1.1Safety instructions and warnings for user .......................................................................................... 7
1.2Declaration of icons ............................................................................................................................ 7
1.3Intended use ....................................................................................................................................... 8
1.4General hints for process reliability .................................................................................................... 8
2Technical data ........................................................................................................................................ 9
2.1L20 Technical data ............................................................................................................................. 9
2.2Sensor system LAAS40 .................................................................................................................... 10
2.3Sensor system LAAS40+.................................................................................................................. 10
3.2Control unit ....................................................................................................................................... 14
6.5External I/O control ........................................................................................................................... 55
10.4Replacement of fuses .................................................................................................................... 109
10.5Data backup via fieldbus interface ................................................................................................. 110
10.6Data backup via USB interface ...................................................................................................... 110
10.7Firmware update via USB interface ............................................................................................... 110
10.8Spare parts .................................................................................................................................... 110
11Technical records .............................................................................................................................. 111
12Order data .......................................................................................................................................... 117
12.1Versions of control unit L20 ........................................................................................................... 117
12.2Sensor systems ............................................................................................................................. 117
12.3Sensor spare parts ......................................................................................................................... 118
13.2System configuration form ............................................................................................................. 119
4
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 5
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
Declaration of conformity according to EC directives
Manufacturer: Roland Electronic GmbH
Otto-Maurer-Str. 17
DE 75210 Keltern
Product name:
Product type:
Roland Electronic GmbH declares that the product listed above complies with the requirements of
the EMC directives listed below.
Applied Directives:
2006/95/EG Low Voltage Directive
EN61010-1: 2010
L20
Double Sheet Control System
R1000 series
De
claration of conformity
2004/108/EG: EMC Directive
EN61000-6-2: 2005-08 EN61000-6-4: 2007-01
Date of mark’s apposition: 04.03.2015
Keltern, 04.03.2015
Place, Date Signature Function of the signer
Managing Director
The declaration confirms the compliance with the cited directives. However, it is not any implied warranty of fitness for a
particular purpose especially as it may relate to product liability.
The safety instructions and warnings must be observed.
ISO 9001 : 2008
Reg.-no. 5152 QM08
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
5
Page 6
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
Blank page
6
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 7
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
1 Safety advice
1.1 Safety instructions and warnings for user
This manual contains all information required for the correct operation of the Roland equipment.
It has been written for technically qualified personnel.
Unauthorized tampering with the unit, especially ignoring the warnings in this manual can cause
malfunction and damage to the unit. Only authorized personnel should be allowed to make
changes to the unit and perform cable connections especially the power supply.
Should it be necessary, e.g. in case of service or repair, to make measurements within the unit,
then all customary accidents prevention procedures should be observed. Only professional
electrical tools should be used.
NoteThe factory pre-settings – especially the upper / lower limit values – have
Diverging settings can impair the machine protection.
Safety instructions for handling of laser sensors!!
been chosen such that an optimal machine protection is ensured.
Safety advice
Caution! Laser radiation! Do not stare into the beam!
1.2 Declaration of icons
Warning – Laser radiation!
Risk to the eyes by laser radiation.
Attention - Damage of construction units!
Reference to a potential imminent situation, which can result in damage to the
product or environs.
Note
Useful reference to an application or deepening information.
Do not stare into the reflected beam.
Max. power: 1 mW
Impuls duration: max. 6.4 ms
Wavelength: 658 nm
Medium: Semi conductor laser
Laser class II (EN 60825-1)
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
7
Page 8
Manual
Double Sheet Control System R1000 series L20
Safety advice B0063191 / 1.3
with integrated fieldbus interface
1.3 Intended use
Flexible Manufacturing Systems in the sheet processing industry require reliable Double Sheet
Control systems in order to protect presses and other sheet processing machines against damage
caused by feeding multiple sheets.
The Double Sheet Detector R1000 L20 was specifically developed for this technical environment.
The reliable function of the Double Sheet Detector depends therefore most importantly on the
selection of the correct sensors and the mounting of the sensors.
1.4 General hints for process reliability
The process security of the system is influenced by the following factors:
• Stability of the measuring values
• Setting of under-gauge threshold and over-gauge threshold
• Evaluation of the status signals
Stable measuring conditions will result in stable measuring results. Varying measuring results are
undesirable, because in such cases the user is inclined to decrease the under-gauge threshold
LOW and to increase the over-gauge threshold UP. On doing so, the user puts up with the
drastically increasing risk of not detecting a double sheet.
The following external factors decisively influence the stability of measuring results and need to be
considered for operation of a double sheet detector:
• Optical characteristics of the material
• Tolerance in material thickness
• Contamination of the material
• Geometric conditions at the place of measurement (Stability of the sensor gaps)
• Contamination of the sensors (dirt, oil …)
From this some simple rules can be derived, which enable a high process security when abided by:
• Every different sheet (Thickness, material and contour) is measured with separate
measuring program.
