NOTICERead these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Danger or Warning safety label indicates
that an electrical hazard exists, which will result in personal injury if the
instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will
result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result
in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result
in injury or equipment damage.
08/20075
Safety Information
PLEASE NOTEElectrical equipment should be installed, operated, serviced, and maintained only by
Document ScopeThe XPSLCM1150 Mute Module is an accessory device used to provide a safety-
rated muting function in conjunction with safety light curtains. Muting is defined as
«bypassing the protective function on safety related control system such as a safety
light curtain, during a pre-determined operation of a machine.»
Validity NoteThe data and illustrations found in this book are not binding. We reserve the right to
modify our products in line with our policy of continuous product development. The
information in this document is subject to change without notice and should not be
construed as a commitment by Schneider Electric.
08/20077
About the Book
Product Related
Warnings
WARNING
IMPROPER SET UP OR INSTALLATION.
Read all responsibilties and requirements listed below before installing the
XPSLCM1150 module.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
UNINTENDED OPERATION.
Muting can disable the safety functions of a machine. The proper installation,
checkout and operation of a machine and muting system in accordance with all
applicable laws and standards, is critical to the safe operation of the machine.
Failure to comply with these instructions may result in severe injury to personnel..
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
REDUCED PROTECTION LEVEL
When the XPSLCM1150 module is used with a Type 2 rated light curtain or another
Type 2 device, the overall system protection is reduced to Category 2.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Whether a specific machine application and XPSLCM1150 installation complies with
safety regulations depends on several factors, including the proper application,
installation, maintenance and operation of the XPSLCM1150 and its associated
sensors. These items are the responsibility of the purchaser, installer and employer.
The employer is responsible for the selection and training of personnel to properly
install, operate and maintain the machine and its safeguarding systems.
This product is designed to comply with:
IEC61496-1
ANSI B11.19 - 1990
EN954-1
8
08/2007
About the Book
The XPSLCM1150 should only be installed, verified and maintained by a qualified
person, as «a person or persons who, by possession of a recognized degree or
certificate of professional training, or who, by extensive knowledge, training or
experience, has successfully demonstrated the ability to solve problems relating to
the subject matter and work.».
Use of a muting function requires special precautions by the safety system machine
controller, installer, operator and employer. The following is only a partial list of
requirements when utilizing muting and is not intended to be a complete guide to
muting standards. The employer must contact the local safety authority for specific
requirements regarding the machine, machine controller and safety related control
system. Schneider provides the following information for user reference only and
makes no claim regarding the accuracy, completeness or effectiveness for a specific
application from any organization:
Muting of the light curtain is only permitted during the nonhazardous portion of
the machine cycle.
If the machine tool has reversing capability where a muting hazard is possible the
control shall include an automatic means through which muting is only permitted
in the forward direction.
Selection of the muting feature shall be by a key-operated switch under
supervisory control by the employer.
One or more visual indicator(s) shall be provided which are illuminated when the
light curtain is in a muted condition.
Any fault condition of the mute indicator(s) shall not allow the light curtain to enter
a mute condition.
The mute indicator(s) should be readily visible from any normal machine operator
position and from the position at which any adjustment of the muting is normally
carried out.
There shall be at least two, independent muting signal sources to be used with
the XPSLCM1150. A single, simple cam-operated limit switch is inadequate as a
muting signal source since its failure can remain undetected.
The proper selection, installation and orientation of the muting sensors are the
responsibility of the employer and installer.
The muting position (of the mute signal source) shall be secured against
unauthorized adjustment by provision of special tools, key entry, electronics
passwords and the positioning and mounting of associated limit switches.
The guarded machine must be able to stop anywhere in its cycle. Do not use an
XPSLCM1150 on a press with a full-revolution clutch.
The guarded machine must have a consistent stopping time and adequate
control mechanisms.
Severe smoke, particulate matter and corrosives may degrade the efficiency of
the optical safety devices. Do not use optical safety devices in this type of severe
environment.
All applicable governmental, state, local and employers rules, codes and
regulations must be satisfied. This is the employers responsibility.
08/20079
About the Book
All safety-related machine control elements must be designed so that a fault in
the control logic or failure of the control circuit does not lead to a failure or danger.
Additional guarding may be required for access to dangerous areas not covered
by the safety device system.
Perform the test procedure at installation and after maintenance, adjustment,
repair or modification to the machine controls, tooling, dies or machine, or the
XPSLCM1150 and safety device system.
Follow all procedures in this manual for proper operation of the XPSLCM1150
Mute Module.
The enforcement of these requirements is beyond the control of the manufacturer.
The employer has the sole responsibility to follow the preceding requirements and
any other procedures, conditions and requirements specific to his machinery.
User CommentsWe welcome your comments about this document. You can reach us by e-mail at
techpub@schneider-electric.com
10
08/2007
Description of XPSLCM1150
At a glance
OverviewThis chapter describes the XPSLCM1150.
1
What's in this
Chapter?
This chapter contains the following topics:
TopicPage
Description of XPSLCM1150 mute module12
Description of Controls14
Adjusting the safe mounting distance19
Technical ratings20
Terminal assignments22
Installation wiring example23
XPSLCM1150 visible indicators28
Operating states and corresponding outputs30
Cable lengths33
Setting XPSLCM1150 configuration switches34
Dimensions36
08/200711
Description of XPSLCM1150 mute module
Front panelXPSLCM1150 Front panel
Features
The XPSLCM1150 Mute Module is a Category 4 safety device that interfaces
between a machine and certain protective safety devices to temporarily suspend
those devices during the non-hazardous portion of the machine cycle. It conforms
with EN 954-1 and has been certified to IEC 61496-1.
Fast 1 ms response time.
Works with either 1 or 2 safety devices (safety light curtain, safety controller, etc.)
Two-channel mute sensor inputs for 2, 3 or 4 PNP-type electro-optic sensors, or
limit switches or other sensing devices.
LED indications for individual input and output status.
Two-digit diagnostic display.
External mute indication for operator awareness.
1208/2007
Applications
Automatic conveyer, stacker and palletizing machines.
Mechanical and hydraulic presses with automatic or manual feed with the muting
function is only used in the non-hazardous portion of the press cycle.
When the mute mode is disabled, the XPSLCM1150 outputs are the same as those
of the connected safety devices. Any entry into the guarded area will result in a stop
signal being sent to the guarded machine.
The XPSLCM1150 provides two "mute safety channels", each accepts a single
safety device, and either two, three or four mute sensors to activate the mute mode.
The mute mode is active when the correct sequence of mute sensor input signals is
achieved.
Each safety device output must be capable of supplying two 24 V (PNP) output
signals when the sensing field is clear. Mute sensors must have PNP type outputs,
sensor pairs are made-up of both "dark operate" and "light operate" sensors.
An indicator lamp for each safety channel is required to illuminate anytime the
XPSLCM1150 is in the mute state. These lamps must be visible to personnel in the
immediate area. The XPSLCM1150 monitors the lamp circuit to ensure the indicator
is operational.
