Schneider ABL8RPS24050, ABL8RPS24100, ABL8RPS24030 User Manual

XPSLCM1150

Safety light curtains mute module
User’s Manual
08/2007
W917063480211A03
2

Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Chapter 1 Description of XPSLCM1150 . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
At a glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Description of XPSLCM1150 mute module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Description of Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Adjusting the safe mounting distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Technical ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Terminal assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installation wiring example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
XPSLCM1150 visible indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Operating states and corresponding outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Cable lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Setting XPSLCM1150 configuration switches. . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Chapter 2 Application examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
At a glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Application information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Two sensor muting system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Three sensor muting system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Four sensor muting system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Description of the bypass-allowed feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Chapter 3 Diagnostic display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
At a glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
System diagnostic codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Mute operation diagnostic codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Chapter 4 Test procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Test procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
08/2007 3
4 08/2007

Safety Information

§
Important Information
NOTICE Read these instructions carefully, and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
08/2007 5
Safety Information
PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2007 Schneider Electric. All Rights Reserved.
6

About the Book

At a Glance
Document Scope The XPSLCM1150 Mute Module is an accessory device used to provide a safety-
rated muting function in conjunction with safety light curtains. Muting is defined as «bypassing the protective function on safety related control system such as a safety light curtain, during a pre-determined operation of a machine.»
Validity Note The data and illustrations found in this book are not binding. We reserve the right to
modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.
08/2007 7
About the Book
Product Related Warnings
WARNING
IMPROPER SET UP OR INSTALLATION.
Read all responsibilties and requirements listed below before installing the XPSLCM1150 module.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
UNINTENDED OPERATION.
Muting can disable the safety functions of a machine. The proper installation, checkout and operation of a machine and muting system in accordance with all applicable laws and standards, is critical to the safe operation of the machine. Failure to comply with these instructions may result in severe injury to personnel..
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
REDUCED PROTECTION LEVEL
When the XPSLCM1150 module is used with a Type 2 rated light curtain or another Type 2 device, the overall system protection is reduced to Category 2.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Whether a specific machine application and XPSLCM1150 installation complies with safety regulations depends on several factors, including the proper application, installation, maintenance and operation of the XPSLCM1150 and its associated sensors. These items are the responsibility of the purchaser, installer and employer. The employer is responsible for the selection and training of personnel to properly install, operate and maintain the machine and its safeguarding systems. This product is designed to comply with:
IEC61496-1
ANSI B11.19 - 1990
EN954-1
8
About the Book
The XPSLCM1150 should only be installed, verified and maintained by a qualified person, as «a person or persons who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training or experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.». Use of a muting function requires special precautions by the safety system machine controller, installer, operator and employer. The following is only a partial list of requirements when utilizing muting and is not intended to be a complete guide to muting standards. The employer must contact the local safety authority for specific requirements regarding the machine, machine controller and safety related control system. Schneider provides the following information for user reference only and makes no claim regarding the accuracy, completeness or effectiveness for a specific application from any organization:
Muting of the light curtain is only permitted during the nonhazardous portion of the machine cycle.
If the machine tool has reversing capability where a muting hazard is possible the control shall include an automatic means through which muting is only permitted in the forward direction.
Selection of the muting feature shall be by a key-operated switch under supervisory control by the employer.
One or more visual indicator(s) shall be provided which are illuminated when the light curtain is in a muted condition.
Any fault condition of the mute indicator(s) shall not allow the light curtain to enter a mute condition.
The mute indicator(s) should be readily visible from any normal machine operator position and from the position at which any adjustment of the muting is normally carried out.
There shall be at least two, independent muting signal sources to be used with the XPSLCM1150. A single, simple cam-operated limit switch is inadequate as a muting signal source since its failure can remain undetected.
The proper selection, installation and orientation of the muting sensors are the responsibility of the employer and installer.
The muting position (of the mute signal source) shall be secured against unauthorized adjustment by provision of special tools, key entry, electronics passwords and the positioning and mounting of associated limit switches.
The guarded machine must be able to stop anywhere in its cycle. Do not use an XPSLCM1150 on a press with a full-revolution clutch.
The guarded machine must have a consistent stopping time and adequate control mechanisms.
Severe smoke, particulate matter and corrosives may degrade the efficiency of the optical safety devices. Do not use optical safety devices in this type of severe environment.
All applicable governmental, state, local and employers rules, codes and regulations must be satisfied. This is the employers responsibility.
08/2007 9
About the Book
All safety-related machine control elements must be designed so that a fault in the control logic or failure of the control circuit does not lead to a failure or danger.
Additional guarding may be required for access to dangerous areas not covered by the safety device system.
Perform the test procedure at installation and after maintenance, adjustment, repair or modification to the machine controls, tooling, dies or machine, or the XPSLCM1150 and safety device system.
Follow all procedures in this manual for proper operation of the XPSLCM1150
Mute Module. The enforcement of these requirements is beyond the control of the manufacturer. The employer has the sole responsibility to follow the preceding requirements and any other procedures, conditions and requirements specific to his machinery.
User Comments We welcome your comments about this document. You can reach us by e-mail at
techpub@schneider-electric.com
10

Description of XPSLCM1150

At a glance
Overview This chapter describes the XPSLCM1150.
1
What's in this Chapter?
This chapter contains the following topics:
Topic Page
Description of XPSLCM1150 mute module 12
Description of Controls 14
Adjusting the safe mounting distance 19
Technical ratings 20
Terminal assignments 22
Installation wiring example 23
XPSLCM1150 visible indicators 28
Operating states and corresponding outputs 30
Cable lengths 33
Setting XPSLCM1150 configuration switches 34
Dimensions 36
08/2007 11

Description of XPSLCM1150 mute module

Front panel XPSLCM1150 Front panel
Features
The XPSLCM1150 Mute Module is a Category 4 safety device that interfaces
between a machine and certain protective safety devices to temporarily suspend
those devices during the non-hazardous portion of the machine cycle. It conforms
with EN 954-1 and has been certified to IEC 61496-1.
Fast 1 ms response time.
Works with either 1 or 2 safety devices (safety light curtain, safety controller, etc.)
Two-channel mute sensor inputs for 2, 3 or 4 PNP-type electro-optic sensors, or
limit switches or other sensing devices.
LED indications for individual input and output status.
Two-digit diagnostic display.
External mute indication for operator awareness.
12 08/2007
Applications
Automatic conveyer, stacker and palletizing machines.
Mechanical and hydraulic presses with automatic or manual feed with the muting
function is only used in the non-hazardous portion of the press cycle. When the mute mode is disabled, the XPSLCM1150 outputs are the same as those of the connected safety devices. Any entry into the guarded area will result in a stop signal being sent to the guarded machine. The XPSLCM1150 provides two "mute safety channels", each accepts a single safety device, and either two, three or four mute sensors to activate the mute mode. The mute mode is active when the correct sequence of mute sensor input signals is achieved. Each safety device output must be capable of supplying two 24 V (PNP) output signals when the sensing field is clear. Mute sensors must have PNP type outputs, sensor pairs are made-up of both "dark operate" and "light operate" sensors. An indicator lamp for each safety channel is required to illuminate anytime the XPSLCM1150 is in the mute state. These lamps must be visible to personnel in the immediate area. The XPSLCM1150 monitors the lamp circuit to ensure the indicator is operational.
08/2007 13

