SARGENT 2900 User Manual

Wiring Instructions for the 2900 Series FIREGUARD
®
Combination Door Closer-Holder and Releasing Device
with Integral Smoke Detector
CAUTION: FAILURE TO INSTALL OR ADJUST PROPERLY MAY RESULT IN INJURY OR DAMAGE.
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
CAUTION
INSTALLER: LEAVE INSTRUCTION with building owner.
• Refer to data sticker for proper input voltage and current specifications
• 9- Companion units are designed to work with 12- smoke detector units (12-2960, 12-2990, 12-2980) only
• Wire companion unit to 12- smoke detector unit as shown on wiring diagram if required
• Do not disconnect any existing wires on smoke detector unit’s terminal strip
• Energize power supply. Current draw .1 AMP per 12- unit.
• Open door(s) to hold-open point. Door(s) should hold open
• Depress On/Off test switch on circuit board. Doors should close and latch
• Adjustment of spring power may be necessary to ensure proper latching
• Depress On/Off test switch to reactivate hold open latch assembly(s)
A7408B
1
1. DISCONNECT ALL POWER BEFORE BEGINNING INSTALLATION TO PREVENT ELECTRICAL SHOCK AND EQUIPMENT DAMAGE.
2. INSTALLER MUST BE A TRAINED, EXPERIENCED SERVICE PERSON.
3. ALL WIRING MUST COMPLY WITH APPLICABLE LOCAL ELECTRICAL CODES, ORDINANCES AND REGULATIONS.
4. MAXIMUM WIRE SIZE IS 18AWG.
Wiring 12- Units with and without 9- Companion Unit
Wiring Optional Remote Push Button
Terminal strip for power input wiring
Opening for surface or concealed wiring
9- Companion Unit (If required)
Black
Black
Field wiring by others
Yellow
Data Sticker
Red
Yellow
Black
3
7
Wire nut
On/Off Test switch
12- Smoke Detector Unit
User supplied normally closed momentary switch
Remove jumper and install output connector assembly (Part No. 63-2868) required for this option
Yellow
Red
1112
9
RED LED/
14
Reset Switch
Earth ground connection is required when 120VDC power is used
120VAC
Power
Supply
Wire the appropriate Power Supply to circuit board. Power is either 120VAC or 24VDC/VAC depending on circuit board supplied.
When 24VDC/VAC board is supplied, wire 24VDC/VAC power supply to + and - terminals on circuit board.
Line
Neutral
Earth Ground
Smoke detector unit
*120VAC
wiring shown
Circuit board 120VAC or 24VAC/DC
Self resetting fuse
(120VAC shown)
*120VAC Circuit Board shown
*CAUTION: Refer to data sticker on circuit board for proper input voltage required.
Do NOT wire 120VAC power to 24VDC/VAC circuit board.
2
A7408B
Smoke Detector Operation and Application
The closer/holder unit includes a 4-wire, photoelectric type smoke detector. It provides: smoke detection, door holder solenoid control, N.O. alarm contact, N.C. supervisory contact and interconnection to other smoke detectors. Field option: one form C auxiliary contact (cut jumper wire between 11 and 12).
Terminal Inputs and Outputs
24VDC input power is applied to terminals 3 (-) and 14 (+) by the adjacent circuit board. Red LED flashes every 8 seconds
Terminals 1 and 2 provide a normally open (alarm) contact. This contact closes when smoke is detected. Red LED illuminates continuously
Terminals 5 and 13 provide a normally closed supervisory (trouble) contact. This contact opens when power is lost to the detector circuity. Red LED stops flashing
Terminals 9 and 6 provide rectified, unfiltered 24VDC to the door holder solenoid. This power is cut in alarm and the door closes
Terminals 7 and 8 provide rectified, unfiltered 24VDC to auxiliary devices when the detector alarms
Terminal 10 is rail + output. It is a continuous, rectified, unfiltered 24VDC used for remote detector interconnect applications
Terminals 8, 9 and 10 may be field configured to a dry form contact by cutting jumper between terminal 11 and 12. Terminal 10 is Common, 9 is N.C. and 8 is N.O. If this is done, Aux.+ is lost; solenoid power must be supplied by a separate source.
