14.33 lb (6,5 kg) Plastic
1" BSP/NPT (F) and flange
_
1" BSP/NPT (F) and flange
* (oz,ft,gal/min) all in EEUU units
2013_12_17-16:30
R. 12/13 855 822
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
1
Warnings and cautions
In this document you will find warnings and cautions for installation, use
and maintenance of the Direcflo pumps.
Warning
This symbol aware that there is a danger of serious bodily injury or death
if you ignore the warning described.
Warning
Carefully read the instructions and warnings before operating the equipment!
• This equipment is for professional use only
• Do not degrade the integrity of the equipment. Use only original
replacement components from Samson Corporation.
• Fluids not suitable for the pump can cause damage to the pump unit
and involve risk of serious personal injury.
• Always consult Samson Corporation if you have any questions about
the compatibility within the fluids and the pump materials, including
elastomers.
• Install and use the pump according to all local and national regulations
and abide all health and safety laws or legislation.
• The pump can produce fluid pressures equal to the air supply pressure.
Do not exceed the maximum allowable pressure of 100 psi (7 bar) air
supply. The total hydraulic pressure (differential pressure + system)
should never exceed 100 psi (7 bar).
• Never use a pump that leaks, that is damaged, that is corroded or
otherwise it may lack the capacity to contain the fluid.
• Frequently check that the bolts on the diaphragm cover of the pump are
torqued correctly.
Here’s the meaning of symbols you may find in this document and general
warnings that you should keep in mind.
Caution
This symbol aware that there is a danger of personal injury or property
damage if you ignore the caution described.
• Do not use a model with aluminium wetted surfaces to pump fluids for
human consumption, there is a possibility of trace contamination of lead.
• Danger of explosion if used 1,1,1-trichloroethane, methylene chloride
or other halogenated hydrocarbon solvents with aluminium wetted
materials. It could cause serious injury and property damage.
• Inside the pump, diaphragms separate the fluid that is being pumped
from the air supply. If a diaphragm breaks, the fluid can leak out of the
air exhaust and contaminate the environment.
• When handling hazardous fluids, always route the air exhaust into a
suitable container and locate it in a safe place.
• When the fluid source level is situated higher than the pump, (flooded
suction), the outlet tank must be at a higher level than the product to
prevent spills.
• For pumps handling hazardous fluids that are a danger to humans or to
the environment, install a suitable container surrounding the pump to
prevent any leaks or spills.
• Ensure that the operators of this equipment are trained on the operation
and limitations. Use safety equipment as safety goggles or other
equipment required.
Description
Air operated double diaphragm pumps are air-powered, reciprocating
positive displacement pumps with two pumping chambers. Two
diaphragms, centrally located in the chambers, separate the compressed
air (dry side) from the fluid being pumped (wet side). A shaft transmits
2013_12_17-16:30
the reciprocating motion of one diaphragm to the other. A directional valve
alternatively distributes the air from one chamber to the other; thus a
reciprocating movement of the diaphragms is created. With each stroke,
fluid is discharged by one of the diaphragms whilst the opposite
diaphragm sucks new fluid into the expanding chamber. Check valves, two
on the discharge side and two on the suction side, control and direct the
fluid flow.
2
855 822 R. 12/13
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
1"BSP
NPT
8.27"
3/8" NPSM
Installation
Installation recommendations
• Remove the pump from its package and install it on the chosen location.
• Try to minimize the suction head. Install the pump as close as possible
to the fluid being pumped.
• Remember to have enough space around the pump to perform
maintenance tasks.
• Keep in mind to connect the inlet and outlet of the pump correctly.
• In case of diaphragm pump failure, the air exhaust will expell the
product being pumped.
• When the pump is installed in a place where a spill of fluid can cause
an environmental impact, the exhaust should be directed to a place.
where this spill could be contained.
• When installing the pump in its place, use brackets to secure its base.
• Fasten all bolts with the torques contained in this manual.
DF pumps are very easily configured and easy to install.
Flooded:
The pumping system was designed with positive pressure at the inlet. This
is the best possible installation when you need to evacuate the liquid from
the drum or tank, or when working with viscous fluids.
Not recommended for hazardous fluids.