Description of Controls

IMPROPER INSTALLATION
Muting can disable the safety functions of a machine. The proper installation,
checkout and operation of a machine and muting system; in accordance with all
applicable laws and standards, is critical to the safe operation of the machine.
Failure to comply with these instructions may result in severe injury to personnel.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
WARNING
Power requirements
The XPSLCM1150 requires a dedicated power supply of 24 V +/- 10 %, providing a minimum of 2 amperes that meets the requirements of IEC61496-1 and IEC60204-1, part number ABL8RPS24030 or equivalent.
System Common Return For proper operation, the power supply common, (0 V ), must be connected to each of the components in the system, including start/enable switches, EDM/MPCE monitor, all OSSD and Auxiliary loads.
Chassis Ground or Protective Earth (PE) Connection The chassis ground terminal of the XPSLCM1150 must be connected to the earth ground of the installation site to ensure protection from electrical interference and high voltage transients.
14 08/2007
XPSLCM1150 input devices
Sensor Inputs The XPSLCM1150 module accommodates up to two independent channels identified as Channel 1 & Channel 2. Each channel is comprised of one safety input device and either two, three, or four mute input sensors.
Safety Input Devices (OSSD Inputs) The XPSLCM1150 supports safety devices such as safety light curtains, safety controllers or other safety-rated devices that provide two 24 V inputs into the XPSLCM1150 whenever their protected area is clear.
Note: If using an input from a relay-type safety device, the two OSSD signals must switch to the On and Off state within 300 msec of each other to be recognized as proper OSSD inputs.
Mute Sensor Inputs Muting is controlled by two or more separate input sources. These devices can be optical, inductive or mechanical. Sensors S1A, S1C, S2A & S2C must have «Dark­On» PNP type outputs, nominal 24 V when Ok to mute. Sensors S1B, S1D, S2B & S2D must have «Light-On» PNP type outputs, nominal 0 volts (no current flow) when Ok to mute.
WARNING
IMPROPER SET UP OR INSTALLATION
You must have at least two independent mute sensors to activate the mute circuit. A single device with multiple outputs such as single limit switch, is inadequate as a mute sensor since its failure can remain undetected. Failure to comply with this requirement may cause the muting circuit to activate at the incorrect part of the machine cycle. Serious injury to personnel could result.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Mute Enable / Disable A single selector switch is used to enable the XPSLCM1150 to detect the mute input sensors, or disable the XPSLCM1150 from entering the mute state. When in the disable position all muting errors are cleared from the diagnostic display.
08/2007 15
Start Switch A push-button switch is required to reset the XPSLCM1150 from a Start/Interlock condition, a fault interlock, or allow the Bypass feature to be used. The input is DIP switch selectable for N/O or N/C operation.
WARNING
IMPROPER INSTALLATION OF THE START BUTTON
The Start switch shall be located outside of the safeguarded area such that it cannot be reached from within the safeguarded area. The location must allow complete visibility of the guarded area. The operator must ensure that the safeguarding zone is clear before press & release of Start.This prevents the machine or muting function from starting while personnel may be in the hazardous area and avoids possible serious injury to personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
16 08/2007
XPSLCM1150 outputs
WARNING
IMPROPER OUTPUT OPERATION
Muting is only allowed during the non-hazardous portion of the machine cycle! A muting application must be designed so that no single component failure can prevent the stop command or allow subsequent cycles until the failure is corrected. (USA standard OSHA 1910.217(c)(3)(iii) (d), ANSI B11.19-1990 section 4.2.3.3.7) Failure to comply with this requirement may cause the muting circuit to activate at the incorrect part of the machine cycle, serious injury to personnel could be resulted.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Output Signal Switching Devices (OSSD’s) The XPSLCM1150 uses two solid-state outputs to send a stop signal to the guarded machine. When the XPSLCM1150 is in the normal Run mode with the safety device(s) clear, or in the Mute mode regardless of the safety device(s) status, the OSSD outputs are turned on, sourcing 24 V @ a maximum of 625 mA. Solid-state outputs achieve their safety ratings by periodically switching the output state and verifying that the device did indeed switch. This operation is performed periodically and is essentially transparent to the machine control circuit.
WARNING
IMPROPER OUTPUT SET UP
You Must Use both OSSD safety outputs from the XPSLCM1150! Each output must be wired such that it is capable of stopping the guarded machine. Failure to use both XPSLCM1150 safety outputs may prevent the machine from stopping, resulting in possible severe injury to personnel.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Auxiliary Outputs The XPSLCM1150 provides non-safety auxiliary outputs in both PNP and NPN configurations. The PNP output source 24 V @ 500 mA, the NPN output sinks up to 100 mA. The auxiliary outputs are user selected to either follow the OSSD outputs, or activate when a fault condition is detected.
08/2007 17
Mute Lamp Outputs 1 & 2 A visible mute lamp is required for each channel of the XPSLCM1150 to indicate the mute function is active. Mute Lamp outputs are NPN current sinking inputs. Each input is monitored to ensure 40-300 mA is flowing through the circuit when Mute is activated. If the required current is not detected, then the XPSLCM1150 will not enter the Muting state and will display diagnostic codes. If a current is detected when the mute function is NOT activated, the XPSLCM1150 will enter the Lockout state.
WARNING
IMPROPER MUTE INDICATION
An indication that the protected area is muted must be provided and readily observable to the machine operator. The mute lamp is an important warning device to the machine operator, indicating that muting is active.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Mute Indicator Auxiliary Outputs Mute Auxiliary and Mute Armed functions are available as non-safety-rated outputs. Each is configured as NPN sinking at a maximum of 100 mA. Mute Aux will indicate whenever the XPSLCM1150 is in the Muting state. Mute Armed will indicate the XPSLCM1150 is Mute Enabled.
EDM/MPCE Monitor The XPSLCM1150 OSSD outputs are designed to connect directly to the machine primary control element, or EDM/MPCE. EDM/MPCE monitoring is the capability to directly monitor machine control devices and ensure their operation coincides with the commands of the XPSLCM1150.
18 08/2007

Adjusting the safe mounting distance

Using the XPSLCM1150 without mechanical relays
Using the XPSLCM1150 with safety mechanical relays
The XPSLCM1150, when used without mechanical relays, will add 1 millisecond (0.001 sec) to the overall response time of the safety control system. This will increase the safe mounting distance of the safety sensing device. See the installation manual of the safety sensing device for further information on calculating the proper safeguarding distance.
The XPSLCM1150 itself adds 1 millisecond (0.001 sec) to the response time of the safety control system. Additionally, you must also add the response time of the mechanical relays to determine the total impact on the safety control system. This will increase the safe mounting distance of the safety device. The XPSLCM1150 should only be used with safety rated mechanical relays employing force guided contacts. Contact the relay supplier for the safety rating suitability and response time. Refer to the installation manual of the safety sensing device for further information on the safe mounting distance.
08/2007 19