08/200713
Description of Controls
IMPROPER INSTALLATION
Muting can disable the safety functions of a machine. The proper installation,
checkout and operation of a machine and muting system; in accordance with all
applicable laws and standards, is critical to the safe operation of the machine.
Failure to comply with these instructions may result in severe injury to personnel.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
Power
requirements
The XPSLCM1150 requires a dedicated power supply of 24 V +/- 10 %, providing
a minimum of 2 amperes that meets the requirements of IEC61496-1 and
IEC60204-1, part number ABL8RPS24030 or equivalent.
System Common Return
For proper operation, the power supply common, (0 V ), must be connected to
each of the components in the system, including start/enable switches, EDM/MPCE
monitor, all OSSD and Auxiliary loads.
Chassis Ground or Protective Earth (PE) Connection
The chassis ground terminal of the XPSLCM1150 must be connected to the earth
ground of the installation site to ensure protection from electrical interference and
high voltage transients.
1408/2007
XPSLCM1150
input devices
Sensor Inputs
The XPSLCM1150 module accommodates up to two independent channels
identified as Channel 1 & Channel 2. Each channel is comprised of one safety input
device and either two, three, or four mute input sensors.
Safety Input Devices (OSSD Inputs)
The XPSLCM1150 supports safety devices such as safety light curtains, safety
controllers or other safety-rated devices that provide two 24 V inputs into the
XPSLCM1150 whenever their protected area is clear.
Note: If using an input from a relay-type safety device, the two OSSD signals must
switch to the On and Off state within 300 msec of each other to be recognized as
proper OSSD inputs.
Mute Sensor Inputs
Muting is controlled by two or more separate input sources. These devices can be
optical, inductive or mechanical. Sensors S1A, S1C, S2A & S2C must have «DarkOn» PNP type outputs, nominal 24 V when Ok to mute. Sensors S1B, S1D, S2B
& S2D must have «Light-On» PNP type outputs, nominal 0 volts (no current flow)
when Ok to mute.
WARNING
IMPROPER SET UP OR INSTALLATION
You must have at least two independent mute sensors to activate the mute circuit.
A single device with multiple outputs such as single limit switch, is inadequate as a
mute sensor since its failure can remain undetected. Failure to comply with this
requirement may cause the muting circuit to activate at the incorrect part of the
machine cycle. Serious injury to personnel could result.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Mute Enable / Disable
A single selector switch is used to enable the XPSLCM1150 to detect the mute input
sensors, or disable the XPSLCM1150 from entering the mute state. When in the
disable position all muting errors are cleared from the diagnostic display.
08/200715
Start Switch
A push-button switch is required to reset the XPSLCM1150 from a Start/Interlock
condition, a fault interlock, or allow the Bypass feature to be used. The input is DIP
switch selectable for N/O or N/C operation.
WARNING
IMPROPER INSTALLATION OF THE START BUTTON
The Start switch shall be located outside of the safeguarded area such that it
cannot be reached from within the safeguarded area. The location must allow
complete visibility of the guarded area. The operator must ensure that the
safeguarding zone is clear before press & release of Start.This prevents the
machine or muting function from starting while personnel may be in the hazardous
area and avoids possible serious injury to personnel.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
1608/2007
XPSLCM1150
outputs
WARNING
IMPROPER OUTPUT OPERATION
Muting is only allowed during the non-hazardous portion of the machine cycle! A
muting application must be designed so that no single component failure can
prevent the stop command or allow subsequent cycles until the failure is corrected.
(USA standard OSHA 1910.217(c)(3)(iii) (d), ANSI B11.19-1990 section 4.2.3.3.7)
Failure to comply with this requirement may cause the muting circuit to activate at
the incorrect part of the machine cycle, serious injury to personnel could be
resulted.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Output Signal Switching Devices (OSSD’s)
The XPSLCM1150 uses two solid-state outputs to send a stop signal to the guarded
machine. When the XPSLCM1150 is in the normal Run mode with the safety
device(s) clear, or in the Mute mode regardless of the safety device(s) status, the
OSSD outputs are turned on, sourcing 24 V @ a maximum of 625 mA.
Solid-state outputs achieve their safety ratings by periodically switching the output
state and verifying that the device did indeed switch. This operation is performed
periodically and is essentially transparent to the machine control circuit.
WARNING
IMPROPER OUTPUT SET UP
You Must Use both OSSD safety outputs from the XPSLCM1150! Each output
must be wired such that it is capable of stopping the guarded machine. Failure to
use both XPSLCM1150 safety outputs may prevent the machine from stopping,
resulting in possible severe injury to personnel.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Auxiliary Outputs
The XPSLCM1150 provides non-safety auxiliary outputs in both PNP and NPN
configurations. The PNP output source 24 V @ 500 mA, the NPN output sinks
up to 100 mA.
The auxiliary outputs are user selected to either follow the OSSD outputs, or activate
when a fault condition is detected.
08/200717
Mute Lamp Outputs 1 & 2
A visible mute lamp is required for each channel of the XPSLCM1150 to indicate the
mute function is active. Mute Lamp outputs are NPN current sinking inputs. Each
input is monitored to ensure 40-300 mA is flowing through the circuit when Mute is
activated. If the required current is not detected, then the XPSLCM1150 will not
enter the Muting state and will display diagnostic codes. If a current is detected when
the mute function is NOT activated, the XPSLCM1150 will enter the Lockout state.
WARNING
IMPROPER MUTE INDICATION
An indication that the protected area is muted must be provided and readily
observable to the machine operator. The mute lamp is an important warning device
to the machine operator, indicating that muting is active.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Mute Indicator Auxiliary Outputs
Mute Auxiliary and Mute Armed functions are available as non-safety-rated outputs.
Each is configured as NPN sinking at a maximum of 100 mA. Mute Aux will indicate
whenever the XPSLCM1150 is in the Muting state. Mute Armed will indicate the
XPSLCM1150 is Mute Enabled.
EDM/MPCE Monitor
The XPSLCM1150 OSSD outputs are designed to connect directly to the machine
primary control element, or EDM/MPCE. EDM/MPCE monitoring is the capability to
directly monitor machine control devices and ensure their operation coincides with
the commands of the XPSLCM1150.
1808/2007
Adjusting the safe mounting distance
Using the
XPSLCM1150
without
mechanical
relays
Using the
XPSLCM1150
with safety
mechanical
relays
The XPSLCM1150, when used without mechanical relays, will add 1 millisecond
(0.001 sec) to the overall response time of the safety control system. This will
increase the safe mounting distance of the safety sensing device. See the
installation manual of the safety sensing device for further information on calculating
the proper safeguarding distance.
The XPSLCM1150 itself adds 1 millisecond (0.001 sec) to the response time of the
safety control system. Additionally, you must also add the response time of the
mechanical relays to determine the total impact on the safety control system. This
will increase the safe mounting distance of the safety device.
The XPSLCM1150 should only be used with safety rated mechanical relays
employing force guided contacts. Contact the relay supplier for the safety rating
suitability and response time.
