UNLESS SPECIFICALLY AGREED TO IN WRITING, SAMLEX AMERICA INC.:
1. MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION
PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
2. ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY
SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK.
Samlex America reserves the right to revise this document and to periodically make changes to the content
hereof without obligation or organization of such revisions or changes.
SAVE THESE INSTRUCTIONS. This manual contains important instructions for models
PST-60S / 100S / 150S / 200S that shall be followed during installation, operation and
maintenance.
The following safety symbols will be used in this manual to highlight safety
and information:
Indicates possibility of physical harm to the user in case of non-compliance.
Indicates possibility of damage to the equipment in case of non-compliance.
Indicates useful supplemental information.
Please read these instructions before installing or operating the unit to prevent personal
injury or damage to the unit.
WARNING!
CAUTION!
INFO
1.2 SAFETY INSTRUCTIONS - GENERAL
Installation and wiring compliance
• Installation and wiring must comply with the Local and National Electrical Codes and
must be done by a certied electrician.
Preventing electrical shock
• Both the output sockets L1 and L2 of the Schuko Receptacle are LIVE/HOT and are
oating with respect to the metal chassis Ground/Earth Ground (there is NO Neutral).
Do not touch! Refer to Section 8.5.1 for details.
• Always connect the grounding connection on the unit to the appropriate grounding
system.
• Disassembly / repair should be carried out by qualied personnel only.
• Disconnect all AC and DC side connections before working on any circuits associated
with the unit. Turning the ON/OFF switch on the unit to OFF position may not entirely
remove dangerous voltages.
• Be careful when touching bare terminals of capacitors. Capacitors may retain high lethal voltages even after the power has been removed. Discharge the capacitors before
working on the circuits.
SECTION 1 | Safety Instructions
Installation environment
• The inverter should be installed indoor only in a well ventilated, cool, dry environment.
• Do not expose to moisture, rain, snow or liquids of any type.
• To reduce the risk of overheating and re, do not obstruct the suction and discharge
openings of the cooling fan.
• To ensure proper ventilation, do not install in a low clearance compartment.
Preventing re and explosion hazards
• Working with the unit may produce arcs or sparks. Thus, the unit should not be used
in areas where there are ammable materials or gases requiring ignition protected
equipment. These areas may include spaces containing gasoline-powered machinery,
fuel tanks, and battery compartments.
Precautions when working with batteries
• Batteries contain very corrosive diluted Sulphuric Acid as electrolyte. Precautions
should be taken to prevent contact with skin, eyes or clothing.
• Batteries generate Hydrogen and Oxygen during charging resulting in evolution of
explosive gas mixture. Care should be taken to ventilate the battery area and follow
the battery manufacturer’s recommendations.
• Never smoke or allow a spark or ame near the batteries.
• Use caution to reduce the risk of dropping a metal tool on the battery. It could spark
or short circuit the battery or other electrical parts and could cause an explosion.
• Remove metal items like rings, bracelets and watches when working with batteries.
The batteries can produce a short circuit current high enough to weld a ring or the
like to metal and, thus, cause a severe burn.
• If you need to remove a battery, always remove the ground terminal (Negative) from
the battery rst. Make sure that all the accessories are off so that you do not cause
a spark.
1.3 SAFETY INSTRUCTIONS - INVERTER RELATED
Preventing Paralleling of the AC Output
The AC output of the unit should never be connected directly to an Electrical Breaker
Panel / Load Centre which is also fed from the utility power / generator. Such a direct
connection may result in parallel operation of the different power sources and AC power
from the utility / generator will be fed back into the unit which will instantly damage
the output section of the unit and may also pose a re and safety hazard. If an Electrical
Breaker Panel / Load Center is fed from this unit and this panel is also required to be fed
from additional alternate AC sources, the AC power from all the AC sources (like the utility
/ generator / this inverter) should rst be fed to an Automatic / Manual Selector Switch
and the output of the Selector Switch should be connected to the Electrical Breaker Panel
/ Load Center.
4 | SAMLEX AMERICA INC.
SECTION 1 | Safety Instructions
!
!
CAUTION!
To prevent possibility of paralleling and severe damage to the unit, never
use a simple jumper cable with a male plug on both ends to connect the
AC output of the unit to a handy wall receptacle in the home / RV /
motorhome / caravan.
Preventing DC Input Over Voltage
It is to be ensured that the DC input voltage of this unit does not exceed 16.5 VDC for
the 12V versions or 33.0 VDC for the 24V versions to prevent permanent damage to the
unit. Please observe the following precautions:
• Ensure that the maximum charging voltage of the external battery charger / alternator / solar charge controller does not exceed 16.5 VDC for the 12V versions or 33.0
VDC for the 24V versions.
• Do not use unregulated solar panels to charge the battery connected to this unit.
Under cold ambient temperatures, the output of the solar panel may reach > 22 VDC
for 12V Battery System and > 44 VDC for the 24V Battery system. Always use a charge
controller between the solar panel and the battery.
• Do not connect this unit to a battery system with a voltage higher than the rated
battery input voltage of the unit [e.g. do not connect the 12V versions to 24V or 48V
battery system or the 24V versions to the 48V Battery System].
• When using Diversion Charge Control Mode in a charge controller, the solar / wind /
hydro source is directly connected to the battery bank. In this case, the controller will
divert excess current to an external load. As the battery charges, the diversion duty
cycle will increase. When the battery is fully charged, all the source energy will ow
into the diversion load if there are no other loads. The charge controller will disconnect the diversion load if the current rating of the controller is exceeded. Disconnection of the diversion load may damage the battery as well as the inverter or other DC
loads connected to the battery due to high voltages generated during conditions of
high winds (for wind generators), high water ow rates (for hydro generators). It is,
therefore, to be ensured that the diversion load is sized correctly to prevent the above
over voltage conditions.
Preventing Reverse Polarity on the Input Side
When making battery connections on the input side, make sure that the polarity of battery connections is correct (Connect the Positive of the battery to the Positive terminal
of the unit and the Negative of the battery to the Negative terminal of the unit). If the
input is connected in reverse polarity, the external DC fuse and the DC fuses inside the
inverter will blow and may also cause permanent damage to the inverter.
CAUTION!
Damage caused by reverse polarity is not covered by warranty.
SECTION 1 | Safety Instructions
Use of External Fuse in DC Input Circuit
Use UL Class T (As per UL Standard UL 248-15 / Type "HRC" as per BS88-2 or as per IEC
60269-2) or equivalent fuse of appropriate capacity within 7" of the battery Positive terminal. This fuse is required to protect DC input cable run from damage due to short circuit
along the length of the cable. Please read instructions under Section 8.4.5 - Installation.
Hard Wiring of AC Output to AC Panelboards in RVs / Motor Homes / Trailers /Campers
WARNING!
RISK OF ELECTRIC SHOCK
When this unit is installed in RV / Motor Homes / Trailers / Campers and hard-
wiring connection is used to feed the AC output of the inverter to the AC
Distribution Panelboard / Load Center in the vehicle, it is to be ensured that
the AC output is fed to the Panel Board through appropriate Residual Current
Detector (RCD) or Ground Fault Circuit Interrupter [GFCI].
SECTION 2 | General Information
2.1. DEFINITIONS
The following denitions are used in this manual for explaining various electrical
concepts, specications and operations:
Peak Value: It is the maximum value of electrical parameter like voltage / current.
RMS (Root Mean Square) Value: It is a statistical average value of a quantity that varies
in value with respect to time. For example, a pure sine wave that alternates between
peak values of Positive 329.22V and Negative 329.22V has an RMS value of 230 VAC.
Also, for a pure sine wave, the RMS value = Peak value ÷ 1.414.
Voltage (V), Volts: It is denoted by “V” and the unit is “Volts”. It is the electrical force
that drives electrical current (I) when connected to a load. It can be DC (Direct Current
– ow in one direction only) or AC (Alternating Current – direction of ow changes periodically). The AC value shown in the specications is the RMS (Root Mean Square) value.
Current (I), Amps, A: It is denoted by “I” and the unit is Amperes – shown as “A”. It is
the ow of electrons through a conductor when a voltage (V) is applied across it.
Frequency (F), Hz: It is a measure of the number of occurrences of a repeating event per
unit time. For example, cycles per second (or Hertz) in a sinusoidal voltage.
Efciency, (
in Watts.
6 | SAMLEX AMERICA INC.
η): This is the ratio of Active Power Output in Watts ÷ Active Power Input
SECTION 2 | General Information
Phase Angle, (φ): It is denoted by “φ” and species the angle in degrees by which the
current vector leads or lags the voltage vector in a sinusoidal voltage. In a purely inductive load, the current vector lags the voltage vector by Phase Angle (φ) = 90°. In a purely
capacitive load, the current vector leads the voltage vector by Phase Angle, (φ) = 90°. In
a purely resistive load, the current vector is in phase with the voltage vector and hence,
the Phase Angle, (φ) = 0°. In a load consisting of a combination of resistances, inductances and capacitances, the Phase Angle (φ) of the net current vector will be > 0° < 90°
and may lag or lead the voltage vector.
Resistance (R), Ohm, Ω: It is the property of a conductor that opposes the ow of current when a voltage is applied across it. In a resistance, the current is in phase with the
voltage. It is denoted by "R" and its unit is "Ohm" - also denoted as "Ω".
Inductive Reactance (X
opposition of a circuit element to a change of electric current or voltage due to that
element's inductance or capacitance. Inductive Reactance (X
of wire in resisting any change of electric current through the coil. It is proportional to
), Capacitive Reactance (XC) and Reactance (X): Reactance is the
L
) is the property of a coil
L
frequency and inductance and causes the current vector to lag the voltage vector by
Phase Angle (φ) = 90°. Capacitive reactance (X
oppose changes in voltage. X
and causes the current vector to lead the voltage vector by Phase Angle (φ) = 90°. The
unit of both X
tance X
tance X
effect is a tendency to cancel each other. Hence, in a circuit containing both inductances
and XC is "Ohm" - also denoted as "Ω". The effects of inductive reac-
L
to cause the current to lag the voltage by 90° and that of the capacitive reac-
L
to cause the current to lead the voltage by 90° are exactly opposite and the net
C
is inversely proportional to the frequency and capacitance
C
) is the property of capacitive elements to
C
and capacitances, the net Reactance (X) will be equal to the difference between the
values of the inductive and capacitive reactances. The net Reactance (X) will be inductive
if X
> XC and capacitive if XC > XL.
L
Impedance, Z: It is the vectorial sum of Resistance and Reactance vectors in a circuit.
Active Power (P), Watts: It is denoted as “P” and the unit is “Watt”. It is the power that
is consumed in the resistive elements of the load. A load will require additional Reactive
Power for powering the inductive and capacitive elements. The effective power required
would be the Apparent Power that is a vectorial sum of the Active and Reactive Powers.
Reactive Power (Q), VAR: Is denoted as “Q” and the unit is VAR. Over a cycle, this power
is alternatively stored and returned by the inductive and capacitive elements of the load.
It is not consumed by the inductive and capacitive elements in the load but a certain
value travels from the AC source to these elements in the (+) half cycle of the sinusoidal
voltage (Positive value) and the same value is returned back to the AC source in the (-)
half cycle of the sinusoidal voltage (Negative value). Hence, when averaged over a span
of one cycle, the net value of this power is 0. However, on an instantaneous basis, this
power has to be provided by the AC source. Hence, the inverter, AC wiring and over cur-
rent protection devices have to be sized based on the combined effect of the Active and
Reactive Powers that is called the Apparent Power.
SECTION 2 | General Information
Apparent (S) Power, VA: This power, denoted by "S", is the vectorial sum of the Active
Power in Watts and the Reactive Power in “VAR”. In magnitude, it is equal to the RMS
value of voltage “V” X the RMS value of current “A”. The Unit is VA. Please note that
Apparent Power VA is more than the Active Power in Watts. Hence, the inverter, AC wiring and over current protection devices have to be sized based on the Apparent Power.
Maximum Continuous Running AC Power Rating: This rating may be specied as “Active Power” in Watts (W) or “Apparent Power” in Volt Amps (VA). It is normally specied in “Active Power (P)” in Watts for Resistive type of loads that have Power Factor
=1. Reactive types of loads will draw higher value of “Apparent Power” that is the sum
of “Active and Reactive Powers”. Thus, AC power source should be sized based on the
higher “Apparent Power” Rating in (VA) for all Reactive Types of AC loads. If the AC
power source is sized based on the lower “Active Power” Rating in Watts (W), the AC
power source may be subjected to overload conditions when powering Reactive Type of
loads.