Technical ratings

Specifications
Safety Category Type 4 per IEC 61496-1.
Response Time Less than 1 msec.
Input Power 24 V +/- 10%, 150 W max. (a) 24 V +/- 10%, 6 W (250mA)
min
Operating Temperature 0 °C to 55 °C.
Humidity Less than 95% Non Condensing
Storage Temperature -25 °C to 75 °C
Vibration In accordance with IEC 60068-2-6, 0.35mm displacement, 10 to
55 Hz.
Shock In accordance with IEC 60068-2-29, 10g, 16 ms pulses, 1000/
axis.
Enclosure IP-20
Outputs
Safety Outputs (OSSD) Two independent 625 mA (max.) current sources (PNP), 24 V
.
Auxiliary Outputs Auxiliary NPN output: 100 mA (max.) current sink, 24 V max.
Auxiliary PNP output: 500 mA (max.) current source, 24 V .
Mute-Lamp Two (NPN) Outputs 40-300 mA, 24 V Max. (b)
Mute Auxiliary NPN Output 100 mA (max.), 24 V Max
Mute-Armed NPN Output 100 mA (max.), 24 V Max
EDM/MPCE Monitor 24 V , 50 mA (sourced by XPS)
Inputs
Safety Devices(OSSD Inputs)
Mute Sensor PNP 24 V (20 mA consumption)
Mute-Enable Selector Key-Operated Switch, Maintained Contacts
Start / Restart Either N/O or N/C Momentary Contact (10 mA consumption)
PNP 24V @ 50 mA Machine Run, 0 volt Machine Stop
(a) Power to the XPSLCM1150 must be provided from a dedicated power supply that meets the requirements of IEC 60204-1 and IEC 61496-1, Schneider part number ABL8RPS24100 (150 W) or equivalent maxi loads on outputs.(not included NPN outputs, mute lamps, sensors and light curtains).
20 08/2007
(b) The external lamp must provide a current load between 40 mA and 300 mA for the lamp monitoring circuit to sense proper operation of the mute lamp.
Power Supply Requirement
Total System Components
4 sensor muting system Full output load + Full
temperature range
1 light curtain XUSLT ABL8RPS24050 ABL8RPS24030 (Iout < 1.45 A)
1 light curtain XUSLM ABL8RPS24030 (Iout < 1.60 A)
1 light curtain XUSLP ABL8RPS24030 (Iout < 1,7 A)
1 light curtain XUSLN ABL8RPS24030 (Iout < 1,9 A)
2 light curtains XUSLN ABL8RPS24030 (Iout < 1,4 A)
2 light curtains XUSLP ABL8RPS24030 (Iout < 0,9 A)
1 light curtain XUSLT 1 light curtain XUSLN
1 light curtain XUSLN 1 light curtain XUSLP
2 light curtains XUSLT ABL8RPS24100 ABL8RPS24030
2 light curtains XUSLM ABL8RPS24030
1 light curtain XUSLT 1 light curtain XUSLP
1 light curtain XUSLT 1 light curtain XUSLM
1 light curtain XUSLM 1 light curtain XUSLN
1 light curtain XUSLM 1 light curtain XUSLP
Reduced output load (1)+ Full temperature range
ABL8RPS24030 (Iout < 0,9 A)
ABL8RPS24030 (Iout < 1,2 A)
ABL8RPS24050
(Iout < 0.5 A)
(Iout < 0.75 A)
ABL8RPS24030 (Iout < 0.65 A)
ABL8RPS24030 (Iout < 1,1 A)
ABL8RPS24030 (Iout < 0,8 A)
(Iout < 2.3 A)
ABL8RPS24050 (Iout < 2.55 A)
ABL8RPS24050 (Iout < 2.45 A)
ABL8RPS24050 (Iout < 2,9 A)
ABL8RPS24050 (Iout < 2,6 A)
Note: (1): Output load I out = XPSLCM1150 OSSD output currents including light curtain Aux output, Mute lamp Aux output and Mute Lamps.
08/2007 21

Terminal assignments

Function Pin Assignment
Pin # Function Assignment Pin # Function Assignment
1 XPS Outputs
2 OSSD B 33
3EDM/MPCE MON32
40 V 31
5 AUX-PNP 30
6 AUX-NPN 29 Mute Input
7 Mute Outputs MUTE-LAMP 1 28 OSSD 2B
8 MUTE-LAMP 2 27 SENSOR 2A
9 MUTE-AUX 26 SENSOR 2B
10 MUTE-ARMED 25 SENSOR 2C
11 XPS Control
12 MUTE-ENABLE HI 23 Mute Input
13 MUTE-ENABLE
14 Not used 21 SENSOR 1A
15 Power +24 V 20 SENSOR 1B
16 0 V 19 SENSOR 1C
17 Earth Ground 18 SENSOR 1D
& EDM/MPCE
Input
Inputs
OSSD A 34
OSSD 2A
Channel 2
START 24 SENSOR 2D
OSSD 1A
22 OSSD 1B
LO
Channel 1
The XPSLCM1150 power input return (0 V ) must be connected to the overall system component returns. Safety Light curtains, start switch, EDM/MPCE monitor, OSSD loads and auxiliary loads must be all connected in common for proper system operation. The Earth Ground terminal of the XPSLCM1150 must be connected to the enclosure or chassis ground of the installation site. Protection devices internal to the XPSLCM1150 that provide immunity from electrical interference connect to this earth ground terminal.
22 08/2007