Refer to the installation manual of the safety sensing device for further information
on the safe mounting distance.
08/200719
Technical ratings
Specifications
Safety CategoryType 4 per IEC 61496-1.
Response TimeLess than 1 msec.
Input Power24 V +/- 10%, 150 W max. (a) 24 V +/- 10%, 6 W (250mA)
min
Operating Temperature0 °C to 55 °C.
HumidityLess than 95% Non Condensing
Storage Temperature-25 °C to 75 °C
VibrationIn accordance with IEC 60068-2-6, 0.35mm displacement, 10 to
55 Hz.
ShockIn accordance with IEC 60068-2-29, 10g, 16 ms pulses, 1000/
axis.
EnclosureIP-20
Outputs
Safety Outputs (OSSD)Two independent 625 mA (max.) current sources (PNP), 24 V
.
Auxiliary OutputsAuxiliary NPN output: 100 mA (max.) current sink, 24 V max.
Auxiliary PNP output: 500 mA (max.) current source, 24 V .
Mute-LampTwo (NPN) Outputs 40-300 mA, 24 V Max. (b)
Start / RestartEither N/O or N/C Momentary Contact (10 mA consumption)
PNP 24V @ 50 mA Machine Run, 0 volt Machine Stop
(a) Power to the XPSLCM1150 must be provided from a dedicated power supply
that meets the requirements of IEC 60204-1 and IEC 61496-1, Schneider part
number ABL8RPS24100 (150 W) or equivalent maxi loads on outputs.(not included
NPN outputs, mute lamps, sensors and light curtains).
2008/2007
(b) The external lamp must provide a current load between 40 mA and 300 mA for
the lamp monitoring circuit to sense proper operation of the mute lamp.
Power Supply
Requirement
Total System Components
4 sensor muting system Full output load + Full
temperature range
1 light curtain XUSLTABL8RPS24050ABL8RPS24030 (Iout < 1.45 A)
1 light curtain XUSLMABL8RPS24030 (Iout < 1.60 A)
1 light curtain XUSLPABL8RPS24030 (Iout < 1,7 A)
1 light curtain XUSLNABL8RPS24030 (Iout < 1,9 A)
2 light curtains XUSLNABL8RPS24030 (Iout < 1,4 A)
2 light curtains XUSLPABL8RPS24030 (Iout < 0,9 A)
1 light curtain XUSLT
1 light curtain XUSLN
1 light curtain XUSLN
1 light curtain XUSLP
2 light curtains XUSLTABL8RPS24100ABL8RPS24030
2 light curtains XUSLMABL8RPS24030
1 light curtain XUSLT
1 light curtain XUSLP
1 light curtain XUSLT
1 light curtain XUSLM
1 light curtain XUSLM
1 light curtain XUSLN
1 light curtain XUSLM
1 light curtain XUSLP
Reduced output load (1)+ Full
temperature range
ABL8RPS24030 (Iout < 0,9 A)
ABL8RPS24030 (Iout < 1,2 A)
ABL8RPS24050
(Iout < 0.5 A)
(Iout < 0.75 A)
ABL8RPS24030
(Iout < 0.65 A)
ABL8RPS24030
(Iout < 1,1 A)
ABL8RPS24030
(Iout < 0,8 A)
(Iout < 2.3 A)
ABL8RPS24050
(Iout < 2.55 A)
ABL8RPS24050
(Iout < 2.45 A)
ABL8RPS24050
(Iout < 2,9 A)
ABL8RPS24050
(Iout < 2,6 A)
Note: (1): Output load I out = XPSLCM1150 OSSD output currents including light
curtain Aux output, Mute lamp Aux output and Mute Lamps.
08/200721
Terminal assignments
Function Pin
Assignment
Pin #FunctionAssignmentPin #FunctionAssignment
1XPS Outputs
2OSSD B33
3EDM/MPCE MON32
40 V 31
5AUX-PNP30
6AUX-NPN29Mute Input
7Mute OutputsMUTE-LAMP 128OSSD 2B
8MUTE-LAMP 227SENSOR 2A
9MUTE-AUX26SENSOR 2B
10MUTE-ARMED25SENSOR 2C
11XPS Control
12MUTE-ENABLE HI23Mute Input
13MUTE-ENABLE
14Not used21SENSOR 1A
15Power+24 V 20SENSOR 1B
160 V 19SENSOR 1C
17Earth Ground18SENSOR 1D
& EDM/MPCE
Input
Inputs
OSSD A34
OSSD 2A
Channel 2
START24SENSOR 2D
OSSD 1A
22OSSD 1B
LO
Channel 1
The XPSLCM1150 power input return (0 V ) must be connected to the overall
system component returns. Safety Light curtains, start switch, EDM/MPCE monitor,
OSSD loads and auxiliary loads must be all connected in common for proper system
operation.
The Earth Ground terminal of the XPSLCM1150 must be connected to the enclosure
or chassis ground of the installation site. Protection devices internal to the
XPSLCM1150 that provide immunity from electrical interference connect to this
earth ground terminal.
2208/2007
Installation wiring example
DescriptionXPSLCM1150 Mute Module with two sensing channels connected.
Note:
The Start switch must be located in an area that allows complete visibility of the
guarded area. The operator must ensure that the protection zone is clear before
press & release of Start.
Mute sensors S1A, S1C, S2A & S2C must have 'Dark-On' PNP type outputs,
nominal 24 V when Ok to mute and nominal 0 V when no mute. Mute
sensors S1B, S1D, S2B & S2D must have ‘Light-On' PNP type outputs, nominal
0 V when Ok to mute and nominal 24 V when no mute.
08/200723
WiringWiring Diagram Example with 2 Light Curtains Connected (XUSLT and XUSLM):
Mute
9
rm
Mu_Aux
Mu_A
Mute
outputs
inputs
B
S-2
S-2C24S-2D23OSS 1
26
8
27
M-Lamp27M-Lam
A
S-2
Lamp
(XUSLM)
Mute
Lamp
(XUSLT)
6
5
p1
Aux NPN
B
OSS 2A28OSS 2
29
K1K1
K2
4
32
PNP
0VDC
x
OSSDB1OSSDA
Au
EDM/MPCE Mo n
Outputs
K2
22
XPSLCB1141
Ret
OSSD218OSSD119OSSD
20
101189
Start
Start Ret
Shielded
cables
EDM/MPCE
EDM/MPCE Ret
Tran smit terReceiver
3
GND
0VDC3+24V
1
2
NL
GND NL
ABL8RPS
dedicated
supply
0V 24V
GND
F1
Start
Mute
Mute
enable
Disable
17
16
15
14 13
12
11
10
t
o
r
l
GND
Power
0VDC
+24VDC
Mu-en-
Inputs
Sta
Mu-en-hi
XPSLCM1150
Channel 1Channel 2
1
inputs
A
S-1A20S-1B19S-1C18S-1D
OSS 1B
21
25
22
tart
AUX
GND
3
BN
BU
BK
BN
BU
BK
BN
BU
BK
BN
BU
BK
S
+24V
0VDC
OSSD2
EDM/MPCE
ReceiverTransmitter
XUSLTXUSLT
OG
Sensor A
PNP dark-on type
OG
Sensor B
PNP light-on type
OG
Sensor C
PNP dark-on type
OG
Sensor D
PNP light-on type
OSSD1
GND
0VDC
MTS
+24V
MTS Ret
Sensor A‘
PNP dark-on type
Sensor B‘
PNP light-on type
Sensor C’
PNP dark-on type
Sensor D’
PNP light-on type
Receiver
XUSLM
BN
BU
BK
BN
BU
BK
BN
BU
BK
BN
BU
BK
Transm itter
XUSLM
OG
OG
OG
OG
2408/2007
Note: Transmitter and receiver sensors can also be used.
