UNLESS SPECIFICALLY AGREED TO IN WRITING, SAMLEX AMERICA INC.:
1. MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION
PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
2. ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF
ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK.
Samlex America reserves the right to revise this document and to periodically make changes to the content
hereof without obligation or organization of such revisions or changes.
SAVE THESE INSTRUCTIONS. This manual contains important instructions for models
PST-600-48 and PST-1500-48 that shall be followed during installation, operation and
maintenance.
The following safety symbols will be used in this manual to highlight safety
and information:
Please read these instructions before installing or operating the unit to prevent personal
injury or damage to the unit.
WARNING!
Indicates possibility of physical harm to the user in case of non-compliance.
CAUTION!
Indicates possibility of damage to the equipment in case of non-compliance.
INFO
Indicates useful supplemental information.
1.2 SAFETY INSTRUCTIONS - GENERAL
Installation and wiring compliance
• Installation and wiring must comply with the Local and National Electrical Codes and
must be done by a certied electrician.
Preventing electrical shock
• Always connect the grounding connection on the unit to the appropriate grounding
system.
• Disassembly / repair should be carried out by qualied personnel only.
• Disconnect all AC and DC side connections before working on any circuits associated
with the unit. Turning the ON/OFF switch on the unit to OFF position may not entirely
remove dangerous voltages.
• Be careful when touching bare terminals of capacitors. Capacitors may retain high lethal voltages even after the power has been removed. Discharge the capacitors before
working on the circuits.
SECTION 1 | Safety Instructions
Installation environment
• The inverter should be installed indoor only in a well ventilated, cool, dry environment.
• Do not expose to moisture, rain, snow or liquids of any type.
• To reduce the risk of overheating and re, do not obstruct the suction and discharge
openings of the cooling fan.
• To ensure proper ventilation, do not install in a low clearance compartment.
Preventing re and explosion hazards
• Working with the unit may produce arcs or sparks. Thus, the unit should not be used
in areas where there are ammable materials or gases requiring ignition protected
equipment. These areas may include spaces containing gasoline-powered machinery,
fuel tanks, and battery compartments.
Precautions when working with batteries
• Batteries contain very corrosive diluted Sulphuric Acid as electrolyte. Precautions
should be taken to prevent contact with skin, eyes or clothing.
• Batteries generate Hydrogen and Oxygen during charging resulting in evolution of
explosive gas mixture. Care should be taken to ventilate the battery area and follow
the battery manufacturer’s recommendations.
• Never smoke or allow a spark or ame near the batteries.
• Use caution to reduce the risk of dropping a metal tool on the battery. It could spark
or short circuit the battery or other electrical parts and could cause an explosion.
• Remove metal items like rings, bracelets and watches when working with batteries.
The batteries can produce a short circuit current high enough to weld a ring or the
like to metal and, thus, cause a severe burn.
• If you need to remove a battery, always remove the ground (Negative) terminal from
the battery rst. Make sure that all the accessories are off so that you do not cause a
spark.
1.3 SAFETY INSTRUCTIONS - INVERTER RELATED
Preventing Paralleling of the AC Output
The AC output of the unit should never be connected directly to an Electrical Breaker
Panel / Load Centre which is also fed from the utility power / generator. Such a direct
connection may result in parallel operation of the different power sources and AC power
from the utility / generator will be fed back into the unit which will instantly damage
the output section of the unit and may also pose a re and safety hazard. If an Electrical
Breaker Panel / Load Center is fed from this unit and this panel is also required to be fed
from additional alternate AC sources, the AC power from all the AC sources (like the
utility / generator / this inverter) should rst be fed to an Automatic / Manual Selector
Switch and the output of the Selector Switch should be connected to the Electrical Breaker
Panel / Load Center. Samlex America Inc. Automatic Transfer Switch Model No. STS-30 is
recommended for this application.
4 | SAMLEX AMERICA INC.
SECTION 1 | Safety Instructions
!
!
CAUTION!
To prevent possibility of paralleling and severe damage to the unit, never use a
simple jumper cable with a male plug on both ends to connect the AC output
of the unit to a handy wall receptacle in the home / RV.
Preventing DC Input Over Voltage
It is to be ensured that the DC input voltage of these units is less than 64.0 VDC to prevent permanent damage to the unit. Please observe the following precautions:
• Ensure that the maximum charging voltage of the external battery charger / alternator / solar charge controller is less than 64.0 VDC.
• Do not use unregulated solar panels to charge the battery connected to this unit. Under
cold ambient temperatures, the output of 48V nominal solar panel / array may reach >
88 VDC. Always use a charge controller between the solar panel and the battery.
• When using Diversion Charge Control Mode in a charge controller, the solar / wind /
hydro source is directly connected to the battery bank. In this case, the controller will
divert excess current to an external load. As the battery charges, the diversion duty
cycle will increase. When the battery is fully charged, all the source energy will ow
into the diversion load if there are no other loads. The charge controller will disconnect the diversion load if the current rating of the controller is exceeded. Disconnection of the diversion load may damage the battery as well as the inverter or other DC
loads connected to the battery due to high voltages generated during conditions of
high winds (for wind generators), high water ow rates (for hydro generators). It is,
therefore, to be ensured that the diversion load is sized correctly to prevent the above
over voltage conditions.
• These units are designed to operate from Lead Acid Battery System with nominal
voltage of 48 VDC. Do not operate these units from a battery system voltage higher /
lower than 48 VDC nominal.
Preventing Reverse Polarity on the Input Side
When making battery connections on the input side, make sure that the polarity of battery connections is correct (Connect the Positive of the battery to the Positive terminal
of the unit and the Negative of the battery to the Negative terminal of the unit). If the
input is connected in reverse polarity, the external DC fuse and the DC fuses inside the
inverter will blow and may also cause permanent damage to the inverter.
CAUTION!
Damage caused by reverse polarity is not covered by warranty.
Use of External Fuse in DC Input Circuit
Use Class-T or equivalent fuse of appropriate capacity within 7" of the battery Positive terminal. This fuse is required to protect DC input cable run from damage due to short circuit
along the length of the cable. Please read instructions under Section 8.4.5 - Installation.
SECTION 2 | General Information
2.1. DEFINITIONS
The following denitions are used in this manual for explaining various electrical
concepts, specications and operations:
Peak Value: It is the maximum value of electrical parameter like voltage / current.
RMS (Root Mean Square) Value: It is a statistical average value of a quantity that varies
in value with respect to time. For example, a pure sine wave that alternates between
peak values of Positive 169.68V and Negative 169.68V has an RMS value of 120 VAC.
Also, for a pure sine wave, the RMS value = Peak value ÷ 1.414.
Voltage (V), Volts: It is denoted by “V” and the unit is “Volts”. It is the electrical force
that drives electrical current (I) when connected to a load. It can be DC (Direct Current
– ow in one direction only) or AC (Alternating Current – direction of ow changes periodically). The AC value shown in the specications is the RMS (Root Mean Square) value.
Current (I), Amps, A: It is denoted by “I” and the unit is Amperes – shown as “A”. It is
the ow of electrons through a conductor when a voltage (V) is applied across it.
Frequency (F), Hz: It is a measure of the number of occurrences of a repeating event per
unit time. For example, cycles per second (or Hertz) in a sinusoidal voltage.
Efciency, (
η): This is the ratio of Active Power Output in Watts ÷ Active Power Input
in Watts.
Phase Angle, (φ): It is denoted by “φ” and species the angle in degrees by which the
current vector leads or lags the voltage vector in a sinusoidal voltage. In a purely inductive load, the current vector lags the voltage vector by Phase Angle (φ) = 90°. In a purely
capacitive load, the current vector leads the voltage vector by Phase Angle, (φ) = 90°. In
a purely resistive load, the current vector is in phase with the voltage vector and hence,
the Phase Angle, (φ) = 0°. In a load consisting of a combination of resistances, inductances and capacitances, the Phase Angle (φ) of the net current vector will be > 0° < 90°
and may lag or lead the voltage vector.
Resistance (R), Ohm, Ω: It is the property of a conductor that opposes the ow of current when a voltage is applied across it. In a resistance, the current is in phase with the
voltage. It is denoted by "R" and its unit is "Ohm" - also denoted as "Ω".
Inductive Reactance (X
opposition of a circuit element to a change of electric current or voltage due to that
element's inductance or capacitance. Inductive Reactance (X
of wire in resisting any change of electric current through the coil. It is proportional to
), Capacitive Reactance (XC) and Reactance (X): Reactance is the
L
) is the property of a coil
L
frequency and inductance and causes the current vector to lag the voltage vector by
Phase Angle (φ) = 90°. Capacitive reactance (X
oppose changes in voltage. X
and causes the current vector to lead the voltage vector by Phase Angle (φ) = 90°.
The unit of both X
and XC is "Ohm" - also denoted as "Ω". The effects of inductive
L
is inversely proportional to the frequency and capacitance
C
) is the property of capacitive elements to
C
6 | SAMLEX AMERICA INC.
SECTION 2 | General Information
reactance X
reactance X
the net effect is a tendency to cancel each other. Hence, in a circuit containing both
to cause the current to lag the voltage by 90° and that of the capacitive
L
to cause the current to lead the voltage by 90° are exactly opposite and
C
inductances and capacitances, the net Reactance (X) will be equal to the difference
between the values of the inductive and capacitive reactances. The net Reactance (X)
will be inductive if X
> XC and capacitive if XC > XL.
L
Impedance, Z: It is the vectorial sum of Resistance and Reactance vectors in a circuit.
Active Power (P), Watts: It is denoted as “P” and the unit is “Watt”. It is the power that
is consumed in the resistive elements of the load. A load will require additional Reactive
Power for powering the inductive and capacitive elements. The effective power required
would be the Apparent Power that is a vectorial sum of the Active and Reactive Powers.
Reactive Power (Q), VAR: Is denoted as “Q” and the unit is VAR. Over a cycle, this power
is alternatively stored and returned by the inductive and capacitive elements of the load.
It is not consumed by the inductive and capacitive elements in the load but a certain
value travels from the AC source to these elements in the (+) half cycle of the sinusoidal
voltage (Positive value) and the same value is returned back to the AC source in the (-)
half cycle of the sinusoidal voltage (Negative value). Hence, when averaged over a span
of one cycle, the net value of this power is 0. However, on an instantaneous basis, this
power has to be provided by the AC source. Hence, the inverter, AC wiring and over cur-
rent protection devices have to be sized based on the combined effect of the Active and
Reactive Powers that is called the Apparent Power.
Apparent (S) Power, VA: This power, denoted by "S", is the vectorial sum of the Active
Power in Watts and the Reactive Power in “VAR”. In magnitude, it is equal to the RMS
value of voltage “V” X the RMS value of current “A”. The Unit is VA. Please note that
Apparent Power VA is more than the Active Power in Watts. Hence, the inverter, AC wiring and over current protection devices have to be sized based on the Apparent Power.
Maximum Continuous Running AC Power Rating: This rating may be specied as “Active
Power” in Watts (W) or “Apparent Power” in Volt Amps (VA). It is normally specied in
“Active Power (P)” in Watts for Resistive type of loads that have Power Factor =1. Reactive types of loads will draw higher value of “Apparent Power” that is the sum of “Active and Reactive Powers”. Thus, AC power source should be sized based on the higher
“Apparent Power” Rating in (VA) for all Reactive Types of AC loads. If the AC power
source is sized based on the lower “Active Power” Rating in Watts (W), the AC power
source may be subjected to overload conditions when powering Reactive Type of loads.
Surge Power Rating: During start up, certain loads require considerably higher surge of power
for short duration (lasting from tens of millisecs to few seconds) as compared to their Maximum Continuous Running Power Rating. Some examples of such loads are given below:
• Electric Motors: At the moment when an electric motor is powered ON, the rotor
is stationary (equivalent to being “Locked”), there is no “Back EMF” and the
windings draw a very heavy surge of starting current (Amperes) called “Locked Rotor
SECTION 2 | General Information
Amperes” (LRA) due to low DC resistance of the windings. For example, in motor
driven loads like Air-conditioning and Refrigeration Compressors and in Well Pumps
(using Pressure Tank), the Starting Surge Current / LRA may be as high as 10 times its
rated Full Load Amps (FLA) / Maximum Continuous Running Power Rating. The value
and duration of the Starting Surge Current / LRA of the motor depends upon the
winding design of the motor and the inertia / resistance to movement of mechanical
load being driven by the motor. As the motor speed rises to its rated RPM, “Back
EMF” proportional to the RPM is generated in the windings and the current draw
reduces proportionately till it draws the running FLA / Maximum Continuous Running
Power Rating at the rated RPM.
• Transformers (e.g. Isolation Transformers, Step-up / Step-down Transformers, Power Trans-former in Microwave Oven etc.): At the moment when AC power is supplied to a transformer,
the transformer draws very heavy surge of “Magnetization Inrush Current” for a few millisecs
that can reach up to 10 times the Maximum Continuous Rating of the Transformer.
• Devices like Infrared Quartz Halogen Heaters (also used in Laser Printers) / Quartz Halogen Lights / Incandescent Light Bulbs using Tungsten heating elements: Tungsten
has a very high Positive Temperature Coefcient of Resistance i.e. it has lower resistance when cold and higher resistance when hot. As Tungsten heating element will be
cold at the time of powering ON, its resistance will be low and hence, the device will
draw very heavy surge of current with consequent very heavy surge of power with a
value of up to 8 times the Maximum Continuous Running AC Power.
• AC to DC Switched Mode Power Supplies (SMPS): This type of power supply is used as
stand-alone power supply or as front end in all electronic devices powered from Utility / Grid e.g. in audio/video/ computing devices and battery chargers (Please see Section 4 for more details on SMPS). When this power supply is switched ON, its internal
input side capacitors start charging resulting in very high surge of Inrush Current for a
few millisecs (Please see Fig 4.1). This surge of inrush current / power may reach up to
15 times the Continuous Maximum Running Power Rating. The surge of inrush current
/ power will, however, be limited by the Surge Power Rating of the AC source.
Power Factor, (PF): It is denoted by “PF” and is equal to the ratio of the Active Power
(P) in Watts to the Apparent Power (S) in VA. The maximum value is 1 for resistive types
of loads where the Active Power (P) in Watts = the Apparent Power (S) in VA. It is 0 for
purely inductive or purely capacitive loads. Practically, the loads will be a combination of
resistive, inductive and capacitive elements and hence, its value will be > 0 <1. Normally
it ranges from 0.5 to 0.8 e.g. (i) AC motors (0.4 to 0.8), (ii) Transformers (0.8) (iii) AC to
DC Switch Mode Power Supplies (0.5 to 0.6) etc.