Installation wiring example

Description XPSLCM1150 Mute Module with two sensing channels connected.
Note:
The Start switch must be located in an area that allows complete visibility of the guarded area. The operator must ensure that the protection zone is clear before press & release of Start.
Mute sensors S1A, S1C, S2A & S2C must have 'Dark-On' PNP type outputs, nominal 24 V when Ok to mute and nominal 0 V when no mute. Mute sensors S1B, S1D, S2B & S2D must have ‘Light-On' PNP type outputs, nominal 0 V when Ok to mute and nominal 24 V when no mute.
08/2007 23
Wiring Wiring Diagram Example with 2 Light Curtains Connected (XUSLT and XUSLM):
Mute
9
rm
Mu_Aux
Mu_A
Mute
outputs
inputs
B
S-2
S-2C24S-2D23OSS 1
26
8
27
M-Lamp27M-Lam
A
S-2
Lamp
(XUSLM)
Mute
Lamp
(XUSLT)
6
5
p1
Aux NPN
B
OSS 2A28OSS 2
29
K1 K1
K2
4
32
PNP
0VDC
x
OSSDB1OSSDA
Au
EDM/MPCE Mo n
Outputs
K2
22
XPSLCB1141
Ret
OSSD218OSSD119OSSD
20
101189
Start
Start Ret
Shielded
cables
EDM/MPCE
EDM/MPCE Ret
Tran smit terReceiver
3
GND
0VDC3+24V
1
2
NL
GND N L
ABL8RPS
dedicated
supply
0V 24V
GND
F1
Start
Mute
Mute
enable
Disable
17
16
15
14 13
12
11
10
t
o
r
l
GND
Power
0VDC
+24VDC
Mu-en-
Inputs
Sta
Mu-en-hi
XPSLCM1150
Channel 1 Channel 2
1
inputs
A
S-1A20S-1B19S-1C18S-1D
OSS 1B
21
25
22
tart
AUX
GND
3
BN BU BK
BN BU BK
BN BU BK
BN BU BK
S
+24V
0VDC
OSSD2
EDM/MPCE
Receiver Transmitter
XUSLT XUSLT
OG
Sensor A PNP dark-on type
OG
Sensor B PNP light-on type
OG
Sensor C PNP dark-on type
OG
Sensor D PNP light-on type
OSSD1
GND
0VDC
MTS
+24V
MTS Ret
Sensor A‘ PNP dark-on type
Sensor B‘ PNP light-on type
Sensor C’ PNP dark-on type
Sensor D’ PNP light-on type
Receiver
XUSLM
BN BU BK
BN BU BK
BN BU BK
BN BU BK
Transm itter
XUSLM
OG
OG
OG
OG
24 08/2007
Note: Transmitter and receiver sensors can also be used.
Legend
Install a wire between 0V and Ground
1
To choose the dedicated supply, see Power Supply Requirement, p. 21
The coils must be suppressed with the arc suppressors provided in the
2
documentation kit of the light barriers
The light barriers must be configured with EDM/MPCE monitoring disabled
3
08/2007 25
Wiring Wiring Diagram Example with 2 Light Curtains Connected (XUSLP and XUSLN):
Mute
9
8
x Au u_
M
Mu_Ar m
M-Lamp 27M-
Mute
outputs
inputs
B
S-2A26S-2
S-2C24S-2D23OSS 1A
27
MTS
+24V
XUSLPZ
Transmitter
Lamp
(XUSLN)
Lamp
(XUSLP)
Lamp1
OSS 2B
29
28
0VDC
Mute
6
GND
K1 K1
K2
5
4
32
P N
0VDC
Aux P
Aux NPN
EDM/MPC E Mon
Outputs
OSS 2A
Sensor A‘ PNP dark-on type
OSSDB1OSSDA
K2
22
+24V
0VDC
4
rt ta S
XUSLN
+24V
XUSLN
TransmitterReceiver
0VDC
OG
OSSD2
OSSD1
BN BU BK
NL
GND N L
ABL8RPS
dedicated
supply
0V 24V
GND
F1
Start
Mute
Mute
Disable
enable
17
16
15
14 13
12
11
10
o
l
GND
Power
0VDC
+24VDC
Mu-en-
Inputs
Start
Mu-en-hi
XPSLCM1150
Channel 1 Channel 2
GND
0VDC
3
XUSLPZ
Receiver
BN BU BK
inputs
+24V
EDM/MP CE
OG
B
S-1A20S-1B19S-1C18S-1D
OSS 1
21
22
AUX
Start
OSSD2
XUSLPB
Transmitter
Receiver
Sensor A PNP dark-on type
25
Ret
OSSD1
MTS
1
OG
BN BU BK
BN BU BK
BN BU BK
Sensor B PNP light-on type
OG
Sensor C PNP dark-on type
OG
Sensor D PNP light-on type
Sensor B‘ PNP light-on type
Sensor C’ PNP dark-on type
Sensor D’ PNP light-on type
OG
BN BU BK
OG
BN BU BK
OG
BN BU BK
26 08/2007
Note: Tranmiter and receiver sensors can also be used.
Legend
Install a wire between 0V and Ground
1
To choose the dedicated supply, see Power Supply Requirement, p. 21
The coils must be suppressed with the arc suppressors provided in the
2
documentation kit of the light barriers
The light barriers must be configured with EDM/MPCE monitoring disabled
3
When the XPSLCM1150 module is used with a Type 2 rated light curtain or
4
another Type 2 device (XUSLN for example), the overall system protection is reduced to Category 2
08/2007 27

XPSLCM1150 visible indicators

Description Front panel and indicators
28 08/2007
XPS Status Color State Description
Mute Enable Yellow ON External mute enable switch is set to ON
Interlock Yellow ON Interlock State, waiting Start signal
Yellow FLASH Lockout State (Internal or External Fault
Detected)
Machine Stop Red ON XPS OSSD Safety outputs are OFF
Machine Run Green ON XPS OSSD Safety Outputs are ON
Channel 1 & 2 Status
OSSD A/B Green ON Both OSSD Inputs from Safety Device are On.
S-A Yellow ON Muting Sensor S1-A is blocked (activated)
S-B Yellow ON Muting Sensor S1-B is blocked (activated)
S-C Yellow ON Muting Sensor S1-C is blocked (activated)
S-D Yellow ON Muting Sensor S1-D is blocked (activated)
Diagnostic Display two digit numeric display that provides diagnostic codes.
08/2007 29

Operating states and corresponding outputs

Corresponding table
XPSLCM1150 Operating States and Corresponding Outputs:
Output Muting Bypass
Allowed
Machine Run, Green LED
Machine Stop, Red LED
Interlock or Fault, Yellow LED
OSSD A OUTPUT ON OFF ON OFF OFF OFF
OSSD B OUTPUT ON OFF ON OFF OFF OFF
AUXILIARY OUTPUTS
MUTE-LAMP 1 * OUTPUT
MUTE-LAMP 2 * OUTPUT
MUTE-AUX OUTPUT ON BLINKING OFF OFF OFF OFF
MUTE-ARMED OUTPUT
Follow OSSD
Alarm Mode
ON OFF ON OFF OFF OFF
OFF ON OFF ON ON ON
OFF OFF OFF OFF ON Blinking
ON OFF ON OFF OFF OFF
OFF OFF OFF OFF OFF ON
ON when
Ch#1 is
being
muted
ON when
Ch#2 is
being
muted
ON ON X X X X
BLINKING
when Ch #1
causes Bypass
BLINKING
when Ch #2
causes Bypass
Machine
Run
OFF OFF OFF OFF
OFF OFF OFF OFF
Machine
Stop
Interlock Lockout
(Fault)
X = This output is dependent on Mute Enable input signal. * = Use the mute lamp supplied with the module or be ordered separately in accessory.
30 08/2007
Waveform Diagram
On state
"Start/Restart Interlock" mode with 2 sensors
Muting < 10 mn
1 Light
Curtain
Cut off
< 3 s
Off state
Module Setup
Module alarm
Power supply
< 3 s
1 Light
Curtain
Cut off
< 1 ms
< 1 ms
Mu-en-hi
Mu-en-lo (13)
Start (11) (*)
S.1A
S.1B (20)
OSSD 1A
OSSD 1B (22)
Channel 1 Inputs Inputs
M-lamp-1 (7)
Mu-Aux (9)
Mu-Arm (10)
Mute Outputs
EDM/MPCE (3)
OSSD A (1)
OSSD B (2)
Aux PNP
Output
Aux NPN
(12)
(21)
(23)
Aux
(5)
Alm
Aux
(6)
Alm
(*) Press “START” button
08/2007 31
On state
"Start/Restart Interlock" mode with 4 sensors
Off state
Module Setup
Module alarm
Power supply
Muting < 10 mn
< 3 s
1 Light Curtain
Cut off
< 3 s
1 Light
Curtain
Cut off
< 1 ms
Mu-en-hi
Mu-en-lo
Start
OSSD 1A
Channel 1 Inputs Inputs
OSSD 1B
M-lamp-1
Mu-Aux
Mu-Arm
Mute Outputs
EDM/MPCE
OSSD A
OSSD B
Aux PNP
Output
Aux NPN
(11)
S.1A
S.1B
S.1C
S.1D
(12)
(13)
(*)
(21)
(20)
(19)
(18)
(23)
(22)
(7)
(9)
(10)
(3)
(1)
(2)
Aux
(5)
Alm
Aux
(6)
Alm
(*) Press “START” button
32 08/2007