Legend
Install a wire between 0V and Ground
1
To choose the dedicated supply, see Power Supply Requirement, p. 21
The coils must be suppressed with the arc suppressors provided in the
2
documentation kit of the light barriers
The light barriers must be configured with EDM/MPCE monitoring disabled
3
08/200725
WiringWiring Diagram Example with 2 Light Curtains Connected (XUSLP and XUSLN):
Mute
9
8
x
Au
u_
M
Mu_Ar m
M-Lamp 27M-
Mute
outputs
inputs
B
S-2A26S-2
S-2C24S-2D23OSS 1A
27
MTS
+24V
XUSLPZ
Transmitter
Lamp
(XUSLN)
Lamp
(XUSLP)
Lamp1
OSS 2B
29
28
0VDC
Mute
6
GND
K1K1
K2
5
4
32
P
N
0VDC
Aux P
Aux NPN
EDM/MPC E Mon
Outputs
OSS 2A
Sensor A‘
PNP dark-on type
OSSDB1OSSDA
K2
22
+24V
0VDC
4
rt
ta
S
XUSLN
+24V
XUSLN
TransmitterReceiver
0VDC
OG
OSSD2
OSSD1
BN
BU
BK
NL
GND NL
ABL8RPS
dedicated
supply
0V 24V
GND
F1
Start
Mute
Mute
Disable
enable
17
16
15
14 13
12
11
10
o
l
GND
Power
0VDC
+24VDC
Mu-en-
Inputs
Start
Mu-en-hi
XPSLCM1150
Channel 1Channel 2
GND
0VDC
3
XUSLPZ
Receiver
BN
BU
BK
inputs
+24V
EDM/MP CE
OG
B
S-1A20S-1B19S-1C18S-1D
OSS 1
21
22
AUX
Start
OSSD2
XUSLPB
Transmitter
Receiver
Sensor A
PNP dark-on type
25
Ret
OSSD1
MTS
1
OG
BN
BU
BK
BN
BU
BK
BN
BU
BK
Sensor B
PNP light-on type
OG
Sensor C
PNP dark-on type
OG
Sensor D
PNP light-on type
Sensor B‘
PNP light-on type
Sensor C’
PNP dark-on type
Sensor D’
PNP light-on type
OG
BN
BU
BK
OG
BN
BU
BK
OG
BN
BU
BK
2608/2007
Note: Tranmiter and receiver sensors can also be used.
Legend
Install a wire between 0V and Ground
1
To choose the dedicated supply, see Power Supply Requirement, p. 21
The coils must be suppressed with the arc suppressors provided in the
2
documentation kit of the light barriers
The light barriers must be configured with EDM/MPCE monitoring disabled
3
When the XPSLCM1150 module is used with a Type 2 rated light curtain or
4
another Type 2 device (XUSLN for example), the overall system protection is
reduced to Category 2
08/200727
XPSLCM1150 visible indicators
DescriptionFront panel and indicators
2808/2007
XPS StatusColorStateDescription
Mute EnableYellowONExternal mute enable switch is set to ON
InterlockYellowONInterlock State, waiting Start signal
YellowFLASH Lockout State (Internal or External Fault
Detected)
Machine StopRedONXPS OSSD Safety outputs are OFF
Machine RunGreenONXPS OSSD Safety Outputs are ON
Channel 1 & 2 Status
OSSD A/BGreenONBoth OSSD Inputs from Safety Device are On.
S-AYellowONMuting Sensor S1-A is blocked (activated)
S-BYellowONMuting Sensor S1-B is blocked (activated)
S-CYellowONMuting Sensor S1-C is blocked (activated)
S-DYellowONMuting Sensor S1-D is blocked (activated)
Diagnostic Display two digit numeric display that provides diagnostic codes.
08/200729
Operating states and corresponding outputs
Corresponding
table
XPSLCM1150 Operating States and Corresponding Outputs:
OutputMutingBypass
Allowed
Machine Run, Green
LED
Machine Stop, Red
LED
Interlock or Fault,
Yellow LED
OSSD A OUTPUTONOFFONOFFOFFOFF
OSSD B OUTPUTONOFFONOFFOFFOFF
AUXILIARY
OUTPUTS
MUTE-LAMP 1 *
OUTPUT
MUTE-LAMP 2 *
OUTPUT
MUTE-AUX OUTPUTONBLINKINGOFFOFFOFFOFF
MUTE-ARMED
OUTPUT
Follow
OSSD
Alarm
Mode
ONOFFONOFFOFFOFF
OFFONOFFONONON
OFFOFFOFFOFFONBlinking
ONOFFONOFFOFFOFF
OFFOFFOFFOFFOFFON
ON when
Ch#1 is
being
muted
ON when
Ch#2 is
being
muted
ONONXXXX
BLINKING
when Ch #1
causes
Bypass
BLINKING
when Ch #2
causes
Bypass
Machine
Run
OFFOFFOFFOFF
OFFOFFOFFOFF
Machine
Stop
Interlock Lockout
(Fault)
X = This output is dependent on Mute Enable input signal.
* = Use the mute lamp supplied with the module or be ordered separately in
accessory.
3008/2007
Waveform
Diagram
On state
"Start/Restart Interlock" mode with 2 sensors
Muting < 10 mn
1 Light
Curtain
Cut off
< 3 s
Off state
Module Setup
Module alarm
Power supply
< 3 s
1 Light
Curtain
Cut off
< 1 ms
< 1 ms
Mu-en-hi
Mu-en-lo (13)
Start (11) (*)
S.1A
S.1B (20)
OSSD 1A
OSSD 1B (22)
Channel 1 InputsInputs
M-lamp-1 (7)
Mu-Aux (9)
Mu-Arm (10)
Mute Outputs
EDM/MPCE (3)
OSSD A (1)
OSSD B (2)
Aux PNP
Output
Aux NPN
(12)
(21)
(23)
Aux
(5)
Alm
Aux
(6)
Alm
(*) Press “START” button
08/200731
On state
"Start/Restart Interlock" mode with 4 sensors
Off state
Module Setup
Module alarm
Power supply
Muting < 10 mn
< 3 s
1 Light Curtain
Cut off
< 3 s
1 Light
Curtain
Cut off
< 1 ms
Mu-en-hi
Mu-en-lo
Start
OSSD 1A
Channel 1 InputsInputs
OSSD 1B
M-lamp-1
Mu-Aux
Mu-Arm
Mute Outputs
EDM/MPCE
OSSD A
OSSD B
Aux PNP
Output
Aux NPN
(11)
S.1A
S.1B
S.1C
S.1D
(12)
(13)
(*)
(21)
(20)
(19)
(18)
(23)
(22)
(7)
(9)
(10)
(3)
(1)
(2)
Aux
(5)
Alm
Aux
(6)
Alm
(*) Press “START” button
3208/2007
Cable lengths
CablesThe following table lists the recommended maximum lengths for the XPSLCM1150
input & output signals. Unshielded cables and wires may be used for all connections.