Surge Power Rating: During start up, certain loads require considerably higher surge of power
for short duration (lasting from tens of millisecs to few seconds) as compared to their Maximum Continuous Running Power Rating. Some examples of such loads are given below:
• Electric Motors: At the moment when an electric motor is powered ON, the rotor is
stationary (equivalent to being “Locked”), there is no “Back EMF” and the windings
draw a very heavy surge of starting current (Amperes) called “Locked Rotor Amperes” (LRA) due to low DC resistance of the windings. For example, in motor driven
loads like Air-conditioning and Refrigeration Compressors and in Well Pumps (using
Pressure Tank), the Starting Surge Current / LRA may be as high as 10 times its rated
Full Load Amps (FLA) / Maximum Continuous Running Power Rating. The value and
duration of the Starting Surge Current / LRA of the motor depends upon the winding
design of the motor and the inertia / resistance to movement of mechanical load
being driven by the motor. As the motor speed rises to its rated RPM, “Back EMF”
proportional to the RPM is generated in the windings and the current draw reduces
proportionately till it draws the running FLA / Maximum Continuous Running Power
Rating at the rated RPM.
• Transformers (e.g. Isolation Transformers, Step-up / Step-down Transformers, Power Trans-former in Microwave Oven etc.): At the moment when AC power is supplied to a transformer,
the transformer draws very heavy surge of “Magnetization Inrush Current” for a few millisecs
that can reach up to 10 times the Maximum Continuous Rating of the Transformer.
• Devices like Infrared Quartz Halogen Heaters (also used in Laser Printers) / Quartz Halogen Lights / Incandescent Light Bulbs using Tungsten heating elements: Tungsten
has a very high Positive Temperature Coefcient of Resistance i.e. it has lower resistance when cold and higher resistance when hot. As Tungsten heating element will be
cold at the time of powering ON, its resistance will be low and hence, the device will
draw very heavy surge of current with consequent very heavy surge of power with a
value of up to 8 times the Maximum Continuous Running AC Power.
8 | SAMLEX AMERICA INC.
SECTION 2 | General Information
• AC to DC Switched Mode Power Supplies (SMPS): This type of power supply is used as
stand-alone power supply or as front end in all electronic devices powered from Utility / Grid e.g. in audio/video/ computing devices and battery chargers (Please see Section 4 for more details on SMPS). When this power supply is switched ON, its internal
input side capacitors start charging resulting in very high surge of Inrush Current for a
few millisecs (Please see Fig 4.1). This surge of inrush current / power may reach up to
15 times the Continuous Maximum Running Power Rating. The surge of inrush current
/ power will, however, be limited by the Surge Power Rating of the AC source.
Power Factor, (PF): It is denoted by “PF” and is equal to the ratio of the Active Power
(P) in Watts to the Apparent Power (S) in VA. The maximum value is 1 for resistive types
of loads where the Active Power (P) in Watts = the Apparent Power (S) in VA. It is 0 for
purely inductive or purely capacitive loads. Practically, the loads will be a combination of
resistive, inductive and capacitive elements and hence, its value will be > 0 <1. Normally
it ranges from 0.5 to 0.8 e.g. (i) AC motors (0.4 to 0.8), (ii) Transformers (0.8) (iii) AC to
DC Switch Mode Power Supplies (0.5 to 0.6) etc.
Load: Electrical appliance or device to which an electrical voltage is fed.
Linear Load: A load that draws sinusoidal current when a sinusoidal voltage is fed to it.
Examples are, incandescent lamp, heater, electric motor, etc.
Non-Linear Load: A load that does not draw a sinusoidal current when a sinusoidal voltage is fed to it. For example, non-power factor corrected Switched Mode Power Supplies
(SMPS) used in computers, audio video equipment, battery chargers, etc.
Resistive Load: A device or appliance that consists of pure resistance (like lament
lamps, cook tops, toaster, coffee maker etc.) and draws only Active Power (Watts) from
the inverter. The inverter can be sized based on the Active Power rating (Watts) of
resistive type of loads without creating overload (except for resistive type of loads with
Tungsten based heating element like in Incandescent Light Bulbs, Quartz Halogen Lights
and Quartz Halogen Infrared Heaters. These require higher starting surge power due to
lower resistance value when the heating element is cold).
Reactive Load: A device or appliance that consists of a combination of resistive, inductive
and capacitive elements (like motor driven tools, refrigeration compressors, microwaves,
computers, audio/ video etc.). The Power Factor of this type of load is <1 e.g. AC motors
(PF=0.4 to 0.8), Transformers (PF=0.8), AC to DC Switch Mode Power Supplies (PF=0.5
to 0.6) etc. These devices require Apparent Power (VA) from the AC power source. The
Apparent Power is a vectorial sum of Active Power (Watts) and Reactive Power (VAR).
The AC power source has to be sized based on the higher Apparent Power (VA) and also
based on the Starting Surge Power.
SECTION 2 | General Information
2.2 OUTPUT VOLTAGE WAVEFORMS
V
= 325.22V
PEAK
V
= 280 to 320V
360
320
280
240
VOLTS (+)VOLTS (–)
200
160
120
80
40
0
40
120
160
200
240
280
320
360
80
Pure Sine Wave
crosses Zero Volt
instantaneously
TIME
Fig. 2.1: Pure and Modied Sine Waveforms for 230 VAC, 50/60 Hz
The output waveform of the Samlex PST series inverters is a Pure Sine Wave like the
waveform of Utility / Grid Power. Please see Sine Wave represented in the Fig. 2.1 that
also shows Modied Sine Waveform for comparison.
PEAK
V
20.00 ms for 50 Hz
16.66 ms for 60 Hz
= 230 VAC
RMS
Modied Sine
Wave sits at
ZERO for some
time and then
rises or falls
Sine Wave
Modied Sine Wave
In a Sine Wave, the voltage rises and falls smoothly with a smoothly changing phase
angle and also changes its polarity instantly when it crosses 0 Volts. In a Modied Sine
Wave, the voltage rises and falls abruptly, the phase angle also changes abruptly and
it sits at zero V for some time before changing its polarity. Thus, any device that uses a
control circuitry that senses the phase (for voltage / speed control) or instantaneous zero
voltage crossing (for timing control) will not work properly from a voltage that has a
Modied Sine Waveform.
Also, as the Modied Sine Wave is a form of Square Wave, it is comprised of multiple
Sine Waves of odd harmonics (multiples) of the fundamental frequency of the Modied
Sine Wave. For example, a 50 Hz Modied Sine Wave will consist of Sine Waves with
odd harmonic frequencies of 3rd (150 Hz), 5th (250 Hz), 7th (350 Hz) and so on. The high
frequency harmonic content in a Modied Sine Wave produces enhanced radio interference, higher heating effect in inductive loads like microwaves and motor driven devices
like hand tools, refrigeration / air-conditioning compressors, pumps etc. The higher
frequency harmonics also produce overloading effect in low frequency capacitors due to
lowering of their capacitive reactance by the higher harmonic frequencies. These capacitors are used in ballasts for uorescent lighting for Power Factor improvement and in
single-phase induction motors as Start and Run Capacitors. Thus, Modied and Square
Wave inverters may shut down due to overload when powering these devices.
10 | SAMLEX AMERICA INC.
SECTION 2 | General Information
i
2.3 ADVANTAGES OF PURE SINE WAVE INVERTERS
• The output waveform is a Sine Wave with very low harmonic distortion and cleaner
power like Utility / Grid supplied electricity.
• Inductive loads like microwaves, motors, transformers etc. run faster, quieter
and cooler.
• More suitable for powering uorescent lighting xtures containing Power Factor
Improvement Capacitors and single phase motors containing Start and Run Capacitors
• Reduces audible and electrical noise in fans, uorescent lights, audio ampliers, TV,
fax and answering machines, etc.
• Does not contribute to the possibility of crashes in computers, weird print outs and
glitches in monitors.
2.4 SOME EXAMPLES OF DEVICES THAT MAY NOT WORK PROPERLY WITH
MODIFIED SINE WAVE AND MAY ALSO GET DAMAGED ARE GIVEN BELOW:
• Laser printers, photocopiers, and magneto-optical hard drives.
• Built-in clocks in devices such as clock radios, alarm clocks, coffee makers, bread-makers, VCR, microwave ovens etc. may not keep time correctly.
• Output voltage control devices like dimmers, ceiling fan / motor speed control may
not work properly (dimming / speed control may not function).
• Sewing machines with speed / microprocessor control.
• Transformer-less capacitive input powered devices like (i) Razors, ashlights, nightlights, smoke detectors etc. (ii) Some re-chargers for battery packs used in hand power
tools. These may get damaged. Please check with the manufacturer of these types of
devices for suitability.
• Devices that use radio frequency signals carried by the AC distribution wiring.
• Some new furnaces with microprocessor control / Oil burner primary controls.
• High intensity discharge (HID) lamps like Metal Halide Lamps. These may get dam-
aged. Please check with the manufacturer of these types of devices for suitability.
• Some uorescent lamps / light xtures that have Power Factor Correction Capacitors.
The inverter may shut down indicating overload.
• Induction Cooktops
2.5 POWER RATING OF INVERTERS
INFO
For proper understanding of explanations given below, please refer to deni-
tions of Active / Reactive / Apparent / Continuous / Surge Powers, Power Factor,
and Resistive / Reactive Loads at Section 2.1 under “DEFINITIONS”.
i
SECTION 2 | General Information
The power rating of inverters is specied as follows:
• Maximum Continuous Running Power Rating
• Surge Power Rating to accommodate high, short duration surge of power required
during start up of certain AC appliances and devices.
Please read details of the above two types of power ratings in Section 2.1 under
“DEFINITIONS”
INFO
The manufacturers’ specication for power rating of AC appliances and devices
indicates only the Maximum Continuous Running Power Rating. The high,
short duration surge of power required during start up of some specic types
of devices has to be determined by actual testing or by checking with the
manufacturer. This may not be possible in all cases and hence, can be guessed
at best, based on some general Rules of Thumb.
Table 2.1 provides a list of some common AC appliances / devices that require high, short
duration surge of power during start up. An “Inverter Sizing Factor” has been recommended against each which is a Multiplication Factor to be applied to the Maximum
Continuous Running Power Rating (Active Power Rating in Watts) of the AC appliance
/ device to arrive at the Maximum Continuous Running Power Rating of the inverter
(Multiply the Maximum Continuous Running Power Rating (Active Power Rating in
Watts) of the appliance / device by recommended Sizing Factor to arrive at the Maximum Continuous Running Power Rating of the inverter.
TABLE 2.1: INVERTER SIZING FACTOR
Type of Device or Appliance
Air Conditioner / Refrigerator / Freezer (Compressor based)5
Air Compressor4
Sump Pump / Well Pump / Submersible Pump3
Dishwasher / Clothes Washer3
Microwave (where rated output power is the cooking power)2
Furnace Fan3
Industrial Motor3
Portable Kerosene / Diesel Fuel Heater3
Circular Saw / Bench Grinder3
Incandescent / Halogen / Quartz Lamps3
Laser Printer / Other Devices using Infrared Quartz Halogen Heaters4
Switch Mode Power Supplies (SMPS): no Power Factor correction2
Photographic Strobe / Flash Lights4 (See Note 2)
12 | SAMLEX AMERICA INC.
Inverter
Sizing Factor
(See note 1)
SECTION 2 | General Information
NOTES FOR TABLE 2.1
1. Multiply the Maximum Continuous Running Power Rating (Active Power Rating in
Watts) of the appliance / device by the recommended Sizing Factor to arrive at the
Maximum Continuous Running Power Rating of the inverter.
2. For photographic strobe / ash unit, the Surge Power Rating of the inverter should be
> 4 times the Watt Sec rating of photographic strobe / ash unit.
SECTION 3 | EMC (EMI / EMS) Compliance
3.1 EMC (EMI / EMS) COMPLIANCE
These inverters contain internal switching devices that generate conducted and radiated
electromagnetic interference (EMI). The EMI is unintentional and cannot be entirely
eliminated. The magnitude of EMI is, however, limited by circuit design to acceptable
levels as per limits laid down in European Standard EN 55022, Class B. These limits are
designed to provide reasonable protection against harmful interference when the
equipment is operated in business / commercial / industrial environments. These inverters can conduct and radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio communications.
The unit complies with European EMC Directive 2014/30/EU. Please see specications at
Section 12 for relevant European Standards.
3.2 REDUCING EMI THROUGH PROPER INSTALLATION
The effects of EMI will also depend upon a number of factors external to the inverter
like proximity of the inverter to the EMI receptors, types and quality of connecting wires
and cables etc. EMI due to factors external to the inverter may be reduced as follows:
- Ensure that the inverter is rmly grounded to the ground system of the building or
the vehicle
- Locate the inverter as far away from the EMI receptors like radio, audio and video
devices as possible
- Keep the DC side wires between the battery and the inverter as short as possible.