Cable lengths

Cables The following table lists the recommended maximum lengths for the XPSLCM1150
input & output signals. Unshielded cables and wires may be used for all connections.
Signal Names Cable or Wire Specified max. length
Safety outputs A & B
Aux PNP and Mute Lamps 1 & 2 outputs
Aux NPN, Mute Aux and Mute Armed outputs
Light curtain safety inputs
Mute sensor inputs
Start input
EDM/MPCE Monitor input
20 AWG (0.3117 mm
2
with cable capacitance < 100 pF/ft. (<30pF/m)
18 AWG (0.82 mm
22 AWG (0.4418 mm
20 AWG (0.3117 mm
2
) wire
2
2
with cable capacitance < 100 pF/ft. (<30pF/m)
22 AWG (0.4418 mm
22 AWG (0.4418 mm
22 AWG (0.4418 mm
300 mA load: 70 meter (230 ft.)
) wire
625 mA load: 35 meter (115 ft.)
50 meter (164 ft.)
100 meter (330 ft.)
) wire
100 meter (330 ft.)
) wire
2
100 meter (330 ft.)
) wire
2
100 meter (330 ft.)
) wire
2
100 meter (330 ft.)
) wire
08/2007 33

Setting XPSLCM1150 configuration switches

Principle The XPSLCM1150 is configured for the various operating modes through the use of
two banks of eight-position DIP switches and a single two-position DIP switch.
Accessing to configuration switches
The DIP switches are accessible by removing the front cover. The redundant DIP switches must be set exactly the same.
Aux and Start
DIP SWITCHES
SWITCHES
SWA
SWB
OPEN
WARNING
IMPROPER MUTE INDICATION
Disconnect power before removing the controller cover. Replace the controller cover before re-applying power.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
34 08/2007
Field configuration switch settings
Eight-Position Redundant DIP Switch Settings
Switch Function Selection Description
1 & 2 Start Mode Automatic Start: 1 = On, 2 = On
Start Interlock: 1 = On, 2 = Off Invalid Setting: 1 = Off, 2 = On Start/Restart Interlock: 1 = Off, 2 = Off
3 EDM/MPCE Monitoring Enabled = Off, Disabled = On
4 Bypass Allowed Enabled = On, Disabled = Off
5 Number of Light Curtains 1 Light Curtain System = On
2 Light Curtain System = Off
6 & 7 Number of Mute Sensors Invalid Setting: 6 = On, 7 = On
2 Sensor System: 6 = On, 7 = Off 3 Sensor System: 6 = Off, 7 = On 4 Sensor System: 6 = Off, 7 = Off
8 Muting Time Limit No time limit = On
2 minute time limit = Off
Two-Position DIP Switch Settings
Switch Function Selection Description
1 Auxiliary Output Mode Follow OSSD output = On
Alarm mode = Off
2 Start switch type Normally Closed switch = On
Normally Open switch = Off
08/2007 35

Dimensions

Mechanical drawing
The drawing below gives the XPSLCM1150 dimensions:
Front View
Top View
Bottom View
36 08/2007
Right View

Application examples

At a glance
Overview This chapter describes some application examples.
2
What's in this Chapter?
This chapter contains the following topics:
Topic Page
Application information 38
Two sensor muting system 40
Three sensor muting system 43
Four sensor muting system 46
Description of the bypass-allowed feature 50
08/2007 37

Application information

Principle The following section contains several application examples of how the
XPSLCM1150 may be used with various arrangements of sensors to start and end the muting sequence. Although photoelectric sensors are used in the example, other types of sensors, such as limit switches, inductive proximity sensors and ultrasonic sensors may be used as sensor inputs to the XPSLCM1150, provided that they met the electrical requirements of XPSLCM1150 input devices, p. 15.
Note: Schneider provides the following application examples for user reference only and makes no claim regarding the accurary, completeness or effectiveness for a specific application from any organization.
WARNING
IMPROPER INSTALLATION OF SENSORS
The system installer and employer are responsible for the proper selection, installation and orientation of the muting sensors are critical to ensure that muting can never be initiated by personnel attempting access through the safeguarding device. Serious injury to personnel may result.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
38 08/2007
Selection and orientation of the muting sensors
The object of the correct muting sensor selection and orientation is to always recognize the presence of the workpiece material as the intended means to start or stop the muting sequence. The presence of any person in the detection zone of the muting sensors must never be able to initiate a muting sequence, or otherwise bypass the safe guarding device. The proper selection, installation and orientation of the muting sensors are the sole responsibility of the employer and installer. The following recommendations must be observed, especially in conveyorized applications.
The muting sensors should detect the material, and not the transportation means, such as a pallet, cart or other transport device. Ensure that a person on the transport device cannot initiate muting and enter the hazardous area.
Do not allow interruption in the sensing of the material while passing the muting sensors. The detection of the material should be continuous over its length.
If using photoelectric sensors, do not allow reflective material to interrupt or cause optical short circuits among different sensors. Likewise, do not allow sensors in adjacent areas to interfere or provide false indication.
Position the sensors such that before a new load of material is detected by the first sensor, the prior material has passed the last sensor and all muting sensors are deactivated for a period of time.
Consider the overall speed and cycle the material as it moves through the process. Time must be allowed for evaluating the muting sensors¡¯ output prior to the material reaching the safeguarding device.
Access by persons into the hazardous area of the machine must be prevented or detected such that a safeguarding device is able to send a stop signal to the machine before entering into the hazardous area. Other safeguarding methods, such as physical barriers or fences, may be necessary.
The muting position (of the sensors) shall be secured against unauthorized adjustment by provision of special tools, key entry, electronics passwords and the positioning and mounting of associated limit switches.
08/2007 39

Two sensor muting system

Conveyor belt muting system example
The figure below illustrates one application of a conveyor belt muting system using a two sensor configuration. The two sensor configuration muting system is bi­directional.
Sensor A
Object
Sensor B
Sensor A
Object
Sensor B
Sensor A
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Conveyor
Bi-Directional
Object
Sensor B
40 08/2007
Light
Curtain
Mechanical press example
The figure below illustrates muting on a mechanical press using two switches to sense when to enter Muting state. Bottom Dead Center (BDC) is the point at which the tool is closest to the die. Top Dead Center (TDC) is the point at which the tool is furthest from the die.
Transition conditions
Switch B
Switch A
1
BDC
Protected Muting
B
A
2
Opening
Stroke
Started
A
Opening Stroke
Muting in
Progress
B
3
B
A
4
TDC
Muting
Maintained
B
A
5
Closing Stroke
Muting
Interrupted
B
A
6
Closing Stroke
Protected
The table below describes conditions required to transition to Muting state with a two sensor system:
No. of
Sensors
2 Sensor
System
State Mute
Enable
State 1OFFXXXXProtected
State 2 ON OFF OFF XX XX Protected
State 3 ON OFF ON XX XX Protected
State 4 ON ON OFF XX XX Protected
State 5 ON ON ON XX XX Muting
Sensor A Sensor B Sensor C Sensor D System
Status
X = Sensor can be in any state, does not apply to selected mode. XX = Under normal conditions, these Sensor Inputs should not be connected. When the MUTE-ENABLE input is active, if at anytime these Sensor Inputs become active, the Muting system will transition to the LOCKOUT (FAULT) state.
08/2007 41
Sensor requirements
Sensor A must be a Dark-On type sensor with PNP type output or a switch that closes its contact to provide +24 V when it is Ok to mute. Sensor B must be a Light-On type sensor with PNP type output or a switch that opens its contact when it is Ok to mute. In a two sensor system, each sensor must transition to the ON state within 3 seconds of each other for the muting state to occur. Two Sensor Muting System Waveform Diagram
Muting state
ON state
Sensor-A Input
(Dark -On type sensor)
Sensor-B Input
(Light -On type sensor)
Safety Inputs
(OSSD inputs)
XPS Safety
Outputs (OSSD)
Mute Lamp Output
OFF
OFF
OFF
OFF
OFF
ON state
OFF
0.05<x< 3 sec.
OFF
ON state
ON state
OFF
ON state
ON state
OFF
42 08/2007

