to follow these instructions can result in equipment damage.
BBV28581 05/201331
Page 32
Programming
5 is displayed for "0.5"0.
HMI description
Functions of the display and keys
1. Value LED (a) (b).
2. Charge LED
3. Unit LED (c)
4. ESC button: Exits a menu or parameter, or aborts the displayed
value to return to the previous value in the memory. In LOCAL
configuration, 2 s press on ESC button switches between the
control/programming modes.
5. STOP button: stops the motor (could be hidden by door if function
disabled). Note:See instructions for "RUN/STOP" cover
removal.
6. RUN button: Starts running in LOCAL configuration and in
REMOTE configuration if the function is configured (could be
hidden by door if function disabled).
7. Jog dial
- Acts as a potentiometer in LOCAL configuration and in
REMOTE configuration if the function is configured.
- For navigation when turned clockwise or counterclockwise
- and selection / validation when pushed.
This action is represented by this symbol
8. MODE button
Switches between the control/programming modes. 3s press on
MODE button switches between the REMOTE/LOCAL
configurations.
The MODE button is only accessible with the HMI door open.
9. CONFIGURATION mode LED (b)
10. MONITORING mode LED
11. REFERENCE mode LED
12. 4 x 7-segment displays
Note: In LOCAL configuration, the three Leds 9, 10, 11 are blinking
simultaneously in programming mode and are working as a Led
chaser in control mode.
(a) If illuminated, indicates that a value is displayed, for example,
(b)When changing a value the Configuration mode LED and the value LED are on steady.
(c) If illuminated, indicates that a unit is displayed, for example, AMP is displayed for "Amps"
32BBV28581 05/2013
Page 33
Programming
Remote control
Remote operation and programming by HMI is possible using the optional remote HMI part VW3A1006. The dimensions are 70 mm
(2.76 in) x 50 mm (2.76 in).
Note: when connected, the remote control shows an exact copy of the drive display, it is totally interactive with the embedded keypad.
Note: Set the remote keypad with
- Modbus rate = 19.2 Kbps, (see tbr)
- Modbus format = 8E1, 8 bit, even parity, 1 stop bit (see tFO)
BBV28581 05/201333
Page 34
Programming
COnFMOn
rEF
LOC
35.
rdY
rEN
3s
MODE
3s
MODE
2s
ESC
rdY
ESCENT
ESCESC
ESC
[SPEED REFERENCE][MONITORING][CONFIGURATION]
MODEMODEMODE
[REMOTE configuration]
[LOCAL configuration]
[Analog input virtual
(Hz)]
First power-up
At first power-up you are prompted to set Standard motor frequencybFr page 45. Next time power is applied rdY appears. Operating
mode selection is then possible using the MODE key as detailed below.
Menus structure
Access to menus and parameters is possible through 3 modes: Reference rEF page 37, Monitoring MOn page 38 and Configuration
COnF page 44
the MODE key moves from the current position to the top of the branch. A second press switches to the next mode.
. Switching between these modes is possible at any time using the MODE key or Jog Dial on keyboard. The first press on
Menu customization using SoMove
ATV12 factory settings enable drive operation with most applications. You can use SoMove software to customize the "MyMenu" and FULL
menus of COnF mode (see page 44
configuration has been adjusted, it can be downloaded to the ATV12 by connecting the drive to the computer or by downloading the
configuration through the multiloader or simpleloader.
SoMove can be used to operate the drive for testing and commissioning.
), by selecting which menus and parameters will be hidden or accessible for the user. Once the
DescriptionReferences
SoMoveUSB/RJ45 cableTCSMCNAM3M002P
Simple-loader toolVW3A8120
Multi-loader toolVW3A8121
Bluetooth adapterVW3A8114
For further information, please consult the SoMove help.
34BBV28581 05/2013
Page 35
Structure of parameter tables
3
4
1
5
8
2
7
6
9
10
1. Name of mode
2. Name of section, if any
3. Menu code on 4-digit display, followed by a "-"
4. Submenu code on 4-digit display, if any
5. Parameter code
6. Value code
7. Name of menu
8. Name of submenu
9. Parameter description
10. Possible value(s) / state of parameter, if any.
The modes, sections, menus, submenus and parameter tables description is organized as below.
Note: Parameters containing the sign
Example:
T in the code column can be modified with the drive running or stopped
The function indicated by the arrow has priority over the other.
Priority function (function which can be active at the same time)
)
PI regulator (page 72
Preset speed (page 70)
Preset speed (page 70)
)
Auto DC injection (page 67
)
Catch on the fly (page 92
)
Fast stop (page 66
)
Freewheel (page 66
)
Jog operation (page 68
A
PI regulator (page 72
Jog operation (page 68
Auto DC injection (page 67
Catch on the fly (page 92
Fast stop (page 66
Freewheel (page 66
Stop functions have priority over run commands.
Speed references via logic command have priority over analog references.
)
)
)
)
)
)
Xp
p
X
A
XAX
A
X
A
36BBV28581 05/2013
Page 37
Reference Mode rEF
Use the reference mode to monitor and if local control is enabled (Reference channel 1Fr1 page 45 set to AIU1) adjust the actual
reference value by rotating the jog dial.
When local control is enabled, the jog dial on the HMI acts as a potentiometer to change the reference value up and down within the limits
preset by other parameters (LSP or HSP). There is no need to press the ENT key to confirm the change of the reference.
If local command mode is disabled, using Command channel 1Cd1 page 63
will be "read only" and cannot be modified by the jog dial (the reference is no longer given by the jog dial but from an AI or other source).
The actual reference displayed depends on the choice made in Reference channel 1Fr1 page 62
Organization tree
, only reference values and units are displayed. The value
.
(1) Depending on the active reference channel
Possible values:
LFr
AIU1
FrH
rPI
rPC
(2) 2s or ESC
Displayed parameter value and unit of the
diagram is given as examples
Code
LFr
T
(1)
Name/DescriptionAdjustment
M External reference value
Frequency reference visible if reference channel active is remote display.
Reference channel 1 Fr1 page 62
or Forced local referenceFLOC page 63
This parameter allows to modify the frequency reference with the jog dial.
Visibility depends on the drive settings.
Value - Unit
Factory
range
–400 to +400 Hz-
set to LCC
set to LCC.
settings
AIU1
T
(1)
FrH
AI1
LCC
Mdb
AIUI
rPI
T
(1)
rPC
(1) It is not necessary to press the ENT key to confirm the modification of the reference.
T
Parameter that can be modified during operation or when stopped.
M Analog input virtual
This parameter allows to modify the frequency reference with an analog input.
Reference channel 1 Fr1 page 62
or Forced local referenceFLOC page 63
or PID manual referencePIM page 74
Visibility depends on the drive settings.
M Speed reference
Actual frequency reference. This parameter is in read-only mode. Visibility depends on the drive settings.
v Terminal
v Remote display
v Modbus
v Integrated display with Jog dial
M Internal PID reference
This parameter allows to modify the PID internal reference with the jog dial.
Visibility depends on the drive settings.
M PID reference value
This parameter is the PID reference expressed as a %.
set to AIU1
set to AIU1
set to AIU1.
0 to 100 % of HSP -
0 Hz to HSP-
0 to 100%-
0 to 100%-
BBV28581 05/201337
Page 38
Monitoring mode MOn
values
units
When the drive is running, the value displayed is that of one of the monitoring parameters. The default value displayed is the motor Output
frequencyrFr page 39
While the value of the desired new monitoring parameter is being displayed, press a second time on the jog dial button to display the units.
Organization tree
.
(1) Depending on reference channel active.
Possible values:
LFr
AIU1
Displayed parameter values and units of the diagram are given as
examples.
(2) 2 sec or ESC
38BBV28581 05/2013
Page 39
Monitoring mode MOn
Code
LFr
T
AIU1
T
FrH
rFr
LCr
rPE
rPF
rPC
ULn
Name/DescriptionUnit
M External reference value
External keypad or local force mode configured. Forced local referenceFLOC page 63 set to LCC and
Forced local assignmentFLO page 63
Displays the speed reference coming from the remote keypad. This value is not visible in factory setting.
M Analog input virtual
Embedded keypad active or local force mode configured, Forced local referenceFLOC page 63 set to
AIU1 and Forced local assignmentFLO page 63
Displays the speed reference coming from the jog dial. This value is not visible in factory setting.
M Speed reference
Actual frequency reference.
M Output frequency
This function provides the estimated motor speed. It corresponds to the estimated motor frequency (on the
motor shaft). In Standard law Std page 57
In Performance law PErF page 57
motor speed.
Range: –400 to 400 Hz
M Motor current
Estimation of the effective motor current from phase current measurements with an accuracy of 5%.
During DC injection, the current displayed is the maximum value of current injected in the motor.
M PID error
Visible only if the PID function is configured (PID feedback assignmentPIF page 72 set to nO).
See PID diagram on page 71
M PID Feedback
Visible only if PID function configured (PID feedback assignmentPIF page 72 set to nO). See
PID diagram on page 71
M PID reference
Visible only if PID function configured (PID feedback assignmentPIF page 72 set to nO). See
PID diagram on page 71
M Main voltage
Line voltage from the point of view of the DC bus, motor running or stopped.
different to nO.
different to nO.
, the Output frequencyrFr is equal to stator frequency.
, the Output frequency rFr motor speed is equal to the estimated
Hz
%
Hz
Hz
A
%
%
%
V
tHr
tHd
Opr
T
BBV28581 05/201339
Parameter that can be modified during operation or when stopped.
M Motor thermal state
Display of the motor thermal state. Above 118%, the drive trips in Motor overloadOLF page 110.
M Drive thermal state
Display of the drive thermal state. Above 118%, the drive trips in Drive overheatOHF page 110.
M Output power
This parameter displays the motor power (on the shaft) that is estimated by the drive.
%
%
%
Page 40
Monitoring mode MOn
Code
StAt
rdY
rUn
ACC
dEc
dCb
CLI
nSt
Obr
CtL
tUn
FSt
nLP
FrF
rEM
LOC
Name/Description
M Product status
This parameter shows the state of the drive and motor.
v Drive ready
v Drive running, the last 6 segments to the right of the code also indicate direction and speed.
v Acceleration, the last 6 segments to the right of the code also indicate direction and speed.
v Deceleration, the last 6 segments to the right of the code also indicate direction and speed.
v DC injection braking in progress
v Current limit, the 4 segments located on right down of display are blinking.
v Freewheel stop control
v Auto-adapted deceleration
v Controlled stop on mains phase loss
v Auto-tuning in progress
v Fast stop
v No line power. When the control part is energized via the RJ45 connector and there is no power on the
main input and no run order is present.
v Drive is running and using the withdrawal reference LFF
v Remote configuration
v Local configuration
40BBV28581 05/2013
Page 41
Monitoring mode MOn
State 1
State 0
LI1 LI2 LI3 LI4
State 1
State 0
r1 LO1
Code
MAI-
LIS1
LOS1
HSU
nCU
UCAL
SPn
C1SU
C2SU
Name/DescriptionUnit
Maintenance menu
Parameters of MAI menu cannot be selected for monitoring
M State of logic inputs LI1 to LI4
Can be used to visualize the state of the 4 logic inputs LI.
Example above: LI1 and LI3 are at 1; LI2 and LI4 are at 0.
M State of the logic output LO1 and relay R1
Can be used to visualize the state of the LO.
M Display of high speed value
Display of high-speed value. Range Low speedLSP page 45 to Maximum frequencytFr page 57.