• Adjust the switching thresholds as tight as possible!
• Keep the sensor gap constant!
• Make use of the air connection to keep the sensors clean!
Furthermore it is necessary that the machine control:
• checks all status signals of the L20,
• checks the 0-sheet signal.
While measuring, only the 1-sheet signal may occur. If 0-sheet or 2-sheet occurs, the measured
sheet may not be transported on. In such cases, the sheet will usually be removed.
• The machine controls needs to evaluate all status signals !
Checking-up through the 0-sheet signal is to assure that a sheet really is between the sensors
during measuring. If 0-sheet occurs while measuring, the measurement is not correct. For example,
a defective sensor holder might change the sensor gap. Monitoring the sheet thickness would then
only be seemingly performed.
In case of double sheet severe consequences could then result.
8
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 9
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
2 Technical data
2.1 L20 Technical data
Technical Data L20-XX-S L20-3-XX-S
Operating voltage: 24 VDC, +6 V / -4 V
Power consumption: 18W
Switch on current::10 A for 1 ms
External fuse:1 Amp medium time lag
Weight: approx. 3.5 kg (7.71 lbs) approx. 3.9 kg (8.60 lbs)
Ambient temperature: 0 - 50 °C (30 - 122° F)
Wall mount enclosure:
Protection category: IP65
L20-XX-S: approx. 225 x 206 x 112 mm (L x H x T)
approx. 8.9 x 8.1 x 4.4 inch (L x H x D)
L20-3-XX-S: approx. 225 x 206 x 132 mm (L x H x T)
approx. 8.9 x 8.1 x 5.2 inch (L x H x D)
Additional characteristics:
• 255 parameter sets memory
• Programming via front panel keys or fieldbus
• 3 potential free optocoupler inputs 24 VDC with common external supply:
Specification
min. switching voltage HIGH: 13 VDC min. switching voltage LOW: 0 VDC
max. switching voltage HIGH: 30 VDC max. switching voltage LOW: 8 VDC
• 5 potential free outputs with positive external supply
Specification
max. switching voltage: 30 VDC max. switching current: 500 mA
with integrated fieldbus interface
Technical data
Attention In case of inductive load a coil protection diode should be used.
Otherwise the signal output could be destroyed by the excess
voltage generated by switching the inductive load off.
• Fieldbus interface (depending on type of unit)
Interfaces
Profibus-DP Interface according to EN 50170, Protocol
Version 1.10, max. baud rate 12 Mbit/s
CanOpen Interface, acc. to DS301 v4.02 compliantProfiNet IO Interface
CC-Link V1 EtherNet/IP
EtherCAT
DeviceNet communication adapter (profile number 12)
acc. to ODVA specification (group two only server)
• Virtual RS232 interface (via USB) for data backup
• USB interface for Firmware update
Included device accessories:
• Fieldbus plug
• Plug for connecting to the power supply, inputs and outputs
• USB cable for data backup, restoring data and for performing the firmware update
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
9
Page 10
Manual
Double Sheet Control System R1000 series L20
System description B0063191 / 1.3
with integrated fieldbus interface
2.2 Sensor system LAAS40
Technical data
Application: Double Sheet Control
Material thickness: 0.3 - 15 mm (at nominal sensor distance Ax = 40 mm)
Repetition accuracy: +/- 0.05 mm
Measuring principle:
Laser triangulation, Laser Class 2, EN 60825-1
Class of protection: IP54
Weight: approx. 2 kg (4.409 lbs) – without mounting angle and alignment aid
Material of enclosure: Aluminum
Sensor cable: Each pluggable with 0.5 m (19.68 in) length
Air connection: Tube, 8 mm outer diameter
2.3 Sensor system LAAS40+
Technical data
Application: Double Sheet Control
Material thickness: 0.3 - 15 mm (at nominal sensor distance Ax = 40 mm)
Repetition accuracy: +/- 0.05 mm
Measuring principle:
Laser triangulation, Laser Class 2, EN 60825-1
Class of protection: IP54
Weight: approx. 2.2 kg (4.85 lbs) – without mounting angle and alignment aid
Material of enclosure: Aluminum
Sensor cable: Each pluggable with 0.5 m (19.68 in) length
Air connection: Tube, 8 mm outer diameter
Beam control: Photo element
2.4 Sensor cable
Cable marking:
SCL20S-GG with straight cable socket at the sensor and straight cable plug at the unit
Technical data