Three sensor muting system

Description The three sensor system is a uni-directional system. In this application Sensor C is
used as a direction detector, and must transition to the ON state prior to activation of sensor pair Sensor B and Sensor A. Sensors Sensor B and Sensor A must activate within 3 seconds of each other and Sensor C must turn OFF before Sensor B or Sensor A turn OFF. The figure below illustrates a muting system used in a three sensor conveyor belt configuration. Three Sensor System Design
Sensor A
Light
Curtain
Sensor C
Sensor C
Sensor C
Object
Sensor B
Sensor A
Object
Sensor B
Sensor A
Sensor B
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Conveyor
Object
08/2007 43
Transition conditions
The table below describes conditions required to transition to Muting state with a three sensor system:
No. of
Sensors
3 Sensor
System
State Mute
Enable
State 1 OFF X X X X Protected
State 2 ON OFF OFF OFF XX Protected
State 3 ON OFF OFF ON XX Protected
State 4 ON ON ON ON XX Muting
State 5 ON ON ON OFF XX Muting
Sensor ASensor B Sensor C Sensor DSystem
Status
X = Sensor can be in any state, does not apply to selected mode. XX = Under normal conditions, these Sensor Inputs should not be connected. When the MUTE-ENABLE input is active, if at anytime these Sensor Inputs become active, the Muting system will transition to the LOCKOUT (FAULT) state.
44 08/2007
Sensor requirements
The following conditions must be met for muting state to occur:
Sensors A & C must be a Dark-On type sensor with PNP type output or a switch that closes its contact to provide +24 V when it is Ok to mute.
Sensor B must be a Light-On type sensor with PNP type output or a switch that opens its contact when it is Ok to mute.
Sensor C must activate at least 0.05 seconds before sensors A & B.
Concurrence of activation of the sensor pair, sensor A & B, must be within 3 seconds of each other.
Sensor C must remain active until both sensors A & B activate.
Three Sensor Muting System Waveform Diagram
Muting state
ON state
Sensor-C Input
(Dark -On type sensor)
Sensor-A Input
(Dark -On type sensor)
Sensor-B Input
(Light -On type sensor)
Safety Inputs
(OSSD inputs)
XPS Safety
Outputs (OSSD)
Mute Lamp Output
OFF
OFF
OFF
OFF
OFF
OFF
ON state
OFF
0.05 sec.<y
ON state
OFF
0.05<x< 3 sec.
OFF
ON state
ON state
OFF
ON state
ON state
OFF
08/2007 45

Four sensor muting system

Description To mute in this bi-directional configuration, a sensor pair (Sensor A & Sensor B or
Sensor C & Sensor D) must transition to the ON state and concur within 3 seconds. Since conveyor is bi-directional either Sensor A or Sensor D can first be active in the sequence. The figure below illustrates a Muting system used in a four sensor conveyor belt configuration.
Light
Curtain
Bi-Directional
Object
Sensor A
Sensor A
Sensor A
Sensor A
Object
Sensor B
Sensor B
Sensor B
Sensor B
Light
Curtain
Light
Curtain
Light
Curtain
Light
Curtain
Object
Light
Curtain
Light
Curta in
Light
Curta in
Light
Curta in
Sensor C
Sensor C
Sensor C
Sensor C
Conveyor
Sensor D
Conveyor
Sensor D
Conveyor
Sensor D
Object
Conveyor
Sensor D
Bi-Directional
Bi-Directional
Bi-Directional
Bi-Directional
Object
Conveyor
Light
Sensor A
Curta in
Sensor B
Sensor C
Sensor D
46 08/2007
Transition conditions
The table below describes conditions required to transition to Muting state with a four sensor system:
No. of
Sensors
4 Sensor
System
State Mute
Enable
State 1 OFF X X X X Protected
State 2 ON OFF OFF OFF OFF Protected
State 3 ON ON OFF OFF OFF Protected
State 4 ON ON ON OFF OFF Muting
State 5 ON ON ON ON OFF Muting
State 6 ON ON ON ON ON Muting
State 7 ON OFF ON ON ON Muting
State 8 ON OFF OFF ON ON Muting
State 9 ON OFF OFF OFF ON Protected
Sensor ASensor BSensor CSensor DSystem
Status
X = Sensor can be in any state, does not apply to selected mode.
08/2007 47
Sensor Requirements
The following must be met for the XPSLCM1150 to enter or remain in the muting state:
Sensors A & C must be a Dark-On type sensor with PNP type output or a switch
that closes its contact to provide +24 V when it is Ok to mute.
Sensors B & D must be a Light-On type sensor with PNP type output or a switch
that opens its contact when it is Ok to mute.
Concurrence of activation of sensor pair Sensor A & Sensor B must be within 3
seconds and the concurrence of activation of sensor pair Sensor C & Sensor D
must be within 3 seconds.
Sequence of sensor activation is Sensor A before Sensor B before Sensor C
before Sensor D or the sequence may be in reverse direction, Sensor D before
Sensor C before Sensor B before Sensor A. The time difference between sensor
activation must be at least 0.05 seconds.
To stay in muting state sensor pair Sensor A & Sensor B must remain active until
sensor pair Sensor C & Sensor D activate. In reverse direction sensor pair
Sensor C & Sensor D must remain active until sensor pair Sensor A & Sensor B
activate.
48 08/2007
Four Sensor Muting System Waveform Diagram
Muting state
ON state
Sensor-A Input
(Dark -On type sensor)
Sensor-B Input
(Light -On type sensor)
Sensor-C Input
(Dark -On type sensor)
Sensor-D Input
(Light -On type sensor)
Safety Inputs
(OSSD inputs)
XPS Safety
Outputs (OSSD)
OFF
OFF
OFF
OFF
OFF
OFF
0.05<y
ON state
OFF
0.05<x< 3 sec.
OFF
ON state
ON state
OFF
0.05<z< 3 sec.
OFF
ON state
ON state
OFF
ON state
ON state
Mute Lamp Output
08/2007 49
OFF
OFF