- Do NOT keep the battery wires far apart. Keep them taped together to reduce their
inductance and induced voltages. This reduces ripple in the battery wires and improves performance and efciency.
- Shield the DC side wires with metal sheathing / copper foil / braiding:
- Use coaxial shielded cable for all antenna inputs (instead of 300 ohm twin leads)
- Use high quality shielded cables to attach audio and video devices to one another
- Limit operation of other high power loads when operating audio / video equipment
SECTION 4 | Powering Direct / Embedded Switch
Mode Power Supplies (SMPS)
4.1 CHARACTERISTICS OF SWITCHED MODE POWER SUPPLIES (SMPS)
Switch Mode Power Supplies (SMPS) are extensively used to convert the incoming AC
power into various voltages like 3.3V, 5V, 12V, 24V etc. that are used to power various devices and circuits used in electronic equipment like battery chargers, computers,
audio and video devices, radios etc. SMPS use large capacitors in their input section for
ltration. When the power supply is rst turned on, there is a very large inrush current drawn by the power supply as the input capacitors are charged (The capacitors act
almost like a short circuit at the instant the power is turned on). The inrush current at
turn-on is several to tens of times larger than the rated RMS input current and lasts for
a few milliseconds. An example of the input voltage versus input current waveforms is
given in Fig. 4.1. It will be seen that the initial input current pulse just after turn-on is >
15 times larger than the steady state RMS current. The inrush dissipates in around 2 or 3
cycles i.e. in around 33 to 50 milliseconds for 60 Hz sine wave.
Further, due to the presence of high value of input lter capacitors, the current drawn
by an SMPS (With no Power Factor correction) is not sinusoidal but non-linear as shown
in Fig 4.2. The steady state input current of SMPS is a train of non-linear pulses instead
of a sinusoidal wave. These pulses are two to four milliseconds duration each with a very
high Crest Factor of around 3 (Crest Factor = Peak value ÷ RMS value).
Many SMPS units incorporate “Inrush Current Limiting”. The most common method is
the NTC (Negative Temperature Coefcient) resistor. The NTC resistor has a high resistance when cold and a low resistance when hot. The NTC resistor is placed in series with
the input to the power supply. The cold resistance limits the input current as the input
capacitors charge up. The input current heats up the NTC and the resistance drops
during normal operation. However, if the power supply is quickly turned off and back
on, the NTC resistor will be hot so its low resistance state will not prevent an inrush
current event.
The inverter should, therefore, be sized adequately to withstand the high inrush current
and the high Crest Factor of the current drawn by the SMPS. Normally, inverters have
short duration Surge Power Rating of 2 times their Maximum Continuous Power Rating.
Hence, it is recommended that for purposes of sizing the inverter to accommodate
Crest Factor of 3, the Maximum Continuous Power Rating of the inverter should be > 2
times the Maximum Continuous Power Rating of the SMPS. For example, an SMPS rated
at 100 Watts should be powered from an inverter that has Maximum Continuous Power
Rating of > 200 Watts.
14 | SAMLEX AMERICA INC.
NOTE: Voltage
SECTION 4 | Powering Direct / Embedded Switch
Mode Power Supplies (SMPS)
and current scales
are dierent
Input voltage
Peak inrush
current
Inrush current
Fig 4.1: Inrush current in an SMPS
Non-linear
Input Current
Voltage (+)Voltage (–)
Current (+)Current (–)
Pulse
Rated steady state
input RMS current
Peak Current
RMS Current
NOTE: Voltage
and current scales
are dierent
Input Sine
Wave Voltage
TIME
Fig. 4.2: High Crest Factor of current drawn by SMPS
Crest Factor = Peak Current = 3
RMS Current
SECTION 5 | Principle of Operation
5.1 GENERAL
These inverters convert DC battery voltage to AC voltage with an RMS (Root Mean
Square) value of 230 VAC, 50/60 Hz.
5.2 PURE SINE WAVE OUTPUT WAVEFORM
The waveform of the AC voltage is a pure Sine Waveform that is same as the waveform
of Grid / Utility power (Supplementary information on pure Sine Waveform and its
advantages are discussed in Sections 2.2 to 2.4).
Fig. 5.1 below species the characteristics of 230 VAC, 50 Hz/60 Hz pure Sine Waveform.
The instantaneous value and polarity of the voltage varies cyclically with respect to time.
For example, in one cycle in a 230 VAC, 50 Hz/60 Hz system, it slowly rises in the Positive direction from 0V to a peak Positive value “Vpeak” = + 325.22V, slowly drops to 0V, changes
the polarity to Negative direction and slowly increases in the Negative direction to a peak
Negative value “Vpeak” = - 325.22V and then slowly drops back to 0V. There are 50 such
cycles in 1 sec in 50 Hz and 60 in 60 Hz. Cycles per second is called the “Frequency” and is
also termed “Hertz (Hz)”. The Time Period of 1 Cycle is 20.00 ms for 50 Hz and 16.66 ms
for 60 Hz.
Peak Positive Voltage
PEAK = + 325.22V
+ V
V
Voltage (+)Voltage (–)
RMS = 230 VAC
0V
20.00 ms for 50 Hz
16.66 ms for 60 Hz
TIME
Peak Negative Voltage
PEAK = - 325.22V
- V
Fig. 5.1: 230 VAC, 50/60 Hz Pure Sine Waveform
5.3 PRINCIPLE OF OPERATION
The voltage conversion takes place in two stages. In the rst stage, the DC voltage of
the battery is converted to a high voltage DC using high frequency switching and Pulse
Width Modulation (PWM) technique. In the second stage, the high voltage DC is converted to 230 VAC, 50/60 Hz sine wave AC again using PWM technique. This is done by
using a special wave shaping technique where the high voltage DC is switched at a high
frequency and the pulse width of this switching is modulated with respect to a reference sine wave.
16 | SAMLEX AMERICA INC.
SECTION 6 | Layout
6
6. LAYOUT
10
PST-60S: Front
NEG – POS +
WARNING:
REVERSE POLARITY WILL DAMAGE UNIT
LEGEND
1. Power ON/OFF Switch
2. Green LED - Power Ouptut Status
3. Red LED - Overload
11
4. Red LED - Over temperature
5. “Schuko” type AC outlet
6. Cooling Fan Opening
7. Grounding Terminal - M5
8. Negative (-) DC Input Terminal
9. Positive (+) DC Input Terminal
10. Modular Jack for RC-15 Remote
Control (Bottom of Unit)
11. 50 / 60 Hz Selector Switch
Cylindrical hole
diameter 11 mm
}
with M8 Set Screw
PST-60S: Back
6
Fig. 6.1: Layout of PST-60S-12E, PST-60S-24E
10
PST-100S: Front
PST-100S: Back
NEG – POS +
WARNING:
REVERSE POLARITY WILL DAMAGE UNIT
Fig. 6.2: Layout of PST-100S-12E, PST-100S-24E
LEGEND
1. Power ON/OFF Switch
2. Green LED - Power
Output Status
3. Red LED - Over load
11
4. Red LED - Over Temperature
5. Schuko Type AC Output
Receptacle
6. Opening for Cooling Fan
7. Grounding Terminal - M5
8. DC Input “-”
9. DC Input “+”
10. Remote Control Jack
(Bottom of the unit)
11. 50 / 60 Hz Selector Switch
Cylindrical hole
diameter 11 mm
}
with M8 Set Screw
SECTION 6 | Layout
i
115432110
PST-200S, PST-150S: Front
9
REVERSE POLARITY WILL DAMAGE UNIT
NEG –POS +
WARNING:
8
LEGEND
1. Power ON/OFF Switch
2. Green LED - Power Output Status
3. Red LED - Over Load
4. Red LED - Over Temperature
5. “Schuko” Type AC Outlets
6. Cooling Fan Opening
7. Grounding Terminal - cylindrical
hole diameter 8 mm and M8 Set
Screw
8. DC Input “-”
9. DC Input “+”
10. Remote Control Jack
11. 50 / 60 Hz Selector Switch
Cylindrical hole
diameter 11 mm
}
with M8 Set Screw
6
PST-200S, PST-150S: Back
7
6
Fig. 6.3: Layout of PST-150S-12E, PST--150S-24E, PST-200S-12E, PST--200S-24E
SECTION 7 | General Information on Lead Acid
Batteries
7.1 GENERAL
INFO
For complete background information on Lead Acid Batteries and charging
process, please visit www.samlexamerica.com > support > white papers >
White Paper - Batteries, Chargers and Alternators.
Lead-acid batteries can be categorized by the type of application:
1. Automotive service - Starting/Lighting/Ignition (SLI, a.k.a. cranking), and
2. Deep cycle service.
Deep Cycle Lead Acid Batteries of appropriate capacity are recommended for powering
of inverters.
18 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
7.2 DEEP CYCLE LEAD ACID BATTERIES
Deep cycle batteries are designed with thick-plate electrodes to serve as primary power
sources, to have a constant discharge rate, to have the capability to be deeply discharged up
to 80 % capacity and to repeatedly accept recharging. They are marketed for use in recreation vehicles (RV), boats and electric golf carts – so they may be referred to as RV batteries,
marine batteries or golf cart batteries. Use Deep Cycle batteries for powering these inverters.
7.3 RATED CAPACITY SPECIFIED IN AMPERE-HOUR (Ah)
Battery capacity “C” is specied in Ampere-hours (Ah). An Ampere is the unit of measurement for electrical current and is dened as a Coulomb of charge passing through an electrical conductor in one second. The Capacity “C” in Ah relates to the ability of the battery to
provide a constant specied value of discharge current (also called “C-Rate”: See Section 7.6)
over a specied time in hours before the battery reaches a specied discharged terminal
voltage (Also called “End Point Voltage”) at a specied temperature of the electrolyte. As a
benchmark, the automotive battery industry rates batteries at a discharge current or C-Rate
of C/20 Amperes corresponding to 20 Hour discharge period. The rated capacity “C” in Ah
in this case will be the number of Amperes of current the battery can deliver for 20 Hours at
80ºF (26.7ºC) till the voltage drops to 1.75V / Cell. i.e. 10.5V for 12V battery, 21V for 24V battery and 42V for a 48V battery. For example, a 100 Ah battery will deliver 5A for 20 Hours.
7.4 RATED CAPACITY SPECIFIED IN RESERVE CAPACITY (RC)
Battery capacity may also be expressed as Reserve Capacity (RC) in minutes typically for
automotive SLI (Starting, Lighting and Ignition) batteries. It is the time in minutes a
vehicle can be driven after the charging system fails. This is roughly equivalent to the
conditions after the alternator fails while the vehicle is being driven at night with the
headlights on. The battery alone must supply current to the headlights and the computer/ignition system. The assumed battery load is a constant discharge current of 25A.
Reserve capacity is the time in minutes for which the battery can deliver 25 Amperes at
80ºF (26.7ºC) till the voltage drops to 1.75V / Cell i.e. 10.5V for 12V battery, 21V for 24V
battery and 42V for 48V battery.
Approximate relationship between the two units is:
Capacity “C” in Ah = Reserve Capacity in RC minutes x 0.6
7.5 TYPICAL BATTERY SIZES
The Table 7.1 below shows details of some popular battery sizes:
Electrical energy is stored in a cell / battery in the form of DC power. The value of the
stored energy is related to the amount of the active materials pasted on the battery
plates, the surface area of the plates and the amount of electrolyte covering the plates.
As explained above, the amount of stored electrical energy is also called the Capacity of
the battery and is designated by the symbol “C”.
The time in Hours over which the battery is discharged to the “End Point Voltage” for
purposes of specifying Ah capacity depends upon the type of application. Let us denote
this discharge time in hours by “T”. Let us denote the discharge current of the battery
as the “C-Rate”. If the battery delivers a very high discharge current, the battery will be
discharged to the “End Point Voltage” in a shorter period of time. On the other hand,
if the battery delivers a lower discharge current, the battery will be discharged to the
“End Point Voltage” after a longer period of time. Mathematically:
EQUATION 1: Discharge current “C-Rate” = Capacity “C” in Ah ÷ Discharge Time “T”
Table 7.2 below gives some examples of C-Rate specications and applications:
TABLE 7.2: DISCHARGE CURRENT RATES - “C-RATES”
Hours of discharge time “T” till
the “End Point Voltage”
0.5 Hrs.2C200A
1 Hrs.1C100A
5 Hrs. (Inverter application)C/5 or 0.2C20A
8 Hrs. (UPS application)C/8 or 0.125C12.5A
10 Hrs. (Telecom application)C/10 or 0.1C10A
20 Hrs. (Automotive application)C/20 or 0.05C5A
100 Hrs.C/100 or 0.01C1A
NOTE:
When a battery is discharged over a shorter time, its specied “C-Rate” discharge current will
be higher. For example, the “C-Rate” discharge current at 5 Hour discharge period i.e. C/5 Amps will
be 4 times higher than the “C-Rate” discharge current at 20 Hour discharge period i.e. C/20 Amps.