Visible only if 2 HSP assignmentSH2 or 4 HSP assignmentSH4 page 90
M Drive Power rating
Indicates the drive rating. This value is part of the drive reference, see page 11. Possible values:
018 = 0.18 kW (0.25 HP)
037 = 0.37 kW (0.50 HP)
055 = 0.55 kW (0.75 HP)
075 = 0.75 kW (1 HP)
U15 = 1.5 kW (2 HP)
U22 = 2.2 kW (3 HP)
U30 = 3 kW (3 HP)
U40 = 4 kW (5 HP)
M Drive voltage rating
Drive rate supply voltage. This value is part of the drive reference, see page 11. Possible values:
F1 = 100-120 V 1-phase in, 200-240 V 3-phase out
M2 = 200-240 V 1-phase in, 200-240 V 3-phase out
M3 = 200-240 V 3-phase in, 200-240 V 3-phase out
M Specific Product Number
This parameter is used in order to identify the possible specification of the product.
Visible only if SPn is different to zero.
Motor software version.
Example: 1105 for 1.1 ie 05.
1 (version, major). 1 (version, minor). 05 (ie, evolution number)
is configured.
-
-
Hz
-
-
-
-
-
BBV28581 05/201341
Page 42
Monitoring mode MOn
Code
MAI-
rtHI
PtH
FtH
PEt
T
Name/DescriptionUnit
Maintenance menu (continued)
M Run elapsed time display
Total time the motor has been powered up. Range: 0 to 65535 hours. Value displayed is as described in the
table below. Parameter resettable by services
HoursDisplay
10.01
100.10
1001.00
100010.0
10000100
M Power On time display
Total time the drive has been powered on. Range: 0 to 65535 hours. Value displayed is as described in
the table above. Parameter resettable by services.
M Fan time display
Range: 0 to 65535 hours. Value displayed is as described in the table above. Parameter resettable by
customer.
M Process elapsed time
Range: 0 to 65535 hours. Value displayed is as described in the table above. Parameter resettable by
customer.
0.01
0.01
0.01
0.01
COM1
r0t0
rOt1
r1t0
r1t1
dP1
EP1
M Modbus communication status
v Modbus no reception, no transmission = communication idle
v Modbus no reception, transmission
v Modbus reception, no transmission
v Modbus reception and transmission
M Last detected fault 1
This parameter describes the last detected fault.
M State of drive at detected fault 1
This parameter describes the state at the moment of the first detected fault.
bit 0bit 1bit 2bit 3bit 4
ETA.1: Switched
on
bit 5bit 6bit 7bit 8bit 9
ETI.4: Run order
present
bit 10bit 11bit 12bit 13 - 14bit 15
ETI.10: Product in
deceleration
ETA.5:
Quick stop
ETI.5:
DC injection
running
ETI.11: Current
limitation or torque
limitation is
running
ETA.6:
Switch on
disabled
ETI.7:
Motor thermal
threshold reached
Fast stop in
progress
Forced local
enabled
ETI.8: ReservedETI.9:
ETI.14= 0 + ETI.13=0:
Drive controlled by terminal or local
ETI.14= 0 + ETI.13=1:
Drive controlled by remote keypad
ETI.14= 1 + ETI.13=0:
Drive controlled by Modbus
ETI.14= 1 + ETI.13=0: Reserved
Motor rotation in forward direction
(or stopped)
Product in
acceleration
keypad
-
-
-
ETA.15:
ETI.15:
Reverse
direction
applied to the
ramp
T
42BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
Page 43
Monitoring mode MOn
Code
MAI-
dP2
EP2
dP3
EP3
dP4
EP4
COd
Name/DescriptionAdjustment range Factory setting
Maintenance menu (continued)
M Last detected fault 2
This parameter describes the second detected fault.
M State of drive at detected fault 2
This parameter describes the state at the moment of the second detected fault. See EP1.
M Last detected fault 3
This parameter describes the third detected fault.
M State of drive at detected fault 3
This parameter describes the state at the moment of the third detected fault. See EP1
M Last detected fault 4
This parameter describes the fourth detected fault.
M State of drive at detected fault 4
This parameter describes the state at the moment of the fourth detected fault. See EP1
2 to 9999OFF
OFF
On
M HMI Password
Possible state value:
v Code disabled
v Code activated
-
-
-
-
-
-
Range 2 to 9999
If you have lost your code, please contact Schneider Electric.
This parameter is used to restrict access to the drive.
To lock the drive, go to the HMI PasswordCOd parameter, enter a code within the above range.
Once activated, the code state changes to On:
The protection enables only access to rEF(see page 37
using SoMove. Return to factory settings or access to FULL section are disabled,
Download configuration from SoMove is possible,
Upload configuration to SoMove is disabled.
To unlock the drive, go to the COd parameter, enter the valid code, then press ENT.
Code protection removal is then possible and carried out by entering OFF using the jog dial, then press
ENT.
) and MOn (see page 38) modes, except when
BBV28581 05/201343
Page 44
Configuration Mode ConF
Configuration mode includes 3 parts:
1. MyMenu includes 11 factory set parameters (among them 9 visible by default). Up to 25 parameters are available for user customization
using SoMove software.
2. store/recall parameter set: these 2 functions are used to store and recall customer settings.
3. FULL: This menu provides access to all other parameters. It includes 6 submenus:
- Macro-configurationCFG- page 47
- Input Output menuI_O- page 48
- Motor control menudrC- page 58
- Control menuCtL- page 62
- Function menuFUn- page 64
- Fault detection management menuFLt- page 91
- Communication menuCOM-page 98.
Organization tree
Motor frequency
Reference channel1
Acceleration
Deceleration
Low speed
High speed
Motor rated power
Motor rated current
AI1 type
Store customer parameter set
Factory / recallcustomer parameter set
FULL
Displayed parameter values are given as examples only
(1) Depending on reference channel
active.
Possible values: LFr or AIU1
44BBV28581 05/2013
(2) 2 seconds or ESC.(3) plus 14 other customizable parameters selectable (in "FULL" list)
using SoMove.
Page 45
Configuration Mode - MyMenu
Code
LFr
T
AIU1
T
bFr
Fr1
AI1
LCC
Mdb
AIUI
Name/DescriptionAdjustment rangeFactory setting
–400 Hz to 400 Hz-
set to LCC and
0% to 100%-
50 Hz
AI1
50
60
M External reference value
This parameter allows to modify the frequency reference with the jog dial.
External keypad or local force mode configured. Forced local referenceFLOC page 63
Forced local assignmentFLO page 63
M Analog input virtual
This parameter allows to modify the frequency reference when
• Forced local referenceFLOC page 63
•and Forced local assignmentFLO page 63
Visible if reference channel active is integrated display (Reference channel 1 Fr1 set to AIU1).
M Standard motor frequency
External keypad or local force mode configured (FLOC = LCC) (not visible in the factory setting).
v 50 Hz
v 60 Hz
Set to 50 Hz or 60 Hz, taken from the motor rating plate. Changing bFr sets back parameters:
FrS, Ftd and HSP: 50 Hz or 60 Hz
itH is set to nCr
nCr according to drive rating
nPr Watt or HP
nSP according to drive rating
tFr 60 Hz or 72 Hz
M Reference channel 1
This parameter allows selection of the reference source.
different to nO. Visibility depends on the drive settings.
is set to AIU1
is different to nO.
v Terminal
v Remote display
v Modbus
v Integrated display with Jog dial
ACC
T
dEC
T
LSP
T
HSP
T
M Acceleration
Acceleration time between 0 Hz and the Rated motor frequencyFrS page 57.
Make sure that this value is compatible with the inertia being driven.
M Deceleration
Time to decelerate from the Rated motor frequencyFrS page 57 to 0 Hz.
Make sure that this value is compatible with the inertia being driven.
M Low speed
Motor frequency at minimum reference
If HSP, HSP2, HSP3 and HSP4 are already set then LSP is limited to the minimum of those
values.
M High speed
Motor frequency at maximum reference.
Check that this setting is appropriate for the motor and the application. The values of HSP, HSP2,
HSP3 and HSP4 are independent but each HSP value is linked to the values of Low speed LSP
and Maximum frequencytFr page 57
• HSPx is limited to LSP and tFr (LSP y HSPx y tFr).
•If tFr is decreased below the current HSPx value, then HSPx automatically decreases to the new
value of tFr.
• Once HSP, HSP2, HSP3 and HSP4 are set, LSP is limited to their minimum.
0.0 s to 999.9 s3.0 s
0.0 s to 999.9 s3.0 s
0 Hz to HSP0 Hz
LSP to tFr (Hz)50 or 60 Hz
according to BFr,
max TFr
according to the following rules:
T
BBV28581 05/201345
Parameter that can be modified during operation or when stopped.
Page 46
Configuration Mode - MyMenu
2 s
2 s
2 s
Code
nPr
SCS
Str1
FCS
rEC1
InI1
nO
nO
InI
Name/DescriptionAdjustment rangeFactory setting
M Rated Motor Power
Visible only if Motor parameter choiceMPC page 60 is set to nPr. If nPr is available CoS disappears.
Rated motor power given on the nameplate. Motors can range from 5 ratings lower up to 2 ratings higher
than the drive rating.. Performance is optimized when there is a maximum of one rating difference.
If Standard motor frequencybFr page 45
otherwise it will be HP.
M Store customer parameter set
This function creates a backup of the present configuration:
NCV –5 to
NCV +2
is set to 50Hz, the Rated motor power nPr unit will be kW,
According to drive
rating
nO
v Function inactive
v Saves the current configuration in the drive memory. SCS automatically switches to nO as soon as the
save has been performed.
When a drive leaves the factory, the current configuration and the backup configuration are both
initialized with the factory configuration.
M Factory / recall customer parameter set
This function permits to restore a configuration.
nO
v Function inactive.
FCS automatically changes to nO as soon as one of the following actions has been performed.
v The current configuration becomes identical to the backup configuration previously saved by SCS.
FCS automatically changes to nO
if the backup has been carried out. If this value appears, InI1 is not visible.
as soon as this action has been performed. rEC1 is only visible
v The current configuration becomes identical to the factory setting. If this value appears, InI1 is not
visible.
v The current configuration becomes identical to the backup configuration previously defined by SoMove
software. If this value appears, Ini and rEC1 are not visible.
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the current configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
How to control the drive locally
In factory settings "RUN" and the jog dial are inactive. To control the drive locally, adjust the following parameter:
set Reference channel 1 Fr1 page 45
LI assignment information
It is possible with ATV12 to use multi assignment function (ie: AC2 and rrS on the same LI).
It is also possible on some functions to assign LIH (high) or LIl (low), which means that the assigned function will be activated to high (LIH)
or low level (LIl) of LI.
Check that the selected macro configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
Macro configuration provides a shortcut to configure a set of parameters suited to a specific field of
application.
3 macro configurations are available:
v Start/stop. Only forward is assigned
v PID regulation. Activate PID function, dedicated AI1 for feedback and AIV1 for reference.
v Speed. Allocate LI to preset speed (same allocation as ATV11) which provides a means of speeding up
the configuration of functions for a specific field of application.
Selecting a macro configuration assigns the parameters in this macro configuration.
Each macro configuration can still be modified in the other menus.
BBV28581 05/201347
To change the assignment of this parameter press the “ENT” key for 2 s.
Page 48
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s
Code
I_O-
tCC
Name/DescriptionAdjustment rangeFactory setting
Input Output menu
2C
2C
3C
M Type of control
v 2-wire control (see page 51)
The open or closed state of the input controls the running or stopping.