Description of the bypass-allowed feature

Principle The XPSLCM1150 allows supervisory personnel to momentarily override the
machine stop signal of the XPSLCM1150. This function is used during instances where processing sequence operations did not allow an automatic transition to the muting state and the XPSLCM1150 safety outputs are in the Off state.
Signals in bypass-Allowed state
Enter the bypass-Allowed state
The XPSLCM1150 signals that it is in the Bypass-Allowed state by the following indications:
The mute lamp of the effected safety channel will flash at about a 1-second
interval.
The Mute Aux output will switch between active and inactive at about a 1 Hz rate.
The diagnostic display will show a code of 03.
The XPSLCM1150 will enter the Bypass-Allowed state under the following conditions:
Redundant DIP switches must be set to enable Bypass-Allowed feature to occur.
The mute enable inputs are active.
The light curtain safety outputs (OSSD) are in the Off state and a minimum of one
mute sensor is active in the effected safety channel.
50 08/2007
Transition to the Muting state
To allow the XPSLCM1150 to transition to the Muting state the supervisory personnel must press-and-release the start button. When entering the Muting state through the Bypass-Allowed feature the following will occur:
The mute lamp of the effected safety channel will now be On continuously.
The Mute Aux output will now be continuously in the active state.
The diagnostic display will show a code of 02.
If the light curtain is clear of obstructions before all of mute sensors have cleared then the XPSLCM1150 will leave the Muting state and enter the Machine Run state. Note, all of the mute sensors must clear for the XPSLCM1150 to automatically enter the Muting state during the next process cycle.
If all of the mute sensors clear of obstructions before the light curtain has cleared then the XPSLCM1150 will leave the Muting state and enter the Machine Stop state.
When the Muting state is entered through the Bypass-Allowed state then the maximum time for the XPSLCM1150 to be continuously in the Muting state is 10 minutes.
If the 10 minute time limit is exceeded the XPSLCM1150 will automatically change from the Muting state to the Bypass-Allowed state.
There is no limit on the number of times that the XPSLCM1150 can enter the Bypass- Allowed state and then with the press-and-release of the Start button into the Muting state.
08/2007 51
Example of bypass-allowed
A conveyor is operated with an XPSLCM1150 that has one light curtain and three mute sensors connected. The XPSLCM1150 is set to Start Interlock mode and Bypass-Allowed is enable.
Conveyor System Condition
System power is restored. Sensor is
Supervisor verifies that system is safe to start, the XPSLCM1150 Start button is pressed and released.
Conveyor motors are initially running. Conveyor motors stop when light curtain becomes block.
Conveyor motors stop. Sensor is
Supervisor verifies that system is safe to bypass, the XPSLCM1150 Start button is pressed and released.
Conveyor motors are running.
Conveyor motors are running.
Sensor A
Condition
Clear
Sensor is
Clear
Sensor
becomes
Blocked
blocked
Sensor is
blocked
Sensor is
blocked
Sensor
becomes
Clear
Sensor B
Condition
Sensor is
Clear
Sensor is
Clear
Sensor
becomes
Blocked
Sensor is
Blocked
Sensor is
blocked
Sensor is
blocked
Sensor
becomes
Clear
Sensor C
Condition
Sensor is
Blocked
Sensor is
Blocked
Sensor
becomes
Clear
Sensor is
Clear
Sensor is
Clear
Sensor is
Clear
Sensor is
Clear
Light
Curtain
Condition
Curtain is
Cleared
Curtain is
Cleared
Curtain
becomes
Blocked
Curtain is
Blocked
Curtain is
Blocked
Curtain
becomes
Cleared
Curtain is
Cleared
XPSLCM1150 Response to these conditions
Powers-up and enters Interlock state and senses that sensor C is active.
Enters Machine Run state, safety outputs (OSSD) switch to On state and conveyor motors start.
Enters Machine Stop (Bypass­Allowed) state since muting sensor C was not inactive at power-up, safety outputs (OSSD) switch to Off state.
XPSLCM1150 indicates Bypass­Allowed by blinking mute lamp and diagnostic code of «03» is dislayed.
Enters Muting state, safety outputs (OSSD) switch to On-state, mute lamp is lit and diagnostic code of «02» is displayed.
Enters Machine Run state, mute lamp turns off and diagnostic code of «00» is displayed.
Stays in Machine Run state and is ready to automatically enter muting when next object passes through sensors.
52 08/2007

Diagnostic display

At a glance
Overview This chapter describes the XPSLCM1150 Diagnostic display.
3
What's in this Chapter?
This chapter contains the following topics:
Topic Page
System diagnostic codes 54
Mute operation diagnostic codes 56
08/2007 53

System diagnostic codes

Operational codes
DIP switch fault codes
The operational codes are described in the table below
Code Displayed System Status
00 Normal operation, no faults
01 In the Interlock state and waiting for Start input.
02 Operating in Muting state.
03 In Bypass Allowed state & waiting for Start input.
88 PowerUp Indication
The DIP switch fault codes are described in the table below.
Code Displayed Fault Indicated
21 Invalid Mode Selection setting.
22 Switch Setting Changed During Operation.
23 DIP Switch Settings Not Identical.
27 Invalid selection for the number of safety inputs connected.
28 Invalid selection for the number of mute sensors connected.
OSSD faults The safety output (OSSD) fault codes are described in the table below.
Code Displayed Fault Indicated
31 Safety outputs A & B shorted together
32 Safety outputs A shorted to power
33 Safety outputs B shorted to power
34 Safety outputs A shorted to ground
35 Safety outputs B shorted to ground
54 08/2007
EDM/MPCE codes
The EDM/MPCE fault codes are described in the table below.
Code Displayed Fault Indicated
41 EDM/MPCE monitoring signal was in the Wrong state Before
entering the Machine Run state.
42 EDM/MPCE monitoring signal was in the Wrong state After entering
the Machine Run state.
43 EDM/MPCE monitoring signal was in the Wrong state during power
up of XPSLCM1150.
Internal fault code
The Internal Fault codes are described in the table below.
Code Displayed Internal Fault
50 Detected Fault of XPSLCM1150 internal circuits.
08/2007 55

Mute operation diagnostic codes

Mute errors (not faults)
Safety input devices, light curtain OSSD input signals, errors
The operational codes are described in the table below
Code Displayed Errors
61 Incorrect activation sequence of Channel 1 mute sensors did not
allow Muting.
62 Incorrect activation sequence of Channel 2 mute sensors did not
allow Muting.
63 The activation time period between the mute sensor pairs (S1A &
S1B or S1C & S1D) of Channel 1 exceeded 3 seconds, concurrency error.
64 The activation time period between the mute sensor pairs (S2A &
S2B or S2C & S2D) of Channel 2 exceeded 3 seconds, concurrency error.
65 The 2 minute time limit of being in the Muting state was exceeded,
mute was initiated by the sensors of Channel 1.
66 The 2 minute time limit of being in the Muting state was exceeded,
mute was initiated by the sensors of Channel 2.
67 The lamp connected to Mute Lamp 1 output is open circuit, this error
will not allow muting to occur.
68 The lamp connected to Mute Lamp 2 output is open circuit, this error
will not allow muting to occur.
Safety input devices, light curtain OSSD input signals, errors
Code Displayed Safety input devices, light curtain OSSD input signals, errors
71 The On state or Off state switching time between Light Curtain 1
OSSD inputs 1A & 1B exceeded 300 msec, concurrency error.
72 The On state or Off state switching time between Light Curtain 2
OSSD input 2A & 2B exceeded 300 msec, concurrency error.
56 08/2007