Cable length: From 0.5 m to 50 m, pluggable
Cable bending radius: 50 mm at fixed wiring; 100 mm at flexible wiring
Cable diameter: 7.1 mm
Suitable for drag chains, oil proof, PUR jacket; Superflex TRONIC[C]PUR TP 4 x 2 x 0.25 mm²
2.5 Beam control cable
Cable marking:
SC5M12S-GG with straight cable socket at the sensor and straight cable plug at the unit
Technical data
Cable length: From 0.5 m to 50 m, pluggable
Cable bending radius: 50 mm at fixed wiring; 100 mm at flexible wiring
Cable diameter: 5.3 mm
Suitable for drag chains, oil proof, PUR jacket; Superflex TRONIC[C] UL 5 x 0.25 mm²
10
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 11
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
3 System description
The L20 is based on the product platform R1000 and consists of three components:
• the control unit
• one to three sensor systems (each with two sensors and brackets)
• sensor cables
with integrated fieldbus interface
System description
*SCL20S-GG
RBA
**
LAS40
LAAS40
LAS40
A1 B1 C1A2 B 2 C2A3 B3 C3
*
*
SC5M12S-GG
*
*
SC5M12S-GG
*SCL20S-GG
AS40+
L
AS40+
L
LAS40
LAS40
Kanal 1
Channel 1
LAAS40+
LAS40+
LAS40+
LAS40
LAS40
Kanal 2
Channel 2
LAAS40+
Kanal 3
Channel 3
*
*
LAS40+
LAS40+
LAAS40 +
LAS40
LAS40
SC5M12S-GG
L20-XX-SL20-3-XX-S
Fig. 1: System L20
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
11
Page 12
Manual
Double Sheet Control System R1000 series L20
System description B0063191 / 1.3
with integrated fieldbus interface
3.1 Measurement principle
The function of the Double Sheet Detector is based on the principle of laser triangulation. The
sensor system consists of two sensors which measure the distance.
If the total distance is known it is possible to calculate the sheet thickness.
A
A
x
BD
x-(A+B)
D= A
Fig. 2: Measurement principle
3.1.1 Planning information for mechanics
The total distance Ax of both sensors from each other has a great influence on the measurement
precision.
Important An appropriate stable and rigid mechanism is required.
Possible determining factors are also:
1. Thermal expansion
2. Vibrations
3. Impacts, press travel
4. Force and torque effects
These factors must be considered sufficiently when dimensioning the mechanics and the sensor
mounting. Permissible deviations Delta Ax must be smaller than 1/6 of the smallest thickness D
to be measured.
Example: For a reliable monitoring of sheets for double sheet detection with a nominal thickness of
0.3 mm, the permissible deviation Delta Ax is:
+/- 0.3 mm / 6 = +/- 0.05 mm.
min
12
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 13
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
Considering the typical measurement inaccuracy of +/- 0.05mm of the LAS40 sensors itself,
therefore a total error of +/- 0.1mm may occur.
Sheet thickness 0.3 mm: -> measuring value between 0.2 mm and 0.4 mm
Sheet thickness 0.6 mm: -> measuring value between 0.5mm and 0.7mm
For safe operation, the upper limit must be set to 0.45mm (= 150% of the nominal thickness) and
the lower limit to 0.15 mm (= 50% of the nominal thickness).
If the limits 150% respectively 50% are not sufficient, a calibration must be performed.
When dimensioning the mechanics and the sensor mounting, the Delta values Ax (permissible
deviation of the base distance due to thermal expansion, vibrations, impacts, press travel) must be
considered: According to the smallest sheet thickness, following deviations must be observed:
with integrated fieldbus interface
System description
LAS10
Delta Ax [mm]
Fig. 3: Deviations for LAS10
0,6
0,5
0,4
0,3
0,2
Delta Ax [mm]
0,1
0
0 12 3 4
Fig. 4: Deviations for LAS40
LAS10
Dmin [mm]
LAS40
LAS40
Dmin [mm]
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
13
Page 14
Manual
Double Sheet Control System R1000 series L20
System description B0063191 / 1.3
with integrated fieldbus interface
LAS200
0,9
0,8
0,7
0,6
0,5
0,4
0,3
Delta Ax [mm]
0,2
0,1
0
01 2 3 4 5 6
Dmin [mm]
Fig. 5: Deviations for LAS200
3.1.2 Planning information for calibration
LAS200
If the values Delta Ax cannot be achieved, a regular calibration may be helpful.
Ideally, a gauge block is provided in mechanics. This can be done via a pneumatic cylinder and is
then automated via PLC control.