"C-Rate" Discharge Current in Amps =
Capacity "C" in Ah ÷ Discharge Time
"T" in Hrs.
Example of C-Rate
Discharge Currents
for 100 Ah battery
7.7 CHARGING / DISCHARGING CURVES
Fig. 7.1 shows the charging and discharging characteristics of a typical 12V / 24V Lead Acid
battery at electrolyte temperature of 80°F / 26.7°C. The curves show the % State of Charge
(X-axis) versus terminal voltage (Y-axis) during charging and discharging at different C-Rates.
Please note that X-axis shows % State of Charge. State of Discharge will be = 100% - %
State of Charge. These curves will be referred to in the subsequent explanations.
20 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
Lead-Acid Battery Chart - 80˚F / 26.7˚C
24V 12V
16.5
33.0
16.0
32.0
15.5
31.0
15.0
30.0
14.5
29.0
14.0
28.0
13.5
27.0
13.0
26.0
12.5
25.0
Battery Voltage in VDC
12.0
24.0
11.5
23.0
11.0
22.0
10.5
21.0
10.0
20.0
9.5
19.0
9.0
18.0
0 10 20 30 40 50 60 70 80 90 100 110 120 130
CHARGE
C/100
C/20
C/10
C/5
C/3
Battery State of Charge in Percent (%)
C/5
C/10
C/20
C/40
DISCHARGE
Fig. 7.1: Charging / Discharging Curves for 12V / 24V Lead Acid Battery
7.8 REDUCTION IN USABLE CAPACITY AT HIGHER DISCHARGE RATES –
TYPICAL IN INVERTER APPLICATION
As stated above, the rated capacity of the battery in Ah is normally applicable at a discharge rate of 20 Hours. As the discharge rate is increased as in cases where the inverters
are driving higher capacity loads, the usable capacity reduces due to “Peukert Effect”.
This relationship is not linear but is more or less according to the Table 7.3.
TABLE 7.3 BATTERY CAPACITY VERSUS RATE OF DISCHARGE – C-RATE
C-Rate Discharge CurrentUsable Capacity (%)
C/20100%
C/1087%
C/883%
Table continues on the next page
SECTION 7 | General Information on Lead Acid
Batteries
TABLE 7.3 BATTERY CAPACITY VERSUS RATE OF DISCHARGE – C-RATE
(Continued from the previous page)
C-Rate Discharge CurrentUsable Capacity (%)
C/675%
C/570%
C/360%
C/250%
1C40%
Table 7.3 shows that a 100 Ah capacity battery will deliver 100% (i.e. full 100 Ah) capacity
if it is slowly discharged over 20 Hours at the rate of 5 Amperes (50W output for a 12V
inverter and 100W output for a 24V inverter). However, if it is discharged at a rate of 50
Amperes (500W output for a 12V inverter and 1000W output for a 24V inverter) then
theoretically, it should provide 100 Ah ÷ 50 = 2 Hours. However, Table 7.3 shows that for 2
Hours discharge rate, the capacity is reduced to 50% i.e. 50 Ah. Therefore, at 50 Ampere
discharge rate (500W output for a 12V inverter and 1000W output for a 24V inverter) the
battery will actually last for 50 Ah ÷ 50 Amperes = 1 Hour.
7.9 STATE OF CHARGE (SOC) OF A BATTERY – BASED ON
“STANDING VOLTAGE”
The “Standing Voltage” of a battery under open circuit conditions (no load connected
to it) can approximately indicate the State of Charge (SOC) of the battery. The “Standing Voltage” is measured after disconnecting any charging device(s) and the battery
load(s) and letting the battery “stand” idle for 3 to 8 hours before the voltage measurement is taken. Table 7.4 shows the State of Charge versus Standing Voltage for a typical
12V/24V battery system at 80°F (26.7ºC).
TABLE 7.4: STATE OF CHARGE VERSUS STANDING VOLTAGE
Percentage of
Full Charge
100%2.105V12.63V25.26V
90%2.10V12.6V25.20V
80%2.08V12.5V25.00V
70%2.05V12.3V24.60V
60%2.03V12.2V24.40V
50%2.02V12.1V24.20V
30%1.97V11.8V23.60V
20%1.95V11.7V23.40V
10%1.93V11.6V23.20V
0%= / < 1.93V= / < 11.6V= / < 23.20V
Standing Voltage
of Individual Cells
Standing Voltage of
12V Battery
Standing Voltage
of 24V Battery
22 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
Check the individual cell voltages / specic gravity. If the inter cell voltage difference is
more than a 0.2V, or the specic gravity difference is 0.015 or more, the cells will require
equalization. Please note that only the non-sealed / vented / ooded / wet cell batteries
are equalized. Do not equalize sealed / VRLA type of AGM or Gel Cell Batteries.
7.10 STATE OF DISCHARGE OF A LOADED BATTERY – LOW BATTERY /
DC INPUT VOLTAGE ALARM AND SHUTDOWN IN INVERTERS
Most inverter hardware estimate the State of Discharge of the loaded battery by measuring the voltage at the inverter’s DC input terminals (considering that the DC input cables
are thick enough to allow a negligible voltage drop between the battery and the inverter).
Inverters are provided with a buzzer alarm to warn that the loaded battery has been
deeply discharged to around 80% of the rated capacity. Normally, the buzzer alarm is
triggered when the voltage at the DC input terminals of the inverter has dropped to
around 10.5V for a 12V battery or 21V for 24V battery at C-Rate discharge current of
C/5 Amps and electrolyte temp. of 80°F. The inverter is shut down if the terminal voltage
at C/5 discharge current falls further to 10V for 12V battery (20V for 24V battery).
The State of Discharge of a battery is estimated based on the measured terminal voltage
of the battery. The terminal voltage of the battery is dependent upon the following:
- Temperature of the battery electrolyte: Temperature of the electrolyte affects the
electrochemical reactions inside the battery and produces a Negative Voltage
Coefcient – during charging / discharging, the terminal voltage drops with rise in
temperature and rises with drop in temperature.
- The amount of discharging current or “C-Rate”: A battery has non linear internal
resistance and hence, as the discharge current increases, the battery terminal voltage
decreases non-linearly.
The discharge curves in Fig. 7.1 show the % State of Charge versus the terminal voltage
of typical battery under different charge /discharge currents, i.e. “C-Rates” and xed
temperature of 80°F.
NOTE: The X-Axis of the curves shown in Fig 7.1 indicates the percentage State of
Charge. % State of Discharge should be converted to % State of Charge using the
formula given below:
• % State of Charge = 100% - % State of Discharge
7.11 LOW DC INPUT VOLTAGE ALARM IN INVERTERS
As stated earlier, the buzzer alarm is triggered when the voltage at the DC input terminals of the inverter has dropped to around 10.5V for a 12V battery (21V for 24V battery)
at C-Rate discharge current of C/5 Amps. Please note that the terminal voltage relative
to a particular of State Discharge decreases with the rise in the value of the discharge
current. For example, terminal voltages for a State of Discharge of 80% (State of Charge
of 20%) for various discharge currents will be as given at Table 7.5 (Refer to Fig 7.1 for
parameters and values shown in Table 7.5):
SECTION 7 | General Information on Lead Acid
Batteries
TABLE 7.5 TERMINAL VOLTAGE AND SOC OF LOADED BATTERY
Discharge Current:
C-Rate
C/3 A10.45V20.9V09.50V19.0V
C/5 A10.90V21.8V10.30V20.6V
C/10 A11.95V23.9V11.00V22.0V
C/20 A11.85V23.7V11.50V23.0V
C/100 A12.15V24.3V11.75V23.5V
In the example given above, the 10.5V / 21.0V Low Battery / DC Input Alarm would trigger at around 80% discharged state (20% SOC) when the C-Rate discharge current is C/5
Amps. However, for lower C-Rate discharge current of C/10 Amps and lower, the battery
will be almost completely discharged when the alarm is sounded. Hence, if the C-Rate
discharge current is lower than C/5 Amps, the battery may have completely discharged
by the time the Low DC Input Alarm is sounded.
7.12 LOW DC INPUT VOLTAGE SHUT-DOWN IN INVERTERS
As explained above, at around 80% State of Discharge of the battery at C-Rate discharge current of around C/5 Amps, the Low DC Input Voltage Alarm is sounded at
around 10.5V for a 12V battery (at around 21V for 24V battery) to warn the user to
disconnect the battery to prevent further draining of the battery. If the load is not disconnected at this stage, the batteries will be drained further to a lower voltage and to a
completely discharged condition that is harmful for the battery and for the inverter.
Terminal Voltage at 80% State
of Discharge (20% SOC)
12V24V12V24V
Terminal Voltage When Completely
Discharged (0% SOC)
Inverters are normally provided with a protection to shut down the output of the inverter
if the DC voltage at the input terminals of the inverter drops below a threshold of around
10V for a 12V battery (20V for 24V battery). Referring to the Discharge Curves given in
Fig 7.1, the State of Discharge for various C-Rate discharge currents for battery voltage of
10V / 20V is as follows: (Please note that the X-Axis of the curves shows the % of State of
Charge. The % State od Discharge has to be converted to the % State of Charge using the
formula: % State of Charge = 100% - % State of Discharge):
- 85% State of Discharge (15% State of Charge) at very high C-rate discharge
current of C/3 Amps.
- 100% State of Discharge (0 % State of Charge) at high C-Rate discharge
current of C/5 Amps.
- 100% discharged (0% State of charge) at lower C-rate Discharge current of C/10 Amps.
It is seen that at DC input voltage of 10V / 20V, the battery is completely discharged for
C-rate discharge current of C/5 and lower.
24 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
In view of the above, it may be seen that a xed Low DC Input Voltage Alarm is not useful.
Temperature of the battery further complicates the situation. All the above analysis is based
on battery electrolyte temperature of 80°F. The battery capacity varies with temperature.
Battery capacity is also a function of age and charging history. Older batteries have lower
capacity because of shedding of active materials, sulfation, corrosion, increasing number of
charge / discharge cycles etc. Hence, the State of Discharge of a battery under load cannot
be estimated accurately. However, the low DC input voltage alarm and shut-down functions
are designed to protect the inverter from excessive current drawn at the lower voltage.
7.13 USE OF EXTERNAL PROGRAMMABLE LOW VOLTAGE DISCONNECTS
The above ambiguity can be removed by using an external, programmable Low Voltage
Disconnect where more exact voltage threshold can be set to disconnect the battery
based on the actual application requirements. Please consider using the following
Programmable Low Battery Cut-off / “Battery Guard” Models manufactured by Samlex
America, Inc. www.samlexamerica.com
- BG-40 (40A) – For up to 400W, 12V inverter or 800W, 24V inverter
- BG-60 (60A) - For up to 600W, 12V inverter or 1200W, 24V inverter
- BG-200 (200A) - For up to 2000W, 12V inverter or 4000W, 24V inverter
7.14 DEPTH OF DISCHARGE OF BATTERY AND BATTERY LIFE
The more deeply a battery is discharged on each cycle, the shorter the battery life. Using
more batteries than the minimum required will result in longer life for the battery bank.
A typical cycle life chart is given in the Table 7.6:
TABLE 7.6: TYPICAL CYCLE LIFE CHART
Depth of Discharge
% of Ah Capacity
10100015003800
503204801100
80200300675
100150225550
NOTE: It is recommended that the depth of discharge should be limited to 50%.
Cycle Life of Group
27 /31
Cycle Life of Group 8DCycle Life of Group
GC2
SECTION 7 | General Information on Lead Acid
Batteries
7.15 SERIES AND PARALLEL CONNECTION OF BATTERIES
7.15.1 Series Connection
Cable “A”
Battery 4Battery 3Battery 2Battery 1
24V Inverter
or 24V Charger
Cable “B”
6V
6V6V6V
Fig 7.2: Series Connection
When two or more batteries are connected in series, their voltages add up but their Ah
capacity remains the same. Fig. 7.2 shows 4 pieces of 6V, 200 Ah batteries connected in
series to form a battery bank of 24V with a capacity of 200 Ah. The Positive terminal
of Battery 4 becomes the Positive terminal of the 24V bank. The Negative terminal of
Battery 4 is connected to the Positive terminal of Battery 3. The Negative terminal of
Battery 3 is connected to the Positive terminal of Battery 2. The Negative terminal of
Battery 2 is connected to the Positive terminal of Battery 1. The Negative terminal of
Battery 1 becomes the Negative terminal of the 24V battery bank.