Load: Electrical appliance or device to which an electrical voltage is fed.
Linear Load: A load that draws sinusoidal current when a sinusoidal voltage is fed to it.
Examples are, incandescent lamp, heater, electric motor, etc.
Non-Linear Load: A load that does not draw a sinusoidal current when a sinusoidal voltage is fed to it. For example, non-power factor corrected Switched Mode Power Supplies
(SMPS) used in computers, audio video equipment, battery chargers, etc.
8 | SAMLEX AMERICA INC.
SECTION 2 | General Information
Resistive Load: A device or appliance that consists of pure resistance (like lament
lamps, cook tops, toaster, coffee maker etc.) and draws only Active Power (Watts) from
the inverter. The inverter can be sized based on the Active Power rating (Watts) of
resistive type of loads without creating overload (except for resistive type of loads with
Tungsten based heating element like in Incandescent Light Bulbs, Quartz Halogen Lights
and Quartz Halogen Infrared Heaters. These require higher starting surge power due to
lower resistance value when the heating element is cold).
Reactive Load: A device or appliance that consists of a combination of resistive, inductive
and capacitive elements (like motor driven tools, refrigeration compressors, microwaves,
computers, audio/ video etc.). The Power Factor of this type of load is <1 e.g. AC motors
(PF=0.4 to 0.8), Transformers (PF=0.8), AC to DC Switch Mode Power Supplies (PF=0.5
to 0.6) etc. These devices require Apparent Power (VA) from the AC power source. The
Apparent Power is a vectorial sum of Active Power (Watts) and Reactive Power (VAR).
The AC power source has to be sized based on the higher Apparent Power (VA) and also
based on the Starting Surge Power.
2.2 OUTPUT VOLTAGE WAVEFORMS
V
= 169.68V
PEAK
V
= 140 to 160V
180
160
140
120
VOLTS (+)VOLTS (–)
100
80
60
40
20
0
20
40
Pure Sine Wave
60
crosses Zero Volt
80
100
120
140
160
180
instantaneously
TIME
PEAK
16.66 ms
V
= 120 VAC
RMS
Modied Sine
Wave sits at
ZERO for some
time and then
rises or falls
Sine Wave
Modied Sine Wave
Fig. 2.1: Pure and Modied Sine Waveforms for 120 VAC, 60 Hz
The output waveform of the Samlex PST series inverters is a Pure Sine Wave like the
waveform of Utility / Grid Power. Please see Sine Wave represented in the Fig. 2.1 that
also shows Modied Sine Waveform for comparison.
In a Sine Wave, the voltage rises and falls smoothly with a smoothly changing phase
angle and also changes its polarity instantly when it crosses 0 Volts. In a Modied Sine
Wave, the voltage rises and falls abruptly, the phase angle also changes abruptly and
SECTION 2 | General Information
it sits at zero V for some time before changing its polarity. Thus, any device that uses a
control circuitry that senses the phase (for voltage / speed control) or instantaneous zero
voltage crossing (for timing control) will not work properly from a voltage that has a
Modied Sine Waveform.
Also, as the Modied Sine Wave is a form of Square Wave, it is comprised of multiple
Sine Waves of odd harmonics (multiples) of the fundamental frequency of the Modied
Sine Wave. For example, a 60 Hz Modied Sine Wave will consist of Sine Waves with
odd harmonic frequencies of 3rd (180 Hz), 5th (300 Hz), 7th (420 Hz) and so on. The high
frequency harmonic content in a Modied Sine Wave produces enhanced radio interference, higher heating effect in inductive loads like microwaves and motor driven devices
like hand tools, refrigeration / air-conditioning compressors, pumps etc. The higher
frequency harmonics also produce overloading effect in low frequency capacitors due to
lowering of their capacitive reactance by the higher harmonic frequencies. These capacitors are used in ballasts for uorescent lighting for Power Factor improvement and in
single-phase induction motors as Start and Run Capacitors. Thus, Modied and Square
Wave inverters may shut down due to overload when powering these devices.
2.3 ADVANTAGES OF PURE SINE WAVE INVERTERS
• The output waveform is a Sine Wave with very low harmonic distortion and cleaner
power like Utility / Grid supplied electricity.
• Inductive loads like microwaves, motors, transformers etc. run faster, quieter
and cooler.
• More suitable for powering uorescent lighting xtures containing Power Factor
Improvement Capacitors and single phase motors containing Start and Run Capacitors
• Reduces audible and electrical noise in fans, uorescent lights, audio ampliers, TV,
fax and answering machines, etc.
• Does not contribute to the possibility of crashes in computers, weird print outs and
glitches in monitors.
2.4 SOME EXAMPLES OF DEVICES THAT MAY NOT WORK PROPERLY WITH
MODIFIED SINE WAVE AND MAY ALSO GET DAMAGED ARE GIVEN BELOW:
• Laser printers, photocopiers, and magneto-optical hard drives.
• Built-in clocks in devices such as clock radios, alarm clocks, coffee makers, bread-makers, VCR, microwave ovens etc. may not keep time correctly.
• Output voltage control devices like dimmers, ceiling fan / motor speed control may
not work properly (dimming / speed control may not function).
• Sewing machines with speed / microprocessor control.
• Transformer-less capacitive input powered devices like (i) Razors, ashlights, nightlights, smoke detectors etc. (ii) Some re-chargers for battery packs used in hand power
tools. These may get damaged. Please check with the manufacturer of these types of
devices for suitability.
10 | SAMLEX AMERICA INC.
i
i
SECTION 2 | General Information
• Devices that use radio frequency signals carried by the AC distribution wiring.
• Some new furnaces with microprocessor control / Oil burner primary controls.
• High intensity discharge (HID) lamps like Metal Halide Lamps. These may get dam-
aged. Please check with the manufacturer of these types of devices for suitability.
• Some uorescent lamps / light xtures that have Power Factor Correction Capacitors.
The inverter may shut down indicating overload.
• Induction Cooktops
2.5 POWER RATING OF INVERTERS
INFO
For proper understanding of explanations given below, please refer to deni-
tions of Active / Reactive / Apparent / Continuous / Surge Powers, Power Factor,
and Resistive / Reactive Loads at Section 2.1 under “DEFINITIONS”.
The power rating of inverters is specied as follows:
• Maximum Continuous Running Power Rating
• Surge Power Rating to accommodate high, short duration surge of power required
during start up of certain AC appliances and devices.
Please read details of the above two types of power ratings in Section 2.1 under
“DEFINITIONS”
INFO
The manufacturers’ specication for power rating of AC appliances and devices
indicates only the Maximum Continuous Running Power Rating. The high,
short duration surge of power required during start up of some specic types
of devices has to be determined by actual testing or by checking with the
manufacturer. This may not be possible in all cases and hence, can be guessed
at best, based on some general Rules of Thumb.
Table 2.1 provides a list of some common AC appliances / devices that require high, short
duration surge of power during start up. An “Inverter Sizing Factor” has been recommended against each which is a Multiplication Factor to be applied to the Maximum
Continuous Running Power Rating (Active Power Rating in Watts) of the AC appliance
/ device to arrive at the Maximum Continuous Running Power Rating of the inverter
(Multiply the Maximum Continuous Running Power Rating (Active Power Rating in
Watts) of the appliance / device by recommended Sizing Factor to arrive at the Maximum Continuous Running Power Rating of the inverter.
SECTION 2 | General Information
TABLE 2.1: INVERTER SIZING FACTOR
Type of Device or Appliance
Air Conditioner / Refrigerator / Freezer (Compressor based)5
Air Compressor4
Sump Pump / Well Pump / Submersible Pump3
Dishwasher / Clothes Washer3
Microwave (where rated output power is the cooking power)2
Furnace Fan3
Industrial Motor3
Portable Kerosene / Diesel Fuel Heater3
Circular Saw / Bench Grinder3
Incandescent / Halogen / Quartz Lamps3
Space heaters that use Ceramic / PTC heating element5
Laser Printer / Other Devices using Infrared Quartz Halogen Heaters4
Switch Mode Power Supplies (SMPS): no Power Factor correction2
Photographic Strobe / Flash Lights4 (See Note 2)
Sizing Factor
(See note 1)
NOTES FOR TABLE 2.1
1. Multiply the Maximum Continuous Running Power Rating (Active Power Rating in
Watts) of the appliance / device by the recommended Sizing Factor to arrive at the
Maximum Continuous Running Power Rating of the inverter.
2. For photographic strobe / ash unit, the Surge Power Rating of the inverter should be
> 4 times the Watt Sec rating of photographic strobe / ash unit.
Inverter
12 | SAMLEX AMERICA INC.
SECTION 3 | Limiting Electro-Magnetic
Interference (EMI)
3.1 EMI AND FCC COMPLIANCE
These inverters contain internal switching devices that generate conducted and radiated electromagnetic interference (EMI). The EMI is unintentional and cannot be entirely
eliminated. The magnitude of EMI is, however, limited by circuit design to acceptable
levels as per limits laid down in North American FCC Standard – FCC Part 15(B), Class B. The
limits laid down in this Standard are designed to provide reasonable protection against
harmful radio interference when these units are operated in residential environment.
These inverters can conduct and radiate radio frequency energy and, if not installed and
used in accordance with the instruction manual, may cause harmful interference to radio
communications.
3.2 REDUCING EMI THROUGH PROPER INSTALLATION
The effects of EMI will also depend upon a number of factors external to the inverter
like proximity of the inverter to the EMI receptors, types and quality of connecting wires
and cables etc. EMI due to factors external to the inverter may be reduced as follows:
- Ensure that the inverter is rmly grounded to the ground system of the building or
the vehicle
- Locate the inverter as far away from the EMI receptors like radio, audio and video
devices as possible
- Keep the DC side wires between the battery and the inverter as short as possible.
- Do NOT keep the battery wires far apart. Keep them taped together to reduce their
inductance and induced voltages. This reduces ripple in the battery wires and improves performance and efciency.
- Shield the DC side wires with metal sheathing / copper foil / braiding:
- Use coaxial shielded cable for all antenna inputs (instead of 300 ohm twin leads)
- Use high quality shielded cables to attach audio and video devices to one another
- Limit operation of other high power loads when operating audio / video equipment
SECTION 4 | Powering Direct / Embedded Switch
Mode Power Supplies (SMPS)
4.1 CHARACTERISTICS OF SWITCHED MODE POWER SUPPLIES (SMPS)
Switch Mode Power Supplies (SMPS) are extensively used to convert the incoming AC
power into various voltages like 3.3V, 5V, 12V, 24V etc. that are used to power various devices and circuits used in electronic equipment like battery chargers, computers,
audio and video devices, radios etc. SMPS use large capacitors in their input section for
ltration. When the power supply is rst turned on, there is a very large inrush current drawn by the power supply as the input capacitors are charged (The capacitors act
almost like a short circuit at the instant the power is turned on). The inrush current at
turn-on is several to tens of times larger than the rated RMS input current and lasts for
a few milliseconds. An example of the input voltage versus input current waveforms is
given in Fig. 4.1. It will be seen that the initial input current pulse just after turn-on is >
15 times larger than the steady state RMS current. The inrush dissipates in around 2 or 3
cycles i.e. in around 33 to 50 milliseconds for 60 Hz sine wave.
Further, due to the presence of high value of input lter capacitors, the current drawn
by an SMPS (With no Power Factor correction) is not sinusoidal but non-linear as shown
in Fig 4.2. The steady state input current of SMPS is a train of non-linear pulses instead
of a sinusoidal wave. These pulses are two to four milliseconds duration each with a very
high Crest Factor of around 3 (Crest Factor = Peak value ÷ RMS value).
Many SMPS units incorporate “Inrush Current Limiting”. The most common method is
the NTC (Negative Temperature Coefcient) resistor. The NTC resistor has a high resistance when cold and a low resistance when hot. The NTC resistor is placed in series with
the input to the power supply. The cold resistance limits the input current as the input
capacitors charge up. The input current heats up the NTC and the resistance drops
during normal operation. However, if the power supply is quickly turned off and back
on, the NTC resistor will be hot so its low resistance state will not prevent an inrush
current event.
The inverter should, therefore, be sized adequately to withstand the high inrush current
and the high Crest Factor of the current drawn by the SMPS. Normally, inverters have
short duration Surge Power Rating of 2 times their Maximum Continuous Power Rating.
Hence, it is recommended that for purposes of sizing the inverter to accommodate
Crest Factor of 3, the Maximum Continuous Power Rating of the inverter should be > 2
times the Maximum Continuous Power Rating of the SMPS. For example, an SMPS rated
at 100 Watts should be powered from an inverter that has Maximum Continuous Power
Rating of > 200 Watts.
14 | SAMLEX AMERICA INC.
NOTE: Voltage
SECTION 4 | Powering Direct / Embedded Switch
Mode Power Supplies (SMPS)
and current scales
are dierent
Input voltage
Peak inrush
current
Inrush current
Fig 4.1: Inrush current in an SMPS
Non-linear
Input Current
Voltage (+)Voltage (–)
Current (+)Current (–)
Pulse
Rated steady state
input RMS current
Peak Current
RMS Current
NOTE: Voltage
and current scales
are dierent
Input Sine
Wave Voltage
TIME
Fig. 4.2: High Crest Factor of current drawn by SMPS
Crest Factor = Peak Current = 3
RMS Current
SECTION 5 | Principle of Operation
5.1 GENERAL
These inverters convert DC battery voltage to AC voltage with an RMS (Root Mean
Square) value of 120 VAC, 60 Hz RMS.
5.2 PURE SINE WAVE OUTPUT WAVEFORM
The waveform of the AC voltage is a pure Sine Waveform that is same as the waveform
of Grid / Utility power (Supplementary information on pure Sine Waveform and its
advantages are discussed in Sections 2.2 to 2.4).