Example of "source" wiring:
LI1: forward
LIx: reverse
v 3-wire control (see page 51)
"forward" or "reverse" pulse is sufficient to command starting, a "stop" pulse is sufficient to command
stopping
Example of "source" wiring:
LI1: stop
LI2: forward
LIx: reverse
DANGER
UNINTENDED EQUIPMENT OPERATION
When this parameter is changed, 2 wire type controltCt page 51 and all the assignments involving the logic
inputs will revert to their default values.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
48BBV28581 05/2013
Page 49
I-O-
drC-
CtL-
FUN-
FLt-
COM-
t
Reverse (1)
Forward
Forward
Forward
Reverse (1)
2-Wire with transient detection
2-Wire without transient detection
transient detection forward priority
Drive powered and ready
t
Reverse (1)
Forward
Reverse (1)
(1) Reverse is not factory assigned. See Reverse directionrrS page 66
.
Forward and Reverse realized in same time provides motor starting in Forward direction.
t
t
t
Speed
LI
LI
Speed
Speed
Drive
ready to start
2-Wire without transient detection
Configuration Mode - Complete menu (FULL)
2 wire control diagrams (see page 51)
BBV28581 05/201349
Page 50
I-O-
drC-
CtL-
FUN-
FLt-
COM-
F: motor frequency
LI Run Enable
LI Forward
t
t
t
Reference
Drive ready to respond to commands
t
LI Reverse
Configuration Mode - Complete menu (FULL)
3-wire control diagram (see page 51)
50BBV28581 05/2013
Page 51
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
I_O-
tCt
nPL
LEL
trn
PFO
POS
nEG
EnEG
Name/DescriptionAdjustment rangeFactory setting
Input Output menu (continued)
M 2 wire type control
trn
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the 2 wire type control is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
2-wire type control parameter can only be accessed if Type of controltCC page 48 is set to 2C.
v Level: State 0 or 1 is taken into account for run or stop.
v Transition: A change of state (transition or edge) is necessary to initiate operation, to help prevent
accidental restarts after a power supply interruption.
v Priority FW: State 0 or 1 is taken into account for run or stop, but the "forward" input takes priority over
the "reverse" input.
M Logic inputs type
v Positive: the inputs are active (state 1) at a voltage equal to or higher than 11 V (for example +24 V
terminal). They are inactive (state 0) when the drive is disconnected or at a voltage lower than 5 V.
v Negative using internal supply: the inputs are active (state 1) at a voltage lower than 10 V (for example
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V or when the drive is
disconnected.
v Negative using external supply: the inputs are active (state 1) at a voltage lower than 10 V (for example
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V.
POS
Note: The modification will be taken into account only at the next control power-on.
See Control connection diagrams, page 25.
BBV28581 05/201351
Page 52
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
I_O-
AI1-
AI1t
CrL1
CrH1
I_O-
r1
5U
10U
0A
nO
FLt
rUn
FtA
FLA
CtA
SrA
tSA
ULA
OLA
AP1
Name/DescriptionAdjustment rangeFactory setting
Input Output menu (continued)
AI1 configuration menu
M AI1 type
This function makes interface from the analog input signal to a drive internal value.
v Voltage: 0-5 Vdc
v Voltage: 0-10 Vdc
v Current: x-y mA. Range determined by the AI1 current scaling parameter of 0%CrL1 and AI1 current
scaling parameter of 100%CrH1 settings below, see page 52
M AI1 current scaling parameter of 0%
Visible only if AI1 typeAI1t is set to 0A
M AI1 current scaling parameter of 100%
Visible only if AI1 typeAI1t is set to 0A
.
0 to 20 mA4 mA
0 to 20 mA20 mA
5U
Input Output menu (continued)
M R1 assignment
v Not assigned
v No error detected
v Drive run
v Frequency threshold reached
v HSP reached
v I threshold reached
v Frequency reference reached
v Motor thermal reached
v Underload alarm
v Overload alarm
v AI1 Al. 4-20 - Visible only if AI1t is set to 0A (see above)
FLt
Note: Relay R1 can be assigned to upstream protection to avoid overvoltage in the drive:
• Connect fault relay R1 to the contactor, see schematic page 18
• Use Relay R1 (R1 assignmentr1 ) with protection.
•Use LO1 assignment LO1 (page 53
) for remote indication of the drive status.
.
52BBV28581 05/2013
Page 53
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
I_O-
LO1-
LO1
LO1S
nO
FLt
rUn
FtA
FLA
CtA
SrA
tSA
ULA
OLA
AP1
Name/DescriptionAdjustment rangeFactory setting
Input Output menu (continued)
LO1 Configuration menu (LO1-)
M LO1 assignment
Allows to adapt the logic output to the application need.
v Not assigned
v No error detected
v Drive run
v Frequency threshold reached
v HSP reached
v I threshold reached
v Frequency reference reached
v Motor thermal reached
v Underload alarm
v Overload alarm
v AI1 Al. 4-20 - Visible only if AI1t is set to 0A (see above)
When MdE = YES, output LO1 is forced to PMP (See page 78
M LO1 status (output active level)
).
nO
POS
WARNING
LOSS OF CONTROL
When LO1S = nEG and LO1 is set to FLt, The output will be active when the drive will detect a fault.
The drive status will not be detected if the wiring is damaged for any reason.
Do not select "nEG" unless you are sure that your signal will be present in any case.
T
Failure to follow these instructions can result in death, serious injury, or equipment damage.
POS
nEG
Parameter that can be modified during operation or when stopped.
v Positive: high activation level
v Negative: low activation level
BBV28581 05/201353
Page 54
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
LOC
Motor current
LOC –10%
Drive stop
on OLC detected fault
tOL
< tOL
(hysteresis)
t
Code
I_O-
tOL
LOC
T
Name/DescriptionAdjustment rangeFactory setting
Input Output menu (continued)
M Application Overload time delay
This function can be used to stop the motor in the event of an application overload. This is not a motor or
drive thermal overload. If the motor current exceeds the Application Overload thresholdLOC, an
Application Overload time delaytOL is activated. Once this time delay tOL has elapsed, if the current
is still greater than the overload threshold LOC –10%, the drive will stop running and display OLC
Process overload.
Overload detection is only active when the system is in steady state (speed reference reached).
A value of 0 will disable application overload detection.
M Application Overload threshold
Visible only if Application Overload time delaytOL above is not set to 0.
This parameter is used to detect an "application overload". LOC can be adjusted between 70 and 150%
of the nominal drive current. This is not a motor or drive thermal overload.
0 to 100 s0 s
70 to 150% of nCr90% of of nCr
FtO
T
T
M Time delay before automatic start for the
overload fault
If Atr = YES the drive restarts automatically after an overload fault OLC once this time delay has elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of Maximum restart timetAr page 91
exceed that of this parameter by at least one minute.
Visible only if Application Overload time delaytOL above is not set to nO.
Parameter that can be modified during operation or when stopped.
0 to 6 min0 min
must
54BBV28581 05/2013
Page 55
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
LUL +10%
Motor current
LUL
Drive stop on ULF
detected fault
ULt< ULt
(hysteresis)
t
Code
I_O-
ULt
LUL
T
Name/DescriptionAdjustment rangeFactory setting
Input Output menu (continued)
M Application underload time delay
ULt can be adjusted between 0 and 100 s.
If the motor current undershoots the underload threshold LUL for longer than the adjustable time delay
ULt, the drive will stop running and display ULF (Process underload fault) page 111
Underload detection is only active when the system is in steady state (speed reference reached).
A value of 0 will disable application underload detection.
M Application Underload threshold
Visible only if Application underload time delayULt is not set to 0. This parameter is used to detect an
application underload condition on the motor. Application Underload thresholdLUL can be adjusted
between 20 and 100% of the nominal drive current.
0 to 100 s0 s
.
20 to 100% of nCr60%
FtU
T
Ftd
T
Ctd
T
ttd
T
M Time delay before automatic start for the
underload fault
If Atr = YES the drive restarts automatically after an underload fault ULF once this time delay has elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of Maximum restart timetAr page 91
exceed that of this parameter by at least one minute.
Visible only if Application underload time delayULt above is not set to nO.
M Motor frequency threshold
Visible only if R1 assignmentr1 page 52 or a LO1 assignmentLO1 page 53 is set to FtA.
M Motor current threshold
Visible only if R1 assignmentr1 page 52 or a LO1 assignmentLO1 page 53 is set to CtA.
M Motor thermal state threshold
Visible only if R1 assignmentr1 page 52 is set to tSA.
Trip threshold for motor thermal alarm (logic output or relay)
0 to 6 min0 min
must
0 to 400 Hz50 or 60 Hz
According to drive
rating
0 to 1.5 In (1)InV
0 to 118% of tHr100%
(1)In = nominal drive current
T
BBV28581 05/201355
Parameter that can be modified during operation or when stopped.
Page 56
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
I_O-
AO1-
AO1
AO1t
nO
OCr
OFr
OrP
OPS
OPF
OPE
OPr
tHr
tHd
10U
OA
4A
Name/DescriptionAdjustment rangeFactory setting
Input Output menu (continued)
AO1 configuration menu
M AO1 assignment
This parameter is used to set the value of an analog output.
v Not assigned
v Motor current, between 0 and 2 In (In = rated drive current indicated on the drive nameplate)
v Output frequency, from 0 to Max frequency tFr
v Ramp output, from 0 to Max frequency tFr
v PID reference, between 0 and 100% of the PID set point - Visible only if PID feedback assignmentPIF
page 72
is not set to nO
v PID feedback, between 0 and 100% of the PID feedback - Visible only if PID feedback assignmentPIF
page 72
is not set to nO
v PID error, between - 5 % and + 5 % of the PID feedback - Visible only if PID feedback assignmentPIF
page 72
is not set to nO
v Output power, between 0 and 2.5 times Rated motor power nPr
v Motor thermal state, between 0 and 200% of the rated thermal state
v Drive thermal state, between 0 and 200% of the rated thermal state
M AO1 type
This parameter provides the interface between the drive internal value and an analog output signal.
v Voltage: 0-10 Vdc
v Current: 0-20 mA
v Current: 4-20 mA
nO
0A
56BBV28581 05/2013
Page 57
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
drC-
bFr
nPr
CoS
UnS
Name/DescriptionAdjustment
range
Motor control menu
M Standard motor frequency
See page 45.
M Rated motor power
See page 46.
M Rated motor cos phi
Visible only if Motor parameter choiceMPC page 60 is set to CoS. If Rated motor cos phiCoS is
available Rated motor powernPr disappears.
Motor nameplate power factor (pf).
Note: Do not confuse this with motor "Service Factor". Setting CoS to or very near to 1 may result in
unsatisfactory motor operation. If the motor power factor is not indicated on the nameplate, leave this
parameter at the factory default (approximately 0.80)
M Rated motor voltage
Rated motor voltage given on the nameplate. If the line voltage is less than the rated motor voltage, Rated
motor voltageUnS should be set to the value of the line voltage applied to the drive terminals.
NCV –5 to
NCV +2
0.5 to 1According to drive rating
100 to 480 V230 V
Factory setting
50 Hz
According to drive rating
nCr
FrS
nSP
tFr
Ctt
PErF
Std
PUMP
M Rated motor current
Rated motor current given on the nameplate. Rated motor current nCr modifies Motor thermal current
ItH page 94
.
M Rated motor frequency
Rated motor frequency given on the nameplate.