7.15.2 Parallel Connection
Cable “A”
12V Inverter
or 12V Charger
Cable “B”
Battery 1Battery 3Battery 2Battery 4
12V
12V12V12V
Fig 7.3: Parallel Connection
When two or more batteries are connected in parallel, their voltage remains the same
but their Ah capacities add up. Fig. 7.3 shows 4 pieces of 12V, 100 Ah batteries connected in parallel to form a battery bank of 12V with a capacity of 400 Ah. The four Positive
terminals of Batteries 1 to 4 are paralleled (connected together) and this common Positive connection becomes the Positive terminal of the 12V bank. Similarly, the four Negative terminals of Batteries 1 to 4 are paralleled (connected together) and this common
Negative connection becomes the Negative terminal of the 12V battery bank.
26 | SAMLEX AMERICA INC.
!
SECTION 7 | General Information on Lead Acid
Batteries
7.15.3 Series – Parallel Connection
12V String 112V String 2
Cable “A”
12V Inverter
or 12V Charger
Cable “B”
Battery 1Battery 3Battery 2Battery 4
6V
6V6V6V
Fig. 7.4: Series-Parallel Connection
Figure 7.4 shows a series – parallel connection consisting of four 6V, 200 AH
batteries to form a 12V, 400 Ah battery bank. Two 6V, 200 Ah batteries, Batteries 1 and 2
are connected in series to form a 12V, 200 Ah battery (String 1). Similarly, two 6V, 200 Ah
batteries, Batteries 3 and 4 are connected in series to form a 12V, 200 Ah battery
(String 2). These two 12V, 200 Ah Strings 1 and 2 are connected in parallel to form a
12V, 400 Ah bank.
CAUTION!
When 2 or more batteries / battery strings are connected in parallel and are
then connected to an inverter or charger (See Figs 7.3 and 7.4), attention
should be paid to the manner in which the charger / inverter is connected
to the battery bank. Please ensure that if the Positive output cable of the
battery charger / inverter (Cable “A”) is connected to the Positive battery
post of the rst battery (Battery 1 in Fig 7.3) or to the Positive battery
post of the rst battery string (Battery 1 of String 1 in Fig. 7.4), then the
Negative output cable of the battery charger / inverter (Cable “B”) should
be connected to the Negative battery post of the last battery (Battery 4 as
in Fig. 7.3) or to the Negative Post of the last battery string (Battery 4 of
Battery String 2 as in Fig. 7.4). This connection ensures the following:
- The resistances of the interconnecting cables will be balanced.
- All the individual batteries / battery strings will see the same series resistance.
- All the individual batteries will charge / discharge at the same charging
current and thus, will be charged to the same state at the same time.
- None of the batteries will see an overcharge condition.
SECTION 7 | General Information on Lead Acid
Batteries
7.16 SIZING THE INVERTER BATTERY BANK
One of the most frequently asked questions is, "how long will the batteries last?" This
question cannot be answered without knowing the size of the battery system and the
load on the inverter. Usually this question is turned around to ask “How long do you
want your load to run?”, and then specic calculation can be done to determine the
proper battery bank size.
There are a few basic formulae and estimation rules that are used:
1. Active Power in Watts (W) = Voltage in Volts (V) x Current in Amperes (A)
x Power Factor.
2. For an inverter running from a 12V battery system, the approximate DC current required from the 12V batteries is the AC power delivered by the inverter to the load
in Watts (W) divided by 10 & for an inverter running from a 24V battery system, the
approximate DC current required from the 24V batteries is the AC power delivered
by the inverter to the load in Watts (W) divided by 20.
3. Energy required from the battery = DC current to be delivered
(A) x Time in Hours (H).
The rst step is to estimate the total AC Watts (W) of load(s) and for how long the
load(s) will operate in hours (H). The AC Watts are normally indicated in the electrical
nameplate for each appliance or equipment. In case AC Watts (W) are not indicated,
Formula 1 given above may be used to calculate the AC Watts. The next step is to
estimate the DC current in Amperes (A) from the AC Watts as per Formula 2 above. An
example of this calculation for a 12V inverter is given below:
Let us say that the total AC Watts delivered by the inverter = 1000W.
Then, using Formula 2 above, the approximate DC current to be delivered by the 12V
batteries = 1000W ÷10 = 100 Amperes, or by 24V batteries = 1000W ÷ 20 = 50A.
Next, the energy required by the load in Ampere Hours (Ah) is determined.
For example, if the load is to operate for 3 hours then as per Formula 3 above, the
energy to be delivered by the 12V batteries = 100 Amperes × 3 Hours = 300 Ampere
Hours (Ah), or by the 24V batteries = 50A x 3 Hrs = 150 Ah.
Now, the capacity of the batteries is determined based on the run time and
the usable capacity.
From Table 7.3 “Battery Capacity versus Rate of Discharge”, the usable capacity at
3 Hour discharge rate is 60%. Hence, the actual capacity of the 12V batteries to
deliver 300 Ah will be equal to: 300 Ah ÷ 0.6 = 500 Ah, and the actual capacity of the
24V battery to deliver 150 Ah will be equal to 150 Ah ÷ 0.6 = 250 Ah.
And nally, the actual desired rated capacity of the batteries is determined based on
the fact that normally only 80% of the capacity will be available with respect to the
rated capacity due to non availability of ideal and optimum operating and charging
conditions. So the nal requirements will be equal to:
28 | SAMLEX AMERICA INC.
SECTION 7 | General Information on Lead Acid
Batteries
FOR 12V BATTERY:
500 Ah ÷ 0.8 = 625 Ah (note that the actual energy required by the load was 300 Ah).
FOR 24V BATTERY:
250 Ah ÷ 0.8 = 312.5 Ah (Note that the actual energy required was 150 Ah).
It will be seen from the above that the nal rated capacity of the batteries is almost
2 times the energy required by the load in Ah. Thus, as a Rule of Thumb, the Ah
capacity of the batteries should be twice the energy required by the load in Ah.
7.17 CHARGING BATTERIES
Batteries can be charged by using good quality AC powered battery charger or from alternative energy sources like solar panels, wind or hydro systems. Make sure an appropriate
Battery Charge Controller is used. It is recommended that batteries may be charged at
10% to 13% of their Ah capacity (Ah capacity based on C-Rate of 20 Hr Discharge Time).
Also, for complete charging (return of 100% capacity) of Sealed Lead Acid Battery, it is
recommended that a 3 Stage Charger may be used (Constant Current Bulk Charging Stage
} Constant Voltage Boost / Absorption Charging } Constant Voltage Float Charging).
In case, Wet Cell / Flooded Batteries are being used, a 4-stage charger is recommended
(Constant Current Bulk Charging Stage } Constant Voltage Boost / Absorption Stage }
Constant Voltage Equalization Stage } Constant Voltage Float Stage).
SECTION 8 | Installation
WARNING!
1. Before commencing installation, please read the safety instructions
explained in Section 1 titled “Safety Instructions”.
2. It is recommended that the installation should be undertaken by a
qualied, licensed / certied electrician.
3. Various recommendations made in this manual on installation will
be superseded by the National / Local Electrical Codes related to the
location of the unit and the specic application.
8.1 LOCATION OF INSTALLATION
Please ensure that the following requirements are met:
Working Environment: Indoor use.
SECTION 8 | Installation
Cool: Heat is the worst enemy of electronic equipment. Hence, please ensure that the
unit is installed in a cool area that is also protected against heating effects of direct
exposure to the sun or to the heat generated by other adjacent heat generating devices.
Well Ventilated: The unit is cooled by convection and by forced air-cooling by temperature controlled fan. The fan draws cool air from air intake openings on the front (5, Fig
6.1a) and expels hot air through the exhaust openings next to the fan (18, Fig 6.1c). To
avoid shut down of the inverter due to over temperature, do not cover or block these
intake / exhaust openings or install the unit in an area with limited airflow. Keep a
minimum clearance of 10” around the unit to provide adequate ventilation. If installed
in an enclosure, openings must be provided in the enclosure, directly opposite to the air
intake and exhaust openings of the inverter.
Dry: There should be no risk of condensation, water or any other liquid that can enter
or fall on the unit.
Clean: The area should be free of dust and fumes. Ensure that there are no insects or
rodents. They may enter the unit and block the ventilation openings or short circuit electrical circuits inside the unit.
Protection Against Fire Hazard: The unit is not ignition protected and should not be
located under any circumstance in an area that contains highly ammable liquids like
gasoline or propane as in an engine compartment with gasoline-fueled engines. Do not
keep any flammable / combustible material (i.e., paper, cloth, plastic, etc.) near the unit
that may be ignited by heat, sparks or flames.
Closeness to the Battery Bank: Locate the unit as close to the battery bank as possible to
prevent excessive voltage drop in the battery cables and consequent power loss and reduced
efciency. However, the unit should not be installed in the same compartment as the batteries (ooded or wet cell) or mounted where it will be exposed to corrosive acid fumes and
ammable Oxygen and Hydrogen gases produced when the batteries are charged. The corrosive fumes will corrode and damage the unit and if the gases are not ventilated but
allowed to collect, they could ignite and cause an explosion.
Accessibility: Do not block access to the front panel. Also, allow enough room to access
the AC receptacles and DC wiring terminals and connections, as they will need to be
checked and tightened periodically.
Preventing Electro Magnetic Interference (EMI): The unit uses high power switching
circuits that generate RFI. This RFI is limited to the required standards. Locate any electronic equipment susceptible to radio frequency and electromagnetic interference as
far away from the inverter as possible. Read Section 3 “EMC (EMI/EMS) Compliance” for
additional information.
8.2 OVERALL DIMENSIONS
The overall dimensions and the location of the mounting slots are shown in Fig. 8.1 to
8.3 on next page.
30 | SAMLEX AMERICA INC.
240.6
SECTION 8 | Installation
5
5
15.3
200
230.6
240.6
15.3
5
32 1216212321.61.6
Fig. 8.1: PST-60S-12E, PST-60S-24E Dimensions and
Mounting Slots / Dimensions (mm): 281 x 241 x 82
281
Height: 82 mm
15.3
230.6
15.3
400
5
200
5
1.6
5
Height: 82 mm
44 1228212 32 1.6
Fig. 8.2: PST-100S-12E, PST-100S-24E Dimensions and
Mounting Slots / Dimensions (mm): 240.6 x 400 x 82
SECTION 8 | Installation
380.5225
4.5
273
282
4.5
Fig. 8.3: Dimensions and Mounting Slots for PST-150S-12E, PST-150S-24E
and PST-200S-12E, PST-200S-24E / Dimensions (mm): 282 x 415 x 101
5
Height: 101 mm
7
389
415
8.3 MOUNTING ORIENTATION
The unit has air intake and exhaust openings for the cooling fan. It has to be mounted
in such a manner so that small objects should not be able to fall easily into the unit from
these openings and cause electrical / mechanical damage. Also, the mounting orientation should be such that if the internal components overheat and melt / dislodge due to
a catastrophic failure, the melted / hot dislodged portions should not be able to fall out
of the unit on to a combustible material and cause a re hazard. The size of openings
has been limited as per the safety requirements to prevent the above possibilities when
the unit is mounted in the recommended orientations. In order to meet the regulatory
safety requirements, the mounting has to satisfy the following requirements:
- Mount on a non-combustible material.
- The mounting surface should be able to support the weight of the unit
- Mount horizontally on a horizontal surface - above a horizontal surface
(e.g. table top or a shelf).
- Mount horizontally on a vertical surface – The unit can be mounted on a vertical
surface (like a wall) with the fan axis horizontal (fan opening facing left or right).
32 | SAMLEX AMERICA INC.
!
SECTION 8 | Installation
WARNING!
Mounting the unit vertically on a vertical surface is NOT recommended (fan opening
facing up or down). As explained above, this is to prevent falling of objects into the unit
through the fan opening when the fan opening faces up. If fan opening faces down,
hot damaged component may fall out.
The surface of the unit is likely to be at an elevated temperature in conditions of higher
load and higher ambient temperature. Hence, the unit should be installed in a manner
where it is not likely to come in contact with any person.
8.4 DC SIDE CONNECTIONS
8.4.1 Preventing DC Input Over Voltage
It is to be ensured that the DC input voltage of this unit does not exceed 16.5 VDC for
the 12V versions and 33.0 VDC for the 24V versions to prevent permanent damage to
the unit. Please observe the following precautions:
- Ensure that the maximum charging voltage of the external battery charger / alternator / solar charge controller does not exceed 16.5 VDC for the 12V versions and 33.0
VDC for the 24V versions
- Do not use unregulated solar panels to charge the battery connected to this unit. Under
open circuit conditions and in cold ambient temperatures, the output of the solar panel
may be > 22 VDC for 12V nominal panel and > 44V for 24V nominal panel. Always use a
charge controller between the solar panel and the battery.