Signal NamesCable or WireSpecified max. length
Safety outputs A & B
Aux PNP and Mute Lamps 1
& 2 outputs
Aux NPN, Mute Aux and
Mute Armed outputs
Light curtain safety inputs
Mute sensor inputs
Start input
EDM/MPCE Monitor input
20 AWG (0.3117 mm
2
with cable capacitance <
100 pF/ft. (<30pF/m)
18 AWG (0.82 mm
22 AWG (0.4418 mm
20 AWG (0.3117 mm
2
) wire
2
2
with cable capacitance <
100 pF/ft. (<30pF/m)
22 AWG (0.4418 mm
22 AWG (0.4418 mm
22 AWG (0.4418 mm
300 mA load: 70 meter (230 ft.)
) wire
625 mA load: 35 meter (115 ft.)
50 meter (164 ft.)
100 meter (330 ft.)
) wire
100 meter (330 ft.)
) wire
2
100 meter (330 ft.)
) wire
2
100 meter (330 ft.)
) wire
2
100 meter (330 ft.)
) wire
08/200733
Setting XPSLCM1150 configuration switches
PrincipleThe XPSLCM1150 is configured for the various operating modes through the use of
two banks of eight-position DIP switches and a single two-position DIP switch.
Accessing to
configuration
switches
The DIP switches are accessible by removing the front cover. The redundant DIP
switches must be set exactly the same.
Aux and Start
DIP SWITCHES
SWITCHES
SWA
SWB
OPEN
WARNING
IMPROPER MUTE INDICATION
Disconnect power before removing the controller cover.
Replace the controller cover before re-applying power.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
3408/2007
Field
configuration
switch settings
Eight-Position Redundant DIP Switch Settings
SwitchFunction SelectionDescription
1 & 2Start ModeAutomatic Start: 1 = On, 2 = On
Start Interlock: 1 = On, 2 = Off
Invalid Setting: 1 = Off, 2 = On
Start/Restart Interlock: 1 = Off, 2 = Off
3EDM/MPCE MonitoringEnabled = Off, Disabled = On
4Bypass AllowedEnabled = On, Disabled = Off
5Number of Light Curtains1 Light Curtain System = On
2 Light Curtain System = Off
6 & 7Number of Mute SensorsInvalid Setting: 6 = On, 7 = On
2 Sensor System: 6 = On, 7 = Off
3 Sensor System: 6 = Off, 7 = On
4 Sensor System: 6 = Off, 7 = Off
8Muting Time LimitNo time limit = On
2 minute time limit = Off
Two-Position DIP Switch Settings
SwitchFunction SelectionDescription
1Auxiliary Output ModeFollow OSSD output = On
Alarm mode = Off
2Start switch typeNormally Closed switch = On
Normally Open switch = Off
08/200735
Dimensions
Mechanical
drawing
The drawing below gives the XPSLCM1150 dimensions:
Front View
Top View
Bottom View
3608/2007
Right View
Application examples
At a glance
OverviewThis chapter describes some application examples.
2
What's in this
Chapter?
This chapter contains the following topics:
TopicPage
Application information38
Two sensor muting system40
Three sensor muting system43
Four sensor muting system46
Description of the bypass-allowed feature50
08/200737
Application information
PrincipleThe following section contains several application examples of how the
XPSLCM1150 may be used with various arrangements of sensors to start and end
the muting sequence.
Although photoelectric sensors are used in the example, other types of sensors,
such as limit switches, inductive proximity sensors and ultrasonic sensors may be
used as sensor inputs to the XPSLCM1150, provided that they met the electrical
requirements of XPSLCM1150 input devices, p. 15.
Note: Schneider provides the following application examples for user reference
only and makes no claim regarding the accurary, completeness or effectiveness for
a specific application from any organization.
WARNING
IMPROPER INSTALLATION OF SENSORS
The system installer and employer are responsible for the proper selection,
installation and orientation of the muting sensors are critical to ensure that muting
can never be initiated by personnel attempting access through the safeguarding
device. Serious injury to personnel may result.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
3808/2007
Selection and
orientation of the
muting sensors
The object of the correct muting sensor selection and orientation is to always
recognize the presence of the workpiece material as the intended means to start or
stop the muting sequence. The presence of any person in the detection zone of the
muting sensors must never be able to initiate a muting sequence, or otherwise
bypass the safe guarding device.
The proper selection, installation and orientation of the muting sensors are the sole
responsibility of the employer and installer. The following recommendations must be
observed, especially in conveyorized applications.
The muting sensors should detect the material, and not the transportation means,
such as a pallet, cart or other transport device. Ensure that a person on the
transport device cannot initiate muting and enter the hazardous area.
Do not allow interruption in the sensing of the material while passing the muting
sensors. The detection of the material should be continuous over its length.
If using photoelectric sensors, do not allow reflective material to interrupt or cause
optical short circuits among different sensors. Likewise, do not allow sensors in
adjacent areas to interfere or provide false indication.
Position the sensors such that before a new load of material is detected by the
first sensor, the prior material has passed the last sensor and all muting sensors
are deactivated for a period of time.
Consider the overall speed and cycle the material as it moves through the
process. Time must be allowed for evaluating the muting sensors¡¯ output prior
to the material reaching the safeguarding device.
Access by persons into the hazardous area of the machine must be prevented or
detected such that a safeguarding device is able to send a stop signal to the
machine before entering into the hazardous area. Other safeguarding methods,
such as physical barriers or fences, may be necessary.
The muting position (of the sensors) shall be secured against unauthorized
adjustment by provision of special tools, key entry, electronics passwords and the
positioning and mounting of associated limit switches.
08/200739
Two sensor muting system
Conveyor belt
muting system
example
The figure below illustrates one application of a conveyor belt muting system using
a two sensor configuration. The two sensor configuration muting system is bidirectional.
Sensor A
Object
Sensor B
Sensor A
Object
Sensor B
Sensor A
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Conveyor
Bi-Directional
Object
Sensor B
4008/2007
Light
Curtain
Mechanical
press example
The figure below illustrates muting on a mechanical press using two switches to
sense when to enter Muting state. Bottom Dead Center (BDC) is the point at which
the tool is closest to the die. Top Dead Center (TDC) is the point at which the tool is
furthest from the die.