Fig. 5.1 below species the characteristics of 120 VAC, 60 Hz pure Sine Waveform. The
instantaneous value and polarity of the voltage varies cyclically with respect to time. For
example, in one cycle in a 120 VAC, 60 Hz system, it slowly rises in the Positive direction
from 0V to a peak Positive value “Vpeak” = + 169.68V, slowly drops to 0V, changes the
polarity to Negative direction and slowly increases in the Negative direction to a peak
Negative value “Vpeak” = - 169.68V and then slowly drops back to 0V. There are 60 such
cycles in 1 sec. Cycles per second is called the “Frequency” and is also termed “Hertz (Hz)”.
The Time Period of 1 Cycle is 16.66 ms.
Peak Positive Voltage
PEAK = + 169.68V
+ V
V
Voltage (+)Voltage (–)
RMS = 120 VAC
0V
16.66 ms
TIME
Peak Negative Voltage
PEAK = - 169.68V
- V
Fig. 5.1: 120 VAC, 60 Hz Pure Sine Waveform
5.3 PRINCIPLE OF OPERATION
The voltage conversion takes place in two stages. In the rst stage, the DC voltage
of the battery is converted to a high voltage DC using high frequency switching and
Pulse Width Modulation (PWM) technique. In the second stage, the high voltage DC is
converted to 120 VAC, 60 Hz sine wave AC again using PWM technique. This is done by
using a special wave shaping technique where the high voltage DC is switched at a high
frequency and the pulse width of this switching is modulated with respect to a reference sine wave.
16 | SAMLEX AMERICA INC.
SECTION 6 | Layout
b
a
cd
PST-1500-48: FRONT
17
17
PST-1500-48: FRONT
terminals for hardwiring.
- showing compartment containing AC output
12
1413
15
L
N
16
PST-1500-48: BACK
LEGEND
1. Power ON/OFF Switch
2. Green LED - “POWER”
3. Red LED - “OVERLOAD”
4. Red LED - “OVER TEMP”
5. NEMA5-20R GFCI Duplex Outlets
5a. Reset Button
5b. Test Button
5c. Red LED marked “Life End Alarm”
5d. Green LED: AC output ON
6. Air-exhaust opening for cooling fan
(Fans are located behind the openings)
7. Grounding Lug
8. Negative (-) DC Input Terminal
9. Positive (+) DC Input Terminal
Fig. 6.1: Layout of PST-1500-48
5/16”,
}
18 TPI
10. Modular Jack for RC-200
Remote Control
11. Metal Strain Relief Clamp for
AC Output Cable
12. Cover Plate for Compartment Containing
AC Output Terminals
13. Compartment Containing AC Output
Terminals for Hardwiring
14. Terminal for AC Output Ground
(Chassis Ground)
15. AC Output: Line Terminal
16. AC Output: Neutral Terminal
17. Air-suction slots for cooling fans
(Additional slots at the bottom - not shown)
Hole dia.: 4 mm / 0.16”
Set screw:#6, 40TPI or
}
M3.5 (Pitch 0.6 mm)
SECTION 6 | Layout
PST-600 & PST-1000-12-24: Layout
a
1
2
120VAC / 60Hz
3
10
PST-600-48: FRONT
6
PST-600-48: BACK
LEGEND
1. Power ON/OFF Switch
2. Green LED - Power ON
3. Red LED - Overload
4. Red LED - Over Temperature
5. NEMA5-20R GFCI Duplex Outlets
5a. Reset Button
5b. Test Button
5c. Red LED marked “Life End Alarm”
5d. Green LED: AC output ON
6. Air-exhaust opening for cooling fan
(Fan is located behind this opening)
7. Grounding Lug
8. Negative (-) DC Input Terminal
9. Positive (+) DC Input Terminal
10. Modular Jack for RC-15A Remote Control
11. Air-suction openings for the fan (At the bottom of the unit − not shown)
4
789
}
Wire hole diameter: 5/16”
Set screw: • 5/16” x 24 TPI
• 3/8” long; slotted head
}
Wire hole diameter: 7/16”
Set screw: • 5/16” x 24 TPI
• 1/2” long; slotted head
bd
NEG –
NEG –POS +
WARNING:
Reverse polarity will damage the unit.
AVERTISSEMENT :
Inversion de polarité peut endommager l’unité.
c
5
18 | SAMLEX AMERICA INC.
Fig. 6.2: Layout of PST-600-48
i
SECTION 7 | General Information on Lead Acid
Batteries
7.1 GENERAL
INFO
For complete background information on Lead Acid Batteries and charging
process, please visit www.samlexamerica.com > support > white papers >
White Paper - Batteries, Chargers and Alternators.
Lead-acid batteries can be categorized by the type of application:
1. Automotive service - Starting/Lighting/Ignition (SLI, a.k.a. cranking), and
2. Deep cycle service.
Deep Cycle Lead Acid Batteries of appropriate capacity are recommended for powering
of inverters.
7.2 DEEP CYCLE LEAD ACID BATTERIES
Deep cycle batteries are designed with thick-plate electrodes to serve as primary power
sources, to have a constant discharge rate, to have the capability to be deeply discharged
up to 80 % capacity and to repeatedly accept recharging. They are marketed for use in
recreation vehicles (RV), boats and electric golf carts – so they may be referred to as RV batteries, marine batteries or golf cart batteries. Use Deep Cycle batteries for powering these
inverters.
7.3 RATED CAPACITY SPECIFIED IN AMPERE-HOUR (Ah)
Battery capacity “C” is specied in Ampere-hours (Ah). An Ampere is the unit of measurement for electrical current and is dened as a Coulomb of charge passing through an electrical conductor in one second. The Capacity “C” in Ah relates to the ability of the battery to
provide a constant specied value of discharge current (also called “C-Rate”: See Section 7.6)
over a specied time in hours before the battery reaches a specied discharged terminal
voltage (Also called “End Point Voltage”) at a specied temperature of the electrolyte. As a
benchmark, the automotive battery industry rates batteries at a discharge current or C-Rate
of C/20 Amperes corresponding to 20 Hour discharge period. The rated capacity “C” in Ah
in this case will be the number of Amperes of current the battery can deliver for 20 Hours at
80ºF (26.7ºC) till the voltage drops to 1.75V / Cell. i.e. 10.5V for 12V battery, 21V for 24V battery and 42V for a 48V battery. For example, a 100 Ah battery will deliver 5A for 20 Hours.
7.4 RATED CAPACITY SPECIFIED IN RESERVE CAPACITY (RC)
Battery capacity may also be expressed as Reserve Capacity (RC) in minutes typically for
automotive SLI (Starting, Lighting and Ignition) batteries. It is the time in minutes a
vehicle can be driven after the charging system fails. This is roughly equivalent to the
conditions after the alternator fails while the vehicle is being driven at night with the
headlights on. The battery alone must supply current to the headlights and the computer/ignition system. The assumed battery load is a constant discharge current of 25A.
SECTION 7 | General Information on Lead Acid
Batteries
Reserve capacity is the time in minutes for which the battery can deliver 25 Amperes at
80ºF (26.7ºC) till the voltage drops to 1.75V / Cell i.e. 10.5V for 12V battery, 21V for 24V
battery and 42V for 48V battery.
Approximate relationship between the two units is:
Capacity “C” in Ah = Reserve Capacity in RC minutes x 0.6
7.5 TYPICAL BATTERY SIZES
The Table 7.1 below shows details of some popular battery sizes:
Electrical energy is stored in a cell / battery in the form of DC power. The value of the
stored energy is related to the amount of the active materials pasted on the battery
plates, the surface area of the plates and the amount of electrolyte covering the plates.
As explained above, the amount of stored electrical energy is also called the Capacity of
the battery and is designated by the symbol “C”.
GC2**6220
The time in Hours over which the battery is discharged to the “End Point Voltage” for
purposes of specifying Ah capacity depends upon the type of application. Let us denote
this discharge time in hours by “T”. Let us denote the discharge current of the battery
as the “C-Rate”. If the battery delivers a very high discharge current, the battery will be
discharged to the “End Point Voltage” in a shorter period of time. On the other hand,
if the battery delivers a lower discharge current, the battery will be discharged to the
“End Point Voltage” after a longer period of time. Mathematically:
EQUATION 1: Discharge current “C-Rate” = Capacity “C” in Ah ÷ Discharge Time “T”
Table 7.2 below gives some examples of C-Rate specications and applications:
TABLE 7.2: DISCHARGE CURRENT RATES - “C-RATES”
Hours of discharge time “T” till
the “End Point Voltage”
0.5 Hrs.2C200A
1 Hrs.1C100A
5 Hrs. (Inverter application)C/5 or 0.2C20A
20 | SAMLEX AMERICA INC.
"C-Rate" Discharge Current in Amps =
Capacity "C" in Ah ÷ Discharge Time
"T" in Hrs.
Table Continues Next Page }
Example of C-Rate
Discharge Currents
for 100 Ah battery
SECTION 7 | General Information on Lead Acid
Batteries
TABLE 7.2: DISCHARGE CURRENT RATES - “C-RATES” (continued from Previous page)
C/100
C/20
C/10
C/5
C/3
DISCHARGE
Example of C-Rate
Discharge Currents
for 100 Ah battery
C/5
C/10
C/20
C/40
Hours of discharge time “T” till
the “End Point Voltage”
"C-Rate" Discharge Current in Amps =
Capacity "C" in Ah
÷ Discharge Time
"T" in Hrs.
8 Hrs. (UPS application)C/8 or 0.125C12.5A
10 Hrs. (Telecom application)C/10 or 0.1C10A
20 Hrs. (Automotive application)C/20 or 0.05C5A
100 Hrs.C/100 or 0.01C1A
When a battery is discharged over a shorter time, its specied “C-Rate” discharge current will
NOTE:
be higher. For example, the “C-Rate” discharge current at 5 Hour discharge period i.e. C/5 Amps will
be 4 times higher than the “C-Rate” discharge current at 20 Hour discharge period i.e. C/20 Amps.
7.7 CHARGING / DISCHARGING CURVES
Fig. 7.1 shows the charging and discharging characteristics of a typical 12V / 24V / 48 Lead
Acid battery at electrolyte temperature of 80°F / 26.7°C. The curves show the % State of
Charge (X-axis) versus terminal voltage (Y-axis) during charging and discharging at different
C-Rates. Please note that X-axis shows % State of Charge. % State of Discharge will be = 100% - % State of Charge. These curves will be referred to in the subsequent explanations.
Lead-Acid Battery Chart - 80˚F / 26.7˚C
24V
12V48V
16.5
33.0
66.0
16.0
32.0
64.0
15.5
31.0
62.0
15.0
30.0
60.0
14.5
29.0
58.0
14.0
28.0
56.0
13.5
27.0
54.0
13.0
26.0
52.0
12.5
25.0
50.0
Battery Voltage in VDC
48.0
46.0
44.0
42.0
40.0
38.0
36.0
24.0
23.0
22.0
21.0
20.0
19.0
18.0
12.0
11.5
11.0
10.5
10.0
9.5
9.0
0 10 20 30 40 50 60 70 80 90 100 110 120 130
Battery State of Charge in Percent (%)
CHARGE
Fig. 7.1: Charging / Discharging Curves for 12V / 24V / 48V Lead Acid Batteries
SECTION 7 | General Information on Lead Acid
Batteries
7.8 REDUCTION IN USABLE CAPACITY AT HIGHER DISCHARGE RATES –
TYPICAL IN INVERTER APPLICATION
As stated above, the rated capacity of the battery in Ah is normally applicable at a discharge rate of 20 Hours. As the discharge rate is increased as in cases where the inverters
are driving higher capacity loads, the usable capacity reduces due to “Peukert Effect”.
This relationship is not linear but is more or less according to the Table 7.3.
TABLE 7.3 BATTERY CAPACITY VERSUS RATE OF DISCHARGE – C-RATE
C-Rate Discharge CurrentUsable Capacity (%)
C/20100%
C/1087%
C/883%
C/675%
C/570%
C/360%
C/250%
1C40%
Table 7.3 shows that a 100 Ah capacity battery will deliver 100% (i.e. full 100 Ah) capacity
if it is slowly discharged over 20 Hours at the rate of 5 Amperes (50W output for a 12V
inverter and 100W output for a 24V inverter). However, if it is discharged at a rate of 50
Amperes (500W output for a 12V inverter and 1000W output for a 24V inverter) then
theoretically, it should provide 100 Ah ÷ 50 = 2 Hours. However, Table 7.3 shows that for 2
Hours discharge rate, the capacity is reduced to 50% i.e. 50 Ah. Therefore, at 50 Ampere
discharge rate (500W output for a 12V inverter and 1000W output for a 24V inverter) the
battery will actually last for 50 Ah ÷ 50 Amperes = 1 Hour.
7.9 STATE OF CHARGE (SOC) OF A BATTERY – BASED ON
“STANDING VOLTAGE”
The “Standing Voltage” of a battery under open circuit conditions (no load connected to
it) can approximately indicate the State of Charge (SOC) of the battery. The “Standing Voltage” is measured after disconnecting any charging device(s) and the battery load(s) and
letting the battery “stand” idle for 3 to 8 hours before the voltage measurement is taken.
Table 7.4 shows the State of Charge versus Standing Voltage for a typical 12V / 24V / 48V
battery system at 80°F (26.7ºC).
22 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
TABLE 7.4: STATE OF CHARGE VERSUS STANDING VOLTAGE
Standing
Percentage of
Full Charge
100%2.105V12.63V25.26V50.52V
90%2.10V12.6V25.20V50.40V
80%2.08V12.5V25.00V50.00V
70%2.05V12.3V24.60V49.20V
60%2.03V12.2V24.40V48.80V
50%2.02V12.1V24.20V48.40V
30%1.97V11.8V23.60V47.20V
20%1.95V11.7V23.40V46.80V
10%1.93V11.6V23.20V46.40V
0%= / < 1.93V= / < 11.6V= / < 23.20V= / < 46.40V
Check the individual cell voltages / specic gravity. If the inter cell voltage difference is
more than a 0.2V, or the specic gravity difference is 0.015 or more, the cells will require
equalization. Please note that only the non-sealed / vented / ooded / wet cell batteries
are equalized. Do not equalize sealed / VRLA type of AGM or Gel Cell Batteries.
Voltage of
Individual Cells
7.10 STATE OF DISCHARGE OF A LOADED BATTERY – LOW BATTERY /
DC INPUT VOLTAGE ALARM AND SHUTDOWN IN INVERTERS
Most inverter hardware estimate the State of Discharge of the loaded battery by measuring the voltage at the inverter’s DC input terminals (considering that the DC input cables
are thick enough to allow a negligible voltage drop between the battery and the inverter).