3.1.3 Planning information for air blow-off
The operation of the system in ambience containing oils, as it occurs at press lines in the
immediate vicinity of oiling is generally possible if following is respected:
1. The air blow-off of the sensors is used.
2. The system test of the L20-3-XX-S (only LAASxx+ sensors) is accessed cyclical via PLC.
3. The sensors are well accessible for cleaning.
Normally the air blow-off is sufficient to allow reliable operation in vicinity of oiling. However, failure
of air blow-off, can cause serious contamination. This requires the cleaning of the sensor optics.
Therefore, in any case, the safe access to the sensors must be ensured.
3.2 Control unit
The L20 is based on the product platform R1000.
Major features of the control unit:
• Programmable for 255 different sheet thicknesses / types of sheets
• Fieldbus interface for the control, operation and data exchange with the PLC
• Calibration of the measuring point with a calibration sheet
• Digital display of sheet thickness and operating parameters
• Monitoring of over gauge and under gauge limits
• Monitoring of operating voltage and cable breakage
• Optocoupler for direct I/O control via the PLC for fast measurement operations
• Software firmware update
• Data backup via fieldbus interface or USB interface
14
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 15
Manual
b
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
3.2.1 Versions of the control unit L20
The control unit article key is coded as follows:
Control unit L20 with fieldbus interface
all sensors are directly connected at the control unit by pluggable contacts.
L20- XX-S
L20-3-XX-S
A B C D
* 1 is omitted in article key for the 1-channel control unit
The article key above leads to following version of the control unit:
L20-X-S:
L20-3-XX-S
Data backup via
fieldbus or serial
USB interface
Control unit for connecting 1 pair of sensors in wall mounting, fieldbus interface
Control unit for connecting up to 3 pairs of sensors in wall mounting, fieldbus
interface
System description
A Type of unit L20
B Measuring channels
C Fieldbus code XX Bus code
D Connection S Cables pluggable
XX Bus code
PR Profibus-DP
DNT DeviceNet (A-coded)
PN ProfiNet IO
CP CanOpen
CC CC-Link
EN EtherNet/IP
ET EtherCAT
„ „* 3 1 channel unit
1 channels unit
3.2.2 Parameters of the control unit
The L20 provides for extensive configuration. So, different customer requirements can be served.
Configuration is performed by setting system parameters, adjust parameters and program
parameters. System parameters are set only once during commissioning, and will then remain
unchanged. Program parameters contain items which are material and job depending, and enable
individual adaptation to the measuring task. The adjustment parameters contain the adjustment of
the measuring point.
The parameters are explained in depth in the chapter 7.3 „Operation“.
Pay special attention to the program parameters „low“, „up“ and „moving average above xx ms“
The switching thresholds of the status signals depend on the settings of „low“ and „up“.
The measuring signal is fed to a window comparator. The signal “0-sheet“ is generated when the
measuring signal falls below the lower switching threshold “ low”. The lower switching threshold
“low” can be set from 1...100%. The signal “2-sheet“ is generated when the upper switching
threshold is exceeded. The upper switching threshold “up” can be set from 100...180%. If the
measuring value is within both limits, the signal “1-sheet“ is generated.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
15
Page 16
Manual
Double Sheet Control System R1000 series L20
System description B0063191 / 1.3
with integrated fieldbus interface
The preset values (up=120% resp. low=80%) should only be changed under the following aspects:
1. Target: Increasing the process reliability
Prerequisite: Very stable measurement values
Implementation: Restrict the 1-sheet area. This is done by decreasing the “low” value
and/or increasing the “up” value.
2. Target: Keep the system function alive despite fluctuating measuring values
(e.g. mechanical problems)
Prerequisite: Exceptional situation till correction of the problem.
A reduction of the process reliability is hereby taken into account by the operator.
Implementation: Expand the 1-sheet area temporarily.
„moving average above xx ms“
Defines the time which is required by the system to perform an average measurement.
See chapter 8.3 “Averaging time t
and Measuring time tm”
a
16
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 17
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
4 Mounting
The mounting of the Double Sheet Detector R1000 L20 determines the measurement accuracy
and the reliability of operation. The system was designed for operating in rough industrial
environments. However, the following mounting instructions should be observed in order to
minimize mechanical, thermal, and electromagnetic influences on the operation.
4.1 General mounting instructions
The enclosure for wall mounting meets IP65 and is designed for mounting the enclosure close to
the sensor location. By using short sensor cables, the influence of interference on data
transmission is reduced.
The control unit should be installed in locations where no vibration exists and no additional heat is
transferred into the system (even better reduce the heat in the control unit). In addition the control
unit should be installed in such a fashion that it can be easily opened for service purposes. During
the operation the control unit and the sensors should be under visual control of the operating
personnel.
Attention Strong vibrations and additional heat can damage the control unit.