- When using Diversion Charge Control Mode in a charge controller, the solar / wind /
hydro source is directly connected to the battery bank. In this case, the controller will
divert excess current to an external load. As the battery charges, the diversion duty
cycle will increase. When the battery is fully charged, all the source energy will ow
into the diversion load if there are no other loads. The charge controller will disconnect the diversion load if the current rating of the controller is exceeded. Disconnection of the diversion load may damage the battery as well as the inverter or other DC
loads connected to the battery due to high voltages generated during conditions of
high winds (for wind generators), high water ow rates (for hydro generators). It is,
therefore, to be ensured that the diversion load is sized correctly to prevent the above
over voltage conditions.
- Do not connect this unit to a battery system with a voltage higher than the rated
battery input voltage of the unit (e.g. do not connect the 12V versions to 24V or 48V
Battery System or the 24V versions to 48V Battery System).
8.4.2 Preventing Reverse Polarity on the DC Input Side
CAUTION!
Damage caused by reverse polarity is not covered by warranty! When making
battery connections on the input side, make sure that the polarity of battery
connections is correct (Connect the Positive of the battery to the Positive termi-
SECTION 8 | Installation
!
nal of the unit and the Negative of the battery to the Negative terminal of the
unit). If the input is connected in reverse polarity, DC fuse(s) inside the inverter
will blow and may also cause permanent damage to the inverter.
8.4.3 Connection from Batteries to the DC Input Side – Sizing of Cables
and Fuses
CAUTION!
The input section of the inverter has large value capacitors connected across the
input terminals. As soon as the DC input connection loop (Battery (+) terminal
" External Fuse " Positive input terminal " Negative input terminal " Battery
(–) terminal) is completed, these capacitors will start charging and the unit will
momentarily draw very heavy current to charge these capacitors that will produce
sparking on the last contact in the input loop even when the unit is in OFF condition. Ensure that the fuse is inserted only after all the connections in the loop have
been completed so that sparking is limited to the fuse area.
Flow of electric current in a conductor is opposed by the resistance of the conductor.
The resistance of the conductor is directly proportional to the length of the conductor
and inversely proportional to its cross-section (thickness). The resistance in the conductor produces undesirable effects of voltage drop and heating. The size (thickness /
cross-section) of the conductors is specied in mm
Conductors thicker than AWG #4/0 are sized in MCM/kcmil. Table 8.1 below gives Resistance in Ohm (Ω) per Foot at 25°C / 77°F for the wire sizing recommended for use with
this inverter.
Table 8.1 Wiring Resistance per Foot
WIRE SIZE,
AWG
16 mm2 / AWG#60.000403 Ω / ft
2
/ AWG#40.000253 Ω / ft
25 mm
2
/ AWG#20.000159 Ω / ft
35 mm
2
/ AWG#1/00.000100 Ω / ft
50 mm
2
/ AWG#2/00.000079 Ω / ft
70 mm
2
/ AWG#3/00.000063 Ω / ft
95 mm
2
/ AWG#4/00.000049 Ω / ft
120 mm
2
or in AWG (American Wire Gauge).
RESISTANCE IN OHM (Ω)
PER FOOT AT 25°C / 77°F
Conductors are protected with insulating material rated for specic temperature e.g.
90˚C/194˚F. As current ow produces heat that affects insulation, there is a maximum
permissible value of current (called “Ampacity”) for each size of conductor based on
temperature rating of its insulation. The insulating material of the cables will also be
affected by the elevated operating temperature of the terminals to which these are connected. Ampacity of cables is based on guidelines given under “Notes for Table 8.2”.
34 | SAMLEX AMERICA INC.
SECTION 8 | Installation
The DC input circuit is required to handle very large DC currents and hence, the size of the
cables and connectors should be selected to ensure minimum voltage drop between the
battery and the inverter. Thinner cables and loose connections will result in poor inverter
performance and will produce abnormal heating leading to risk of insulation melt down
and re. Normally, the thickness of the cable should be such that the voltage drop due to
the current & the resistance of the length of the cable should be less than 2% to 5%. Use
oil resistant, multi-stranded copper wire cables rated at 90ºC / 194°F minimum. Do not use
aluminum cable as it has higher resistance per unit length. Cables can be bought at a marine
/ welding supply store. Effects of low voltage on common electrical loads are given below:
• Lighting circuits - incandescent and Quartz Halogen: A 5% voltage drop causes an
approximate 10% loss in light output. This is because the bulb not only receives
less power, but the cooler lament drops from white-hot towards red-hot, emitting
much less visible light.
• Lighting circuits - uorescent: Voltage drop causes a nearly proportional drop in
light output.
• AC induction motors - These are commonly found in power tools, appliances, well
pumps etc. They exhibit very high surge demands when starting. Signicant voltage drop in these circuits may cause failure to start and possible motor damage.
• PV battery charging circuits - These are critical because voltage drop can cause a
disproportionate loss of charge current to charge a battery. A voltage drop greater
than 5% can reduce charge current to the battery by a much greater percentage.
8.4.4 Fuse Protection in the Battery Circuit
A battery is an unlimited source of current. Under short circuit conditions, a battery can
supply thousands of Amperes of current. If there is a short circuit along the length of
the cables that connects the battery to the inverter, thousands of Amperes of current
can ow from the battery to the point of shorting and that section of the cable will
become red-hot, the insulation will melt and the cable will ultimately break. This interruption of very high current will generate a hazardous, high temperature, high-energy
arc with accompanying high-pressure wave that may cause re, damage nearby objects
and cause injury. To prevent occurrence of hazardous conditions under short circuit
conditions, the fuse used in the battery circuit should limit the current (should be "Current Limiting Type"), blow in a very short time (should be Fast Blow Type) and at the
same time, quench the arc in a safe manner. For this purpose, fuse Type UL Class-T (as
per UL standard UL 248-15) / Type "HRC" (as per BS88-2 or as per IEC 60269-2) should be
used. This special purpose current limiting, very fast acting fuse will blow in less than 8
ms under short circuit conditions. Appropriate capacity of the above fuse or equivalent should be installed within 7” of the battery Plus (+) Terminal (Please see Table 8.2 for
fuse sizing). Marine Rated Battery Fuses, MRBF-xxx Series made by Cooper Bussmann
may also be used. These fuses comply with ISO 8820-6 for road vehicles.
SECTION 8 | Installation
WARNING!
Use of an appropriately sized external fuse as described above is mandatory to
provide safety against re hazard due to accidental short circuit in the battery
cables. Please note that the internal DC side fuses are designed to protect the
internal components of the inverter against DC side overloading. These fuses
will NOT blow if there is a short circuit along the length of wires connecting the
battery and the inverter.
8.4.5 Recommended Sizes of Battery Cables and Fuses
Sizes of cables and fuses are shown in Table 8.2. Sizing is based on safety considerations
specied in British Standard BS 7671. Please refer to “Notes for Table 8.2” for details.
Table 8.2 Sizing of Battery Side Cables and External Battery Side Fuses
Item
(Column 1)
PST-60S-12E80A80A25 mm
PST-60S-24E40A40A6 mm
PST-100S-12E160A175A50 mm
PST-100S-24E80A80A16 mm
PST-150S-12E200A200A50 mm
PST-150S-24E100A100A16 mm
PST-200S-12E240A250A50 mm
PST-200S-24E120A125A25 mm
Rated
continuous
DC input
current
(See Note
1)
(Column 2)
Size of
external fuse
based on DC
input current
at Column 2
(See Note 2)
(Column 3)
90°C / 194°F Copper conductor. Size based on
Ampacity at Column (3) or 2%voltage drop,
whichever is thicker (See Note 3)
Cable Running Distance between
the Unit and the Battery
(Cable Routing In Free Air)
Up to 5 ft.
(Column 5)
2
/ AWG#450 mm2 / AWG#1/0
2
/ AWG#1016 mm2 / AWG#6
2
/ AWG1/095 mm2 / AWG#3/0
2
/ AWG#625 mm2 / AWG#4
2
/ AWG#1/095 mm2 / AWG#3/0
2
/ AWG#635 mm2 / AWG#2
2
/ AWG#1/0120 mm2 / AWG#4/0
2
/ AWG#435 mm2 / AWG#2
Up to 10 ft.
(Column 6)
NOTES FOR TABLE 8.2 - SIZING OF BATTERY SIDE CABLES AND EXTERNAL
BATTERY SIDE FUSES
1) Column 2 indicates the Rated Continuous DC Input Current drawn from the battery.
2) Column 3 indicates size of external fuse not less than the Rated DC Input
Current at Column 2. Next standard capacity is to be used.
3) Columns 5 and 6 indicate cable conductor size that is based on the following
2 considerations. Thicker conductor out of the following 2 considerations has
been chosen:
a) As per guidelines in British Standard BS 7671 - Table 4E 1A (Reference
Method "C" for 2 cables). Following have been considered: (i) Ampacity =
the fuse size at Column 3, (ii) Copper conductor with temperature rating
36 | SAMLEX AMERICA INC.
SECTION 8 | Installation
of 90°C / 194°F, (iii) Ambient temperature of 30°C / 86°F and (iv) Fixed on
(clipped direct) or spaced less than 0.3x cable diameter from wooden or
masonary wall.
b) Voltage drop across the length of cables has been limited to 2% of 12V
/ 24V. Voltage drop has been calculated by multiplying the Rated DC
Input Current (Column 2) and the resistance of the total length of Copper
conductor (the total length of conductor has been taken as 2 times the
running distance between the unit and the battery to cover 2 lengths of
Positive and Negative cable conductors).
4) Column 3 indicates the size of external fuse in the battery circuit. It is
mandatory to install this fuse within 7” of the battery Positive terminal to
protect the battery cables against short circuit. Amp rating of the fuse is
based on the following considerations:
a) Not less than the Rated Continuous DC Input Current (Column 2)
b) Closest Standard Ampere Rating of Fuse has been used
c) Type of fuse: Fast-acting, Current Limiting, UL Class – Type "Class T" as per
UL Standard 248-15 or Type "HRC" as per BS 88-2 / IEC60269-2
8.4.6 DC Input Terminals for Batttery Connection
The DC input terminals for battery connection (8 and 9 in Figs 6.1, 6.2, 6.3) have 11 mm
cylindrical hole with M8 set screw.
8.4.7 Using proper wiring termination
The battery end and the inverter end of the DC input wiring should have proper terminals
that will ensure a rm and tight connection.
Terminal lugs have been provided to suit recommended cable sizes as per Column 5 of
Table 8.2.
8.4.8 Reducing RF Interference
Please comply with recommendations given in Section 3 - "EMC (EMI / EMS) Compliance".
8.5 AC SIDE CONNECTIONS
WARNING! Preventing Paralleling of the AC Output
1. The AC output of the inverter cannot be synchronized with another AC source
and hence, it is not suitable for paralleling. The AC output of the inverter should
never be connected directly to an electrical breaker panel / load center which
is also fed from the utility power/ generator. Such a connection will result in
parallel operation and AC power from the utility / generator will be fed back
into the inverter which will instantly damage the output section of the inverter
and may also pose a re and safety hazard. If an electrical breaker panel /
SECTION 8 | Installation
5
load center is being fed from the utility power / generator and the inverter is
required to feed this panel as backup power source, the AC power from the
utility power/ generator and the inverter should rst be fed to a manual selector
switch / Automatic Transfer Switch and the output of the manual selector switch
/ Automatic Transfer Switch should be connected to the electrical breaker panel /
load center.
2. To prevent possibility of paralleling and severe damage to the inverter, never
use a simple jumper cable with a male plug on both ends to connect the AC
output of the inverter to a handy wall receptacle in the home.
8.5.1 AC Output Receptacle(s)
For AC output connection, the inverter uses European "Schuko" Receptacle Type CEE
7/3 (6 in Fig 6.1). This type of receptacle is used in Germany, Australia, the Netherlands,
Sweden, Norway and Finland amongst others. Corresponding “Schuko” Plug, Type CEE
7/4 or CEE 7/7 is required on the power cord feeding the AC loads to be connected to
the inverter. The construction of the “Schuko” Receptacle (Type CEE 7/3) and Plug (CEE
7/7) is shown at Figs 8.2.1 and 8.2.2 respectively.