Self-priming:
Pump is designed to generate vacuum. It is possible to evacuate all the air
from a hose or pipe without damaging the pump. Maximum suction height
is 19.69 ft (6 m), with the suction hose empty and up to 26.25 ft (8 m)
with the hose primed. (See page 1 for corresponds suction lift).
Submerged:
All pumps can be immersed in fluids. It is important to verify that all
components that are in contact with the fluid are chemically compatible.
In this case, air exhaust and fluid must be carried by hoses (optional air
connection).
NOTE: Use a pressure regulator with built-in filter inlet.
NOTE: The compressed air supply must be between 43.5 psi
(3 bar) and 100 psi (7 bar).
ENGLISHESPAÑOL
Recommended installation
The figure below shows the recommended configuration for the installation of a diaphragm pump.
Read the warnings and recommendations of the previous page before starting.
Air exhaust disposal
Warning
• Optional kit is required for remote exhaust.
The pump exhaust should be directed to a safe place, away from people,
animals and food.
• Remove the muffler.
• Connect a hose to the exhaust port of the pump and install the muffler
at the end of the hose. Use a hose with the same diameter as the
exhaust port. (If the hose is more than 5 feet (1.5 m), consult your
dealer or Samson Corporation).
• Have a moat, a protective housing, etc. at the end of the hose.
2013_12_17-16:30
R. 12/13 855 822
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
5
Installation
Warning
Air connection
To ensure that the air supply is sufficient to meet the demand of the pump,
the diameter of the pipe must be equal to the diameter of the supply port
of the pump. Choose auxiliary air treatment equipment and fittings with
sufficient airflow to exceed the air consumption of the pump. In addition,
Operating instructions
This pump is self-priming.
To prime it the first time, you must connect the air pump supply to a low
pressure using the pressure regulators while keeping the outlet valve open.
When fluid begins to flow from the pump outlet, the pump is primed. For
Stopping the pump
• Close the inlet valve of the pump and stop the air supply.
• Make sure for your safety that the air valve is closed.
• Turn off the air compressor, or close the valve on the air supply side of
the auxiliary equipment.
• Close the discharge valve on the discharge side, then begin to slowly
open the drain valve and discharge pressure fluid.
• Open the air valve of the pump, turn on the pump and flush the
remaining fluid.
• After ensuring that the pump was turned off and the pressure was released,
fully open and close the regulator valve and drain valve of the pump.
peripheral air treatment equipment must be installed as close as possible
to the pump unit.
The use of a coupler to connect the hoses aids future operation and
maintenance tasks.
regulation of fluid pressure, the unit must be supplied with an air pressure
between 43.5 and 100 psi (3 and 7 bar). Adjust the discharge valve on the
discharge side to control flow. For the performance characteristics of the
pump see the capacity curve shown on page 3.
Grounding the pump
• When installing the pump, be sure to perform grounding in the
specified location.
• Also connect ground wires for the auxiliary equipment and piping.
• Use a grounding cable of at least 12 gauge (2.0 mm
STICKER THAT SHOWS
THE POSITION OF THE
GROUND WIRE
2013_12_17-16:30
2
).
Warning
• Connect grounding wires to the pump, piping and all other equipment too.
• When the pump operates ungrounded or with an incorrect connection,
friction between parts and abrasion caused by some fluids that flow
inside the pump, can generate static electricity. Moreover, according to
the type of fluid pump and the installation environment (such as gases
in the air or the type of the surrounding facilities) static electricity can
cause fire or electric shock.
• If the pump you have purchased is valid for Atex, a specific Atex manual
will accompany this one. Read this manual before operating the pump.
• If the unit is marked with the symbol,
it can be used in potentially
explosive atmospheres. Below this symbol, in the nameplate of the
pump, are indicated the areas for which the equipment is approved. You
will also find the maximum allowable surface temperature in the same
plate.
6
855 822 R. 12/13
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
DF30 and DF30T
Composite body pump parts
ENGLISHESPAÑOL
Externally controlled
Directional valve is sold do a
kit. Assembled and verified in
Samson.