Mounting
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
17
Page 18
Manual
Double Sheet Control System R1000 series L20
Mounting B0063191 / 1.3
with integrated fieldbus interface
4.2 Dimensions of the system
4.2.1 Dimensions of the unit in industrial enclosure
1-channel unit L20-XX-S and 3-channel unit L20-3-XX-S
* L20-XX-S: 112 mm
L20-3-XX-S: 132 mm
18
Fig. 7: Dimensions of the 1-channel unit in wall mount enclosure in mm.
Note Observe the clearance for connecting the plugs.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 19
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
4.3 Mounting of sensors
The sensors must be installed opposite each other in alignment. If circumstances require it, the
mechanical mounting angles can be rotated or swapped.
To ensure an accurate measurement, ensure that the laser axes of the two sensors are identical
(on each other). For this purpose Roland Electronic provides the bracket SHLAS40H, which allows
easy alignment (not shown). The sensors provided within the sensor system LAAS40 have already
been aligned using the bracket SHLAS40H.
For an initial installation, they can be mounted directly. If the sensors are adapted or exchanged,
they must be aligned before mounting.
with integrated fieldbus interface
Mounting
The provided bracket SHLAS40H is not shown above.
Fig. 8: Dimensions of the sensors
All dimensions in mm.
To prevent contamination of the sensors it is necessary to provide a continuous air blow-off.
See chapter 4.3.8 "Air blow-off for laser sensors".
Attention In general baffles must be mounted in order to prevent damage to
the sensors at incoming coil / sheet.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
19
Page 20
Manual
Double Sheet Control System R1000 series L20
Mounting B0063191 / 1.3
with integrated fieldbus interface
4.3.1 Procedure at mounting
The alignment-bracket must be removed only at the end of the mounting process!
1. Screw the sensors loosely on the angles.
2. Screw the angles to the system, but do not tighten the screws. Make sure that no mechanical
tension occurs between the sensor enclosures.
3. Tighten all screws. Take care that no tensions persist between the parts.
4. Finally remove the alignment-bracket.
5. At L20-3-XX-S with LAAS40+:
Verify sensor alignment with adjust parameter 4, “alignment”.
Attention After mounting a measuring point calibration should be performed to
the L20. See also chapter 8.4 "Measuring point calibration".
4.3.2 Alignment of the sensors at remounting, exchange or change
1. For alignment of the sensors place the sensors one to each other with the mounting side on a
adjusting plate or an equally smooth surface.
2. Lay a gauge block or equivalent with 40 mm between the sensors.
3. Screw the adjustment-bracket tight. The screws may be screwed in this case depending on the
mounting situation from both sides in order to be easily removed after the alignment. Thereby
make sure that the sensors lay plane to the plate and fit firmly against the gauge block.
4. Fasten the sensor pair as described previously.
Attention After mounting a measuring point, a calibration should be performed
to L20. See also chapter 8.4 "measuring point calibration".
4.3.3 Control of the laser beam axis
After mounting or adjusting a sensor it might be necessary to control the axis of the laser beam.
In the program switch the „sensor alignment help“ on, see chapter 7.4.3 substructure „alignment
parameters“ (details in chapter 7.8)
To check hold a non-reflective piece of paper at various points in the beam. The sensors will flash
alternately. The laser beam is visible through the paper, so that a properly aligned system should
have no offset between the two points on the paper. At a larger displacement or angular deviation
of the laser beam, an inclined position of the sheet can lead to variations in measurements.
At an offset of several millimetres, the sensors should be realigned. At usage of LAAS40+, the
alignment can be verified with adjust parameter 4, “alignment”.
Warning – Laser radiation!
Eye hazard from laser radiation. Do not stare into the laser beam.
20
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 21
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
4.3.4 Position and location of the sheet between the sensors
Ideally the sheet should be transferred through the middle of the sensor gap. This guarantees
reliable and accurate results of the measurement.
The sheet must be guided perpendicular to the laser axis; otherwise it comes due to geometry to
measurement errors.
Avoid mechanical damage due to incoming material and take appropriate measures such as
baffles.
*
Mounting
Fig. 9: Position of the sheet between the sensors
4.3.5 Sensor gaps
The gap between the sensors is derived from the sensor name in mm. The sensor LAAS40 has a
gap of the sensors of 40 mm with a tolerance of ± 2.5 mm.
In the final mounted and aligned state the start-up at the L20 must be done by performing the
"Measuring channel calibration".
This is done with a calibration sheet having a defined thickness in order to define the total distance
between the sensors.
This total distance serves as a reference for the thickness measurement and must remain constant
during operation.
This requires a correspondingly stable and rigid mechanism, see chapter 3.1.1 "Planning
Information for Mechanics".
Transportrichtung
Transport direction
*
*Einlaufschikanen
Inlet baffles
A
1
d
A
Ax
2
A
A
=
1
2
Blechmittigdurchführen!