The factory setting is 50 Hz, or preset to 60 Hz if Standard motor frequencybFr page 45
M Rated motor speed
Rated motor speed given on the nameplate.
M Maximum frequency
Maximum frequency tFr gives the upper value possible for High speedHSP page 90.
The factory setting is 60 Hz, or preset to 72 Hz if Standard motor frequencybFr page 57
M Motor control type
Allows selection of the motor control type suitable for the application and the required performances.
0.25 In to 1.5 In
(1)
10 to 400 Hz50 Hz
0 to 24000 rpMAccording to drive rating
10 to 400 Hz60 Hz
According to drive rating
is set to 60 Hz.
is set to 60 Hz.
Std
v Performance: SVCU; Sensorless vector control with internal speed loop based on voltage feedback
calculation. For applications needing high performance during starting or operation.
v Standard: U/F 2 points (Volts/Hz) without internal speed loop
For simple applications that do not require high performance. Simple motor control law keeping a constant
Voltage Frequency ratio, with a possible adjustment of the curve bottom.
This law is generally used for motors connected in paralell. Some specific applications with motors in
paralell and high performance levels may require PErF.
v Pump: U²/F; dedicated to variable torque pump and fan applications that do not require high starting torque.
(1)In = nominal drive current
BBV28581 05/201357
Page 58
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
drC-
UFr
T
SLP
T
StA
T
Name/DescriptionAdjustment rangeFactory setting
Motor control menu
M IR compensation (law U/F)
Used to optimize torque at very low speed, or to adapt to special cases (for example: for motors connected
in parallel, decrease IR compensation (law U/F)UFr). If there is insufficient torque at low speed,
increase IR compensation (law U/F)UFr. Too high a value can cause the motor not to start (locking) or
a change to current limiting mode.
M Slip compensation
Visible only if Motor control type Ctt page 57 is not set to PUMP
Used to adjust the slip compensation around the value set by the nominal motor slip, or to adapt to special
cases (example: for motors connected in parallel, decrease Slip compensationSLP).
If the set slip compensation is lower than the actual slip compensation, the motor doesn't run at nominal
speed at steady state but at a speed lower than the reference.
If the set slip compensation is greater than the actual slip compensation, motor speed is unstable.
M Frequency loop stability
The StA parameter can be used to reduce overshoots and oscillations at the end of acceleration. After
a period of acceleration or deceleration, StA adapts the return to a steady state to the dynamics of the
machine;
Too high a value causes an extended response time.
Too low a value causes an overspeed, or even instability.
(continued)
25 to 200%100%
0 to 150%100%
0 to 100%20%
FLG
T
Low StACorrect StAHigh StA
In this case, increase StAIn this case, reduce StA
Visible only if Motor control type Ctt page 57
M Frequency loop gain
The FLG parameter adjusts the slope of the speed increase according to the inertia of the machine being
driven.
Too high a value causes an overspeed, or even instability.
Too low a value causes an extended response time
Low FLGCorrect FLGHigh FLG
In this case, increase FLGIn this case, reduce FLG
is set to PErF.
0 to 100%20%
Visible only if Motor control type Ctt page 57
T
58BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
is set to PErF.
Page 59
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
drC-
PFL
T
SFr
T
Name/DescriptionAdjustment rangeFactory setting
Motor control menu (continued)
M Flux Profile
It defines the magnetizing current at zero frequency, as a % of the rated magnetizing current
Adjustment of PUMP law.
Visible only if Motor control type Ctt page 57
M Switching frequency
Switching frequency setting.
In the event of overheating, the drive automatically decreases the switching frequency.
It is restored to its original value when the temperature returns to normal.
Frequency
is set to PUMP
0 to 100%20%
2 to 16 kHz4 kHz
SFt
HF1
HF2
nrd
YES
nO
NOTICE
RISK OF DAMAGE TO THE DRIVE
On ATV12ppppM2 ratings, if the filters are disconnected, the drive’s switching frequency must not exceed 4 kHz.
Failure to follow these instructions can result in equipment damage.
M Switching frequency type
The motor switching frequency will always be modified (reduced) when the internal temperature of the
drive is too high.
v HF1: Heating optimization.
Allows the system to adapt the switching frequency according to the motor frequency.
v HF2: Motor noise optimization (for high switching fequency).
Allows system to keep a constant chosen switching frequency (SFr) whatever the motor frequency (rFr).
In the event of overheating, the drive automatically decreases the switching frequency.
It is restored to its original value when the temperature returns to normal.
M Motor noise reduction
Noise means audible noise. Depending on the environment it must be possible to adjust the motor noise.
Random frequency modulation avoids possible resonance noises that can occur at fixed frequency.
v No
v Yes
HF1
nO
T
BBV28581 05/201359
Parameter that can be modified during operation or when stopped.
Page 60
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
drC-
tUn
Name/DescriptionAdjustment rangeFactory setting
Motor control menu (continued)
M Auto-tuning
nO
DANGER
HAZARD OF ELECTRIC SHOCK OR ARC FLASH
• During auto-tuning, the motor operates at rated current.
• Do not service the motor during auto-tuning.
Failure to follow these instructions will result in death or serious injury.
WARNING
LOSS OF CONTROL
• It is essential that the following parameters UnS, FrS, nCr, nSP, and nPr or COS are correctly
configured before starting auto-tuning.
• When one or more of these parameters have been changed after auto-tuning has been performed, tUn will
return nO and the procedure will have to be repeated.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
YES
dOnE
MPC
nPr
COS
nO
v No: When factory parameters of standard motors
v Yes: Launches auto-tuning
v Done: If auto-tuning has already been performed
Attention:
• Auto-tuning must be performed with the motor connected and cold.
• Parameters Rated Motor PowernPr page 46
consistent.
• Auto-tuning is performed only if no stop command has been activated. If a freewheel stop or fast stop
function has been assigned to a logic input, this input must be set to 1 (active at 0).
• Auto-tuning takes priority over any run or prefluxing commands, which will take effect after the auto-
tuning sequence.
• Auto-tuning may last for 1 to 2 seconds. Do not interrupt, wait for tUn value to change to dOnE or
nO.
Note: During auto-tuning the motor operates at rated current.
M Motor parameter choice
This parameter allows to choose which motor parameter will be configured (npr or CoS).
v Rated Motor PowernPr page 46
v Rated motor cos phiCoS page 57
and Rated motor currentnCr page 57 must be
nPr
60BBV28581 05/2013
Page 61
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Stop
key
priority
Preset speed
PID
reg.
JOG
orPIF
Control menu
Control channel diagram
tEr
LOC
LCC
Mdb
SIM
SEP
AI1
LCC
Mdb
AIV1
SP1
Cd1
CHCF
Fr1
SPx
nO
PSx
LI
5Hz
JOG
nO
nO
PIF
nO
AI1
LCC
AIV1
nO
AI1
LCC
AIV1
FLOC
FLOC
FLO
nO
LI
FLO
nO
LI
PSt
nO
rIn
SPx
nO
YES
HSPACC AC2
LSP
DEC DE2
BBV28581 05/201361
Page 62
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s
CtL-
AIU1
l
Code
Fr1
AI1
LCC
Mdb
AIUI
LFr
T
T
rIn
Name/DescriptionAdjustment rangeFactory setting
Control menu
M Reference channel 1
v Terminal
v Remote display
v Modbus
v Integrated display with Jog dial
nO
YES
This parameter is already included in "my menu" section, page 45
M External reference value
This parameter is already included in "my menu" section, page 45.
M Analog input virtual
This parameter is already included in "my menu" section, page 45.
M Reverse inhibition
Inhibition of movement in reverse direction, does not apply to direction requests sent by logic inputs.
- Reverse direction requests sent by logic inputs are taken into account.
- Reverse direction requests sent by the display are not taken into account.
- Reverse direction requests sent by the line are not taken into account.
- Any reverse speed reference originating from the PID, etc., is interpreted as a zero reference (0 Hz).
v No
v Yes
.
– 400 Hz to 400 Hz
0% to 100%
AI1
-
nO
PSt
YES
CHCF
SIM
SEP
nO
M Stop key priority
This parameter can enable or disable the stop button located on the drive and remote display.
Disabling the stop button is effective if the active command channel is different from the drive keypad or
remote display
YES
WARNING
LOSS OF CONTROL
You are going to disable the stop button located on the drive and remote display
Do not select nO unless exterior stopping methods exist.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
v No: Stop inactive
v Yes: Stop active
It is advised in case this function is set to YES to use the front door cover or the option display cover on
"run" and "stop" keys.
M Channel configuration
Channel configurationCHCF allows the selection of:
- Not separate mode, (command and reference come from the same channel)
- Separate mode (command and reference come from different channel)
v Not separate mode
v Separate mode
SIM
To change the assignment of this parameter press the “ENT” key for 2 s.
T
62BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
Page 63
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
CtL-
Cd1
FLO
FLOC
tEr
LOC
LCC
Mdb
nO
L1H
L4H
nO
AI1
LCC
AIU1
Name/DescriptionAdjustment rangeFactory setting
Control menu (continued)
M Command channel 1
This parameter allows selection of the command channel.
v Terminals
v Local
v Remote display
v Modbus
This parameter is available if Channel configurationCHCF page 62
is set to Separate
M Forced local assignment
v Function inactive
v L1h to L4h: Forced local mode is active when the input is at state 1.
-
M Forced local reference
Visible only if Forced local assignmentFLO is not set to nO.
v Not assigned
v Terminal
v Remote display
v Integrated display with jog dial
tEr
nO
nO
BBV28581 05/201363
Page 64
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
rPt-
ACC
T
dEC
T
rPt
T
LIn
Name/DescriptionAdjustment rangeFactory setting
Function menu
Ramp menu
M Acceleration
Acceleration time between 0 Hz and the Rated motor frequencyFrS page 57.
Make sure that this value is compatible with the inertia being driven.
M Deceleration
Time to decelerate from the Rated motor frequencyFrS page 57 to 0 Hz
Make sure that this value is compatible with the inertia being driven.
0.0 s to 999.9 s
0.0 s to 999.9 s
M Ramp shape assignment
v Linear
S
U
v S shape
v U shape
S shape
The rounding coefficient is fixed,
t1 = 0.6 set ramp time (linear)
t2 = 0.4 set ramp time (round)
t3 = 1.4 set ramp time
3.0 s
3.0 s
Lin
rPS
T
U shape
M Ramp switching commutation
nO
LIH
L2H
L3H
L4H
LIL
L2L
L3L
L4L
Parameter that can be modified during operation or when stopped.
v Not assigned
v L1H: LI1 active High
v L2H: LI2 active High
v L3H: LI3 active High
v L4H: LI4 active High
v L1L: LI1 active low
v L2L: LI2 active low
v L3L: LI3 active low
v L4L: LI4 active low
See LI assignment information on page 46.
The rounding coefficient is fixed,
t1 = 0.5 set ramp time (linear)
t2 = set ramp time (round)
t3 = 1.5 set ramp time
nO
64BBV28581 05/2013
Page 65
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
rPt-
AC2
T
dE2
T
brA
nO
YES
dYnA
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Ramp menu (continued)
M Acceleration 2
Visible only if Ramp switching commutationrPS page 64 is not set to nO.
Second acceleration ramp time, adjustable from 0.0 to 999.9 s
This ramp will be the active ramp when using PID for the start and wake-up phases only, see PID wake up
level page 75
.
M Deceleration 2
Visible only if Ramp switching commutationrPS page 64 is not set to nO.