Standing
Voltage of
12V Battery
Standing
Voltage of
24V Battery
Standing
Voltage of
48V Battery
Inverters are provided with a buzzer alarm to warn that the loaded battery has been
deeply discharged to around 80% of the rated capacity. Normally, the buzzer alarm is
triggered when the voltage at the DC input terminals of the inverter has dropped to
around (i) 10.5V for a 12V battery, (ii) 21V for 24V battery or (iii) 42V for 48V battery at
C-Rate discharge current of C/5 Amps and electrolyte temp. of 80°F. The inverter is shut
down if the terminal voltage at C/5 discharge current falls further to (i) 10V for 12V battery, (ii) 20V for 24V battery or (iii) 40V for 48V battery.
The State of Discharge of a battery is estimated based on the measured terminal voltage
of the battery. The terminal voltage of the battery is dependent upon the following:
- Temperature of the battery electrolyte: Temperature of the electrolyte affects the
electrochemical reactions inside the battery and produces a Negative Voltage
Coefcient – during charging / discharging, the terminal voltage drops with rise in
temperature and rises with drop in temperature.
- The amount of discharging current or “C-Rate”: A battery has non linear internal
resistance and hence, as the discharge current increases, the battery terminal voltage
decreases non-linearly.
SECTION 7 | General Information on Lead Acid
Batteries
The discharge curves in Fig. 7.1 show the % State of Charge versus the terminal voltage
of typical battery under different charge /discharge currents, i.e. “C-Rates” and xed
temperature of 80°F.
NOTE: The X-axis of Curves shown in Fig 7.1 indicates the % State of Charge. % State of
Charge may be converted to % State of Discharge using formula given below:
% State of Discharge = 100% - % State of Charge
7.11 LOW DC INPUT VOLTAGE ALARM IN INVERTERS
As stated earlier, the buzzer alarm is triggered when the voltage at the DC input terminals of the inverter has dropped to around 10.5V for a 12V battery (21V for 24V battery)
at C-Rate discharge current of C/5 Amps. Please note that the terminal voltage relative
to a particular of State Discharge decreases with the rise in the value of the discharge
current. For example, terminal voltages for a State of Discharge of 80% (State of Charge
of 20%) for various discharge currents will be as given at Table 7.5 (Refer to Fig 7.1 for
parameters and values shown in Table 7.5):
TABLE 7.5 TERMINAL VOLTAGE AND SOC OF LOADED BATTERY
Discharge Current:
C-Rate
C/3 A10.45V20.9V41.8V09.50V19.0V38.0V
C/5 A10.90V21.8V43.6V10.30V20.6V41.2V
C/10 A11.95V23.9V47.8V11.00V22.0V44.0V
C/20 A11.85V23.7V47.4V11.50V23.0V46.0V
C/100 A12.15V24.3V48.6V11.75V23.5V47.0V
Terminal Voltage at 80%
State of Discharge (20% SOC)
12V24V48V12V24V48V
Terminal Voltage When Completely
Discharged (0% SOC)
In the example given above, the 10.5V / 21.0V / 42.0V Low Battery / DC Input Alarm
would trigger at around 80% discharged state (20% SOC) when the C-Rate discharge
current is C/5 Amps. However, for lower C-Rate discharge current of C/10 Amps and
lower, the battery will be almost completely discharged when the alarm is sounded.
Hence, if the C-Rate discharge current is lower than C/5 Amps, the battery may have
completely discharged by the time the Low DC Input Alarm is sounded.
7.12 LOW DC INPUT VOLTAGE SHUT-DOWN IN INVERTERS
As explained above, at around 80% State of Discharge of the battery at C-Rate discharge current of around C/5 Amps, the Low DC Input Voltage Alarm is sounded at
around (i) 10.5V for a 12V battery, (ii) 21V for 24V battery and (iii) 42V for 48V battery
to warn the user to disconnect the battery to prevent further draining of the battery.
If the load is not disconnected at this stage, the batteries will be drained further to a
lower voltage and to a completely discharged condition that is harmful for the battery
and for the inverter.
24 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
Inverters are normally provided with a protection to shut down the output of the inverter
if the DC voltage at the input terminals of the inverter drops below a threshold of around
(i) 10V for a 12V battery, (ii) 20V for 24 battery and (iii) 40V for 48V battery. Referring to
the Discharge Curves given in Fig 7.1, the State of Discharge for various C-Rate discharge
currents for battery voltage of 10V / 20V / 40V is as follows:
- 15% State of Charge or 85% State of Discharge at very high C-rate discharge
current of C/3 Amps.
- 0% State of Charge or 100% State of Discharge at high C-Rate discharge
current of C/5 Amps.
- 0% State of Charge or 100% State of Discharge at lower C-rate Discharge current of
C/10 Amps.
It is seen that at DC input voltage of 10V / 20V / 40V, the battery is completely discharged for C-rate discharge current of C/5 and lower.
In view of the above, it may be seen that a xed Low DC Input Voltage Alarm is not useful.
Temperature of the battery further complicates the situation. All the above analysis is based
on battery electrolyte temperature of 80°F. The battery capacity varies with temperature.
Battery capacity is also a function of age and charging history. Older batteries have lower
capacity because of shedding of active materials, sulfation, corrosion, increasing number of
charge / discharge cycles etc. Hence, the State of Discharge of a battery under load cannot
be estimated accurately. However, the low DC input voltage alarm and shut-down functions
are designed to protect the inverter from excessive current drawn at the lower voltage.
7.13 USE OF EXTERNAL PROGRAMMABLE LOW VOLTAGE DISCONNECTS
The above ambiguity can be removed by using an external, programmable Low Voltage
Disconnect where more exact voltage threshold can be set to disconnect the battery
based on the actual application requirements.
7.14 DEPTH OF DISCHARGE OF BATTERY AND BATTERY LIFE
The more deeply a battery is discharged on each cycle, the shorter the battery life. Using
more batteries than the minimum required will result in longer life for the battery bank.
A typical cycle life chart is given in the Table 7.6:
TABLE 7.6: TYPICAL CYCLE LIFE CHART
Depth of Discharge
% of Ah Capacity
10100015003800
503204801100
80200300675
100150225550
NOTE: It is recommended that the depth of discharge should be limited to 50%.
Cycle Life of Group
27 /31
Cycle Life of Group 8DCycle Life of Group
GC2
48V
48V
48V
48V
SECTION 7 | General Information on Lead Acid
Batteries
7.15 SERIES AND PARALLEL CONNECTION OF BATTERIES
7.15.1 Series Connection
Cable “A”
Battery 4Battery 3Battery 2Battery 1
48V Inverter
or 48V Charger
Cable “B”
12V,
200 Ah
12V,
200 Ah
12V,
200 Ah
12V,
200 Ah
Fig 7.2: Series Connection
When two or more batteries are connected in series, their voltages add up but their Ah
capacity remains the same. Fig. 7.2 shows 4 pieces of 12V, 200 Ah batteries connected
in series to form a battery bank of 48V with a capacity of 200 Ah. The Positive terminal
of Battery 4 becomes the Positive terminal of the 48V bank. The Negative terminal of
Battery 4 is connected to the Positive terminal of Battery 3. The Negative terminal of
Battery 3 is connected to the Positive terminal of Battery 2. The Negative terminal of
Battery 2 is connected to the Positive terminal of Battery 1. The Negative terminal of
Battery 1 becomes the Negative terminal of the 48V battery bank.
7.15.2 Parallel Connection
48V Inverter
or 48V Charger
Cable “A”
Battery
Bank 1
48V*
100 Ah
Battery
Bank 2
48V*
100 Ah
Battery
Bank 3
48V*
100 Ah
Battery
Bank 4
48V*
100 Ah
Cable “B”
* NOTE: Each of the 48V, 100 Ah battery banks will consist of (i) 8 pieces of 6V, 100 Ah batteries in series or
(ii) 4 pieces of 12V, 100 Ah batteries in series.
Fig 7.3: Parallel Connection
When two or more batteries are connected in parallel, their voltage remains the same but
their Ah capacities add up. Fig. 7.3 shows 4 pieces of 48V, 100 Ah Battery Banks connected
in parallel to form a battery bank of 48V with a capacity of 400 Ah. The four Positive
terminals of Batery Banks 1 to 4 are paralleled (connected together) and this common
26 | SAMLEX AMERICA INC.
48V String 148V String 2
(ii) 4x 6V, 200 Ah batteries in series
!
SECTION 7 | General Information on Lead Acid
Batteries
Positive connection becomes the Positive terminal of the 48V bank. Similarly, the four
Negative terminals of Battery Banks 1 to 4 are paralleled (connected together) and this
common Negative connection becomes the Negative terminal of the 48V battery bank.
7.15.3 Series – Parallel Connection
24V
Cable “A”
48V Inverter
or 48V Charger
Cable “B”
* NOTE: Each of the 24V, 200 Ah Battery Banks may be (i) 2x 12V, 200 Ah batteries in series, or
Battery
Bank 1
24V*
200 Ah
24V Battery
Bank 2
24V*
200 Ah
24V
Battery
Bank 3
24V*
200 Ah
24V
Battery
Bank 4
24V*
200 Ah
Fig. 7.4: Series-Parallel Connection
Figure 7.4 shows a series – parallel connection consisting of four 24V, 200 Ah Battery Banks
to form a 48V, 400 Ah battery bank. Two 24V, 200 Ah Battery Banks 1 and 2 are connected
in series to form a 48V, 200 Ah Battery Bank (String 1). Similarly, two 24V, 200 Ah Battery
Banks 3 and 4 are connected in series to form a 48V, 200 Ah Battery Bank (String 2). These
two 48V, 200 Ah Strings 1 and 2 are connected in parallel to form a 48V, 400 Ah bank.
CAUTION!
When 2 or more batteries / battery strings are connected in parallel and are
then connected to an inverter or charger (See Figs 7.3 and 7.4), attention
should be paid to the manner in which the charger / inverter is connected to
the battery bank. Please ensure that if the Positive output cable of the battery
charger / inverter (Cable “A”) is connected to the Positive battery post of the
rst battery bank (Battery Bank 1 in Fig 7.3) or to the Positive battery post of
the rst battery string (Battery Bank 1 of String 1 in Fig. 7.4), then the Negative
output cable of the battery charger / inverter (Cable “B”) should be connected
to the Negative battery post of the last battery bank (Battery Bank 4 as in Fig.
7.3) or to the Negative Post of the last battery string (Battery Bank 4 of Battery
String 2 as in Fig. 7.4). This connection ensures the following:
- The resistances of the interconnecting cables will be balanced.
- All the individual batteries / battery strings will see the same series resistance.
SECTION 7 | General Information on Lead Acid
Batteries
- All the individual batteries will charge / discharge at the same charging
current and thus, will be charged to the same state at the same time.
- None of the batteries will see an overcharge condition.
7.16 SIZING THE INVERTER BATTERY BANK
One of the most frequently asked questions is, "how long will the batteries last?" This
question cannot be answered without knowing the size of the battery system and the
load on the inverter. Usually this question is turned around to ask “How long do you
want your load to run?”, and then specic calculation can be done to determine the
proper battery bank size.
There are a few basic formulae and estimation rules that are used:
1. Active Power in Watts (W) = Voltage in Volts (V) x Current in Amperes (A)
x Power Factor.
2. For an inverter running from a 48V battery system, the approximate DC current
required from the 48V batteries is the AC power delivered by the inverter to the
load in Watts (W) divided by 40.
3. Energy required from the battery = DC current to be delivered
(A) x Time in Hours (H).
The rst step is to estimate the total AC Watts (W) of load(s) and for how long the
load(s) will operate in hours (H). The AC Watts are normally indicated in the electrical
nameplate for each appliance or equipment. In case AC Watts (W) are not indicated,
Formula 1 given above may be used to calculate the AC Watts. The next step is to
estimate the DC current in Amperes (A) from the AC Watts as per Formula 2 above. An
example of this calculation for a 48V inverter is given below:
Let us say that the total AC Watts delivered by the inverter = 1000W.
Then, using Formula 2 above, the approximate DC current to be delivered by the 48V
batteries = 1000W ÷40 = 25 Amperes.
Next, the energy required by the load in Ampere Hours (Ah) is determined.
For example, if the load is to operate for 3 hours then as per Formula 3 above, the energy
to be delivered by the 48V batteries = 25 Amperes × 3 Hours = 75 Ampere Hours (Ah).
Now, the capacity of the batteries is determined based on the run time and
the usable capacity.
From Table 7.3 “Battery Capacity versus Rate of Discharge”, the usable capacity at
3 Hour discharge rate is 60%. Hence, the actual capacity of the 48V batteries to
deliver 75 Ah will be equal to: 75 Ah ÷ 0.6 = 125 Ah.
And nally, the actual desired rated capacity of the batteries is determined based on
the fact that normally only 80% of the capacity will be available with respect to the
rated capacity due to non availability of ideal and optimum operating and charging
conditions. So the nal requirements will be equal to:
28 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
125 Ah ÷ 0.8 = 156.25 Ah (note that the actual energy required by the load was 75 Ah).
It will be seen from the above that the nal rated capacity of the batteries is almost
2 times the energy required by the load in Ah. Thus, as a Rule of Thumb, the Ah
capacity of the batteries should be twice the energy required by the load in Ah.
7.17 CHARGING BATTERIES
Batteries can be charged by using good quality AC powered battery charger or from alternative energy sources like solar panels, wind or hydro systems. Make sure an appropriate
Battery Charge Controller is used. It is recommended that batteries may be charged at
10% to 13% of their Ah capacity (Ah capacity based on C-Rate of 20 Hr Discharge Time).
Also, for complete charging (return of 100% capacity) of Sealed Lead Acid Battery, it is
recommended that a 3 Stage Charger may be used (Constant Current Bulk Charging Stage
} Constant Voltage Boost / Absorption Charging } Constant Voltage Float Charging).
In case, Wet Cell / Flooded Batteries are being used, a 4-stage charger is recommended
(Constant Current Bulk Charging Stage } Constant Voltage Boost / Absorption Stage }
Constant Voltage Equalization Stage } Constant Voltage Float Stage).
SECTION 8 | Installation
WARNING!
1. Before commencing installation, please read the safety instructions explained
in Section 1 titled “Safety Instructions”.
2. It is recommended that the installation should be undertaken by a qualied,
licensed / certied electrician.