2.2
1.2
(See 5 in Figs 6.1 /
6.2 / 6.3)
2.1(b)
1.1
1.3
2.1(a)
1.2
European "Schuko" Plug, Type CEE 7/7
1.1: Non-polarized male pins for current
carrying conductors
1.2: Grounding Contact Strips
1.3: Grounding Socket (Not provided in
Schuko Plug Type CEE 7/4)
Fig. 8.2.1 Schuko Type Plug CEE 7/7
In the “Schuko” Receptacle, Type CEE 7/3 (Fig 8.2.2), there is NO Neutral and both the
sockets L1 and L2 are HOT/LIVE and will be oating and at elevated voltage with respect
to the metal chassis Ground / Earth Ground as per Columns (2) and (3) of Table 8.3:
The 2 grounding spring contacts (2.2, Fig 8.2.2) on the periphery are internally connected
to the metal chassis of the inverter / Grounding Terminal (7 in Figs 6.1 / 6.2 / 6.3) which
is, in turn, connected to the Earth Ground System of the premises where the inverter is
installed. When the “Schuko” Plug, Type CEE 7/7 (Fig 8.2.1) of the Power Cord of the AC
load is inserted into the “Schuko” Receptacle, Type CEE 7/3 (Fig 8.2.2) on the inverter,
the metal chassis of the AC load is automatically connected to the Earth Ground System
of the premises where the inverter is installed.
Voltage between left
socket "L1" and metal
chassis / Grounding
Spring Contact
(2)
Voltage between right
socket "L2" and metal
chassis / Grounding
Spring Contact
(3)
Voltage between left
socket "L1" and right
socket "L2"
(4)
WARNING!
As explained above, in “Schuko” Receptacle, Type CEE 7/3 (Fig 8.2.2), there is NO
Neutral and both the L1 and L2 sockets will be HOT / LIVE and will be at elevated
voltage with respect to the metal chassis of the inverter / Earth as per Column (2)
of Table 8.3. The mating “Schuko” Plug, Type CEE 7/7 (Fig 8.2.1) is NOT polarized
i.e. the plug can be inserted in the receptacle in 2 orientations. Ideally, a Double
Pole Switch / Breaker will be required on the load side to safely disconnect both
the HOT / LIVE AC input lines from the internal downstream sections of the AC
load. If a single pole AC Input ON/ OFF Switch / Breaker is used on the AC load
for AC input, it is likely that the Switch / Breaker may get connected in series with
the lower voltage current carrying conductor (20 to 95 VAC ± 10% with respect
to the metal chassis Ground as per Column (3) of Table 8.3). Hence, even when
the ON/OFF Switch / Breaker on the load has been switched OFF, the higher voltage current carrying conductor (135 to 210 VAC ± 10% as per Column (2) of Table
8.3) may still remain connected to the internal downstream sections of the load
and will be a shock hazard!
8.5.2 Providing Backup Power Using Transfer Switch
For this application, use a Transfer Switch that has Double Pole, Double Throw Contacts.
- Feed utility power and output power from the inverter to the two inputs of the Transfer
Relay.
- Feed the output of the Transfer Switch to a Sub-Panel to feed AC loads requiring backup
power.
SECTION 8 | Installation
!
8.6 GROUNDING TO EARTH OR TO OTHER DESIGNATED GROUND
NOTE: Recommendations given below are based on Protective Multiple Earthing (PME) or
TN-C-S Earthing System.
For safety, connect the metal chassis of the inverter to the Main Earthing Terminal of the
premises or to the other designated Ground (For example, in a vehicle, the metal frame /
chassis of the vehicle is normally designated as the Negative DC Ground). A Chassis Grounding Terminal (7 in Figs 6.1 / 6.2 / 6.3) has been provided for grounding the metal chassis of
the inverter to the appropriate Ground.
When using the inverter in a building, connect a 10 mm
copper wire from the above Chassis Grounding Terminal to the Earth Ground connection ( a
connection that connects to the Ground Rod or to buried metallic water pipe or to another
connection that is solidly bonded to the Earth Ground ). The connections must be tight
against bare metal. Use star washers to penetrate paint and corrosion.
When using the inverter in RVs / Motor Home / Trailers / Campers / Caravans, connect a
2
10 mm
or AWG #8 insulated stranded copper wire from the above Chassis Grounding
Terminal to the Main Grounding Bus Bar of the vehicle (bonded to the vehicle chassis).
The connections must be tight against bare metal. Use star washers to penetrate paint
and corrosion.
8.7 OPTIONAL WIRED REMOTE CONTROL – MODEL RC-15
An optional wired Remote Control Model RC-15 is available for switching ON and switching OFF the AC output of the inverter. RC-15 comes with 15ft of cable. The cable is connected to the Remote Control Jack on the inverter (10 in Figs 6.1, 6.2 and 6.3). The Remote
has a Red LED that will be lighted when the AC output of the inverter has been switched
ON. Please read RC-15 manual for more details.
2
or AWG #8 insulated stranded
CAUTION!
For the Remote Control RC-15 to operate, the inverter has to be FIRST
switched ON using the ON/OFF Switch on the inverter (1 in Figs 6.1, 6.2 and
6.3). The ON/OFF Switch on the inverter has to be kept in ON condition dur-
ing the period the Remote Control RC-15 is being used. The AC output of the
inverter will be switched ON / OFF using the ON/OFF Push Button on RC-15.
As the ON/OFF Switch on the inverter is required to be in ON condition during
the use of RC-15, the inverter will NOT switch OFF completely when its AC output is switched OFF using RC-15 but some control circuitry in the inverter will
still be active. Hence, there will be a minor draw of < 5mA from the battery
even when the AC output of the inverter has been switched OFF using RC-15.
However, when the inverter is switched OFF completely by switching OFF the
ON/OFF Switch on the inverter, there will be no draw from the battery.
40 | SAMLEX AMERICA INC.
SECTION 9 | Operation
!
9.1 SETTING OUTPUT FREQUENCY
Default frequency is 50 Hz. Output frequency may be changed to 60 Hz using 50/60 Hz
Selector Switch (11 in Figs 6.1 / 6.2 / 6.3). Frequency should be changed only after switching
the inverter to OFF condition rst.
9.2 SWITCHING THE INVERTER ON/OFF
Before switching on the inverter, check that all the AC loads have been switched off and
the desired output frequency has been selected (See 9.1 above). The ON/OFF Switch (1 in
Figs 6.1 / 6.2 / 6.3) on the front panel of the inverter is used to switch ON and switch OFF
the inverter. This switch operates a low power control circuitry, which in turn controls all the
high power circuitry.
The unit can also be switched ON/OFF remotely with the help of optional Remote Control
RC-15 (See Section 8.7):
CAUTION!
When the inverter is switched ON, the Green LED marked "POWER" (2 in Figs 6.1 / 6.2 / 6.3)
will be lighted. This LED indicates that the input section of the inverter is operating normally.
Under normal operating conditions, AC output voltage will now be available at the Schuko
Receptacle (5 in Figs 6.1 / 6.2 / 6.3).
Please note that the ON/OFF switch is not switching the high power battery
input circuit. Parts of the DC side circuit will still be alive even when the switch is
in the OFF position. Hence, disconnect the DC and AC sides before working on
any circuits connected to the inverter.
Switch on the AC load(s). The Green LED marked "POWER" (2 in Figs 6.1 / 6.2 / 6.3) should
remain lighted for normal operation of the load.
9.3 POWERING ON THE LOADS
After the inverter is switched ON, it takes a nite time to become ready to deliver full
power. Hence, always switch on the load(s) after a few seconds of switching ON the inverter.
Avoid switching on the inverter with the load already switched on. This may prematurely
trigger the overload protection.
When a load is switched ON, it may require initial higher power surge to start. Hence, if multiple loads are being powered, they should be switched ON one by one so that the inverter
is not overloaded by the higher starting surge if all the loads are switched ON at once.
9.4 TEMPERATURE CONTROLLED COOLING FAN
Cooling is carried out by thermostatically controlled fan(s). PST-60S / PST-100S have 1 fan (6
in Figs 6.1 and 6.2). PST-150S / PST-200S have 2 fans (6 in Fig 6.3). Temperature of a critical hot spot inside the inverter is monitored to activate the fan and the over temperature
shut-down. When the temperature of this hot spot reaches 55°C ± 3°C, the fan is switched
SECTION 9 | Operation
!
ON. The fan will be automatically switched OFF once the hot spot cools down to 45°C ± 3°C.
Please note that the fan may not switch ON at low loads or if the ambient temperature is
cooler. This is normal.
9.5 INDICATIONS FOR NORMAL OPERATION
When the inverter is operating normally and supplying AC load(s), the Green LED marked
"POWER" (2 in Figs 6.1 / 6.2 / 6.3) will be lighted. Please see Section 10 "Protections" and
Section 11 "Troubleshooting Guide" for symptoms of abnormal operation.
9.6 NO LOAD DRAW (IDLE CURRENT)
When the unit is switched ON, all the circuitry inside the inverter becomes alive and the
AC output is made available. In this condition, even when no load is being supplied (or, if a
load is connected but has been switched OFF), the inverter draws a small amount of current
from the batteries to keep the circuitry alive and ready to deliver the required power on
demand. This is called the "Idle Current" or the "No Load Draw". Hence, when the load is
not required to be operated, turn OFF the inverter to prevent unnecessary current drain
from the battery.
CAUTION!
When the AC output of the inverter is switched OFF using the optional
external Remote Control RC-15, there will be a very minor current drain of
< 5 mA. There will be NO drain from the battery when the inverter is
switched OFF by switching OFF the ON/OFF Switch (1 in Figs 6.1 / 6.2 / 6.3).
Refer to Section 8.7 for details.
42 | SAMLEX AMERICA INC.
SECTION 10 | Protections
i
10. PROTECTIONS
The inverter has been provided with protections detailed below:
10.1 POWER SURGE / OVERLOAD / SHORT CIRCUIT SHUT DOWN
INFO
Please refer to denitions of Active Power (Watts), Apparent Power (VA) and
• Active Power (Watts) = Apparent Power (VA) x Power Factor (PF).
• For resistive type of loads, the Power Factor = 1 and hence, Apparent Power
• For reactive types of loads, the Power Factor will be < 1 (up to 0.5) and hence,
The AC output voltage will shut down due to overload and short circuit conditions as follows:
Power Surge Condition: When the AC output current tries to exceed around 160% of
the rated value for PST-600 or 200% of the rated value for PST-100S / 150S / 200S, output
current limiting is carried out instantly resulting in drop in the AC output voltage (the
drop is proportional to the load impedance). Surge Power of 160% / 200% will, thus, be
provided for < 8 ms every half cycle. If this situation continues for 2 to 2.5 sec Overload
Condition is activated.
Power Factor (PF) at Section 2.1. In the explanation below, the values of Power
are expressed in Apparent Power in VA. Corresponding Active Power (Watts, W)
will depend upon the type of load (Resistive or Reactive) and its Power Factor
(Power Factor may range from 1 to 0.5). Please note the following:
(VA) = Active Power (Watts, W)
the Active Power (Watts, W) will be less than the Apparent Power (VA)
Overload Condition for PST-60S/100S: If there is a continuous overload of 110% to
120% for 3 to 5 sec, the AC output voltage will be shut down. Red LED marked “OVERLOAD” (3 in Figs 6.1/6.2/6.3) will turn ON and buzzer alarm will sound. The Green LED
marked “POWER” (2 in Figs 6.1/6.2/6.2) will continue to be lighted. The unit will be
latched in this shut down condition and will require manual reset. To reset, switch the
unit OFF, wait for 3 minutes and then switch ON the unit again. Before switching ON,
determines and remove the cause of overload
Overload Condition for PST-150S/200S: If there is a continuous overload of 110% to
120% for 2 to 4 sec, the AC output voltage will be shut down. Red LED marked “OVERLOAD” (3 in Figs 6.1/6.2/6.3) will turn ON and buzzer alarm will sound. The Green LED
marked “POWER” (2 in Figs 6.1/6.2/6.2) will continue to be lighted. The unit will be
latched in this shut down condition and will require manual reset. To reset, switch the
unit OFF, wait for 3 minutes and then switch ON the unit again. Before switching ON,
determines and remove the cause of overload
Short Circuit Condition: Short circuit condition will be detected when the AC output
voltage drops to < 170 VAC or lower over a period of around 1 to 1.5 sec. The AC output
voltage will be shut down thereafter.
SECTION 10 | Protections
Red LED marked “OVERLOAD” (3 in Figs 6.1 / 6.2 / 6.3) will turn ON and buzzer alarm
will sound. The Green LED marked “POWER” (2 in Figs 6.1 / 6.2 / 6.3) will continue to be
lighted. The unit will be latched in this shut down condition and will require manual reset. To reset, switch OFF the unit, wait for 3 minutes and then switch ON the unit again.
Before switching ON, determine and remove the cause of overloading.