Transition
conditions
Switch B
Switch A
1
BDC
ProtectedMuting
B
A
2
Opening
Stroke
Started
A
Opening
Stroke
Muting in
Progress
B
3
B
A
4
TDC
Muting
Maintained
B
A
5
Closing
Stroke
Muting
Interrupted
B
A
6
Closing
Stroke
Protected
The table below describes conditions required to transition to Muting state with a two
sensor system:
No. of
Sensors
2 Sensor
System
StateMute
Enable
State 1OFFXXXXProtected
State 2ONOFFOFFXXXXProtected
State 3ONOFFONXXXXProtected
State 4ONONOFFXXXXProtected
State 5ONONONXXXXMuting
Sensor A Sensor B Sensor C Sensor DSystem
Status
X = Sensor can be in any state, does not apply to selected mode.
XX = Under normal conditions, these Sensor Inputs should not be connected. When
the MUTE-ENABLE input is active, if at anytime these Sensor Inputs become active,
the Muting system will transition to the LOCKOUT (FAULT) state.
08/200741
Sensor
requirements
Sensor A must be a Dark-On type sensor with PNP type output or a switch that
closes its contact to provide +24 V when it is Ok to mute.
Sensor B must be a Light-On type sensor with PNP type output or a switch that
opens its contact when it is Ok to mute.
In a two sensor system, each sensor must transition to the ON state within 3
seconds of each other for the muting state to occur.
Two Sensor Muting System Waveform Diagram
Muting state
ON state
Sensor-A Input
(Dark -On type sensor)
Sensor-B Input
(Light -On type sensor)
Safety Inputs
(OSSD inputs)
XPS Safety
Outputs (OSSD)
Mute Lamp Output
OFF
OFF
OFF
OFF
OFF
ON state
OFF
0.05<x< 3 sec.
OFF
ON state
ON state
OFF
ON state
ON state
OFF
4208/2007
Three sensor muting system
DescriptionThe three sensor system is a uni-directional system. In this application Sensor C is
used as a direction detector, and must transition to the ON state prior to activation
of sensor pair Sensor B and Sensor A. Sensors Sensor B and Sensor A must
activate within 3 seconds of each other and Sensor C must turn OFF before Sensor
B or Sensor A turn OFF. The figure below illustrates a muting system used in a three
sensor conveyor belt configuration.
Three Sensor System Design
Sensor A
Light
Curtain
Sensor C
Sensor C
Sensor C
Object
Sensor B
Sensor A
Object
Sensor B
Sensor A
Sensor B
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Conveyor
Object
08/200743
Transition
conditions
The table below describes conditions required to transition to Muting state with a
three sensor system:
No. of
Sensors
3 Sensor
System
StateMute
Enable
State 1OFFXXXXProtected
State 2ONOFFOFFOFFXXProtected
State 3ONOFFOFFONXXProtected
State 4ONONONONXXMuting
State 5ONONONOFFXXMuting
Sensor ASensor B Sensor C Sensor DSystem
Status
X = Sensor can be in any state, does not apply to selected mode.
XX = Under normal conditions, these Sensor Inputs should not be connected. When
the MUTE-ENABLE input is active, if at anytime these Sensor Inputs become active,
the Muting system will transition to the LOCKOUT (FAULT) state.
4408/2007
Sensor
requirements
The following conditions must be met for muting state to occur:
Sensors A & C must be a Dark-On type sensor with PNP type output or a switch
that closes its contact to provide +24 V when it is Ok to mute.
Sensor B must be a Light-On type sensor with PNP type output or a switch that
opens its contact when it is Ok to mute.
Sensor C must activate at least 0.05 seconds before sensors A & B.
Concurrence of activation of the sensor pair, sensor A & B, must be within 3
seconds of each other.
Sensor C must remain active until both sensors A & B activate.
Three Sensor Muting System Waveform Diagram
Muting state
ON state
Sensor-C Input
(Dark -On type sensor)
Sensor-A Input
(Dark -On type sensor)
Sensor-B Input
(Light -On type sensor)
Safety Inputs
(OSSD inputs)
XPS Safety
Outputs (OSSD)
Mute Lamp Output
OFF
OFF
OFF
OFF
OFF
OFF
ON state
OFF
0.05 sec.<y
ON state
OFF
0.05<x< 3 sec.
OFF
ON state
ON state
OFF
ON state
ON state
OFF
08/200745
Four sensor muting system
DescriptionTo mute in this bi-directional configuration, a sensor pair (Sensor A & Sensor B or
Sensor C & Sensor D) must transition to the ON state and concur within 3 seconds.
Since conveyor is bi-directional either Sensor A or Sensor D can first be active in the
sequence. The figure below illustrates a Muting system used in a four sensor
conveyor belt configuration.
Light
Curtain
Bi-Directional
Object
Sensor A
Sensor A
Sensor A
Sensor A
Object
Sensor B
Sensor B
Sensor B
Sensor B
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Object
Light
Curtain
Light
Curta in
Light
Curta in
Light
Curta in
Sensor C
Sensor C
Sensor C
Sensor C
Conveyor
Sensor D
Conveyor
Sensor D
Conveyor
Sensor D
Object
Conveyor
Sensor D
Bi-Directional
Bi-Directional
Bi-Directional
Bi-Directional
Object
Conveyor
Light
Sensor A
Curta in
Sensor B
Sensor C
Sensor D
4608/2007
Transition
conditions
The table below describes conditions required to transition to Muting state with a
four sensor system:
No. of
Sensors
4 Sensor
System
StateMute
Enable
State 1OFFXXXXProtected
State 2ONOFFOFFOFFOFFProtected
State 3ONONOFFOFFOFFProtected
State 4ONONONOFFOFFMuting
State 5ONONONONOFFMuting
State 6ONONONONONMuting
State 7ONOFFONONONMuting
State 8ONOFFOFFONONMuting
State 9ONOFFOFFOFFONProtected
Sensor ASensor BSensor CSensor DSystem
Status
X = Sensor can be in any state, does not apply to selected mode.
08/200747
Sensor
Requirements
The following must be met for the XPSLCM1150 to enter or remain in the muting
state:
Sensors A & C must be a Dark-On type sensor with PNP type output or a switch
that closes its contact to provide +24 V when it is Ok to mute.
Sensors B & D must be a Light-On type sensor with PNP type output or a switch
that opens its contact when it is Ok to mute.
Concurrence of activation of sensor pair Sensor A & Sensor B must be within 3
seconds and the concurrence of activation of sensor pair Sensor C & Sensor D
must be within 3 seconds.
Sequence of sensor activation is Sensor A before Sensor B before Sensor C
before Sensor D or the sequence may be in reverse direction, Sensor D before
Sensor C before Sensor B before Sensor A. The time difference between sensor
activation must be at least 0.05 seconds.
To stay in muting state sensor pair Sensor A & Sensor B must remain active until
sensor pair Sensor C & Sensor D activate. In reverse direction sensor pair
Sensor C & Sensor D must remain active until sensor pair Sensor A & Sensor B
activate.