3. Various recommendations made in this manual on installation will be superseded by the National / Local Electrical Codes related to the location of the
unit and the specic application.
8.1 LOCATION OF INSTALLATION
Please ensure that the following requirements are met:
Working Environment: Indoor use.
Cool: Heat is the worst enemy of electronic equipment. Hence, please ensure that the
unit is installed in a cool area that is also protected against heating effects of direct
exposure to the sun or to the heat generated by other adjacent heat generating devices.
SECTION 8 | Installation
Well Ventilated: To avoid shut down of the inverter due to over temperature, do not cover
or block suction / exhaust openings or install the unit in an area with limited airow. Keep
a minimum clearance of 10" around the unit to provide adequate ventilation. If installed
in an enclosure, openings must be provided in the enclosure, directly opposite to the airsuction and air-exhaust openings of the inverter.
Ventilation in PST-600-48: It is cooled by convection and by forced air-cooling by
temperature controlled fan (behind openings 6, Fig 6.2). The fan draws cool air from airsuction openings on the bottom (11, Fig 6.2) and discharges hot air through the exhaust
openings next to the fan (6, Fig 6.2).
Ventilation in PST-1500-48: It is cooled by convection and by forced air-cooling by 2
temperature controlled fans (behind openings 6, Fig 6.1). The fans draw cool air from airsuction openings in the front and bottom (17, Fig 6.1) and discharge hot air through the
exhaust openings next to the fans (6, Fig 6.1).
Dry: There should be no risk of condensation, water or any other liquid that can enter
or fall on the unit.
Clean: The area should be free of dust and fumes. Ensure that there are no insects or
rodents. They may enter the unit and block the ventilation openings or short circuit electrical circuits inside the unit.
Protection Against Fire Hazard: The unit is not ignition protected and should not be
located under any circumstance in an area that contains highly ammable liquids like
gasoline or propane as in an engine compartment with gasoline-fueled engines. Do not
keep any flammable / combustible material (i.e., paper, cloth, plastic, etc.) near the unit
that may be ignited by heat, sparks or flames.
Closeness to the Battery Bank: Locate the unit as close to the battery bank as possible
to prevent excessive voltage drop in the battery cables and consequent power loss and
reduced efciency. However, the unit should not be installed in the same compartment
as the batteries (ooded or wet cell) or mounted where it will be exposed to corrosive
acid fumes and ammable Oxygen and Hydrogen gases produced when the batteries
are charged. The corrosive fumes will corrode and damage the unit and if the gases are
not ventilated and allowed to collect, they could ignite and cause an explosion.
Accessibility: Do not block access to the front panel. Also, allow enough room to access
the AC receptacles and DC wiring terminals and connections, as they will need to be
checked and tightened periodically.
Preventing Radio Frequency Interference (RFI): The unit uses high power switching
circuits that generate RFI. This RFI is limited to the required standards. Locate any electronic equipment susceptible to radio frequency and electromagnetic interference as far
away from the inverter as possible. Read Section 3, “Limiting Electromagnetic Interfer-
ence (EMI)” for additional information.
30 | SAMLEX AMERICA INC.
SECTION 8 | Installation
5
5
8.2. OVERALL DIMENSIONS
8.2.1 PST-1500-48
The overall dimensions and the location of the mounting slots for PST-1500-48 are
shown at Fig. 8.1.
The unit has air intake and exhaust openings for the cooling fan. It has to be mounted
in such a manner so that small objects should not be able to fall easily into the unit from
these openings and cause electrical / mechanical damage. Also, the mounting orientation should be such that if the internal components overheat and melt / dislodge due to
a catastrophic failure, the melted / hot dislodged portions should not be able to fall out
of the unit on to a combustible material and cause a re hazard. The size of openings
has been limited as per the safety requirements to prevent the above possibilities when
the unit is mounted in the recommended orientations. In order to meet the regulatory
safety requirements, the mounting has to satisfy the following requirements:
- Mount on a non-combustible material.
- The mounting surface should be able to support the weight of the unit
- Mount horizontally on a horizontal surface - above a horizontal surface
(e.g. table top or a shelf).
- Mount horizontally on a vertical surface – The unit can be mounted on a vertical
surface (like a wall) with the fan axis horizontal (fan opening facing left or right).
WARNING!
Mounting the unit vertically on a vertical surface is NOT recommended (fan
opening facing up or down). As explained above, this is to prevent falling of
objects into the unit through the fan opening when the fan opening faces up.
If fan opening faces down, hot damaged component may fall out.
The surface of the unit is likely to be at elevated temperature in conditions
of higher load and higher ambient temperature. Hence, the unit should be
installed in a manner where it is not likely to come in contact with any person.
8.4 DC SIDE CONNECTIONS
8.4.1 Preventing DC Input Over Voltage
It is to be ensured that the DC input voltage of this unit is less than 64.0 ± 0.5 VDC to
prevent permanent damage to the unit. Please observe the following precautions:
- Ensure that the maximum charging voltage of the external battery charger / alternator / solar charge controller is less than 64.0 ± 0.5 VDC.
- Do not use unregulated solar panels to charge the battery connected to this unit. Under
open circuit conditions and in cold ambient temperatures, the output of 48V nominal
solar panel / array may reach > 88 VDC. Always use a charge controller between the solar
panel and the battery.
- When using Diversion Charge Control Mode in a charge controller, the solar / wind /
hydro source is directly connected to the battery bank. In this case, the controller will
divert excess current to an external load. As the battery charges, the diversion duty
cycle will increase. When the battery is fully charged, all the source energy will ow
into the diversion load if there are no other loads. The charge controller will discon-
SECTION 8 | Installation
!
!
nect the diversion load if the current rating of the controller is exceeded. Disconnection of the diversion load may damage the battery as well as the inverter or other DC
loads connected to the battery due to high voltages generated during conditions of
high winds (for wind generators), high water ow rates (for hydro generators). It is,
therefore, to be ensured that the diversion load is sized correctly to prevent the above
over voltage conditions.
- These units are designed to operate from Lead Acid Battery System with nominal voltage of 48 VDC. Do not operate these units from battery system voltage higher/lower
than 48 VDC.
8.4.2 Preventing Reverse Polarity on the DC Input Side
CAUTION!
Damage caused by reverse polarity is not covered by warranty! When making
battery connections on the input side, make sure that the polarity of battery
connections is correct (Connect the Positive of the battery to the Positive terminal of the unit and the Negative of the battery to the Negative terminal of the
unit). If the input is connected in reverse polarity, DC fuse(s) inside the inverter
will blow and may also cause permanent damage to the inverter.
8.4.3 Connection from Batteries to the DC Input Side – Sizing of Cables
and Fuses
CAUTION!
The input section of the inverter has large value capacitors connected across the
input terminals. As soon as the DC input connection loop (Battery (+) terminal Ò
External Fuse Ò Positive input terminal of the Inverter Ò Negative input terminal
of the Inverter Ò Battery (–) terminal) is completed, these capacitors will start
charging and the unit will momentarily draw very heavy current to charge these
capacitors that will produce sparking on the last contact in the input loop even
when the unit is in OFF condition. Ensure that the fuse is inserted only after all
the connections in the loop have been completed so that sparking is limited to
the fuse area.
Flow of electric current in a conductor is opposed by the resistance of the conductor.
The resistance of the conductor is directly proportional to the length of the conductor
and inversely proportional to its cross-section (thickness). The resistance in the conductor
produces undesirable effects of voltage drop and heating. The size (thickness / crosssection) of the conductors is designated by AWG (American Wire Gauge). Conductors
thicker than AWG #4/0 are sized in MCM/kcmil. Table 8.1 gives Resistance in Ohm (Ω)
per Foot at 25°C / 77°F for the wire sizing recommended for use with this inverter.
34 | SAMLEX AMERICA INC.
SECTION 8 | Installation
Table 8.1 Wiring Resistance per Foot
WIRE SIZE,
AWG
AWG#100.00108 Ω per Foot
AWG#200.0004028 Ω per Foot
Conductors are protected with insulating material rated for specic temperature e.g.
75˚C/167˚F. As current ow produces heat that affects insulation, there is a maximum
permissible value of current (called “Ampacity”) for each size of conductor based on
temperature rating of its insulation. The insulating material of the cables will also be
affected by the elevated operating temperature of the terminals to which these are connected. Ampacity of cables is based on the National Electrical Code (NEC)-2014. Please
see details given under “Notes for Table 8.2”.
The DC input circuit is required to handle very large DC currents and hence, the size of the
cables and connectors should be selected to ensure minimum voltage drop between the
battery and the inverter. Thinner cables and loose connections will result in poor inverter
performance and will produce abnormal heating leading to risk of insulation melt down
and re. Normally, the thickness of the cable should be such that the voltage drop due to
the current & the resistance of the length of the cable should be less than 2% to 5%. Use
oil resistant, multi-stranded copper wire cables rated at 75ºC / 167°F minimum. Do not use
aluminum cable as it has higher resistance per unit length. Cables can be bought at a marine
/ welding supply store. Effects of low voltage on common electrical loads are given below:
RESISTANCE IN OHM (Ω)
PER FOOT AT 25°C / 77°F
• Lighting circuits - incandescent and Quartz Halogen: A 5% voltage drop causes an approxi-
mate 10% loss in light output. This is because the bulb not only receives less power, but the
cooler lament drops from white-hot towards red-hot, emitting much less visible light.
• Lighting circuits - uorescent: Voltage drop causes a nearly proportional drop in
light output.
• AC induction motors - These are commonly found in power tools, appliances, well
pumps etc. They exhibit very high surge demands when starting. Signicant voltage drop in these circuits may cause failure to start and possible motor damage.
• PV battery charging circuits - These are critical because voltage drop can cause a
disproportionate loss of charge current to charge a battery. A voltage drop greater
than 5% can reduce charge current to the battery by a much greater percentage.
8.4.4 Fuse Protection in the Battery Circuit
A battery is an unlimited source of current. Under short circuit conditions, a battery can
supply thousands of Amperes of current. If there is a short circuit along the length of
the cables that connects the battery to the inverter, thousands of Amperes of current
can ow from the battery to the point of shorting and that section of the cable will
become red-hot, the insulation will melt and the cable will ultimately break. This interruption of very high current will generate a hazardous, high temperature, high-energy
SECTION 8 | Installation
arc with accompanying high-pressure wave that may cause re, damage nearby objects
and cause injury. To prevent occurrence of hazardous conditions under short circuit conditions, the fuse used in the battery circuit should limit the current (should be "Current
Limiting Type"), blow in a very short time (should be Fast Blow Type) and at the same
time, quench the arc in a safe manner. For this purpose, UL Class T Fuse or equivalent
should be used (As per UL Standard 248-15). This special purpose current limiting, very
fast acting fuse will blow in less than 8 ms under short circuit conditions. Appropriate
capacity of the above Class T fuse or equivalent should be installed within 7” of the
battery Plus (+) Terminal (Please see Table 8.2 for fuse sizing). Marine Rated Battery
Fuses, MRBF-xxx Series made by Cooper Bussmann may also be used. These fuses comply
with ISO 8820-6 for road vehicles.
WARNING!
Use of an appropriately sized external fuse as described above is mandatory to
provide safety against re hazard due to accidental short circuit in the battery
cables. Please note that the internal DC side fuses are designed to protect ther
internal components of the inverter against DC side overloading. These fuses
will NOT blow if there is a short circuit along the length of wires connecting the
battery and the inverter.
8.4.5 Recommended Sizes of Battery Cables and Fuses
Sizes of cables and fuses are shown in Table 8.2. Sizing is based on safety considerations specied in NEC-2014. Please refer to “Notes for Table 8.2” for details.
Table 8.2 Recommended Sizing of Battery Cables and External Battery Side Fuse
Model No.
(1)
PST-600-4820A25A20AAWG#10AWG#10AWG#10
PST-1500-4850A62.5A50AAWG#6AWG#6AWG#6
Rated DC
Input Current
(See Note 1)
(2)
Minimum
Ampacity
of cable as
per NEC
(See Note 2)
(3)
External
Battery Fuse
Size (Based
in Column 2)
(See Note 3)
(4)
3 ft / 0.91M
(5)
Minimum cable size
(See Note 4)
6 ft / 1.83M
(6)
10 ft / 3.05M
(7)
NOTES FOR TABLE 8.2
1) Column 2 indicates the Rated DC Input Current drawn from the battery.
2) Column 3 indicates minimum NEC Ampacity for sizing of conductors. NEC Ampacity
is not less than 125% of the rated DC input current (Column 2) - Refer to NEC-2014
(National Electrical Code) - Section 215.2(A)(1)(a) for Feeder Circuits.
3) Column (4) indicates the size of external fuse in the battery circuit. It is mandatory to
install this fuse within 7” of the battery Positive terminal to protect the battery cables
against short circuit. Amp rating of the fuse is based on the following considerations:
a) Not less than the Rated DC Input Current (Column 2)
36 | SAMLEX AMERICA INC.
SECTION 8 | Installation
b) Closest Standard Ampere Rating of Fuse has been used - Refer to NEC-2014
(National Electrical Code) - Section 240.6(A)
c) Where Standard Fuse Rating does not match the required Ampacity (Col-
umn 2), the next higher Standard Rating of the fuse may be used - Refer to
NEC-2014 (National Electrical Code) - Section 240.4(B)
d) Type of fuse: Fast-acting, Current Limiting, UL Class T (UL Standard 248-15)
or equivalent
4) Columns 5 to 7 indicate minimum cable conductor size that is based on the following
2 considerations. Thicker conductor out of the following 2 considerations has been chosen:
a) As per guidelines in NEC (2014) Table 310.15(B)(16) for allowable Ampacities of
Insulated Conductors running in raceway/conduit. Conductor size is based on:
(i) NEC Ampacity specied at Column 3,
(ii) Copper conductor with temperature rating of 75˚C/167˚F and
(iii) Ambient temperature of 30°C / 86°F
b) Voltage drop across the length of cables limited to 2% of 48 VDC i.e. 0.9 VDC
i) Voltage drop has been calculated by multiplying the Rated DC Input Current
(Column 2) and the resistance of the total length of Copper conductor (the
total length of conductor has been taken as 2 times the running distance
between the unit and the battery to cover 2 lengths of Positive and Negative
cable conductors).
ii) Resistance of the cable is based on Table 8.1.
