120VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUTTO UNIT IS
TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.
REQUIREMENTS:
•
U.L. labeled fire or smoke barrier door assemblies require
that the 120VAC, 60Hz power input to the Power Door
Operatorbe supplied through normally closed alarm
contactsofthealarmsystem/alarmpanel.
•
All wiring and connections use standard wiring practice
conformingwithlocalwiringcodes.
•
Power inputs at terminal strip T1 and at terminal strip JP4 must
bemadewithcopperwireonly.
•
Maximumwiresizeis:
12AWGatPowerInputTerminalStrips
14AWGatTerminal StripsJP1 And JP4
Note:
No power/voltage inputs are to be made to the Door
Operator unit except 120VAC, 60Hz (+10% -15%) at terminals
HOTandCOMofthe PowerInputTerminal StripT1.
Low Energy Door Operators
Wiring Instructions For 4051, 4052, 4060, 4067
Power input terminal strip T1 at terminals Hot and COM must be
120VAC at 60Hz (+10% -15%).
•
Current draw at auxiliary contact JP4 – 2 must not exceed 0.500
amps, for auxiliary devices.
GENERAL DATA:
••Maximum current draw of Door Operator units without peripheral
sensors orscanners is1.5 ampswhen motor is operating, .050 amps
instandby.
Maximum current draw from auxiliary devices is 0.500 amps
(terminals JP4 – 1 and JP4 – 2).
Fuse “F2”protects the Electronic Control Module and Transformer
circuit and is a 3 amp slow blow fuse.
Requirements
Unit Wiring
Control Module Layout and (Input/Output Connections;Functions)
Typical Application – Point to Point Wiring Diagrams
Field Reversible
Unit Shown
Square Spindle End
Protrudes
Spindle Timing
Pulley for Field
Reversible
Units
Timing Belt
ELS Board w/
ELS Board
Pulley
ELS Board
LED
JP2
Terminal
Strip
S
P
Rotary Switches/
C
H
US
Timer Pots
(SC) Speed
Control Valve
1
2
3-5
6-15
SW1
Dip
Switches
Main Board
JP3
Terminal
Strip
Bracket for
Input Power
Terminal Strip
T1
Fuse
F2
JP1
Terminal
Strip
JP4
Terminal
Strip
JP5
Terminal
Strip
80-9369-0901-021 (12-02 )
11/16" Power
Adjustment Nut
Door Calibrate
Open Position
Solenoid
Door Calibrate
Close Position
1
Application
(REF)
Handed Unit
Shown
Spindle Timing
Pulley
Handed Units
A7666A
CONCEALEDWIRING
Threadconduitfitting(s) intobackplateasshown.
Asecond conduitfittingis requiredforlow voltage
control wiring. CHECK LOCAL CODES. Pull
conduit out of header and attach to conduit
fittings before mounting Operator to door frame.
Attach incoming ground wire to backplate with
groundscrewasillustratedbelow.
Conduit by Others
(from top)
(Green) Ground Screw
Low Voltage
Control
Wiring
Incoming
Power
SURFACE WIRING
An optional bracket is provided for use with
surfacewiring. Remove thetwo cable clamps
screws and slip the bracket under the cable
clamps. Push the cable clamp screw through
the bracket holes and tighten.½” conduit
fittingscannowbeinstalledonthebracket.
INSTALLER / USER INFORMATION
Input PowerTerminal Strip
Terminals 22 through 25 are factory wired using 18AWG wire.
– 120VAC, (+10% - 15%) InputVoltage. Maximum wire size 12 AWG at terminals HOT and COM.
Cable
Clamps
Optional Bracket
(for surface wiring)
Ground
Lead
“T1” Power
Input
Terminal Strip
Bracket
Power
Leads
Earth GroundWire Connection
InputTerminal Strip bracket. Screw labeled“GND”.
– Groundwire must be secured to backplate under head of (green) groundscrew nearestto “T1” Power
TerminalDescription
COM
(Neutral)
HOT
(Line)
25
24
23
22
2
Commonpowerlead
Hotpowerlead
Fuseconnection
Hot connection to PC board JP5 – 2 and to hot
primarysideof120V/24Vtransformer.
Fuseconnection
Common connection to PC board JP5 – 1 andto
commonprimarysideof 120V /24Vtransformer.