Terminals 15 and 4 provide interconnections to other detectors (See diagram Pg. 4). Up to five smoke detectors may be interconnected. When a single detector alarms, terminal 15 goes high and any interconnected smoke detector will close its doors. The unit that initiated the alarm will have its LED on. The other interconnected units’ LEDs will flash as normal. Refer to interconnection wiring diagram for connections.
Detector Specifications (Part# 63-3210, Revision D)
Type: Photo-Electric Smoke Detector
Complies with UL 228 and UL 268 standards
Power Requirements: 24VDC +/- 10%
Nominal Sensitivity: 2.325 +/- 1.055%/FT
Contact Ratings
Alarm and/or Accessory 2.0 AMPS Max. @ 24VDC (Resistive load) 0.6 AMPS Max. @ 120 VAC
Trouble Contact 0.5 AMPS Max. @ 24VDC (Resistive load)
Connection List
Function Terminal
24VDC input 3 (-), 14 (+)
Alarm contacts 1, 2
Solenoid + 9
Solenoid - 6
Aux + 8
Aux - 7
Interconnect + 15
Interconnect - 4
Trouble contacts 13, 5
+24VDC output (unfiltered) 10
NOTE: Terminals 4, 6 and 7 are same point.
15 7 6 5 4 3 2 1
14
13
12
11
10
9 8
3
A7408B
1. Turn the power to the unit “On”. Red LED pilot light should illuminate at 8 sec. intervals
2. Open door to the hold open point. The door should hold open. Manually pull door out of hold open and release. Door should close
3. Open door to the hold open position. Depress (maintained type) On/Off “test switch” button on the power supply board. Door should close
4. Depress On/Off test switch again. Open door to the hold open position. Inducing smoke into the smoke detector chamber assembly will bring the unit into alarm. The red LED will be continuously illuminated and the door will close. After clearing the smoke chamber, reset unit as follows
Checkout Procedure
1. Remote Reset: Cycle main power by turning the facility main power supply OFF then ON. NOTE: If there are other units connected to the same power supply those doors will close. They will have to be reopened returning them to the hold open position
2. Local Reset: Insert a small flat head screwdriver through the cover and into the slotted light tube on the smoke detector as shown. Turn screwdriver slightly (about 1/8 turn) clockwise until hitting stop and hold for 2 seconds until the Red LED turns OFF. WARNING: Do not force past the stop. Doing so may damage the smoke detector
Once the detector is reset and the smoke has cleared, the detector’s Red LED should flash once every 8 seconds. The door(s) should hold open now
Resetting Instructions
SARGENT recommends cleaning smoke detectors at least every six months. The frequency of cleaning will depend upon local ambient conditions
The smoke detector in this door closer-holder has been enhanced with a feature that detects when a smoke-sensing chamber requires cleaning due to dirt and dust. The need for cleaning is indicated by the flashing of the Red LED light once per second
Normal Supervisory Operation — Red LED flashes once every 8 seconds
Dirty Chamber, needs cleaning — Red LED flashes once every second
Smoke Detection — Red LED is continuously illuminated
To clean the smoke detector assembly, follow the instructions below:
NOTE: Before servicing the system, notify the proper authorities that the smoke detector system is undergoing maintenance and will be temporarily out of service. Disable the zone undergoing maintenance to prevent unwanted alarms
Smoke Detector Maintenance
• Remove detector cover and screen assembly using a standard screwdriver. Turn the screwdriver in the cover slot to loosen the cover and carefully rock the cover back and forth until it snaps out of place. See slot location above
• Inspect chamber for particles and dust. Vacuum the screen, cover, and photo chamber. Then use clean, compressed air to loosen and blow out any remaining debris
• Before reassembling the detector, be sure all parts are free of dust and debris
• Replace cover and screen, aligning cover snaps, press cover onto chamber until it snaps into place
• Measure and record the test voltage at test points RP1 and RP2 (see above). If the smoke detector is operating normally and was cleaned effectively, the test voltage will be greater than .90VDC and less than 1.58VDC. The test voltage will increase with dust accumulation in the smoke sensing chamber. A difference in test voltages over time will provide an indication of dust accumulation
• Enable system and inform proper authorities system is operational
RP2 test point
RP1 test point
Slot for screwdriver To remove cover
Cover and screen
Chamber
Slotted light tube (Red LED)
Loading...
+ 5 hidden pages