Guide the sheed centered!
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
21
Page 22
Manual
Double Sheet Control System R1000 series L20
Mounting B0063191 / 1.3
with integrated fieldbus interface
4.3.6 Electromagnetic interference
Electromagnetic interference can affect the measurement accuracy of sensors. Therefore it is not
allowed to mount the sensors in direct proximity of equipment which emits electromagnetic
interference.
The sensor cables should not be laid adjacent to conductions having a large disturbance potential,
e.g. power cables. This applies especially to longer cable lengths.
4.3.7 Compliance with the transport direction at sensor mounting
Mounting of the sensors regarding to the
following illustration will ensure reliable double
sheet detection.
Fig. 10: Direction of transport
When mounting in "longitudinal direction",
the measuring must be performed only
dynamically (sheet is not allowed to stand
still between the sensors).
22
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 23
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
4.3.1 Air blow-off for laser sensors
To prevent contamination of the sensors it is necessary to provide a continuous air blow-off.
This is done by connecting an air hose with 8 mm outer diameter.
A permanent air blow-off of approx. 0.5 bar pressure is recommended, alternatively 5 bar
cyclic cleaning.
Possible contamination Air blow-off
Oil, oil mist, water Continuous, approx. 0.5 bar
Rough tinder Continuous, approx. 5 bar
Dust, fine tinder Cyclic, approx. 5 bar
Note Air loss causes contamination!
To disconnect the hose use an 8 mm or 9 mm open-ended wrench as shown in Fig. 6, right.
For the supplied purging air there are requirements regarding purity and freedom from oil.
The requirements are:
Operating medium: compressed air according to ISO 8573-1: 2010 [-: 9: -] inert gases (see
table)
Air purity class at the output: compressed air in accordance with ISO 8573-1: 2010 [1: 7: 2] inert
gases (see table)
Oil freedom: remaining oil content 0.01 mg / m
Class
ISO 8573-
1:2010
0
1
2
3
4
5
6
7 5 - 10
8 0,5 - 5
9 5 - 10
X > 10 > 10> 10
We recommend a filter and filter regulator from Festo HE-D Mini series.
As determined by the device users, more stringent requirements than class 1
≤ 20.000
≤ 400.000 ≤ 6000≤ 100
A process-safe operation will be therefore no longer guaranteed!
≤ 400
≤ 90.000≤ 1000
≤ 10
≤ 10.000
≤ 100.000
Mounting
3
Quantity Quantity
0,01
0,1
1
5
≤ 0,5
≤ 5
(Pressure dew
point)
≤ -70
≤ -40
≤ -20
≤ +3
≤ +10
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
23
Page 24
Manual
Double Sheet Control System R1000 series L20
Mounting B0063191 / 1.3
with integrated fieldbus interface
The service unit consists of:
On/off valve HE-D-Mini 170681
Filter regulator unit LFR-1/8-DB-7-0-
Mini 537651
Micro filter LFA-D-Mini 192563
Fig. 11: Service unit
Attention In general baffles must be mounted in order to prevent damage to
the sensors at incoming coil / sheet.
24
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 25
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
5 Electrical installation
5.1 General instructions
The sensor cables should be kept as short as possible in order to minimize the influence of
electromagnetic noise. Cable shields must be connected according to the connection diagrams
only and should not have any additional connections.
Attention Damaged cable installations may result in additional electrical
connections. This can disturb the measured values.
5.1.1 Mounting instruction for M12 connectors with key way
These connectors have a positioning nose at the plug and a positioning slot at the receptacle.
These items are designed to prevent incorrect connecting positions.
For this reason if plug and receptacle are connected together then these positioning features
should fit to each other.
Only then it is possible to connect plug and receptacle without force and with proper pin
configuration.
A Positioning slot at female connector
B Positioning nose at male connector
C Threaded arresting ring
D Connector assembly ring.
Never turn this ring when arresting the plug
with the arresting ring C.
Electrical installation
Fig. 12: Positioning facility and arresting ring
When the connection is established correctly as described, plug and socket can be arrested with
the arresting ring.
AttentionTurn only the threaded arresting ring C !
If the whole plug becomes turned, the locking facility and the contact
pins will break and the connector will become useless.
Attention Under any circumstances it is not allowed to use any part of a
plug connection as a holder for the installation of the
counterpart.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
25
Page 26
Manual
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
Electrical installation B0063191 / 1.3
5.2 Configuration of connectors
5.2.1 Configuration of connectors at L20-XX-S
Legend
X1 Connection for supply and
inputs
Fig. 13: Connections at the L20-3-XX-S
X2 Socket for outputs
X3 Socket for Fieldbus output
X4 Socket for Fieldbus input
X5 Grounding screw bolt
R Not in use
B Socket for sensor B
A Socket for sensor A
(Sockets A and B are identical and
therefore interchangeable)
The USB terminals are at the front
plate.