Fuse F2*
22
23
24
25
HOT
COM
Left Hand Double Lever, Push Side
Right Hand Slide Track, Pull Side
23
22
24
COM
HOT
25
Right Hand Double Lever, Push Side
Left Hand Slide Track, Pull Side
80-9369-0901-021 (12-02 )
Fuse F2*
SW5 Rotary
Switch/Timer
Pot
SW4 Rotary
Switch/Timer
Pot
SW2 Rotary
Switch/Timer
Pot
SW1 Dip
Switches
JP1 Terminal
Strip
JP2 Terminal
Strip
SW3 Rotary
Switch/Timer
Pot
JP3 Terminal
Strip
Fuse F1
1.5 amp,
2AG
JP2
G
EM
G
H+VL2
G
L1
JP3
MOTOR/SOLENOID
CL/AS DLY
3
4
2
1
5
0
6
9
7
8
EXSOL DLY
3
4
2
1
5
0
6
9
7
8
Relay
K2
VEST DLY
3
4
2
1
0
9
7
8
M. DLY
3
4
2
1
0
9
7
8
5
6
5
6
Relay
K1
NEU HOT GND18VAC
DOOR OPERATOR
41-6700-0056 REV A MADE IN USA
Relay
K3
JP5
1 2 3 4 5 6 7 8
GND+24V NO1 CO1
OFF
Relay
K4
NC1
SW1
NO2 CO2 NC2
ON
P/A
A/D
RES1
RES2
JP4
JP1
14
AUX1
13
GND
12
PDET
11
GND
10
AUX2
9
GND
T
F
8
R
7
GND
6
OUTV
5
INV
4
GND
3
AUX2
2
RES1
1
0/0
JP4 Terminal
Strip
Slo-Blo
Electronic Control Module (Main PC Board)
JP1Terminal Strip – Maximum wire size 14AWG. For signaling only, do not make power input connections.
TERMINALD E S CRIPTION
Override Open
10/0
– This terminal has two possible functions that can be used together or separately.
1.– Upon initiation of a closed signal from a fire/ smoke alarm
SmokeVentilation Door or Blow Open Door
panel, door will open and remain open until signal is terminated. Use with any JP1 ground.
2.– Time is set with dip switch SW1 – 2 A/D. (OFF = 30
Alarm Delay (30 second or 60 second time period)
second delay, ON = 60 second delay) Use with any JP1 ground.
2RES1This is not an active contact.
– This is one of two secondary initiating switch contacts (JP1 – 10 is the other.)
3AUX2
Auxiliary 2
For most applications it is equivalent to AUX1 JP1 – 14. For Vestibule Function use, it is the contact for a switch
located within the vestibule. Use with any JP1 ground.
4GNDGround
In Vestibule – Used for Vestibule Function. This contact must be connected to the JP1 – 6 terminal from another
5INV
unit to receive an initiating signal. The signal is then programed to initiate the unit by setting theVEST DLY rotary
switch/timer pot of the receiving unit. Use this contact with any JP1 ground.
6OUTV
Out Vestibule
send an initiating signal. Use with any JP1 ground.
– Used forVestibule Function. This contact must be connecter to terminal JP1 – 5 of another unit to
7GNDGround
– With the unit’s 3 Position Slide Switch in the “ON” position, a signal will open the door and
8RFT
Maintain Hold Open
maintain an indefinite hold open until a second signal releases the door from hold open. Use with any JP1 ground.
This feature recommended for Power Operator Function. If using with the Power Assist Function, consult factory.
9GNDGround
10AUX2– Same as JP1 – 3 / AUX2 above.Auxiliary 2
11GNDGround
12PDET
Presence Detector
fully open from closing. Use with any JP1 ground.
– Permits wiring of a presence detector to prevent a closed door from opening or a door that is
13GNDGround
Auxiliary 1 – Primary initiating switch contact. Initiates door power cycle. Must be Normally Open Momentary Dry
14AUX1
Contact. For Vestibule Function, the switch at outside of vestibule is connected to this terminal. (Outside switch to
outside unit’s JP1 – 14. Inside switch to inside unit’s JP1 – 14). Use with any JP1 ground.
80-9369-0901-021 (12-02 )
3
JP4Terminal Strip – Maximum wire size 14AWG.
TERMINALD E S CRIPTION
1GNDGround
2+24
3NO1
24VDC (unregulated)to a maximum current draw of 0.500 amps. Use with ground terminal JP4 – 1.
DO NOT
A separate 24VDC filtered and regulated supply must be used.
Control (Relay Contact Only – 5Amp @ 24VDC) – Normally open contact that is switched by Relay K3 (on main
board) to close. Relay K3 will remain switched for a period set by SW – 3 EXSOL DLY rotary switch / timer pot.
Use with terminal JP4 – 4 CO1. Coordinate use of this terminal with delayed start of motor using rotary timer pot
SW – 2 M DLY.
use this supply with 56- Latch Retraction Exit Device.
output
4CO1
5NC1
6NO2
7CO2
8NC2
Control (Relay Contact Only) – Common contact for use with terminals JP4 – 3 NO1 and JP4 - 5
Nc1.
Control (Relay Contact Only – 5Amp @ 24VDC) – Normally closed contact that is switched by Relay K3 (on main
board) to open. Relay K3 will remain switched for a period set by SW – 3 EXSOL DLY rotary switch / timer pot.
Use with terminal JP4 – 4 CO1. Coordinate use of this terminal with delayed start of motor using rotary timer pot
SW – 2 M DLY.