6Kit (558301)Air sensors-Not available in externally controlled models
7755117Diaphragm cover2(Not sold as a kit)
8 940380Diaphragm cover bolts12(Not sold as a kit)
9 Table 9Pump shields2 (Not sold as a kit)
11 855420Diaphragm cover washers4 (Not sold as a kit)
12940319Valves cap bolts8(Not sold as a kit)
13 Table 13Valves caps2 (Not sold as a kit)
14Table 14Body1(Not sold as a kit)
15 855414Pump support1(Not sold as a kit)
16 940319Support bolts4 (Not sold as a kit)
17855646Cover2 (Not sold as a kit)
R. 12/13 855 822
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
2013_12_17-16:30
7
DF50 and DF50T Composite pumps
All instances
Externally
controlled
1
Composite body pump parts
Directional valve is sold do a
kit. Assembled and verified in
Samson.
Driven
exhaust
Normal
exhaust
No.CodeDescriptionQty.Notes
Normal exhaust
1 Table 1Directional valve1Options:
Driven exhaust
Externally controlled
2 Table 2Balls-
3 Table 3Ball check seats / O-rings / Ball guides-
4Table 4Bushing / Seal / Push rod-
5Table 5Diaphragms-
6Kit (558301)Air sensor-Not available with externally controlled models
7755106Diaphragm cover2(Not sold as a kit)
2013_12_17-16:30
8 940380Diaphragm cover bolts16(Not sold as a kit)
9 Table 9Pump shields2 (Not sold as a kit)
10 941126Diaphragm cover nuts16 (Not sold as a kit)
11 855413Diaphragm cover washers4 (Not sold as a kit)
12940319Valves cap bolts8(Not sold as a kit)
13 Table 13Valves caps2 (Not sold as a kit)
14Table 14Body1(Not sold as a kit)
15 855414Pump support1(Not sold as a kit)
16 940319Support bolts4 (Not sold as a kit)
17855601Cover2 (Not sold as a kit)
8
855 822 R. 12/13
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
DF50 y DF50T Metallic
Externally
controlled
Composite body pump parts
ENGLISHESPAÑOL
Directional valve is sold do a
kit. Assembled and verified in
Samson.
1
Driven
exhaust
Normal
exhaust
No.CodeDescriptionQty.Notes
Normal exhaust
1 Table 1Directional valve1Options:
Driven exhaust
Externally controlled
2 Table 2Balls-
3 Table 3Ball check seats / O-rings / Ball guides-
4Table 4Bushing / Seal / Push rod-
5Table 5Diaphragms-
6Kit (558301)Air sensor-Not available with externally controlled models
7755106Diaphragm cover2(Not sold as a kit)
8 940380Diaphragm cover bolts16(Not sold as a kit)
9 Table 9Pump shields2 (Not sold as a kit)
10 940506Pump shield bolts8 (Not sold as a kit)
12940319Valves cap bolts8(Not sold as a kit)
13 Table 13Balls caps2 (Not sold as a kit)
14Table 14Body1(Not sold as a kit)
17855601Side cover2 (Not sold as a kit)
R. 12/13 855 822
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
2013_12_17-16:30
9
DF100
Composite body pump parts
Externally
controlled
Directional valve is sold do a
kit. Assembled and verified in
Samson.
Driven
exhaust
Normal
exhaust
No.CodeDescriptionQty.Notes
Normal exhaust
1 Table 1Directional valve1Options:
Driven exhaust
Externally controlled
2 Table 2Balls-
3 Table 3
Ball check seats / O-rings /
Ball guides
-
4Table 4Bushing / Seal / Push rod-
5Table 5Diaphragms-
6Kit (558301)Air sensor-Not available with externally controlled models
2013_12_17-16:30
7755111Diaphragm cover2(Not sold as a kit)
8 940334Diaphragm cover bolts20(Not sold as a kit)
10 940914Diaphragm cover nuts7(Not sold as a kit)
12940319Diaphragm cover washers12(Not sold as a kit)
13 Table 13Valves caps2 (Not sold as a kit)
14Table 14Body1(Not sold as a kit)
17855604Cover2 (Not sold as a kit)
21Table 9Upper shield1(Not sold as a kit)
22Table 9Lower shield 1(Not sold as a kit)
23855416Shield attachment4*Only for composite
10
855 822 R. 12/13
Samson Corporation • One Samson Way • N.C. 28778 Swannanoa USA • Phone (828) 686-8511 • Fax (828) 686-8533
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.