Second deceleration ramp time, adjustable from 0.0 to 999.9 s
M Decel Ramp Adaptation assignment
v Function inactive. The drive will decelerate based on the normal deceleration adjustment. This setting is
compatible with optional dynamic braking if used.
v This function automatically increases deceleration time when stopping or reducing the speed of high inertia
loads to help prevent DC bus overvoltage or overbraking.
v Motor Braking: This mode allows the drive to attempt the most rapid stop possible without the use of a
dynamic brake resistor. It uses motor losses to dissipate energy from regeneration. This function may be
incompatible with positioning. This function should not be used when an optional braking resistor and
module are being used.
0.0 to 999.9 s5.0 s
0.0 to 999.9 s5.0 s
YES
T
Attention: When using a braking resistor set brA to nO.
Parameter that can be modified during operation or when stopped.
BBV28581 05/201365
Page 66
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
Stt-
Stt
nSt
FSt
rMP
FSt
nSt
nO
L1L
L2L
L3L
L4L
nO
L1L
L2L
L3L
L4L
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Stop configuration menu
M Type of stop
Stop mode on disappearance of the run command and appearance of a stop command
v Ramp stop
v Fast stop
v Freewheel
M Freewheel stop assignment
The stop is activated when the input or the bit changes to 0. If the input returns to state 1 and the run
command is still active, the motor will only restart if Type of controltCC page 48
controltCt page 51
= LEL or PFO. If not, a new run command must be sent.
v Not assigned
v L1L: LI1 Active Low to stop
v L2L: LI2 Active Low to stop
v L3L: LI3 Active Low to stop
v L4L: LI4 Active Low to stop
M Fast stop assignment
v Not assigned
v L1L: LI1 Active Low to stop
v L2L: LI2 Active Low to stop
v L3L: LI3 Active Low to stop
v L4L: LI4 Active Low to stop
rMP
nO
= 2C and 2 wire type
nO
dCF
T
Code
FUn-
rrS
T
M Ramp divider
Visible only if Fast stop assignmentFSt page 63 is not set to nO or if FSt is set to Type of stopStt
page 66
The ramp that is enabled (DecelerationdEC page 45
by this coefficient when stop requests are sent.
Value 10 corresponds to a minimum ramp time.
Name/DescriptionAdjustment rangeFactory setting
.
Function menu (continued)
M Reverse direction
LI1 to LI4: choice of the input assigned to the reverse command
nO
LIH
L2H
L3H
L4H
Parameter that can be modified during operation or when stopped.
v Function inactive
v L1h: L1 active high
v L2h: L2 active high
v L3h: L3 active high
v L4h: L4 active high
1 to 10
or Deceleration 2dE2 page 65) is then divided
4
nO
66BBV28581 05/2013
Page 67
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
AdC-
AdC
T
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Auto DC injection menu
M Automatic DC injection
YES
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When AdC = Ct, the injection of current is done even if a run command has not been sent.
Check this action will not endanger personnel or equipment in any way.
Failure to follow these instructions will result in death or serious injury.
WARNING
NO HOLDING TORQUE
• DC injection braking does not provide any holding torque at zero speed.
• DC injection braking does not work when there is a loss of power or when the drive detects a fault.
• Where necessary, use a separate brake to maintain torque levels.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
YES
SdC1
T
tdC1
T
nO
Ct
v Function inactive, no DC injected current.
v Time limited DC injection
v Continuous DC injection
M Automatic DC injection current
0 to 120% of nCr70%
NOTICE
RISK OF DAMAGE TO THE MOTOR
Check that the motor will withstand this current without overheating.
Failure to follow this instruction can result in equipment damage.
Visible only if Automatic DC injectionAdC is not set to nO.
Injection current on stopping and continuous DC injection.
M Automatic DC injection time
0.1 to 30 s0.5 s
NOTICE
RISK OF DAMAGE TO THE MOTOR
• Long periods of DC injection braking can cause overheating and damage the motor.
• Protect the motor by avoiding long periods of DC injection braking.
Failure to follow these instructions can result in equipment damage.
Visible only if Automatic DC injectionAdC is not set to nO.
Injection time on stopping.
T
BBV28581 05/201367
Parameter that can be modified during operation or when stopped.
Page 68
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Jog
Forward
Reverse
Motor
Frequency
5Hz
5Hz
Acceleration
0,5s
Jog
Forward
Reverse
Motor
Frequency
5Hz
5Hz
Normal
ramp
Jog
ramp
LI1 Run
Code
FUn-
JOG
nO
L1H
L2H
L3H
L4H
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
M Jog assignment
This parameter provides step by step control of motor running, using a logic input associated with a 2 and
3-wire control logic input. The jog frequency is fixed at 5 Hz. Acceleration and decelaration ramps taken
into account in the Jog function are 0.1 s.
v Function inactive.
v L1h: LI1 active high
v L2h: LI2 active high
v L3h: LI2 active high
v L4h: LI4 active high
2-wire control
nO
3 wire control
68BBV28581 05/2013
Page 69
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Configuration Mode - Complete menu (FULL)
Preset speeds
2, 4, or 8 speeds can be preset, requiring 1, 2 or 3 logic inputs respectively
Combination table for preset speed inputs
8 speeds
LI (PS8)
000Reference
001SP2
010SP3
011SP4
100SP5
101SP6
110SP7
111SP8
4 speeds
LI (PS4)
2 speeds
LI (PS2)
Speed reference
BBV28581 05/201369
Page 70
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PSS-
PS2
PS4
PS8
SP2
T
SP3
T
nO
L1H
L2H
L3H
L4H
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Preset speed menu
M 2 Preset speeds
v Function inactive
v L1h: LI1 active high
v L2h: LI2 active high
v L3h: LI2 active high
v L4h: LI4 active high
M 4 Preset speeds
as PS2
M 8 Preset speeds
as PS2
M Preset speed 2
Visible only if 2 Preset speedsPS2 is not set to nO.
M Preset speed 3
Visible only if 4 Preset speedsPS4 is not set to nO.
0 to 400 Hz10 Hz
0 to 400 Hz15 Hz
nO
nO
nO
SP4
T
SP5
T
SP6
T
SP7
T
SP8
T
JPF
T
M Preset speed 4
Visible only if 2 Preset speedsPS2 and 4 Preset speedsPS4 are not set to nO.
M Preset speed 5
Visible only if 8 Preset speedsPS8 is not set to nO.
M Preset speed 6
Visible only if 2 Preset speedsPS2 and 8 Preset speedsPS8 are not set to nO.
M Preset speed 7
Visible only if 4 Preset speedsPS4 and 8 Preset speedsPS8 are not set to nO.
M Preset speed 8
Visible only if 2 Preset speedsPS2, 4 Preset speedsPS4 and 8 Preset speedsPS8 are not set to nO.
M Skip frequency
0 to 400 Hz20 Hz
0 to 400 Hz25 Hz
0 to 400 Hz30 Hz
0 to 400 Hz35 Hz
0 to 400 Hz40 Hz
0 to 400 Hz0 Hz
v This parameter prevents prolonged operation around the regulated frequency. This function can be used
to prevent a critical speed, which would cause resonance, being reached. Setting the function to 0 renders
it inactive.
T
70BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
Page 71
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Preset speed
Auto
Man.
Configuration Mode - Complete menu (FULL)
PID diagram
BBV28581 05/201371
Page 72
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
PIF
rPG
T
rIG
T
rdG
T
FbS
T
nO
A11
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu
M PID feedback assignment
v Not assigned
v Terminal. Choice not possible if Fr1 is set to AI1
M PID proportional gain
Visible only if PID feedback assignmentPIF is not set to nO.
M PID integral gain
Visible only if PID feedback assignmentPIF is not set to nO.
M PID derivative gain
Visible only if PID feedback assignmentPIF is not set to nO.
M PID feedback scale factor
This parameter gives the relation between process range and feedback range.
Visible only if PID feedback assignmentPIF is not set to nO.
0.01 to 1001
0.01 to 1001
0.00 to 100.000.00
0.1 to 100.01.0
nO
PII
Pr2
T
M Activation internal PID reference
Visible only if PID feedback assignmentPIF is not set to nO.
nO
YES
v No
v Yes
M 2 preset PID assignment
Visible only if PID feedback assignmentPIF is not set to nO.
nO
L1H
L2H
L3H
L4H
Parameter that can be modified during operation or when stopped.
v No
v L1h
v L2h
v L3h
v L4h
nO
nO
72BBV28581 05/2013
Page 73
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
Pr4
rP2
T
rP3
T
nO
L1H
L2H
L3H
L4H
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
M 4 preset PID assignment
Visible only if PID feedback assignmentPIF page 72 is not set to nO.
v No
v L1h
v L2h
v L3h
v L4h
2 preset PID assignmentPr2 page 72
Pr4.
M 2 preset PID reference
Visible only if PID feedback assignmentPIF page 72 and 2 preset PID assignmentPr2 page 72 are
not set to nO.
M 3 preset PID reference
Visible only if PID feedback assignmentPIFpage 72 and 4 preset PID assignmentPr4 page 72 are
not set to nO.
must be assigned before assigning 4 preset PID assignment
0 to 100%25%
0 to 100%50%
nO
rP4
T
rPI
T
PrP
T
rPL
T
rPH
T
SFS
M 4 preset PID reference
Visible only if PID feedback assignmentPIF page 72 and 2 preset PID assignmentPr2 and 4 preset
PID assignmentPr4 page 72
M Internal PID reference
Visible only if PID feedback assignmentPIF page 72 is not set to nO and if Activation internal PID
referencePII page 72
is set to YES or Reference channel 1Fr1 page 45 is set to LCC.
M PID reference ramp
Visible only if PID feedback assignmentPIF page 72 is not set to nO.
M PID min value reference
Visible only if PID feedback assignmentPIF page 72 is not set to nO.
M PID max value reference
Visible only if PID feedback assignmentPIF page 72 is not set to nO
M PID predictive speed
This parameter allows to go directly to a set speed reference.
Visible only if PID feedback assignmentPIF page 72
0 to 100%75%
are not set to nO.
0 to 100%0%
0 to 99,9 s0 s
0 to 100%0%
0 to 100%100%
0.1 to 400 HznO
is not set to nO.
T
BBV28581 05/201373
Parameter that can be modified during operation or when stopped.
Page 74
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
AC2
T
PIC
PAU
nO
YES
nO
L1H
L2H
L3H
L4H
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
M Acceleration 2
This parameter is active only when the system is starting.
Second acceleration ramp time, adjustable from 0.1 to 999.9 s
Time to accelerate from 0 to the Rated motor frequencyFrS page 57
compatible with the inertia being driven.
Visible only if PID feedback assignmentPIF page 72
set to nO.
M PID correction reverse
This parameter will reverse the internal error value of PID system.
v No
v Yes
Visible only if PID feedback assignmentPIF page 72
M PID auto/manual assignment
At state 0 of input, PID is active.
At state 1 of input, manual run is active
v No
v L1h: LI1 active high
v L2h: LI2 active high
v L3h: LI3 active high
v L4h: LI4 active high
and PID predictive speedSFS page 73 are not
is not set to nO.
0.0 to 999.9 s5.0 s
. Make sure that this value is
nO
nO
PIM
tLS
T
T
Visible only if PID feedback assignmentPIF page 72 is not set to nO.
M PID manual reference
This parameter allows to disable the PID and to run on a standard manual system.
nO
A11
A1U1
v No
v Terminal
v AIV1
Visible only if PID feedback assignmentPIF page 72
are not set to nO.