Alarm Delay (Switching Contact Only) – Normally open contact that is switched by relay K4 (on
main board) to close. Relay K4 will remain switched for a period set by Dip Switch SW1 – 2 A/D (OFF = 30 second
delay;ON = 60 second delay). Use with terminal JP4 – 7 Co2.
Alarm Delay– 5Amp @ 24VDC
and JP4 – 8 NC2.
Alarm Delay
main board) to open. Relay K4 will remain switched for a period set by Dip Switch SW1 – 2 A/D (OFF = 30 second
delay;ON = 60 second delay). Use with terminal JP4 – 7 Co2.
(Switching Contact Only) – Common contact for use with terminals JP4 – 6 NO2
(Switching Contact Only – 5Amp @ 24VDC) – Normally closed contact that is switched by relay K4 (on
– 5Amp @ 24VDC
– 5Amp @ 24VDC
Main Board Switches
DIP SWITCHES (MAIN BOARD)DESCRIPTION
1P/A
2A/D
3RES1DIAGNOSTIC USE. FOR FACTORY AUTHORIZED PERSONAL.
4RES2DIAGNOSTIC USE. FOR FACTORY AUTHORIZED PERSONAL.
Door Operator Function Switch – OFF position selects the Power Operator Function. On
position sets the Power Assist Function.
Alarm System Delay Timer – This switch is used in conjunction with terminal Jp1– 1, 0/0 for
optional function 2. (OFF = 30 second delay, ON = 60 second delay).
ROTARY SWITCHESDESCRIPTION
SW2M DLY
SW3EXSOL DLY
SW4VEST DLY
SW5CL/AS DLY
Chart 1 – SW2, M DLY
Length of Time
(Seconds)
0.0
0.2
0.5
1.0
1.5
2.5
3.5
4.5
Settings
0
1
2
3
4
5
6
7
This rotary switch or timer pot sets the length of delay for motor start up to allow for“unlocking”
of exit devices, electric strikes, magnetic locks, etc. See Chart 1 for delay times.
This rotary switch or timer pot sets the length of time that a solenoid remains either energized or
de-energized to allow “unlocking”. Used in conjunction with terminals JP4 – 3, JP4 – 4, JP5 – 5.
See Chart 2 for length of time.
This switch or timer pot sets the length of time between receipt of the“In Vestibule”signal
(terminal JP1 – 5) and motor start-up. See Chart 3 for delay times.
Controls either one of two function times:
Power Operator Function
Power Assist Function
force. When time elapses, the door force reverts to full opening spring force set.
Chart 2 – SW3, EXSOL DLY
Length of Time
(Seconds)
0
1
2
4
6
8
10
12
– Sets length of time door holds open at fully “taught”open position.
– Sets length of time motor and pump will operate to reduce opening
Chart 3 – SW4, VEST DLY
Settings
0
1
2
3
4
5
6
7
Length of Time
(Seconds)
0
1
3
6
9
14
21
30
Settings
0
1
2
3
4
5
6
7
Chart 4 – SW5, CL/AS DLY
Length of Time
(Seconds)
0
2
5
10
15
20
25
30
Settings
0
1
2
3
4
5
6
7
4
80-9369-0901-021 (12-02 )
JP2Terminal Strip – Factory Wired Connections.
TERMINALD E S CRIPTION
L1
G– Ground. Common connection for L1 and L2 inputs.Black Wire
L2
+V+24VDC. This terminal is used to supply power to the ELS Board.YellowWire
H– Hold Open contact of“OFF” “ON” “H/O”switch assembly.Violet Wire
G– Ground. Common contact of “OFF”“ON” “H/O”switch assembly.White Wire
MOrange Wire – ON contact of “OFF”“ON” “H/O”switch assembly.
E
G– Ground. Use with terminal Jp2 – E for Emergency Hold Open Release.Black Wire
White Wire
or pulled in the open direction. Movement of potentiometer on ELS Board signals L1 input.
Blue Wire
during the teaching mode.
Red Wire
door immediately at any point of door opening once an obstruction on opening is encountered. It is used with
terminal JP2 – G.
– High side of L1 Input signal from ELS Board. Detects door motion to open door when door is pushed
– High side of L2 Input signal for ELS Board. Detects the Fully Open Position stored in the ELS Board
– Emergency Hold Open Release. This contact is used in conjunction with the ELS board to close the
JP5Terminal Strip – Factory Wired Connections.
TERMINALD E S CRIPTION
1NEUCommon 120V connection to Input PowerTerminal 22.
2HOTHot 120V connection to Input PowerTerminal 24.
3GND
418VACFrom secondary of 120V / 24V transformer.
518VACFrom secondary of 120V / 24V transformer.
Ground connection secured to backplate under head of (green) ground screw that is located under Main PC Board.
Screw Labeled “GND”
JP3Terminal Strip – Factory Wired Connections.
TERMINALD ESCRIPTION
MOTORMotor Connection.
SOLENOIDSolenoid coil connection.
80-9369-0901-021 (12-02 )
5
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.