5) Fuse in the battery circuit is primarily required for protection against short circuit in
the battery cable run. The size of this fuse has to be equal to or larger than the Rated
DC Input Current of the inverter at Column (2). Further, the Amp rating of the fuse
used for protecting a battery cable against short circuit has to be lower than the Ampacity of the cable so that the fuse blows before the cable insulation is damaged due
to overheating as a result of fault current higher than the Ampacity of the cable.
8.4.6.1 DC Input Connection for PST-1500-48
The DC input terminals for battery connection (8 & 9 in Fig 6.1) have nut and bolt connection - bolt size is 5/16" (18 Threads per Inch). Use ring tongue type of terminals on
the wire ends to t 5/16" bolt size.
2 pieces of ring terminal lugs have been provided for AWG#6 cable.
8.4.6.2 DC Input Connection for PST-600-48
The DC input terminals for battery connection (8 & 9 in Fig. 6.2) have 11 mm/0.433"
cylindrical hole with M-8 set screw.
DO NOT insert the stranded bare end of the wire directly into the tubular hole as the
set screw will not pinch all the strands, resulting in a partial/loose contact. Appropriate
terminal lug should be crimped/soldered to the bare wire end.
To ensure rm contact, 2 pieces of blade type terminal lugs have been provided for
AWG#10 cable.
SECTION 8 | Installation
8.4.7 Reducing RF Interference
Please comply with recommendations given in Section 3 – "Limiting Electromagnetic
Interference".
8.5 AC SIDE CONNECTIONS
WARNING! Preventing Paralleling of the AC Output
1. The AC output of the inverter cannot be synchronized with another AC
source and hence, it is not suitable for paralleling. The AC output of the inverter should never be connected directly to an electrical breaker panel / load
center which is also fed from the utility power/ generator. Such a connection
will result in parallel operation and AC power from the utility / generator will
be fed back into the inverter which will instantly damage the output section
of the inverter and may also pose a re and safety hazard. If an electrical
breaker panel / load center is being fed from the utility power / generator
and the inverter is required to feed this panel as backup power source, the
AC power from the utility power/ generator and the inverter should rst be
fed to a manual selector switch / Automatic Transfer Switch and the output
of the manual selector switch / Automatic Transfer Switch should be connected to the electrical breaker panel / load center.
2. To prevent possibility of paralleling and severe damage to the inverter, never
use a simple jumper cable with a male plug on both ends to connect the AC
output of the inverter to a handy wall receptacle in the home / RV.
8.5.1 Bonding of AC Output Neutral to Chassis Ground
The Neutral slots of the NEMA5-20R GFCI Duplex Receptacles [(i) 5, Fig 6.1 for PST-1500-48
and (ii) 5, Fig. 6.2 for PST-600-48] are internally bonded to the metal chassis of the inverter.
8.5.2 AC Output Connection Through Ground Fault Circuit
Interrupter (GFCI)
An un-intentional electric path between a source of current and a grounded surface
is referred to as a “Ground Fault”. Ground faults occur when current is leaking somewhere. In effect, electricity is escaping to the ground. How it leaks is very important. If
your body provides a path to the ground for this leakage (dry human body has a low
resistance of only around 1 K Ohm), you could be injured, burned, severely shocked
or electrocuted. A Ground Fault Circuit Interrupter (GFCI) protects people from electric
shock by detecting leakage and cutting off the AC source. The leakage detection circuit
compares the current sent to the load and returned back from the load. If the returned
current is less by 5 to 6 mA due to leakage, the GFCI trips. The GFCI also trips if it sees
Neutral to Ground bond on the load side of the GFCI.
The AC output of this inverter is available through a NEMA5-20R GFCI Duplex Receptacle
[(i) 5, Fig 6.1 for PST-1500-48 and (ii) 5, Fig. 6.2 for PST-600-48]. The Neutral slot of this receptacle (longer rectangular slot) is internally bonded to the metal chassis of the inverter.
38 | SAMLEX AMERICA INC.
!
SECTION 8 | Installation
Self Monitoring GFCI: The GFCI is “Self Monitoring Type” as per UL Standard Ul-943. As
soon as the Inverter is switched ON and 120 VAC is available on the internal Line Side of
the GFCI, Red LED marked “Life End Alarm” (5c in Figs 6.1 and 6.2) will ash once and
then will remain OFF. The Green LED (5d in Figs 6.1and 6.2) will switch ON indicating
that AC power is available at the Load Side outlets.
As soon as the Inverter is switched OFF and 120 VAC is removed from the internal Line
Side of the GFCI, Red LED marked “Life End Alarm” (5c in Figs 6.1and 6.2) will ash once
and then will remain OFF. The Green LED (5d in Figs 6.1 and 6.2) will switch OFF indicating that AC power is NOT available at the Load Side outlets.
The Self Monitoring Function inside the GFCI will monitor proper operation of ground
fault protection circuitry every 1 to 10 minutes. If defect in the ground fault protection
circuit is detected, the Red LED marked “Life End Alarm” (5c in Figs 6.1 and 6.2) will
remain ON and the GFCI will have to be replaced.
Monthly Testing of GFCI: Test the operation of the GFCI monthly as follows:
• Switch ON the inverter. As soon as 120 VAC output from the inverter is available on
the internal Line Side of the GFCI, Red LED marked “Life End Alarm” (5d in Fig 6.1
and Fig 6.2) will ash once within 5 sec and then will remain OFF. The Green LED
(5c in Fig 6.1 and Fig 6.2) will switch ON indicating that AC power is available at the
Load Side outlets.
• Plug a test lamp into the outlet and switch ON the test lamp.
• Press the “Test Button” (5b in Fig 6.1 and 6.2). The “Reset Button” (5a in Fig 6.1 and
6.2) will pop out. The GFCI will be forced to trip and cut off AC power to the load
side outlets. Green LED (5d in Fig 6.1 and 6.2) will switch OFF. The test lamp will also
switch OFF.
• Press the “Reset Button” (5a in Fig 6.1 and 6.2). The GFCI will reset and AC power to
the load side outlets will be restored. Green LED (5d in Fig 6.1 and 6.2) will switch
ON. The test lamp will also switch ON.
• If the above Test / Reset operation cannot be carried out, replace the GFCI.
GFCI Tripping and Reset: If there is a leakage of 5 to 6mA due to ground fault on the
load side or , there is a Neutral to Ground bond on the load side, the GFCI will trip
and the “Reset Button” (5a in Figs 6.1 and 6.2) will pop out. AC power to the load side
outlets will be cut off. Green LED (5d in Figs 6.1 and 6.2) will switch OFF. Remove the
ground fault in the load circuit. Press the “Reset Button” (5a in Fig 6.1 and 6.2). The GFCI
will reset and AC power to the load side outlets will be restored. Green LED (5d in Figs
6.1 and 6.2) will switch ON.
CAUTION!
1. Do not feed the output from the GFCI receptacle to a Panel Board / Load Center
where the Neutral is bonded to the Earth Ground. This will trip the GFCI.
2. If an extension cord is used, please ensure that the cord is 2-Pole Grounding Type
(3 pin).
SECTION 8 | Installation
The following GFCI has been tested to operate satisfactorily and are acceptable. Other
types may fail to operate properly when connected to this inverter:
Mfr. of GFCIMfr.’s Model No.DescriptionUL Listing File No.
Jiaxing Shouxin
Electric Technology
Co. Ltd.
8.5.3.1 AC Output Connections for Hardwiring (PST-1500-48 only)
For connecting the AC output of PST-1500-48 to an AC Distribution Panelboard / Load
Center, separate connections are available for hard wiring. Please refer to Fig 6.1. Compartment (13, Fig 6.1) contains terminals for AC output. The compartment is covered by
Cover Plate (12, Fig 6.1) with the help of 4 screws. AC output connections are as follows:
Line “L” (15, Fig 6.1) and Neutral “N” (16, Fig 6.1) Terminals.
Please note that Line terminal “L” (15, Fig 6.1) of the AC Terminal Block and the Line
terminal on the Line side of the GFCI are internally connected together at the PCB.
Similarly, Neutral terminal “N” (16, Fig 6.1) on the AC Terminal Block and the Neutral
terminal on the Line side of the GFCI are internally connected together at the PCB
• Hole diameter: 4 mm / 0.16"
• Set screw: #6 (UNF, 40 Threads per Inch) or M3.5 ( Coarse Pitch 0.6 mm)
AC Ground Terminal (14, Fig 6.1)
• Stud: #6 (UNC, 32 Threads Per Inch)
Neutral to Chassis Ground Bonding
• Neutral “N” (16, Fig 6.1) is bonded to the metal chassis of the inverter through a loop of
wire connecting the “N” terminal on the Line side of the GFCI to the chassis of the inverter.
TS-20NEMA5-20 Duplex 20A E473989
8.5.3.2 AC Output Cable Sizing & Conductor Termination for Hard-wiring
(For PST-1500-48 only)
Use 3 conductor cable with at least 90°C insulation rating. Based on the maximum output
current of 12.5A for PST-1500-48, the minimum size of each of the 3 conductors of the AC
output cable should be AWG #12. This is the minimum size recommended in NEC (2014)
Table 30.15(B)(16) for up to 20A over current protection. For rm connection when using set
screw type of terminals, use Insulated Pin Type of Terminals for termination of the Line and
Neutral conductors and Non Insulated Ring Type of Terminal for the Grounding conductor.
For convenience, the following terminals have been provided:
For Line and Neutral wires: Nylon Insulated, Cord End
Terminals for AWG #12 wire ........................................................................ 2 pieces
For Neutral wire: Non Insulated Ring Terminal for #6 stud ....................... 1 piece
Use proper crimping Tool to crimp the terminals to the bare ends of the wire. Make sure
that the connections are tight and rm. Please ensure that the AC cable is adequately
clamped by the metal Strain Relief Clamp (11, Fig 6.1). Please use the following type designation of AC cord: "SE, SEOO, ST, STO, SJ, SJEOO, SJT, or SJTO."
40 | SAMLEX AMERICA INC.
SECTION 8 | Installation
8.6 GROUNDING TO EARTH OR TO OTHER DESIGNATED GROUND
For safety, ground the metal chassis of the inverter to the Earth Ground or to the other
designated Ground. An equipment grounding Lug [(i) 7, Fig 6.1 for PST-1500-48 and
(ii) 7, Fig 6.2 for PST-600-48] has been provided for grounding the metal chassis of the
inverter to the Earth Ground or to the other appropriate Ground.
When using the inverter in a building, connect a 10 mm
copper wire from the above equipment grounding lug to the Earth Ground connection (a connection that connects to the Ground Rod or to the water pipe or to another
connection that is solidly bonded to the Earth Ground). The connections must be tight
against bare metal. Use star washers to penetrate paint and corrosion.
2
or AWG #8 insulated stranded
8.7 OPTIONAL WIRED REMOTE CONTROL
8.7.1 Optional Wired Remote Control for PST-1500-48
An optional Wired Remote Control Model No. RC-300 (with 25 ft. / 7.62 metre cable),
is available for switching ON and switching OFF. It is plugged into Modular Jack (10,
Fig 6.1). The Remote Control has LCD display showing AC output V, A, Hz, W, VA and
Power Factor (PF). It also has LED indications similar to the indications on the front panel
(2,3,4 in Fig. 6.1). Read Remote Control Manual for details.
NOTE: For the Remote Control RC-300 to operate, the ON/OFF switch on the inverter (1,
Fig 6.1) should be in ON condition.
8.7.2 Optional Wired Remote Control for PST-600-48
An optional Wired Remote Control Model No. RC-15A (with 16.5 ft. / 5 metre cable),
is available for switching ON and switching OFF. It is plugged into Modular Jack (10,
Fig 6.2). The Remote Control has LED indications similar to the indications on the front
panel (2,3,4 in Fig. 6.2). Read Remote Control Manual for details.
NOTE: For the Remote Control RC-15A to operate, the ON/OFF switch on the inverter (1,
Fig 6.2) should be in ON condition.
SECTION 9 | Operation
9.1 SWITCHING THE INVERTER ON/OFF
Before switching on the inverter, check that all the AC loads have been switched OFF.
The ON/OFF switch (1, Fig 6.1 for PST-1500-48 and 1 in Fig 6.2 for PST-600-48) on the
front panel of the inverter is used to switch ON and switch OFF the inverter. This switch
operates a low power control circuitry, which in turn controls all the high power circuitry. Optional Remote Control Model may also be used for ON/OFF control (RC-15A for
PST-600-48 and RC-300 for PST-1500-48).
!
SECTION 9 | Operation
CAUTION!
Please note that the ON/OFF switch is not switching the high power battery
input circuit. Parts of the DC side circuit will still be alive even when the switch
is in the OFF position. Hence, disconnect the DC and AC sides before working
on any circuits connected to the inverter.
When the inverter is switched ON, the GREEN "POWER" / "POWER ON" LED (2, Fig. 6.1
for PST-1500-48 and 2 in Fig 6.2 for PST-600-48) will be lighted. This LED indicates that
the input section of the inverter is operating normally. Under normal operating conditions, AC output voltage will now be available at the GFCI Duplex Receptacle (5, Fig 6.1
for PST-1500-48 and 5 in Fig 6.2 for PST-600-48) and at the Line "L" and Neutral "N"
terminals (15, 16 in Fig 6.1 for PST-1500-48) located inside the compartment containing
AC output terminals for hard-wiring (13, Fig 6.1 for PST-1500-48). The Green indicator
light on the GFCI (5d in Fig 6.1 for PST-1500-48 and 5d in Fig 6.2 for PST-600-48) will be
lighted.
Switch on the AC load(s). The GREEN "POWER" / "POWER ON" LED (2, Fig 6.1 for PST1500-48 and 2, Fig 6.2 for PST-600-48) and the indication light on the GFCI should remain
lighted for normal operation of the load.
9.2 POWERING ON THE LOADS
After the inverter is switched on, it takes a nite time to become ready to deliver full
power. Hence, always switch on the load(s) after a few seconds of switching on the
inverter. Avoid switching on the inverter with the load already switched on. This may
prematurely trigger the overload protection.
When a load is switched on, it may require initial higher power surge to start. Hence, if multiple loads are being powered, they should be switched on one by one so that the inverter is
not overloaded by the higher starting surge if all the loads are switched on at once.
9.3 TEMPERATURE CONTROLLED COOLING FAN(S)
PST-1500-48 has 2 cooling fans (located behind the air-exhaust openings 6, Fig 6.1).