1)
the fieldbus connections are
specific to each type of fieldbus,
1)
1)
5.2.2 Configuration of connectors at L20-3-XX-S
Legend
X1 Connection for supply and
inputs
X2 Socket for outputs
X3 Socket for Fieldbus output
X6
XA1
X2
XB1
X3
XA2
XB2
XA3
XB3
X5
X4 Socket for Fieldbus input
X5 Grounding screw bolt
NoteWhen using only one pair of sensors they must be connected to
channel 1.
When using two pairs of sensors they must be connected to channel 1
and 2.
26
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 27
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
Electrical installation
5.2.3 Supply voltage connection and Optocoupler inputs (Connection X1)
Here, the supply voltage is connected, as well as the optocoupler inputs.
Allocation of power supply connection
Connector at control unit Input Suppliers / types / notes
Voltage supply Enclosure HAN 3A, EMI-type, metrical
view onto contacts
7-pin insert and PE, Pin contacts at control unit
Pin1 +24VDC
Pin 2 GND
Pin 3 IN0 + 1st Opto coupler input +
Pin 4 IN1 + 2nd Opto coupler input +
Pin 5 IN2 + 3rd Opto coupler input +
Pin 6 PLC GND Voltage supply PLC GND
Pin 7 PLC +24VDC Voltage supply PLC +24VDC
Pin 8 Shield / ground Internal at enclosure (ground)
A corresponding cable plug (/contacts) is part of the standard scope of supply.
Note Pin 6 is connected with pin 7 of connection X2.
Pin 7 is connected with pin 1 of connection X2.
Note The cable for the voltage supply should be kept as short as possible.
Attention Pin 1 (+24 VDC) must not be connected with operation earth.
Optocoupler inputs for fast measurements
For real-time measurements it is possible to start measurement with external optocoupler inputs.
The optocoupler function with a control voltage of 20 to 28 VDC. For connections see table on
page 40 "Pin configuration of voltage supply connection".
The combination of measurement start 1, 2 and 3 can be adjusted in the system configuration
menu.
Note “Measurement start” signals can be issued either via the process channel
or via an opto coupler. Simultaneous measurement start” signals result in
fault messages.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
27
Page 28
Manual
Double Sheet Control System R1000 series L20
Electrical installation B0063191 / 1.3
with integrated fieldbus interface
5.2.4 Connection of Optocoupler outputs (Connection X2)
Note The optocoupler inputs are placed at the supply voltage connection X1
The corresponding cable plugs are part of the standard scope of supply.
Allocation of optocoupler outputs
Connector at control unit (Connection X2) Suppliers / types / notes:
Optocoupler output
2
1
37
8
6
4
5
NotePin 7 is connected with pin 6 of connection X1. Pin 1 is connected with pin 7 of connection X1.
Optocoupler outputs for fast switching operation
For reasons of velocity and for diagnostic purposes it could be useful to issue the relevant
switching signal 0-sheet, 1-sheet, 2-sheet via a real-time interface. By doing this latency periods
and cycle times of fieldbus communications are eliminated.
M12, 8-pin, A-coded, female
connector at control unit
(flange socket)
pin 1 PLC +24VDC External supply PLC +24VDC
pin 2 OUT0 Signal 0-sheet
pin 3 OUT1 Signal 1-sheet
pin 4 OUT2 Signal 2-sheet
pin 5 OUT3 Signal Enable (Ready for operation)
pin 6 OUT4 Signal Warning
pin 7 GND PLC Voltage supply PLC GND
pin 8 Shield / ground Internal at enclosure (common)
Binder type 713 and others
5.2.5 Fieldbus connection (Connection X3 and X4)
5.2.5.1 Profibus-DP
According to the Profibus-DP Organization (PNO) for the protection class IP67 a round connector
M12 with inverse coding should be used. A “T-Connector“ (TEE) is not necessary, because the
control unit is equipped with input and output connectors.
The corresponding cable plugs are part of the standard scope of supply.
NoteIf the L20 is the last participant in the bus, then an external terminating
Input (Connection X4) Output (Connection X3)
M12, 5-pin, B-coded, male connector at control unit M12, 5-pin, B-coded, female connector at control unit
251
3
4
View:
plug side
resistor should be placed into the open connector.
The resistor is not within the scope of supply.
Allocation of Profibus connection (Profibus-DP Slave)
Pin 1 +5V
Pin 2 Linie A
Pin 3 GND
Suppliers / types / notes: Binder, type 715 (B-coded) and others
Pin 4 Linie B
Pin 5 Shield/Earth
21
5
3
4
View:
plug side
28
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 29
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
5.2.5.2 DeviceNet (A-coded)
An M12 plug with inverse coding is used for the DeviceNet connection. A T-connector is not
necessary, because the control unit is equipped with input and output.