M Low speed operating time
Following operation at Low speedLSP page 89 for a defined period, a motor stop is requested
automatically. The motor restarts if the frequency reference is greater than Low speedLSP and if a run
command is still present.
Note:nO value corresponds to an unlimited period.
Visible only if PID feedback assignmentPIF page 72
Parameter that can be modified during operation or when stopped.
nO
and PID auto/manual assignmentPAU page 74
0.1 to 999.9 snO
is not set to nO.
74BBV28581 05/2013
Page 75
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
rSL
UPP
T
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
M PID wake up level
0 to 100%0%
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that unintended restarts will not present any danger.
Failure to follow these instructions will result in death or serious injury.
If PID functions and Low speed operating timetLS are set at the same time, the PID regulator may try to
set a speed lower than LSP, resulting in unwanted operation consisting of start, running at LSP, stopping
and so on…
Parameter PID wake up levelrSL is used to set a minimum PID error threshold to restart after a
prolonged stop at LSP.
Visible only if PID feedback assignmentPIF page 72
not set to nO.
M Wake-up threshold
and Low speed operating timetLS page 74 are
0 to 100%0%
SLE
T
T
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that unintended restarts will not endanger personnel or equipment in any way.
Failure to follow these instructions will result in death or serious injury.
If PID correction reversePIC page 74 is set to nO, enables to set the PID feedback threshold beyond
which the PID regulator is reactivated (wake-up), following a stop caused by exceeding the tLS
maximum time in low speed.
If PIC is set to YES, enables to set the PID feedback threshold above which the PID regulator is
reactivated (wake-up), following a stop caused by exceeding the tLS maximum time in low speed.
Visible only if PID feedback assignmentPIF page 72
not set to nO.
M Sleep Threshold Offset
Adjustable restart threshold (offset) following a stop after prolonged operation at Low speedLSP + Sleep
Offset ThresholdSLE, in Hz. The motor restarts if the reference rises above (LSP + SLE) and if a run
command is still present.
Visible only if Low speed time outtLS page xx is not set to nO and if PID feedback assignmentPIF
page 72
Parameter that can be modified during operation or when stopped.
is not set to nO.
and Low speed operating timetLS page 89 are
0 to HSP1 Hz
BBV28581 05/201375
Page 76
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
LPI
T
tPI
T
AP0
T
MPI
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
M PI feedback supervision threshold
An alarm can be assigned to a relay or a logic output.
Adjustment range:
v No: Function inactive (it will not be possible to access the other function parameters)
v between minimum and maximum PID feedback.
Visible only if PID feedback assignmentPIF page 72
is not set to nO.
M PI feedback supervision function time delay
Visible only if PI feedback supervision thresholdLPI above is not set to nO.
M Maximum frequency detection hysteresis
Visible only if PI feedback supervision thresholdLPI above is not set to nO.
M PI feedback supervision
Fallback mode for the PI feedback supervision function.
v YES: freewheel stop
v LFF: switch to fallback speed LFF as long as the fault is present and the run command is not disabled.
nO to 100%nO
0 to 600 s0 s
0 to HSP0 Hz
YES
LFF
T
Visible only if PI feedback supervision thresholdLPI above is not set to nO.
M Fallback speed
Fallback speed for PID regulator feedback supervision fault.
Parameter that can be modified during operation or when stopped.
0 to HSP0 Hz
76BBV28581 05/2013
Page 77
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
PMP-
tOL
LOC
T
FtO
T
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
Pump sub-menu
M Application Overload time delay
See page 54
Visible only if PID feedback assignmentPIF page 72 is not set to nO.
M Application Overload threshold
See page 54
Visible only if Application Overload time delaytOL above is not set to nO.
M Time delay before automatic start for the
overload fault
If Atr = YES the drive restarts automatically after an overload fault OLC once this time delay has
elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of Maximum restart timetAr page 91
exceed that of this parameter by at least one minute.
0 to 100 s0 s
70 to 150% of nCr90%
0 to 6 min0 min
must
ULt
LUL
T
T
Visible only if Application Overload time delaytOL above is not set to nO.
M Application underload time delay
See page 55
Visible only if PID feedback assignmentPIF page 72 is not set to nO.
M Application Underload threshold
See page 55
Visible only if Application underload time delayULt above is not set to nO.
Parameter that can be modified during operation or when stopped.
0 to 100 s0 s
20 to 100% of nCr60%
BBV28581 05/201377
Page 78
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
PMP-
FtU
T
MdE
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
Pump sub-menu (continued)
M Time delay before automatic start for the
underload fault
If Atr = YES the drive restarts automatically after an underload fault ULF once this time delay has
elapsed.
Minimum time permitted between an underload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of Maximum restart timetAr page 91
exceed that of this parameter by at least one minute.
Visible only if Application underload time delayULt above is not set to nO.
M Selecting the operating mode
v nO: single variable mode
v YES: single variable mode with auxiliary pump
When MdE = YES, output LO1 is forced to PMP (see page 53
Visible only if PID feedback assignmentPIF page 72
is not set to nO.
0 to 6 min0 min
must
nO
).
FOn
T
tOn
T
rOn
T
FOF
T
M Starting frequency of the auxiliary pump
Above this frequency and after the pump starting time delay tOn,
the auxiliary pump starts.
Visible only if Selecting the operating modeMdE above is not set to nO.
M Time delay before starting the auxiliary
pump
This time is necessary to avoid the effects of transient pressure fluctuation and thus prevent oscillation
(pump starting/stopping).
Visible only if Selecting the operating modeMdE above is not set to nO.
M Ramp for reaching the auxiliary pump
nominal speed
Visible only if Selecting the operating modeMdE above is not set to nO.
M Auxiliary pump stopping frequency
Below this frequency and after the time delay for stopping the auxiliary pump tOF, the pump stops.
Visible only if Selecting the operating modeMdE above is not set to nO.
0 to tFrHSP
0 to 999.9 s2 s
0 to 999.9 s2 s
0 to tFr0 Hz
T
78BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
Page 79
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
PId-
PMP-
tOF
T
rOF
T
nFd
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
PID menu (continued)
Pump sub-menu (continued)
M Time delay before the auxiliary pump stop
command
This time is necessary to avoid the effects of transient pressure
fluctuation and thus prevent oscillation (pump starting/stopping)
Visible only if Selecting the operating modeMdE above is not set to nO.
M Ramp for auxiliary pump stopping
Visible only if Selecting the operating modeMdE above is not set to nO.
M Zero flow detection period
The value 0 deactivates zero flow detection.
Visible only if PID feedback assignment PIF page 70 is not set to nO.
0 to 999.9 s2 s
0 to 999.9 s2 s
nO to 20 minnO
FFd
T
LFd
T
T
M Zero flow detection activation threshold
Below this threshold, if nFd > 0 and the auxiliary pump is stopped,
zero flow detection is activated.
Visible only if Zero flow detection periodnFd above is not set to nO.
M Zero flow detection offset
Visible only if Zero flow detection periodnFd above is not set to nO.
Parameter that can be modified during operation or when stopped.
0 to 400 Hz0 Hz
0 to 400 Hz0 Hz
BBV28581 05/201379
Page 80
Configuration Mode - Complete menu (FULL)
Variable pump
ATV12
Pressure sensor
0-20 mA
4-20 mA
0+5 V
0+10 V
Architecture of the pumping installation
Single variable mode - 1 single variable speed pump
Enter the values given on the motor rating plate in the Motor control menu drC
First level adjustment parameters
ACC Acceleration: 0.7 s
dEC Deceleration: 0.7 s
LSP Low speed: 30 Hz
HSP high-speed: 60 Hz
Analog input menu AIt
AI1t Scale of analog input AI1: 0-20 mA
Motor control menu drC
SLP Nominal motor slip: 0 Hz
FLG Frequency loop gain: 70%
UFr IR compensation: 0%
Application functions menu FUn
tCt 2-wire type control: LEL
PI sub-menu
PIF Assignment of the PI function feedback: AI1
rPG PI regulator proportional gain: 5.00
rIG PI regulator integral gain: 8.00
rPI Internal PI regulator reference: 39%
rSL Restart error threshold: 40%
MPI Supervision of the PI regulator function: LFF
LPI PI feedback supervision threshold: 17%
tPI PI feedback supervision function time delay: 1 s
LFF Fallback speed: 50 Hz
Pump sub-menu PMP
nFd Zero flow detection: 1 min
FFd Zero flow detection activation threshold: 50 Hz
LFd Zero flow detection offset: 5 Hz
tLS Sleep threshold operating time: 3 s
SFS Quick start threshold: 25 Hz
SLE Sleep threshold offset: 10 Hz
Automatic DC injection sub-menu AdC
AdC Automatic DC injection assignment: nO
Automatic restart function Atr
Atr Automatic restart: YES
Fault menu FLt
LOC Overload threshold: 11%
FtO Time delay before automatic start for the overload fault: 1
Ap0 Frequency hysteresis reached: 2 Hz
80BBV28581 05/2013
Page 81
Configuration Mode - Complete menu (FULL)
Variable pump
ATV12
Fixed speed auxiliary pump
Pressure
sensor
0-20 mA
4-20 mA
0+5 V
0+10 V
Single variable with auxiliary pump mode - 1 variable speed pump (variable pump) and one fixed
speed pump (auxiliary pump)
The auxiliary pump is controlled by the Altivar 12 via logic output LO.
Enter the values given on the motor rating plate in the Motor control menu drC
First level adjustment parameters
ACC Acceleration: 0.1 s
dEC Deceleration: 0.1 s
LSP Low speed: 35 Hz
Analog input menu AIt
AI1t Scale of analog input AI1: 0-20 mA
Motor control menu drC
SLP Nominal motor slip: 0 Hz
FLG Frequency loop gain: 70%
UFr IR compensation: 0%
Application functions menu FUn
tCt 2-wire type control: LEL
PI sub-menu
PIF Assignment of the PI function feedback: AI1
rPG PI regulator proportional gain: 5.00
rIG PI regulator integral gain: 8.00
rPI Internal PI regulator reference: 51%
rSL Restart error threshold: 42%
Pump sub-menu PMP
MdE Selecting the operating mode: YES
FOn Starting frequency of the auxiliary pump: 49 Hz
tOn Time delay before starting the auxiliary pump: 1 s
rOn Ramp for reaching the nominal speed of the auxiliary pump: 1 s
FOF Stopping frequency of the auxiliary pump: 39.6 Hz
tOF Time delay before the auxiliary pump stop command: 1 s
rOF Ramp for stopping the auxiliary pump: 1 s
nFd Zero flow detection: 1 min
FFd Zero flow detection activation threshold: 42 Hz
LFd Zero flow detection offset: 2 Hz
tLS Sleep threshold operating time: 5 s
SLE Sleep threshold offset: 3 Hz
LO1 Assignment as logic/analog output PMP
Automatic DC injection sub-menu AdC
AdC Automatic DC injection assignment: nO
Automatic restart function Atr
Atr Automatic restart: YES
Fault menu FLt
tUL Underload function time delay 5 s
LUL Underload threshold: 59%
FtU Time delay before automatic restart for the underload fault: 1
BBV28581 05/201381
Page 82
Configuration Mode - Complete menu (FULL)
1-phase supply
200... 230 V
Variable
pump
Pressure sensor
0-20 mA
4-20 mA
0+5 V
0+10 V
Auxiliary pump
1-phase motor
200...230 V
Connection diagram
(1)
R/LI
U/T1
S/L2/N
V/T2
M1
3
W/T3
R1A
R1C
ATV12
LI1
LI2
LI3
LI4
AI1
+5 V
LO+
KM1
LO-
COM
+24 V
M2
3
KM1
(1) Fault relay contacts, for remote indication of the drive status.