PST-600-48 has one cooling fan behind fan air exhaust opening (6, Fig 6.2). The fans are
thermostatically controlled. Temperature of a critical hot spot inside the inverter is monitored to activate the fans and the over temperature shut-down. When the temperature of
this hot spot reaches 55°C ± 3°C, the fans are switched ON. The fans will be automatically
switched OFF once the hot spot cools down to 45°C ± 3°C. Please note that the fan(s) may
not come on at low loads or if the ambient temperature is cooler. This is normal.
9.4 INDICATIONS FOR NORMAL OPERATION
When the inverter is operating normally and supplying AC load(s), the GREEN "POWER" /
"POWER ON" LED (2, Fig 6.1 for PST-1500-48 and 2 in Fig 6.2 for PST-600-48) and the Green
LED indication light on the GFCI (5d, Fig 6.1) will be lighted. Please see Section 10,
"Protections" and Section 11 "Troubleshooting Guide" for symptoms of abnormal operation.
42 | SAMLEX AMERICA INC.
i
i
SECTION 9 | Operation
9.5 NO LOAD DRAW (IDLE CURRENT)
When the ON/OFF Switch (1, Fig 6.1 for PST-1500-48 and 1 in Fig 2 for PST-600-48) is
turned ON, all the circuitry inside the inverter becomes alive and the AC output is made
available. In this condition, even when no load is being supplied (or, if a load is connected but has been switched OFF), the inverter draws a small amount of current from
the batteries to keep the circuitry alive and ready to deliver the required power on
demand. This is called the "Idle Current" or the "No Load Draw". Hence, when the load
is not required to be operated, turn OFF the ON/OFF switch (1, Fig 6.1 for PST-1500-48
and 1 in Fig 2 for PST-600-48) on the inverter to prevent unnecessary current drain from
the battery.
INFO
When the inverter is turned OFF using the optional Remote Control RC-300 (for
PST-1500-48) or RC-15A (for PST-600-48), some control circuitry in the inverter is
still alive and will draw very low current. Therefore, to prevent any drain from
the battery, switch OFF the inverter from the ON/OFF switch (1, Fig 6.1 for PST1500-48 and 1 in Fig 2 for PST-600-48) provided on the front panel of the inverter.
SECTION 10 | Protections
10. PROTECTIONS
The inverters have been provided with protections detailed below:
10.1 POWER SURGE / OVERLOAD / SHORT CIRCUIT SHUT DOWN
INFO
Please refer to denitions of Active Power (Watts), Apparent Power (VA) and
• Active Power (Watts) = Apparent Power (VA) x Power Factor (PF).
• For resistive type of loads, the Power Factor = 1 and hence, Apparent Power
• For reactive types of loads, the Power Factor will be < 1 (up to 0.5) and hence,
The AC output voltage will shut down due to overload and short circuit conditions as follows:
Power Factor (PF) at Section 2.1. In the explanation below, the values of Power
are expressed in Apparent Power in VA. Corresponding Active Power (Watts, W)
will depend upon the type of load (Resistive or Reactive) and its Power Factor
(Power Factor may range from 1 to 0.5). Please note the following:
(VA) = Active Power (Watts, W)
the Active Power (Watts, W) will be less than the Apparent Power (VA)
SECTION 10 | Protections
Power Surge Condition, PST-600-48: The surge rating is 1000W or 8.33A (1000W ÷ 120VAC
= 8.33A). When the instantaneous value of the AC output current tries to exceed the
above value of 8.33A, output current limiting is initiated that clamps the peak instantaneous value of output current at 8.33A. Output current limiting results in drop in the peak
portion of the AC output voltage waveform and hence, the RMS voltage also drops. The
extent of voltage drop is proportional to the rated surge current of the load minus 8.33A.
Hence, higher surge current of the load will produce higher voltage drop. For example,
considering Resistive Load with Power Factor =1 (voltage and current are in phase), current limiting will occur near the peak portion of the voltage waveform during every half
cycle (half cycle lasts for 8.33 msec at 60Hz). 1000W is the value of surge power averaged
over 1 to 2 msec during every half cycle of 8.33msec. If this situation continues for 2 to 2.5
sec, overload condition is activated and the AC output is shut down
Power Surge Condition, PST-1500-48: The surge rating is 3000W or 25A (3000W ÷ 120VAC
= 25A). When the instantaneous value of the AC output current tries to exceed the above
value of 25A, output current limiting is initiated that clamps the peak instantaneous value
of output current at 25A. Output current limiting results in drop in the peak portion of
the AC output voltage waveform and hence, the RMS voltage also drops. The extent of
voltage drop is proportional to the rated surge current of the load minus 25A. Hence,
higher surge current of the load will produce higher voltage drop. For example, considering Resistive Load with Power Factor =1 (voltage and current are in phase), current
limiting will occur near the peak portion of the voltage waveform during every half cycle
(half cycle lasts for 8.33 msec at 60Hz). 3000W is the value of surge power averaged over
1 to 2 msec during every half cycle of 8.33msec. If this situation continues for 2 to 2.5 sec,
overload condition is activated and the AC output is shut down.
Overload Condition: If there is a continuous overload of 110% to 115% for 2 to 2.5 sec,
the output voltage will be shut down. Red LED marked “OVERLOAD” (3 in Fig 6.1 for
PST-1500-48 and 3 in Fig 6.2 for PST-600-48) will turn ON, the Green indication light on the
GFCI outlet will be OFF and buzzer alarm will sound. The Green LED marked “POWER” /
"POWER ON" (2 in Fig 6.1 for PST-1500-48 and 2 in Fig 6.2 for PST-600-48) will continue to
be lighted. The unit will be latched in this shut down condition and will require manual
reset. To reset, switch OFF the unit using the ON/OFF Switch (1 in Fig 6.1 for PST-1500-48
and 1 in Fig 6.2 for PST-600-48), wait for 3 minutes and then switch ON the unit again.
Before switching ON, determine and remove the cause of overloading.
Short Circuit Condition: Short circuit condition will be detected when the AC output
voltage drops to 80VAC or lower over a period of around 1 to 1.5 sec. The AC output
voltage will be shut down thereafter.
Red LED marked “OVERLOAD” (3 in Fig 6.1 for PST-1500-48 and 3 in Fig 6.2 for PST-600-
48) will turn ON, the Green indication light on the GFCI outlet will be OFF and buzzer
alarm will sound. The Green LED marked “POWER” / "POWER ON" (2 in Fig 6.1 for
PST-1500-48 and 2 in Fig 6.2 for PST-600-48) will continue to be lighted. The unit will
be latched in this shut down condition and will require manual reset. To reset, switch
OFF the unit using the ON/OFF Switch (1 in Fig 6.1 for PST-1500-48 and 1 in Fig 6.2 for
PST-600-48), wait for 3 minutes and then switch ON the unit again. Before switching ON,
determine and remove the cause of short circuit.
44 | SAMLEX AMERICA INC.
SECTION 10 | Protections
10.2 WARNING ALARM - LOW DC INPUT VOLTAGE
The voltage at the DC input terminals will be lower than the voltage at the battery terminals due to voltage drop in the battery wires and connectors. The drop in the voltage
at the DC input terminals of the inverter could be due to lower battery voltage or due
to abnormally high drop in the battery wires if the wires are not thick enough (Please
see Section 8.4.3 “Connection from Batteries to the DC Input Side – Sizing of Cables
and Fuses”). If the voltage at the DC input terminals drops to 42.0V ± 0.5V or lower, a
buzzer alarm will be sounded. The Green LED marked "POWER" / "POWER ON" (2 in
Fig 6.1 for PST-1500-48 and 2 in Fig 6.2 for PST-600-48) and indication light on the GFCI
will continue to be lighted and the AC output voltage would continue to be available.
This warning buzzer alarm indicates that the battery is running low and that the inverter will be shut down after sometime if the voltage at the inverter terminals further
drops to 40.0V ± 0.5V or lower.
10.3 LOW DC INPUT VOLTAGE SHUT DOWN
If the voltage at the DC input terminals drops to 40.0V ± 0.5V or lower, the AC output is
shut down. Buzzer alarm is sounded. The Green LED marked "POWER" / "POWER ON"
(2 in Fig 6.1 for PST-1500-48 and 2 in Fig 6.2 for PST-600-48) will remain lighted. The
Green indication light on the GFCI will be OFF.
The unit will reset automatically when the DC input voltage rises to 46.0V ± 0.5V or higher.
10.4 HIGH DC INPUT VOLTAGE SHUTDOWN
If the voltage at the DC input terminals rises to 64.0V or higher, the AC output voltage
will be shut down temporarily. Buzzer alarm will be sounded. The Green LED marked
"POWER" / "POWER ON" (2 in Fig 6.1 for PST-1500-48 and 2 in Fig 6.2 for PST-600-48)
will remain lighted. The Green indicator light on the GFCI will be OFF. The unit will be
reset automatically when the voltage drops down to < 64.0V.
10.5 OVER-TEMPERATURE SHUT DOWN
In case of failure of the cooling fans or in the case of inadequate heat removal due to higher
ambient temperatures / insufcient air exchange, the temperature inside the unit will
increase. The temperature of a critical hot spot inside the inverter is monitored, and at 90°C
± 5°C, the AC output of the inverter is shut down temporarily. Buzzer alarm will be sounded.
The Green LED marked "POWER" / "POWER ON" (2 in Fig 6.1 for PST-1500-48 and 2 in Fig
6.2 for PST-600-48) will remain lighted. The Green indication light on the GFCI will be OFF.
The unit will automatically reset after the hot spot has cooled down to 65°C ± 5°C.
10.6 GROUND FAULT / LEAKAGE PROTECTION
AC Output is supplied through NEMA5-20R GFCI Duplex Receptacle (5 in Fig 6.1 for
PST-1500-48 and 5 in Fig 6.2 for PST-600-48). In PST-1500-48, AC output is also supplied
through hardwiring (13 in Fig 6.1). The GFCI will trip if there is 5 to 6 mA leakage /
i
!
SECTION 10 | Protections
Ground fault on the load side or, if Neutral and Ground are bonded on the load side.
When tripped, the Green LED indication on the receptacle (5d, Fig 6.1) will be switched
OFF. Remove the cause of tripping. Switch ON the inverter if OFF and then, press the
"Reset Button" on the GFCI to reset (GFCI will not reset if the inverter is OFF and there is
no AC volatge on the internal Line Side of the GFCI).
The GFCI has self monitoring. If self monitoring test fails, Red LED indication for "End of
Life" (5c, Fig 6.1) will be lighted. The GFCI will be required to be replaced. See Section
8.2 for details.
10.7 INTERNAL DC SIDE FUSES
The following DC side fuses have been provided for internal protection of the DC input
side. The fuses are 58V.
PST-1500-48: 5 pieces of 10A in parallel = 50A total
PST-600-48: 2 pieces of 10A in parallel = 20A total
NOTE: The fuses are soldered to the PCB. Hence, these can be removed and replaced by
de-soldering and then re-soldering.
10.8 REVERSE POLARITY AT THE DC INPUT TERMINALS
The Positive of the battery should be connected to the Positive DC input terminal of
the inverter and the Negative of the battery should be connected to the Negative DC
input terminal of the inverter. A reversal of polarity (the Positive of the battery wrongly
connected to the Negative DC input terminal of the inverter and the Negative of the
battery wrongly connected to the Positive DC input terminal of the inverter) will blow
the external / internal DC side fuses. If the DC side fuse is blown, the inverter will be
dead. The Green LED marked "POWER" (2 in Fig 6.1 for PST-1500-48 and 2 in Fig 6.2 for
PST-600-48) and the Green indication light on the GFCI will be switched OFF and there
will be no AC output.
INFO
Reverse polarity connection is likely to damage the DC input circuitry. The internal fuse(s)
should be replaced with the same size of fuse(s) used in the unit. If the unit does not work
after replacing the fuse(s), it has been permanently damaged and will require repair /
replacement (Please read Section 11 - “Troubleshooting Guide” for more details).
CAUTION!
Damage caused by reverse polarity is not covered by warranty! When making battery
connections on the input side, make sure that the polarity of battery connections is correct
(Connect the Positive of the battery to the Positive terminal of the unit and the Negative of
the battery to the Negative terminal of the unit). If the input is connected in reverse
polarity, DC fuse(s) inside the inverter / external fuse will blow and may also cause
permanent damage to the inverter.
46 | SAMLEX AMERICA INC.
SECTION 11 | Troubleshooting Guide
11.1 PST-1500-48
ISSUEPOSSIBLE CAUSEREMEDY
When switched ON, the
Green LED marked "POWER"
(2, Fig 6.1) does not light.
Buzzer is OFF. There is no AC
output voltage. Green indication light on the GFCI is OFF.
There is no voltage at the
DC input terminals
• Check the continuity of the battery
input circuit.
• Check that the internal/external battery
fuses are intact. Replace if blown.
• Check that all connections in the battery
input circuit are tight.
Low AC output voltage
(< 120VAC but > 80VAC)
(No buzzer alarm).
AC output voltage is available.
Buzzer alarm is sounded at no
load or, when load is switched
ON. The Green LED marked
"POWER" (2, Fig 6.1) is
lighted. Indication light on the
GFCI is Green.
There is no AC output voltage.
Buzzer alarm is sounded
at no load or when load is
switched ON. The Green LED
marked "POWER" (2, Fig 6.1)
is lighted. GREEN indication
light on the GFCI is OFF. There
is no AC output.
Polarity of the DC input
voltage has been reversed
that has blown the external / internal DC side fuses
(Note: Reverse polarity
may cause permanent
damage. Damage caused
due to reverse polarity is
not covered by warranty)
• AC load is exceeding
Surge Overload of 200%
• Load is approaching
Surge Overload of 200%
during lower DC input
voltage
• Low DC input voltage
alarm
• DC input voltage is
42 ± 0.5 VDC or lower
but higher than 40.0 ±
0.5 VDC
• AC output voltage has
been shut down due to
low DC input voltage
• DC input voltage is 40.0
± 0.5V or lower
• Check external and internal fuses. Replace
fuses. If unit does not work, call Technical
Support for repair.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of battery input circuit.