10.2 WARNING ALARM - LOW DC INPUT VOLTAGE
The voltage at the DC input terminals will be lower than the voltage at the battery terminals due to voltage drop in the battery wires and connectors. The drop in the voltage
at the DC input terminals of the inverter could be due to lower battery voltage or due
to abnormally high drop in the battery wires if the wires are not thick enough (Please
see Section 8.4.3 “Connection from Batteries to the DC Input Side-Sizing of Cables and
Fuses”). If the voltage at the DC input terminals drops to 10.7V ± 0.1V or lower for
the 12V versions or, to 21.4V ± 0.2V or lower for the 24V versions, a buzzer alarm will be
sounded. The Green LED marked "POWER" (2 in Figs 6.1 / 6.2 / 6.3) will continue to be
lighted and the AC output voltage would continue to be available. This warning buzzer
alarm indicates that the battery is running low and that the inverter will be shut down
after sometime if the voltage at the inverter terminals further drops to 10V ± 0.1V or
lower for the 12V versions or 20V ± 0.2V or lower for the 24V versions.
10.3 LOW DC INPUT VOLTAGE SHUT DOWN
If the voltage at the DC input terminals drops to 10V ± 0.1V or lower for the 12V versions
or 20V ± 0.2V or lower for the 24V versions, the AC output is shut down. Buzzer alarm is
sounded. The Green LED marked "POWER" (2 in Figs 6.1 / 6.2 / 6.3) will remain lighted.
The unit will reset automatically when the DC input voltage rises to 11.5V ± 0.3V or
higher for the 12V versions or to 23V ± 0.5V or higher for the 24V versions.
10.4 HIGH DC INPUT VOLTAGE SHUTDOWN
If the voltage at the DC input terminals rises to 16.5V or higher for the 12V versions or, to
33V or higher for the 24V versions, the AC output voltage will be shut down temporarily.
Buzzer alarm will be sounded. The Green LED marked "POWER" (2 in Figs 6.1 / 6.2 / 6.3)
will remain lighted. The unit will be reset automatically when the voltage drops down to
< 16.5V for the 12V versions or to < 33V for the 24V versions.
10.5 OVER-TEMPERATURE SHUT DOWN
In case of failure of the cooling fan or in the case of inadequate heat removal due to
higher ambient temperatures / insufcient air exchange, the temperature inside the
unit will increase. The temperature of a critical hot spot inside the inverter is monitored,
and at 90°C ± 5°C, the AC output of the inverter is shut down temporarily. Buzzer alarm
will be sounded. The Green LED marked "POWER" (2 in Figs 6.1 / 6.2 / 6.3) will remain
lighted.
The unit will automatically reset after the hot spot has cooled down to 65°C ± 5°C.
44 | SAMLEX AMERICA INC.
SECTION 10 | Protections
i
!
10.6 INTERNAL DC SIDE FUSES
Table 10.1 below gives details of DC side fuses that have been provided for internal protection of the DC input side. The fuses are 32V, Automotive Type Blade Fuses, Type "ATO"
by Littel Fuse or equivalent. The fuses are soldered to the PCB.
NOTE: Each fuse is 32V, Automotive Blade Fuse Type "ATO" by Little Fuse or equivalent
individual fuse
10.7 REVERSE POLARITY AT THE DC INPUT TERMINALS
The Positive of the battery should be connected to the Positive DC input terminal of the
inverter and the Negative of the battery should be connected to the Negative DC input
terminal of the inverter. A reversal of polarity (the Positive of the battery wrongly connected
to the Negative DC input terminal of the inverter and the Negative of the battery wrongly
connected to the Positive DC input terminal of the inverter) will blow the external / internal
DC side fuses. If the DC side fuse is blown, the inverter will be dead. The Green LED marked
"POWER" (2, Fig 6.1a) will be switched OFF and there will be no AC output.
No. of fuses
in parallel
Total Amperage of
paralleled fuses
INFO
Reverse polarity connection is likely to damage the DC input circuitry. The
internal fuse(s) should be replaced with the same size of fuse(s) used in the
unit. If the unit does not work after replacing the fuse(s), it has been permanently damaged and will require repair / replacement (Please read Section 11 - “Troubleshooting Guide” for more details).
CAUTION!
Damage caused by reverse polarity is not covered by warranty! When making
battery connections on the input side, make sure that the polarity of battery
connections is correct (Connect the Positive of the battery to the Positive terminal of the unit and the Negative of the battery to the Negative terminal of the
unit). If the input is connected in reverse polarity, DC fuse(s) inside the inverter /
external fuse will blow and may also cause permanent damage to the inverter.
SECTION 11 | Troubleshooting Guide
ISSUEPOSSIBLE CAUSEREMEDY
When switched ON, the
Green LED marked "POWER"
does not light. Buzzer is
OFF. There is no AC output
voltage.
There is no voltage at the
DC input terminals
• Check the continuity of the battery
input circuit.
• Check that the internal/external battery
fuses are intact. Replace if blown.
• Check that all connections in the battery
input circuit are tight.
Low AC output voltage
(No buzzer alarm).
AC output voltage is available.
Buzzer alarm is sounded at no
load or when load is switched
ON. The Green LED marked
"POWER" is lighted.
There is no AC output voltage. Buzzer alarm is sounded
at no load or when load is
switched ON. The Green LED
marked "POWER" is lighted.
Polarity of the DC input
voltage has been reversed
that has blown the external / internal DC side fuses
(Note: Reverse polarity
may cause permanent
damage. Damage caused
due to reverse polarity is
not covered by warranty)
• AC load is exceeding
200% Surge Overload
• Load is approaching
200% Surge Overload
during lower DC input
voltage
• Low DC input voltage
alarm
• DC input voltage is
10.7V or lower but >
10V ± 0.1V for the 12V
versions
• DC input voltage is
21.4V ± 0.2V or lower
but > 20V ± 0.2V for
the 24V versions
• AC output voltage has
been shut down due to
low DC input voltage
• DC input voltage is 10V
± 0.1V or lower for the
12V versions
• DC input voltage is 20V
± 0.2V or lower for the
24V versions
• Check external and internal fuses. Internal
fuses may be soldered and may not be easily
replaceable. Replace fuses. If unit does not
work, call Technical Support for repair.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of battery input circuit.
• Reduce load.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over
the required length. Use thicker cables, if
required.
• Tighten connections of the battery input
circuit.
• Check that the battery is fully charged.
Recharge, if low.
• Check that the battery cables are thick
enough to carry the required current over the
required length. Use thicker cables, if required.
• Tighten connections of the battery input
circuit.
• The AC output voltage will switch ON
automatically when the DC input voltage
rises to 11.5V ± 0.1V or higher for the 12V
versions or 23V ± 0.2V or higher for the
24V versions.
46 | SAMLEX AMERICA INC.
SECTION 11 | Troubleshooting Guide
ISSUEPOSSIBLE CAUSEREMEDY
There is no AC output. The
Green LED marked "POWER"
is lighted. Buzzer is ON.
AC output shuts down
completely. Red LED marked
"OVERLOAD" is lighted.
Buzzer is ON. The Green LED
marked "POWER" (2, Fig
6.1a) is lighted.
There is no AC output.
Buzzer alarm is sounded. Red
LED marked "OVER TEMP"
is lighted. The Green LED
marked "POWER" is lighted.
Shut-down due to high input DC voltage – 16.5V or
higher for the 12V versions
and 33V or higher for the
24V versions.
Permanent shut-down of
the AC output due to:
(i) Continuous overload
of 110% to 120% for
3 to 5 sec for PST-60S /
PST-100S or 2 to 4 sec
for PST-150S / PST-200S
(ii) Short circuit resulting
in output voltage dropping to 170 VAC or
below for 1 to 1.5 sec.
Shut-down due to over
temperature because of
fan failure or inadequate
cooling as a result of high
ambient temperature or
insufcient air exchange
• Check that the voltage at the DC input
terminals is less than 16.5V for the 12V
versions and less than 33V for the 24V
versions.
• Ensure that the maximum charging voltage
of the battery charger / alternator / solar
charge controller is below 16.5V for the
12V versions and below 33V for the 24V
versions.
• Ensure that an unregulated solar panel is not
used to charge a battery. Under cold ambient
temperatures, the output of the solar panels
may exceed 22V for 12V Panels or 42V for
24V Panels. Ensure that a charge controller is
used between the solar panel and the battery.
• Automatic Reset when voltage drops to
< 16.5V for the 12V versions or < 33V for
24V versions.
• Reduce the load / remove the short circuit
• The load is not suitable as it requires higher
power to operate. Use an inverter with
higher power rating.
• If the unit goes into permanent overload
again after resetting and removing the load
completely, the unit has become defective.
Call Technical support.
NOTE: The unit will be latched in this shutdown condition and will require manual reset.
To reset, switch OFF the power ON/OFF switch,
wait for 3 minutes and then switch ON again.
Before switching on again, remove the cause
of the shut-down.
Check that the fans are working. If not, the fan
control circuit may be defective. Call
Technical Support.
If the fans are working, check that the ventilation
slots on the suction side and the openings on the
discharge side of the fans are not obstructed.
If the fans are working and the openings
are not obstructed, check that enough cool
replacement air is available. Also check that the
ambient air temperature is less than 40ºC.
Reduce the load to reduce the heating effect.
After the cause of overheating is removed and
the unit cools down sufciently, it will reset
automatically.
OPERATING TEMPERATURE RANGE-20 to 40˚C / -4 to 104˚F
STORAGE TEMPERATURE-30 to 70˚C / -22 to 158˚F
RELATIVE HUMIDITY90%, non condensing
DIMENSIONS
(W X D X H), MM282 x 415 x 101282 x 415 x 101
(W X D X H), INCHES11.1 x 16.3 x 4.011.1 x 16.3 x 4.0
WEIGHT
KG5.95.9
LBS13.013.0
NOTES:
1. All power ratings are specied for resistive load at Power Factor = 1.
2. All specications given above are at ambient temperature of 25°C / 77°F.
3. Specications are subject to change without notice
SECTION 13 | Warranty
3 YEAR LIMITED WARRANTY
PST-60S-12E / PST-60S-24E / PST-100S-12E / PST-100S-24E / PST-150S-12E / PST-150S-24E /
PST-200S-12E / PST-200S-24E manufactured by Samlex America Inc. (the “Warrantor“) are
warranted to be free from defects in workmanship and materials under normal use and
service. The warranty period is 3 years for the United States and Canada, and is in effect
from the date of purchase by the user (the “Purchaser“).
Warranty outside of the United States and Canada is limited to 6 months. For a warranty
claim, the Purchaser should contact the place of purchase to obtain a Return Authorization Number.
The defective part or unit should be returned at the Purchaser’s expense to the authorized location. A written statement describing the nature of the defect, the date of purchase, the place of purchase, and the Purchaser’s name, address and telephone number
should also be included.
If upon the Warrantor’s examination, the defect proves to be the result of defective
material or workmanship, the equipment will be repaired or replaced at the Warrantor’s option without charge, and returned to the Purchaser at the Warrantor’s expense.
(Contiguous US and Canada only)
No refund of the purchase price will be granted to the Purchaser, unless the Warrantor
is unable to remedy the defect after having a reasonable number of opportunities to do
so. Warranty service shall be performed only by the Warrantor. Any attempt to remedy
the defect by anyone other than the Warrantor shall render this warranty void. There
shall be no warranty for defects or damages caused by faulty installation or hook-up,
abuse or misuse of the equipment including exposure to excessive heat, salt or fresh
water spray, or water immersion.
No other express warranty is hereby given and there are no warranties which extend
beyond those described herein. This warranty is expressly in lieu of any other expressed
or implied warranties, including any implied warranty of merchantability, tness for the
ordinary purposes for which such goods are used, or tness for a particular purpose, or
any other obligations on the part of the Warrantor or its employees and representatives.
There shall be no responsibility or liability whatsoever on the part of the Warrantor or
its employees and representatives for injury to any persons, or damage to person or
persons, or damage to property, or loss of income or prot, or any other consequential
or resulting damage which may be claimed to have been incurred through the use or
sale of the equipment, including any possible failure of malfunction of the equipment,
or part thereof. The Warrantor assumes no liability for incidental or consequential damages of any kind.
Samlex America Inc. (the “Warrantor”)
www.samlexamerica.com
52 | SAMLEX AMERICA INC.
NOTES:
NOTES:
54 | SAMLEX AMERICA INC.
NOTES:
Contact
Information
Toll Free Numbers
Ph: 1 800 561 5885
Fax: 1 888 814 5210
Local Numbers
Ph: 604 525 3836
Fax: 604 525 5221
Website
www.samlexamerica.com
USA Shipping Warehouses
Kent, WA
Plymouth, MI
Canadian Shipping Warehouse
Delta, BC
Email purchase orders to
orders@samlexamerica.com
11001-PST-60S-100S-150S-200S-12E-24E-1119
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.