Note: Fit interference suppressors to all inductive circuits near the drive or connected to the same circuit (relays, contactors, solenoid
valves, etc.).
Note: This wiring example is in source using internal supply.
82BBV28581 05/2013
Page 83
Configuration Mode - Complete menu (FULL)
LPI + 3 %
LPI
LPI - 2 %
HSP
HSP - AP0
LFF
MPI = LFF
MPI = YES
< tPItPI
PI feedback
Motor speed
End-of-time delay
Fallback mode
defined by MPI
PI feedback supervision (MPI)
Used to define the operating mode in the event of detection of a PI feedback lower than the limit set.
Once the variable pump is running at maximum speed (higher than HSP - AP0) and at the same time the PI feedback is lower than the
supervision threshold LPI - 2%, a time delay tPI is launched. If at the end of this time delay the value of the PI feedback is still lower than
the supervision threshold LPI + 3%, the drive switches to fallback mode as defined by parameter MPI.
- MPI = YES:
The drive will perform a freewheel stop and will display fault code SPIF.
- MPI = LFF:
The drive will run at a fixed frequency LFF and will display fault code FrF.
In both cases the drive reverts to PI regulation mode as soon as the PI feedback is higher than the supervision threshold LPI + 3%.
In single variable with auxiliary pump mode (MdE = YES), the PI feedback supervision function is only active when both pumps are
operating.
BBV28581 05/201383
Page 84
Configuration Mode - Complete menu (FULL)
Frequency of the
variable pump
Auxiliary pump starting
Auxiliary pump
stopping
Frequency
corresponding to the
auxiliary pump flow
rate
HSP
Starting frequency
FOn
Stopping frequency
FOF
Flow rate of the installation
HSP
FOn
FOF
tOn
LSP
rOn
0
t
Frequency of the
variable pump
Auxiliary pump starting
Pump submenu PMP
The principal objective is to control a complete pumping installation using a single ATV12 drive by providing constant pressure whatever
the flow rate.
The system is operated using an auxiliary fixed speed pump, and one variable speed pump, which is unable to provide the full flow range
required on its own. A PI regulator is used for drive control. The pressure sensor provides system feedback.
The variable speed pump is called a variable pump.
The fixed speed pump is called an auxiliary pump.
Selecting the operating mode
The ATV12 offers 2 operating modes:
• Single variable mode: 1 single variable speed pump (variable pump).
• Single variable with auxiliary pump mode: 1 variable speed pump (variable pump) and one fixed speed pump (auxiliary pump).
Control of the auxiliary pump
The PI regulator output (frequency reference of the variable pump) is used to control starting or stopping of the auxiliary pump with
hysteresis, as shown in the figure below:
When the frequency exceeds the starting threshold (FOn), a time delay (tOn) is launched to avoid the effects of transient flow fluctuations.
If after this time delay, the frequency remains higher than the starting threshold, the auxiliary pump is started. When the start command is
sent, the variable pump will go from its current speed reference to the auxiliary pump stopping frequency (FOF) following a ramp (rOn) that
equals the time taken for the auxiliary pump to reach its nominal speed. Parameter rOn is used to minimize the booster effect on starting
the auxiliary pump.
84BBV28581 05/2013
Page 85
Configuration Mode - Complete menu (FULL)
HSP
FOn
FOF
tOF
LSP
rOF
t
Frequency of the
variable pump
Auxiliary pump
stopping
When the frequency is lower than the stopping threshold (FOF), a time delay is launched (tOF) to avoid the effects of transient flow
fluctuations. If after this time delay, the frequency remains lower than the stopping threshold, the auxiliary pump is stopped. When the stop
command is sent, the variable pump will go from its current speed reference to the auxiliary pump starting frequency (FOn) following a ramp
(rOF) that equals the auxiliary pump stopping time. Parameter rOF is used to minimize the booster effect on stopping the auxiliary pump.
BBV28581 05/201385
Page 86
Configuration Mode - Complete menu (FULL)
PI feedback
Motor frequency
Low speed or speed threshold
operating time
HSP
SFS
ACC
t
Frequency of the
variable pump
"Sleep" function/"Wake-up" function
This function is used to stop the variable pump when there is zero flow (auxiliary pump stopped). In this case, if the frequency of the variable
pump is lower than the "sleep" threshold (LSP + SLE), a time delay (tLS) is launched. If, after this time delay, the frequency remains lower
than threshold LSP + SLE, the variable pump then stops. The installation is in "sleep" mode.
To switch to "wake-up" mode, the pressure feedback must drop to below the "wake-up" threshold UPP. The variable pump is then started.
UPP
t
LSP + SLE
LSP
tLS
t
Quick start function
The quick start function can be used to overcome problems linked to high rPG and rIG gains (instability on starting). The drive accelerates
until it reaches the quick start threshold SFS following a ramp ACC. Once the threshold has been reached, the PI regulator is activated.
86BBV28581 05/2013
Page 87
Configuration Mode - Complete menu (FULL)
PI feedback
PI error
Frequency reference
PI feedback
Frequency reference
Sleep threshold LSP + SLE
Zero flow detection
This function is only active when the auxiliary pump is stopped and the motor frequency is below threshold FFd.
This function is used in applications where zero flow cannot be detected by the sleep function alone. It forces the drive frequency reference
to LSP + LFd periodically (at each time interval nFd) in order to test for zero flow.
• If the request is still present, the PI error increases, causing the drive to restart.
t
FFd
LSP + LFd
LSP
nFd
nFd
t
• If the request is no longer present (zero flow), the PI error will not increase.
HSP
FFd
LSP + LFd
LSP
nFdtLS
• Set the sleep function so that the drive switches to sleep mode when zero flow is detected (LFd ≤ SLE).
t
t
BBV28581 05/201387
Page 88
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
CLI-
LC2
CLI
T
nO
L1H
L2H
L3H
L4H
L1L
L2L
L3L
L4L
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Current limitation menu
M 2nd current limitation commutation
Assignment
v Function inactive.
v L1H: LI1 active high
v L2H: LI2 active high
v L3H: LI3 active high
v L4H: LI4 active high
v L1L: LI1 active low
v L2L: LI2 active low
v L3L: LI3 active low
v L4L: LI4 active low
If the assigned input is at 0, the first current limitation is active.
If the assigned input is at 1, the second current limitation is active.
See LI assignment information on page 46
M Current limitation
First current limitation.
0.25 to 1.5 In (1)1.5 In
nO
NOTICE
RISK OF DAMAGE TO THE MOTOR AND THE DRIVE
Check that the motor will withstand this current.
Check that the profile mission complies with the derating curve given in the installation manual.
Failure to follow this instruction can result in equipment damage.
CL2
M Current limitation 2
T
RISK OF DAMAGE TO THE MOTOR AND THE DRIVE
Check that the motor will withstand this current.
Check that the profile mission complies with the derating curve given in the installation manual.
Failure to follow this instruction can result in equipment damage.
(1)In = nominal drive current
T
Parameter that can be modified during operation or when stopped.
Second current limitation
This function allows reduction of the drive current limit.
nd
Visible only if 2
current limitation commutationLC2 is not set to nO.
NOTICE
0.25 to 1.5 In (1)1.5 In
88BBV28581 05/2013
Page 89
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FUn-
SPL-
LSP
T
tLS
T
T
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Speed limit menu
M Low speed
Motor frequency at minimum reference.
This parameter is already included in "my menu" section, page 45
M Low speed operating time
Following operation at Low speedLSP for a defined period, a motor stop is requested automatically. The
motor restarts if the frequency reference is greater than Low speedLSP and if a run command is still
present.
Note:nO corresponds to an unlimited period.
Parameter that can be modified during operation or when stopped.
0 Hz to HSP0 Hz
.
0.1 to 999.9 snO
BBV28581 05/201389
Page 90
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
high-speed configuration
The logic inputs enable selection of the desired high-speed.
Desired
high-speed
HSPSH2nO
HSP2SH2assigned
HSP3SH2nO
HSP4SH2assigned
Code
FUn-
SPL-
HSP
Setting
ParameterState
SH4nO
SH4nO
SH4assigned
SH4assigned
Name/DescriptionAdjustment rangeFactory setting
Function menu (continued)
Speed limit menu
M High speed
T
Motor frequency at maximum reference, can be set between Low speedLSP and Maximum frequency
tFr page 57
If tFr is decreased below the value defined for HSP, then HSP automatically decreases to the new
value of tFr.
This parameter is already included in "my menu" section, page 45
SH2
nO
L1H
L2H
L3H
L4H
SH4
nO
L1H
L2H
L3H
L4H
HSP2
T
HSP3
T
HSP4
T
M 2 HSP assignment
v No
v L1h: LI1 active high
v L2h: LI2 active high
v L3h: LI3 active high
v L4h: LI4 active high
M 4 HSP assignment
v No
v L1h: LI1 active high
v L2h: LI2 active high
v L3h: LI3 active high
v L4h: LI4 active high
M High speed 2
Visible only if 2 HSP assignmentSH2 is not set to nO.
M High speed 3
Visible only if 4 HSP assignmentSH4 is not set to nO.
M High speed 4
Visible only if 2 HSP assignmentSH2 and 4 HSP assignmentSH4 are not set to nO.
LSP to tFr50 or 60 Hz
according to BFr,
max TFr
.
.
nO
nO
LSP to tFras HSP
LSP to tFras HSP
LSP to tFras HSP
T
90BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
Page 91
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FLt-
rSF
Atr-
Atr
nO
L1H
L2H
L3H
L4H
Name/DescriptionAdjustment rangeFactory setting
Fault detection management menu
M Detected fault reset assignment
Manual fault reset.
v Function inactive
v L1h: LI1 active high
v L2h: LI2 active high
v L3h: LI3 active high
v L4h: LI4 active high
Faults are reset when the assigned input or bit changes to 1, if the cause of the fault has disappeared.
The STOP/RESET button on the display terminal performs the same function.
See also Diagnostics and Troubleshooting on page 108
.
nO
Automatic restart menu
M Automatic restart
nO
DANGER
UNINTENDED EQUIPMENT OPERATION
•The automatic restart can only be used on machines or installations which do not pose any danger to either
personnel or equipment.
• If the automatic restart is activated, R1 will only indicate a fault has been detected once the time-out period for
the restart sequence has expired.
• The equipment must be used in compliance with national and regional safety regulations.
YES
tAr
nO
10
30
1H
2H
3H
Ct
Failure to follow these instructions will result in death or serious injury.
This function defines drive behavior upon detection of a fault.
If validated, this function allows an automatic restart of the drive when the cause of the detected fault has
disappeared and the other operating conditions permit the restart.
v Function inactive
v Automatic restart, after locking on a detected fault, if the cause has disappeared and the other operating
conditions permit the restart. The restart is performed by a series of automatic attempts separated by
increasingly longer waiting periods: 1 s, 5 s, 10 s, then 1 minute for the following attempts.
The drive status relay remains activated if this function is active. The speed reference and the operating
direction must be maintained.
Use 2-wire control (Type of controltCC page 48
If the restart has not taken place once the Max. automatic restart timetAr has elapsed, the procedure
is aborted and the drive remains locked until it is turned off and then on again.