• Reduce load.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
• The AC output voltage will switch ON automatically when the DC input voltage rises to
46.0V ± 0.5V or higher
SECTION 11 | Troubleshooting Guide
11.1 PST-1500-48 (continued)
ISSUEPOSSIBLE CAUSEREMEDY
There is no AC output. The
Green LED marked "POWER"
(2, FIG 6.1) is lighted. Buzzer
is ON. Green indication light
on the GFCI is OFF.
AC output shuts down
completely. Red LED marked
"OVERLOAD" (3, Fig 6.1) is
lighted. Buzzer is ON. The
Green LED marked "POWER"
(2, Fig 6.1) is lighted. Green
indication light on the GFCI
is OFF.
There is no AC output. Buzzer
alarm is sounded. Red LED
marked "OVER TEMP" (4, Fig
6.1) is lighted. The Green LED
marked "POWER" (2, Fig
6.1) is lighted. Green indication light on the GFCI is OFF.
There is no AC output. Green
indication on the GFCI is
OFF. The Green LED marked
"POWER" (2, Fig 6.1) is
lighted. No buzzer alarm.
• Shut-down due to high
input DC voltage
• DC input voltage is
64.0 VDC
Permanent shut-down
of the AC output due to
continuous overload >
110% - 115% for 2 to 2.5
sec or due to short circuit
on the AC load circuit. (AC
output voltage is 80VAC
or less for 1 to 1.5 sec)
Shut-down due to over
temperature because of
fan failure or inadequate
cooling as a result of high
ambient temperature or
insufcient air exchange
• Internal hot spot is at 90
± 5°C or higher
GFCI has tripped due to
leakage or due to Neutral
to Ground bond on the
load side.
• Check that the voltage at the DC input
terminals is less than 64.0 VDC
• Ensure that the maximum charging voltage
of the battery charger / alternator / solar
charge controller is below 64.0 VDC
• Ensure that an unregulated solar panel is
not used to charge a battery. Under cold
ambient temperatures, the output of 48V
nominal solar panel/array may reach > 88
VDC. Ensure that a charge controller is used
between the solar panel and the battery.
• Reduce the load / remove the short circuit
• The load is not suitable as it requires higher
power to operate. Use an inverter with
higher power rating.
• If the unit goes into permanent overload
again after resetting and removing the load
completely, the unit has become defective.
Call Technical support.
NOTE: The unit will be latched in this shutdown condition and will require manual reset.
To reset, switch OFF the power ON/OFF switch
(1, Fig 6.1), wait for 3 minutes and then switch
ON again.
Before switching ON again, remove the cause
of the shut-down.
Check that the fans are working. If not, the fan
control circuit may be defective. Call
Technical Support.
If the fans are working, check that the ventilation slots on the suction side and the openings
on the discharge side of the fan are not
obstructed.
If the fans are working and the openings
are not obstructed, check that enough cool
replacement air is available. Also check that the
ambient air temperature is less than 40ºC.
Reduce the load to reduce the heating effect.
After the cause of overheating is removed and
the internal hot spot cools down to 65 ± 5°C,
the AC output will be restored automatically.
Check load side circuits for leakage or Neutral
to Ground bond. Switch ON the inverter if in
OFF condition. Check the Green LED marked
"POWER" (2, Fig 6.1) is lighed. Press Reset
Button on the GFCI to reset the GFCI. On
resetting, the Green indication on the GFCI will
switch ON.
48 | SAMLEX AMERICA INC.
SECTION 11 | Troubleshooting Guide
11.2 PST-600-48
ISSUEPOSSIBLE CAUSEREMEDY
Red LED indication on the
GFCI (5c, Fig 6.1) is permanently ON or ashing. The
Green LED indication on the
GFCI may be ON or OFF. The
Green LED marked "POWER"
(2, Fig 6.1) is lighted.
No buzzer alarm.
When switched ON, the
Green LED marked "POWER
ON" (2, Fig 6.2 does not
light. Buzzer is OFF. There is
no AC output voltage. Green
indication light on the GFCI
is OFF.
Self monitoring test of
GFCI has failed or GFCI is
defective.
There is no voltage at the
DC input terminals
• The GFCI will be required to be replaced.
Call Technical Support.
• Check the continuity of the battery
input circuit.
• Check that the internal/external battery
fuses are intact. Replace if blown.
• Check that all connections in the battery
input circuit are tight.
Low AC output voltage
(< 120VAC but > 80VAC)
(No buzzer alarm).
AC output voltage is available.
Buzzer alarm is sounded at no
load or, when load is switched
ON. The Green LED marked
"POWER ON" (2, Fig 6.2) is
lighted. Indication light on the
GFCI is Green.
Polarity of the DC input
voltage has been reversed
that has blown the external / internal DC side fuses
(Note: Reverse polarity
may cause permanent
damage. Damage caused
due to reverse polarity is
not covered by warranty)
• AC load is exceeding
Surge Overload of 166%
• Load is approaching
Surge Overload of 166%
during lower DC input
voltage
• Low DC input voltage
alarm
• DC input voltage is 42.0
± 0.5 VDC or lower but
higher than 40.0 ± 0.5
VDC
• Check external and internal fuses. Replace
fuses. If unit does not work, call Technical
Support for repair.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of battery input circuit.
• Reduce load.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
SECTION 11 | Troubleshooting Guide
11.2 PST-600-48 (continued)
ISSUEPOSSIBLE CAUSEREMEDY
There is no AC output voltage.
Buzzer alarm is sounded at no
load or when load is switched
ON. The Green LED marked
"POWER ON" (2, Fig 6.2)
is lighted. GREEN indication
light on the GFCI is OFF. There
is no AC output.
There is no AC output. The
Green LED marked "POWER
ON" (2, FIG 6.2) is lighted.
Buzzer is ON. Green indication light on the GFCI is OFF.
AC output shuts down
completely. Red LED marked
"OVERLOAD" (3, Fig 6.2) is
lighted. Buzzer is ON. The
Green LED marked "POWER
ON" (2, Fig 6.2) is lighted.
Green indication light on the
GFCI is OFF.
• AC output voltage has
been shut down due to
low DC input voltage
• DC input voltage is 40.0
± 0.5 VDC or lower
• Shut-down due to high
input DC voltage
• DC input voltage is 64.0
VDC or higher.
Permanent shut-down
of the AC output due to
continuous overload >
110% - 115% for 2 to 3
sec or due to short circuit
on the AC load circuit. (AC
output voltage is 80VAC
or less for 1 to 1.5 sec)
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
• The AC output voltage will switch ON automatically when the DC input voltage rises to
46.0 ± 0.5 VDC or higher.
• Check that the voltage at the DC input
terminals is less than 64.0 VDC
• Ensure that the maximum charging voltage
of the battery charger / alternator / solar
charge controller is below 64.0 VDC
• Ensure that an unregulated solar panel is
not used to charge a battery. Under cold
ambient temperatures, the output of 48V
nominal solar panel/array may reach > 88
VDC. Ensure that a charge controller is used
between the solar panel and the battery.
• Reduce the load / remove the short circuit
• The load is not suitable as it requires higher
power to operate. Use an inverter with
higher power rating.
• If the unit goes into permanent overload
again after resetting and removing the load
completely, the unit has become defective.
Call Technical support.
NOTE: The unit will be latched in this shutdown condition and will require manual reset.
To reset, switch OFF the power ON/OFF switch
(1, Fig 6.2), wait for 3 minutes and then switch
ON again.
Before switching ON again, remove the cause
of the shut-down.
50 | SAMLEX AMERICA INC.
SECTION 11 | Troubleshooting Guide
11.2 PST-600-48 (continued)
ISSUEPOSSIBLE CAUSEREMEDY
There is no AC output. Buzzer
alarm is sounded. Red LED
marked "OVER TEMP" (4, Fig
6.2) is lighted. The Green LED
marked "POWER ON" (2, Fig
6.2) is lighted. Green indication light on the GFCI is OFF.
There is no AC output. Green
indication on the GFCI is
OFF. The Green LED marked
"POWER ON" (2, Fig 6.2) is
lighted. No buzzer alarm.
Red LED indication on the
GFCI (5c, Fig 6.1) is permanently ON or ashing. The
Green LED indication on the
GFCI bay be ON or OFF. The
Green LED marked "POWER"
(2, Fig 6.1) is lighted. No
buzzer alarm.
Shut-down due to over
temperature because of
fan failure or inadequate
cooling as a result of high
ambient temperature or
insufcient air exchange
• Internal hot spot is at 90
± 5°C or higher
GFCI has tripped due to
leakage or due to Neutral
to Ground bond on the
load side.
Self monitoring text of
GFCI has failed or GFCI is
defective.
Check that the fan is working. If not, the fan
control circuit may be defective. Call
Technical Support.
If the fan is working, check that the ventilation
slots on the suction side and the openings
on the discharge side of the fan are not
obstructed.
If the fan is working and the openings are not
obstructed, check that enough cool replacement air is available. Also check that the ambient air temperature is less than 40ºC.
Reduce the load to reduce the heating effect.
After the cause of overheating is removed and
the internal hot spot cools down to 65 ± 5°C,
the AC output will be restored automatically.
Check load side circuits for leakage or Neutral
to Ground bond. Switch ON the inverter if in
OFF condition. Check that Green LED marked
"POWER ON" (2, Fig 6.2) is lighted. Press Reset
Button on the GFCI to reset the GFCI. On
resetting, the Green indication on the GFCI will
switch ON.
The GFCI will be required to be replaced. Call
Technical Support.
SECTION 12 | Specications
MODEL NO. PST-1500-48PST-600-48
OUTPUT
OUTPUT VOLTAGE 120 VAC ± 3%120 VAC ± 3%
MAXIMUM OUTPUT CURRENT 12.5A5.1A
OUTPUT FREQUENCY 60 Hz ± 1%60 Hz ± 1%
TYPE OF OUTPUT WAVEFORM Pure Sine WavePure Sine Wave
SHORT CIRCUIT SHUTDOWN When output voltage drops to 80 VAC or lower for 1 to 1.5 sec
OVERLOAD SHUTDOWN At overload of 110% to 115% for 2 to 2.5 sec
GROUND FAULT SHUTDOWN Through GFCI outlets (5 to 6 mA leakage)
OVER TEMPERATURE SHUTDOWN 90°C ± 5°C (Sensed at internal hot spot) ; Auto reset at 65°C ± 5°C
REVERSE POLARITY ON
DC INPUT SIDE
External / internal DC sides fuses will blow
REMOTE CONTROL
WIRED REMOTE CONTROL
RC-300 with LCD/LED display
and 7.62m/25 ft cable
(Sold separately)
RC-15A with LED display
and 5m/16.5 ft cable
(Sold separately)
COOLING
FORCED AIR COOLING
2 Temperature controlled fans1 Temperature controlled fan
(Temperature is sensed at internal hot spot ; Fan ON at 55°C ÷ 3°C ;
Fan OFF at 45°C ± 3°C)
COMPLIANCE
EMI / EMC FCC Part 15(B), Class B
ENVIRONMENT
WORKING ENVIRONMENTIndoor use
OPERATING TEMPERATURE RANGE -20 to 40˚C / -4 to 104˚F-20 to 40˚C / -4 to 104˚F
STORAGE TEMPERATURE -30 to 70˚C / -22 to 158˚F-30 to 70˚C / -22 to 158˚F
RELATIVE HUMIDITY 90% non condensing
DIMENSIONS
(W X D X H), MM 263.0 x 468.2 x 105.6238 x 276.2 x 82
(W X D X H), INCHES 10.35 x 18.43 x 4.169.37 x 10.87 x 3.23
WEIGHT
KG 7.12.7
LBS 15.65.9
NOTES:
1. All power ratings are specied for resistive load at Power Factor = 1.
2. All specications given above are at ambient temperature of 25°C / 77°F.
3. Specications are subject to change without notice
52 | SAMLEX AMERICA INC.
SECTION 13 | Warranty
3 YEAR LIMITED WARRANTY
PST-600-48 and PST-1500-48 are manufactured by Samlex America, Inc. (the “Warrantor“) is warranted to be free from defects in workmanship and materials under normal
use and service. The warranty period is 3 years for the United States and Canada, and is
in effect from the date of purchase by the user (the “Purchaser“).
Warranty outside of the United States and Canada is limited to 6 months. For a warranty
claim, the Purchaser should contact the place of purchase to obtain a Return Authorization Number.
The defective part or unit should be returned at the Purchaser’s expense to the authorized location. A written statement describing the nature of the defect, the date of purchase, the place of purchase, and the Purchaser’s name, address and telephone number
should also be included.
If upon the Warrantor’s examination, the defect proves to be the result of defective
material or workmanship, the equipment will be repaired or replaced at the Warrantor’s option without charge, and returned to the Purchaser at the Warrantor’s expense.
(Contiguous US and Canada only)
No refund of the purchase price will be granted to the Purchaser, unless the Warrantor
is unable to remedy the defect after having a reasonable number of opportunities to do
so. Warranty service shall be performed only by the Warrantor. Any attempt to remedy
the defect by anyone other than the Warrantor shall render this warranty void. There
shall be no warranty for defects or damages caused by faulty installation or hook-up,
abuse or misuse of the equipment including exposure to excessive heat, salt or fresh
water spray, or water immersion.
No other express warranty is hereby given and there are no warranties which extend
beyond those described herein. This warranty is expressly in lieu of any other expressed
or implied warranties, including any implied warranty of merchantability, tness for the
ordinary purposes for which such goods are used, or tness for a particular purpose, or
any other obligations on the part of the Warrantor or its employees and representatives.
There shall be no responsibility or liability whatsoever on the part of the Warrantor or
its employees and representatives for injury to any persons, or damage to person or
persons, or damage to property, or loss of income or prot, or any other consequential
or resulting damage which may be claimed to have been incurred through the use or
sale of the equipment, including any possible failure of malfunction of the equipment,
or part thereof. The Warrantor assumes no liability for incidental or consequential damages of any kind.
Samlex America Inc. (the “Warrantor”)
www.samlexamerica.com
NOTES:
54 | SAMLEX AMERICA INC.
NOTES:
Contact
Information
Toll Free Numbers
Ph: 1 800 561 5885
Fax: 1 888 814 5210
Local Numbers
Ph: 604 525 3836
Fax: 604 525 5221
Website
www.samlexamerica.com
USA Shipping Warehouses
Kent, WA
Plymouth, MI
Canadian Shipping Warehouse
Delta, BC
11001-PST-600-1500-48-0821
Email purchase orders to
orders@samlexamerica.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.