4808/2007
Four Sensor Muting System Waveform Diagram
Muting state
ON state
Sensor-A Input
(Dark -On type sensor)
Sensor-B Input
(Light -On type sensor)
Sensor-C Input
(Dark -On type sensor)
Sensor-D Input
(Light -On type sensor)
Safety Inputs
(OSSD inputs)
XPS Safety
Outputs (OSSD)
OFF
OFF
OFF
OFF
OFF
OFF
0.05<y
ON state
OFF
0.05<x< 3 sec.
OFF
ON state
ON state
OFF
0.05<z< 3 sec.
OFF
ON state
ON state
OFF
ON state
ON state
Mute Lamp Output
08/200749
OFF
OFF
Description of the bypass-allowed feature
PrincipleThe XPSLCM1150 allows supervisory personnel to momentarily override the
machine stop signal of the XPSLCM1150. This function is used during instances
where processing sequence operations did not allow an automatic transition to the
muting state and the XPSLCM1150 safety outputs are in the Off state.
Signals in
bypass-Allowed
state
Enter the
bypass-Allowed
state
The XPSLCM1150 signals that it is in the Bypass-Allowed state by the following
indications:
The mute lamp of the effected safety channel will flash at about a 1-second
interval.
The Mute Aux output will switch between active and inactive at about a 1 Hz rate.
The diagnostic display will show a code of 03.
The XPSLCM1150 will enter the Bypass-Allowed state under the following
conditions:
Redundant DIP switches must be set to enable Bypass-Allowed feature to occur.
The mute enable inputs are active.
The light curtain safety outputs (OSSD) are in the Off state and a minimum of one
mute sensor is active in the effected safety channel.
5008/2007
Transition to the
Muting state
To allow the XPSLCM1150 to transition to the Muting state the supervisory
personnel must press-and-release the start button. When entering the Muting state
through the Bypass-Allowed feature the following will occur:
The mute lamp of the effected safety channel will now be On continuously.
The Mute Aux output will now be continuously in the active state.
The diagnostic display will show a code of 02.
If the light curtain is clear of obstructions before all of mute sensors have cleared
then the XPSLCM1150 will leave the Muting state and enter the Machine Run
state. Note, all of the mute sensors must clear for the XPSLCM1150 to
automatically enter the Muting state during the next process cycle.
If all of the mute sensors clear of obstructions before the light curtain has cleared
then the XPSLCM1150 will leave the Muting state and enter the Machine Stop
state.
When the Muting state is entered through the Bypass-Allowed state then the
maximum time for the XPSLCM1150 to be continuously in the Muting state is 10
minutes.
If the 10 minute time limit is exceeded the XPSLCM1150 will automatically
change from the Muting state to the Bypass-Allowed state.
There is no limit on the number of times that the XPSLCM1150 can enter the
Bypass- Allowed state and then with the press-and-release of the Start button
into the Muting state.
08/200751
Example of
bypass-allowed
A conveyor is operated with an XPSLCM1150 that has one light curtain and three
mute sensors connected. The XPSLCM1150 is set to Start Interlock mode and
Bypass-Allowed is enable.
Conveyor System
Condition
System power is restored.Sensor is
Supervisor verifies that
system is safe to start, the
XPSLCM1150 Start button
is pressed and released.
Conveyor motors are
initially running. Conveyor
motors stop when light
curtain becomes block.
Conveyor motors stop.Sensor is
Supervisor verifies that
system is safe to bypass,
the XPSLCM1150 Start
button is pressed and
released.
Conveyor motors are
running.
Conveyor motors are
running.
Sensor A
Condition
Clear
Sensor is
Clear
Sensor
becomes
Blocked
blocked
Sensor is
blocked
Sensor is
blocked
Sensor
becomes
Clear
Sensor B
Condition
Sensor is
Clear
Sensor is
Clear
Sensor
becomes
Blocked
Sensor is
Blocked
Sensor is
blocked
Sensor is
blocked
Sensor
becomes
Clear
Sensor C
Condition
Sensor is
Blocked
Sensor is
Blocked
Sensor
becomes
Clear
Sensor is
Clear
Sensor is
Clear
Sensor is
Clear
Sensor is
Clear
Light
Curtain
Condition
Curtain is
Cleared
Curtain is
Cleared
Curtain
becomes
Blocked
Curtain is
Blocked
Curtain is
Blocked
Curtain
becomes
Cleared
Curtain is
Cleared
XPSLCM1150 Response to these
conditions
Powers-up and enters Interlock state
and senses that sensor C is active.
Enters Machine Run state, safety
outputs (OSSD) switch to On state
and conveyor motors start.
Enters Machine Stop (BypassAllowed) state since muting sensor C
was not inactive at power-up, safety
outputs (OSSD) switch to Off state.
XPSLCM1150 indicates BypassAllowed by blinking mute lamp and
diagnostic code of «03» is dislayed.
Enters Muting state, safety outputs
(OSSD) switch to On-state, mute
lamp is lit and diagnostic code of
«02» is displayed.
Enters Machine Run state, mute
lamp turns off and diagnostic code of
«00» is displayed.
Stays in Machine Run state and is
ready to automatically enter muting
when next object passes through
sensors.
5208/2007
Diagnostic display
At a glance
OverviewThis chapter describes the XPSLCM1150 Diagnostic display.
3
What's in this
Chapter?
This chapter contains the following topics:
TopicPage
System diagnostic codes54
Mute operation diagnostic codes56
08/200753
System diagnostic codes
Operational
codes
DIP switch fault
codes
The operational codes are described in the table below
Code DisplayedSystem Status
00Normal operation, no faults
01In the Interlock state and waiting for Start input.
02Operating in Muting state.
03In Bypass Allowed state & waiting for Start input.
88PowerUp Indication
The DIP switch fault codes are described in the table below.
Code DisplayedFault Indicated
21Invalid Mode Selection setting.
22Switch Setting Changed During Operation.
23DIP Switch Settings Not Identical.
27Invalid selection for the number of safety inputs connected.
28Invalid selection for the number of mute sensors connected.
OSSD faultsThe safety output (OSSD) fault codes are described in the table below.
Code DisplayedFault Indicated
31Safety outputs A & B shorted together
32Safety outputs A shorted to power
33Safety outputs B shorted to power
34Safety outputs A shorted to ground
35Safety outputs B shorted to ground
5408/2007
EDM/MPCE
codes
The EDM/MPCE fault codes are described in the table below.
Code DisplayedFault Indicated
41EDM/MPCE monitoring signal was in the Wrong state Before
entering the Machine Run state.
42EDM/MPCE monitoring signal was in the Wrong state After entering
the Machine Run state.
43EDM/MPCE monitoring signal was in the Wrong state during power
up of XPSLCM1150.
Internal fault
code
The Internal Fault codes are described in the table below.
The following test procedure MUST be performed by qualified personnel:
Following system installation.