The detected faults, which permit this function, are listed on page 110
M Max. automatic restart time
5
v 5 min
= 2C and 2 wire type controltCt page 51 = LEL).
:
5 min
v 10 min
v 30 min
v 1 hour
v 2 hours
v 3 hours
v Infinite
Visible only if Automatic restartAtr is not set to nO. It can be used to limit the number of consecutive
restarts on a recurrent fault.
BBV28581 05/201391
Page 92
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FLt-
FLr
nO
YES
Name/DescriptionAdjustment rangeFactory setting
Fault detection management menu (continued)
M Catch on the fly
Used to enable a smooth restart if the run command is maintained after the following events:
• Loss of line supply or disconnection
• Reset of current fault or automatic restart
• Freewheel stop.
The speed given by the drive resumes from the estimated speed of the motor at the time of the restart, then
follows the ramp to the reference speed.
This function requires 2-wire level control.
v Function inactive
v Function active
nO
92BBV28581 05/2013
Page 93
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Motor thermal protection
Function:
Thermal protection by calculating the I2t.
• Naturally-cooled motors:
The tripping curves depend on the motor frequency.
• Force-cooled motors:
Only the 50 Hz tripping curve needs to be considered, regardless of the motor frequency.
Trip time in seconds
Motor current/ItH
NOTICE
RISK OF DAMAGE TO THE MOTOR
The use of external overload protection is required under the following conditions:
• Repowering up the product since there is no motor thermal state memory.
• Running multiple motors
• Running motors rated at less than 0.2 times the nominal drive current
•
Using motor switching
Failure to follow these instructions can result in equipment damage
BBV28581 05/201393
Page 94
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FLt-
tHt-
ItH
T
tHt
OLL
ACL
FCL
nO
YES
Name/DescriptionAdjustment rangeFactory setting
Fault detection management menu (continued)
Motor thermal protection menu
M Motor thermal current
Current used for the motor thermal detection. Set ItH to the nominal current on the motor rating plate.
M Motor protection type
v Self-ventilated
v Motor-ventilated
M Overload fault management
Type of stop in the event of a motor thermal fault.
v Fault ignored
v Freewheel stop
Setting Overload fault managementOLL to nO inhibits the Motor overloadOLF page 110
0.2 to 1.5 In (1)According to drive
rating
ACL
YES
.
NOTICE
RISK OF DAMAGE TO THE MOTOR
If OLL is set to nO, motor thermal protection is no longuer provided by the drive. Provide an alternative means
of thermal protection.
Failure to follow these instructions can result in equipment dama ge.
MtM
FLt-
OPL
IPL
nO
YES
nO
YES
nO
YES
M Motor thermal state memo
nO
v Motor thermal state not stored at power off.
v Motor thermal state is stored at power off.
Fault detection management menu (continued)
M Output Phase loss
YES
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If OPL is set to nO, loss of cable is not detected. Provide an alternative means of thermal protection.
Check this action will not endanger personnel or equipment in any way
Failure to follow these instructions will result in death or serious injury.
v Function inactive
v Tripping on OPF1 (1 phase loss) or OPF2 (3-phase loss) fault with freewheel stop.
M Input Phase loss
This parameter is only accessible in this menu on 3-phases drives.
v Fault ignored. To be used when the drive is supplied via a single phase supply.
v Fault with freewheel stop.
If one phase disappears, the drive switches to fault mode Input Phase lossIPL but if 2 or 3 phases
disappear, the drive continues to operate until it trips on an undervoltage fault.
According to
drive rating
(1)In = nominal drive current
T
94BBV28581 05/2013
Parameter that can be modified during operation or when stopped.
Page 95
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s
Code
FLt-
USb-
USb
StP
StM
T
FLt-
Strt
nO
rMP
nO
YES
Name/DescriptionAdjustment rangeFactory setting
Fault detection management menu (continued)
Undervoltage menu
M Undervoltage fault management
Behavior of the drive in the event of an undervoltage
O
1
v Detected fault and R1 relay open.
v Detected fault and R1 relay closed.
M Undervoltage prevention
Behavior in the event of the undervoltage fault prevention level being reached
v No action (freewheel)
v Stop following an adjustable ramp Undervoltage ramp deceleration time StM.
M Undervoltage ramp deceleration time
Ramp time if Undervoltage prevention StP = rMP.
0.0 to 10.0 s1.0 s
0
nO
Fault detection management menu (continued)
M IGBT test
v No test
v The IGBTs are tested on power up and every time a run command is sent. These tests cause a slight
delay (a few ms). In the event of a fault, the drive will lock. The following faults can be detected:
Enabling the fault inhibition parameter InH will disable the drive controller protection features.
• InH should not be enabled for typical applications of this equipment.
• InH should be enabled only in extraordinary situations where a thorough risk analysis demonstrates that the
presence of adjustable speed drive protection poses a greater risk than personnel injury or equipment damage.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
T
BBV28581 05/201395
Parameter that can be modified during operation or when stopped.
Page 96
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
Code
FLt-
SLL
drn
nO
YES
Name/DescriptionAdjustment rangeFactory setting
Fault detection management menu (continued)
M Modbus fault management
Behavior of the drive in the event of a communication fault with integrated Modbus.
v Fault ignored
v Freewheel stop
YES
WARNING
LOSS OF CONTROL
If Modbus fault mgtSLL is set ton0, communication control will be inhibited. For safety reasons, inhibition of
communication fault should only be used for adjustment or special applications purpose.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
M Degraded line supply operation
NOTICE
RISK OF DAMAGE TO THE DRIVE
When Derated operation = Yes, use a line choke.
Failure to follow these instructions can result in equipment damage.
nO
Lowers the tripping threshold of the USF fault to operate on a line supply down to 50% of nominal line
voltage. In this case, the performance of the drive cannot be guaranteed
nO
YES
rPr
T
nO
FtH
To change the assignment of this parameter press the “ENT” key for 2 s.
T
Parameter that can be modified during operation or when stopped.
v nO
v Yes
M Reset power run
This reset will initialize the settings located on MOn section, menu MAI-, page 41.
v nO
v Reset fan time display
nO
96BBV28581 05/2013
Page 97
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
FLt-
EtF-
EtF
EPL
LFF
nO
L1H
L2H
L3H
L4H
L1L
L2L
L3L
L4L
nO
YES
LFF
Name/DescriptionAdjustment rangeFactory setting
Fault detection management menu (continued)
External fault
M External fault assignment
Assignment of the external fault event to a logic input
v Function inactive
v LI1 active High
v LI2 active High
v LI3 active High
v LI3 active High
v LI1 active low
v LI2 active low
v LI3 active low
v LI3 active low
M Stop type - external fault
Type of stop in the event of an external fault
v External fault ignored
v Freewheel stop
v Switch to Fallback speedLFF as long as the external fault is present and the run command is not
disabled.
M Fallback speed
Selection of the fallback speed in case of external fault event.
Visible only if Stop type - external faultEPL is not set to Fallback speedLFF.
Note: This parameter can also be accessed in the PID menu.
0 to HSP0 Hz
nO
nO
BBV28581 05/201397
Page 98
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
COM-
Add
tbr
tFO
ttO
ICS-
4.8
9.6
19.2
38.4
8o1
8E1
8n1
8n2
Name/DescriptionAdjustment rangeFactory setting
Communication menu
Note: For following parameters, the modifications will be taken into account only at the next control power-on.
M Modbus address
Modbus address is adjustable from OFF to 247. When OFF, communication is not active.
M Modbus baud rate
OFF to 247OFF
19.2
v 4.8 kbps
v 9.6 kbps
v 19.2 kbps
v 38.4 kbps
M Modbus format
8E1
v 8o1
v 8E1
v 8N1
v 8N2
M Modbus time out
The drive detects a Modbus fault if it does not receive any Modbus request at its address within a
predefined time period (time-out).
0.1 to 30 s10 s
Input scanner menu (values are expressed in hexadecimal)
nMA1
nMA2
nMA3
nMA4
OCS-
nCA1
nCA2
nCA3
M Com scanner read address parameter 1
Address of the first input word.
M Com scanner read address parameter 2
Address of the second input word.
M Com scanner read address parameter 3
Address of the third input word.
M Com scanner read address parameter 4
Address of the fourth input word.
Output scanner menu (values are expressed in hexadecimal)
M Com scanner write address parameter 1
Address of the first output word.
M Com scanner write address parameter 2
Address of the second output word.
M Com scanner write address parameter 3
Address of the third output word.
0C81
219C
0
0
2135
219A
0
nCA4
98BBV28581 05/2013
M Com scanner write address parameter 4
Address of the fourth output word.
0
Page 99
Configuration Mode - Complete menu (FULL)
I-O-
drC-
CtL-
FUN-
FLt-
COM-
Code
COM-
ISA-
nM1
nM2
nM3
nM4
OSA-
nC1
T
nC2
T
nC3
T
nC4
T
Name/DescriptionAdjustment rangeFactory setting
Communication menu (continued)
Input scanner access menu (values are expressed in hexadecimal)
M Com scanner read address value 1
Value of the first input word
M Com scanner read address value 2
Value of the second input word
M Com scanner read address value 3
Value of the third input word
M Com scanner read address value 4
Value of the 4rd input word
ETA VALUE
RFRD value
8000
8000
Output scanner access menu (values are expressed in hexadecimal)
M Com scanner write address value 1
Value of the first output word
M Com scanner write address value 2
Value of the second output word
M Com scanner write address value 3
Value of the third output word
M Com scanner write address value 4
Value of the fourth output word
CMD value
LFRD value
8000
8000
T
BBV28581 05/201399
Parameter that can be modified during operation or when stopped.
Page 100
Maintenance
Servicing
The Altivar 12 does not require any preventive maintenance. However, it is advisable to perform the following checks regularly:
• The condition and tightness of connections.
• Ensure that the temperature around the unit remains at an acceptable level and that ventilation is effective. Average service life of
fans: 10 years.
• Remove any dust from the drive.
• Ensure proper fan operation.
• Physical damage to covers.
Assistance with maintenance, detected fault display
If a problem arises during setup or operation, ensure that the recommendations relating to the environment, mounting and connections have
been observed.
The first fault detected is stored and displayed, flashing, on the screen: the drive locks and the status relay R1 contact opens.
Clearing the detected fault
In the event of a non-resettable detected fault:
• Remove/cut the power to the drive.
• WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the “Bus Voltage Measurement Procedure”, page 14
verify that the DC voltage is less than 42 V. The drive LEDs are not indicators of the absence of DC bus voltage.
• Find and correct the detected fault.
• Restore power to the drive to confirm the detected fault has been rectified.
to
Certain detected faults can be programmed for automatic restart after the cause has disappeared.
These detected faults can also be reset by cycling power to the drive or by means of a logic input or control bit.
Display menu
Use the display menu to show the status of the drive and it's current values as an aid for finding the causes of detected faults.
Spares and repairs
Serviceable product: Refer to the catalog for replacement of spare parts.
Procedure after a long time storage
NOTICE
RISK OF DEGRADED PERFORMANCE DUE TO CAPACITOR AGING
The product capacitor performances after a long time storage above 2 years can be temporarily degraded and therefore following
reforming procedure should be applied. In that case, before using the product, apply the following procedure:
• Use a variable AC supply connected between L1 and L2.
• Increase AC supply voltage to have:
- 80% of rated voltage during 30 min
- 100% of rated voltage for another 30 min
Failure to follow these instructions can result in death, serious injury, or equipment damage.
100BBV28581 05/2013