Test procedure

Test procedure
4
WARNING
IMPROPER TEST PROCEDURE
The following test procedure MUST be performed by qualified personnel:
Following system installation.
In accordance with the employer’s regular inspection program.
Immediately following any maintenance, adjustment or other modification to any system component.
Testing ensures that the safety devices and associated machine control system work together to properly stop the guarded machine. Failure to perform these procedures could result in serious injury.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Note: It is the user’s responsibility to ensure that the installation conforms to all
federal, state, local and company regulations pertaining to safe operation of the equipment.
08/2007 57
Installation checkout
Step Action
1 Disable the guarded machine.
2 Visually inspect the machine to ensure that access to the danger point is only
through the area (s) protected by the safety light curtain(s).
3 Verify that the mounting distance of the safety light curtain(s) is equal to or
greater than the minimum safety distance required according to the EN 999 and ANSI Minimum Safe Distance calculation. (See (See Adjusting the safe mounting distance, p. 19).
4 Check the overall system for damage, security of electrical cabling and wiring,
or other hazards.
CAUTION
IMPROPER INSTALLATION
If any of the above requirements are not met, immediately lock out the machine and initiate the necessary corrective action.
Failure to follow these instructions can result in injury or equipment damage.
58 08/2007
Normal operation with muting disabled
Step Action
1 Disable the guarded machine. Apply power to the XPSLCM1150 system.
2 Ensure the Muting Enable switch is in the OFF (disabled) position.
3 Using the proper size test object for each light curtain, test the protected area of
the light curtain. Test the area by moving completely through the field, top to bottom, ensuring that all the areas between transmitter and receiver are completely tested. The light curtain should remain blocked at any point with the test object present in the sensing field.
4 Enable the machine and initiate a start. Interrupt the sensing zone with the
correct test object and verify the machine stops immediately. Never attempt to insert the test object directly into the danger area! If the machine fails to stop, discontinue the testing and lock out the machine. Investigate and correct prior to re-testing.
5 With the test object present in the field, verify the machine cannot start.
6 Repeat tests for all safety light curtains installed.
08/2007 59
Mute operation (muting enabled)
Step Action
1 Complete testing requirements in Installation checkout, p. 58 and Normal
operation with muting disabled, p. 59
2 Disable the guarded machine and apply power to the system.
3 Set the Muting Enable Switch to the ON position.
4 Mute the system by blocking the correct sensors at the proper intervals (<3
seconds between sensors) and logical order. (Refer to the appropriate system timing diagram) Verify that the associated mute inputs on XPSLCM1150 are ON. Verify the external Mute active light(s) are ON and the XPSLCM1150 OSSD outputs are in the RUN mode, XPSLCM1150 Display indicates 02 (mute active)
5 Interrupt the safety light curtain (SLC) with the correct test object. Verify that the
SLC outputs switch OFF (Red or blocked). OSSD inputs for that SLC are OFF, XPSLCM1150 outputs remain ON. XPSLCM1150 Display indicates 02 (mute active)
6 With the test object present in the light curtain sensing field, verify the machine
is "run capable". Remove the test object for further tests.
7 If the Mute Time Limit is enabled, maintain the mute state for 2 minutes. After 2
minutes the XPSLCM1150 OSSD outputs will switch from RUN to STOP. The external Mute Active light will flash at a 1-2 Hz rate and the display will indicate 03 (Bypass Allowed). Press the Start switch and verify the XPSLCM1150 outputs return to the RUN state and external Mute Active lamp is ON. XPSLCM1150 Display indicates 02. Bypass is allowed until either the muting sensors clear or light curtain clears or 10 minutes has expired.
8 Reset system to Normal (non-mute) Operation.
9 If a one way or directional system is used, test operation to verify mute is
activated only when the correct sequence and intervals are applied and that the machine (in the case of a machine tool such as a power press) is muted only during the non-hozardous cycle.
10 Repeat test procedure(s) for 2nd muting channel (if installed).
60 08/2007

Glossary

A
Automatic Start Upon completion of power-up, the XPSLCM1150 will enter the MACHINE RUN state
as soon as all of the selected light curtain OSSD inputs are in the ON state. Schneider has traditionally referred to this as the Normal mode.
B
Bypass-Allowed Allows supervisor personnel to momentarily override the Machine Stop operation of
the XPSLCM1150. This function is used during instances where processing sequence operations did not allow a transition to the Muting state and the XPSLCM1150 entered the Machine Stop state. When in the Bypass-Allowed state, a press-and-release of the Start button allows the XPSLCM1150 to transition to the Muting state for only one cycle or a maximum duration of 10 minutes.
D
Dark-On A photo-electric sensor term that means the sensor output will be active when the
sensor detects an object.
08/2007 61
Glossary
E
EDM/MPCE (Machine Primary Control Element) Monitoring
The XPSLCM1150 monitors the state of the EDM/MPCE signal produced by the guarded machine to insure that it is in the correct state with respect to "Machine Run" and "Machine Stop."
I
Interlock For the XPSLCM1150 to enter this state the unit must be set to either the Start
Interlock or Start/Restart Interlock mode. In this state the yellow Interlock LED is on and the red Machine Stop LED is on.
L
Light-On A photo-electric sensor term that means the sensor output will be active when it
receives the sensed light source.
Lockout (Fault) When the XPSLCM1150 detects a fault, it transitions to this state. The Safety
outputs will be held to the off state and the XPSLCM1150 will not attempt to leave this state without performing a comprehensive power-up self-test. A power-up self­test will be initiated by either cycling the XPSLCM1150 power or by a Start signal transition.
M
Machine Run When the XPSLCM1150 is in this state the two Safety outputs are both active. In this
state, the Green Machine Run LED is on, the Red Machine Stop LED is off and the Yellow Interlock LED is off.
Machine Stop When the XPSLCM1150 is in this state the two Safety outputs are both inactive. In
this state the Green Machine Run LED is off, the Red Machine Stop LED is on and the Yellow Interlock LED is off.
62
Glossary
Muting The mute sensors have been properly activated for the XPSLCM1150 to keep the
Safety outputs active when the light curtain detection zone is interrupted.
O
OFF State The state in which the output circuit is interrupted and does not permit the flow of
current.
ON State The state in which the output circuit is completed and permits the flow of current.
R
Response Time The maximum amount of time required for the XPSLCM1150 to recognize a light
curtain detection zone interruption and to set its Safety outputs to the Off state.
S
Safety Output (Output signal switching device (OSSD)
Start Interlock Upon completion of power-up, the XPSLCM1150 must go to the "Interlock" state. A
Start/Restart Interlock
08/2007 63
The component of the XPSLCM1150 connected to the control system of the guarded machine.
Start signal transition must occur before going to Machine Run for the first time. Once the first Start condition has been met, the XPSLCM1150 will operate in the Automatic Start mode.
The XPSLCM1150 will go into the Interlock state upon completion of power-up and after all light curtain detection zone interruptions which cause a transition to the Machine Stop state. A Start signal transition must occur before returning to Machine Run following any transition to Machine Stop.
Glossary
64
Loading...