In accordance with the employer’s regular inspection program.
Immediately following any maintenance, adjustment or other modification to any
system component.
Testing ensures that the safety devices and associated machine control system
work together to properly stop the guarded machine. Failure to perform these
procedures could result in serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Note: It is the user’s responsibility to ensure that the installation conforms to all
federal, state, local and company regulations pertaining to safe operation of the
equipment.
08/200757
Installation
checkout
StepAction
1Disable the guarded machine.
2Visually inspect the machine to ensure that access to the danger point is only
through the area (s) protected by the safety light curtain(s).
3Verify that the mounting distance of the safety light curtain(s) is equal to or
greater than the minimum safety distance required according to the EN 999 and
ANSI Minimum Safe Distance calculation. (See (See Adjusting the safe mounting distance, p. 19).
4Check the overall system for damage, security of electrical cabling and wiring,
or other hazards.
CAUTION
IMPROPER INSTALLATION
If any of the above requirements are not met, immediately lock out the machine and
initiate the necessary corrective action.
Failure to follow these instructions can result in injury or equipment damage.
5808/2007
Normal
operation with
muting disabled
StepAction
1Disable the guarded machine. Apply power to the XPSLCM1150 system.
2Ensure the Muting Enable switch is in the OFF (disabled) position.
3Using the proper size test object for each light curtain, test the protected area of
the light curtain. Test the area by moving completely through the field, top to
bottom, ensuring that all the areas between transmitter and receiver are
completely tested. The light curtain should remain blocked at any point with the
test object present in the sensing field.
4Enable the machine and initiate a start. Interrupt the sensing zone with the
correct test object and verify the machine stops immediately. Never attempt to
insert the test object directly into the danger area! If the machine fails to stop,
discontinue the testing and lock out the machine. Investigate and correct prior
to re-testing.
5With the test object present in the field, verify the machine cannot start.
6Repeat tests for all safety light curtains installed.
08/200759
Mute operation
(muting enabled)
StepAction
1Complete testing requirements in Installation checkout, p. 58 and Normal
operation with muting disabled, p. 59
2Disable the guarded machine and apply power to the system.
3Set the Muting Enable Switch to the ON position.
4Mute the system by blocking the correct sensors at the proper intervals (<3
seconds between sensors) and logical order. (Refer to the appropriate system
timing diagram) Verify that the associated mute inputs on XPSLCM1150 are
ON. Verify the external Mute active light(s) are ON and the XPSLCM1150 OSSD
outputs are in the RUN mode, XPSLCM1150 Display indicates 02 (mute active)
5Interrupt the safety light curtain (SLC) with the correct test object. Verify that the
SLC outputs switch OFF (Red or blocked). OSSD inputs for that SLC are OFF,
XPSLCM1150 outputs remain ON. XPSLCM1150 Display indicates 02 (mute
active)
6With the test object present in the light curtain sensing field, verify the machine
is "run capable". Remove the test object for further tests.
7If the Mute Time Limit is enabled, maintain the mute state for 2 minutes. After 2
minutes the XPSLCM1150 OSSD outputs will switch from RUN to STOP. The
external Mute Active light will flash at a 1-2 Hz rate and the display will indicate
03 (Bypass Allowed). Press the Start switch and verify the XPSLCM1150
outputs return to the RUN state and external Mute Active lamp is ON.
XPSLCM1150 Display indicates 02. Bypass is allowed until either the muting
sensors clear or light curtain clears or 10 minutes has expired.
8Reset system to Normal (non-mute) Operation.
9If a one way or directional system is used, test operation to verify mute is
activated only when the correct sequence and intervals are applied and that the
machine (in the case of a machine tool such as a power press) is muted only
during the non-hozardous cycle.
10Repeat test procedure(s) for 2nd muting channel (if installed).
6008/2007
Glossary
A
Automatic StartUpon completion of power-up, the XPSLCM1150 will enter the MACHINE RUN state
as soon as all of the selected light curtain OSSD inputs are in the ON state.
Schneider has traditionally referred to this as the Normal mode.
B
Bypass-AllowedAllows supervisor personnel to momentarily override the Machine Stop operation of
the XPSLCM1150. This function is used during instances where processing
sequence operations did not allow a transition to the Muting state and the
XPSLCM1150 entered the Machine Stop state. When in the Bypass-Allowed state,
a press-and-release of the Start button allows the XPSLCM1150 to transition to the
Muting state for only one cycle or a maximum duration of 10 minutes.
D
Dark-OnA photo-electric sensor term that means the sensor output will be active when the
sensor detects an object.
08/200761
Glossary
E
EDM/MPCE
(Machine
Primary Control
Element)
Monitoring
The XPSLCM1150 monitors the state of the EDM/MPCE signal produced by the
guarded machine to insure that it is in the correct state with respect to "Machine
Run" and "Machine Stop."
I
InterlockFor the XPSLCM1150 to enter this state the unit must be set to either the Start
Interlock or Start/Restart Interlock mode. In this state the yellow Interlock LED is on
and the red Machine Stop LED is on.
L
Light-OnA photo-electric sensor term that means the sensor output will be active when it
receives the sensed light source.
Lockout (Fault)When the XPSLCM1150 detects a fault, it transitions to this state. The Safety
outputs will be held to the off state and the XPSLCM1150 will not attempt to leave
this state without performing a comprehensive power-up self-test. A power-up selftest will be initiated by either cycling the XPSLCM1150 power or by a Start signal
transition.
M
Machine RunWhen the XPSLCM1150 is in this state the two Safety outputs are both active. In this
state, the Green Machine Run LED is on, the Red Machine Stop LED is off and the
Yellow Interlock LED is off.
Machine StopWhen the XPSLCM1150 is in this state the two Safety outputs are both inactive. In
this state the Green Machine Run LED is off, the Red Machine Stop LED is on and
the Yellow Interlock LED is off.
62
08/2007
Glossary
MutingThe mute sensors have been properly activated for the XPSLCM1150 to keep the
Safety outputs active when the light curtain detection zone is interrupted.
O
OFF StateThe state in which the output circuit is interrupted and does not permit the flow of
current.
ON StateThe state in which the output circuit is completed and permits the flow of current.
R
Response TimeThe maximum amount of time required for the XPSLCM1150 to recognize a light
curtain detection zone interruption and to set its Safety outputs to the Off state.
S
Safety Output
(Output signal
switching device
(OSSD)
Start InterlockUpon completion of power-up, the XPSLCM1150 must go to the "Interlock" state. A
Start/Restart
Interlock
08/200763
The component of the XPSLCM1150 connected to the control system of the
guarded machine.
Start signal transition must occur before going to Machine Run for the first time.
Once the first Start condition has been met, the XPSLCM1150 will operate in the
Automatic Start mode.
The XPSLCM1150 will go into the Interlock state upon completion of power-up and
after all light curtain detection zone interruptions which cause a transition to the
Machine Stop state. A Start signal transition must occur before returning to Machine
Run following any transition to Machine Stop.
Glossary
64
08/2007
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.