The corresponding cable plugs are part of the standard scope of supply.
Power consumption via DeviceNet 30mA
NoteIf the L20 is the last participant in the bus, then an external termination
Input (Connection X4) Output (Connection X3)
M12, 5-pin, A-coded, male connector at control unit M12, 5-pin, A-coded, female connector at control unit
12
5
3
4
View:
plug side
with integrated fieldbus interface
Electrical installation
resistor should be placed into the open connector. The resistor is not
included in the scope of supply.
Allocation of DeviceNet connection
Pin 1 Shield
Pin 2 V +
Pin 3 V -
Suppliers / types / notes: Binder, type 715 (A-coded) and others
Pin 4 CAN High
Pin 5 CAN Low
12
5
43
View:
plug side
5.2.5.3 CanOpen
An M12 plug with inverse coding is used for the CanOpen connection. A T-connector is not
necessary, because the control unit is equipped with input and output.
The corresponding cable plugs are part of the standard scope of supply.
M12, 5-pin, B-coded, male connector at control unit M12, 5-pin, B-coded, female connector at control unit
NoteIf the L20 is the last participant in the bus, then an external termination
resistor should be placed into the open connector. The resistor is not
included in the scope of supply.
Allocation of CanOpen connection
Input (Connection X4) Output (Connection X3)
Pin 1 shield
251
3
4
View:
plug side
Suppliers / types / notes: Binder, type 715 (B-coded) and others
Pin 2 n. a.
Pin 3 GND
Pin 4 CAN_H
Pin 5 CAN_H
4
View:
plug side
21
5
3
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
29
Page 30
Manual
Double Sheet Control System R1000 series L20
Electrical installation B0063191 / 1.3
with integrated fieldbus interface
5.2.5.4 EtherNet/IP
The corresponding cable plugs are part of the standard scope of supply.
System in industrial enclosure
Round-shape connector, M12, 4-pin., D-coded, socket contact at control unit (Connection X4)
Pin 1 TD +
Pin 2 RD +
Pin 3 TD –
Pin 4 RD –
Plug enclosure Shield
2
1
4
View:
Plug side
3
5.2.5.5 ProfiNet IO
The corresponding cable plugs are part of the standard scope of supply.
Allocation of ProfiNet IO connection
System in industrial enclosure
Round-shape connector, M12, 4-pin., D-coded, socket contact at control unit
2
1
4
View:
Plug side
3
Pin 1 TD +
Pin 2 RD +
Pin 3 TD –
Pin 4 RD –
Plug enclosure Shield
5.2.5.6 CC-Link
The protocol version 1 of CC-Link is supported. An M12 plug with A-coding is used for the CC-Link
connection. A T-connector is not necessary, because the control unit is equipped with input and
output.
The corresponding cable plugs are part of the standard scope of supply.
Note If the L20 is the last participant in the bus, then an external
termination resistor should be placed into the open connector. The
resistor is not included in the scope of supply. A resistor between DA und DB 110 Ohm or 130 Ohm ½ Watt can be used.
Allocation of CC-Link connection
Input (Connection X4) Output (Connection X3)
M12, 4-pin, A-coded, male connector at control unit M12, 5-pin, A-coded, female connector at control unit
2
1
3 4
View:plug side
Suppliers / types / notes: Binder, type 715 (A-coded) and others
Pin 1 SLD
Pin 2 DB
Pin 3 DG
Pin 4 DA
Pin 5 ---
12
5
43
View:plug side
30
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 31
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
5.2.5.7 EtherCAT
The corresponding cable plugs are part of the standard scope of supply.
Allocation of EtherCAT connection
Round-shape connector, M12, 4-pin., D-coded, socket contact at control unit
IN (Connection X4) OUT (Connection X3)
View: Plug side
with integrated fieldbus interface
2
1
3
4
Pin 1 TD +
Pin 2 RD +
Pin 3 TD –
Pin 4 RD –
Plug enclosure Shield
1
Electrical installation
2
3
4
5.2.6 Connection of earth ground (Connection X5)
For earth ground connection, the enclosure of the R1000 has an M6 threaded screw. Here the
grounding cable (copper), at least 1.5 mm² cross section must be connected to the earth ground of
the machine.
The connection is obligatory!
Attention The earth ground/central machine ground must not be
connected to + 24 VDC.
5.2.7 Encoder input (Connection X6)
The connection R has no function at this unit.
5.2.8 Connection R
The connection R has no function at this unit.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
31
Page 32
Manual
Double Sheet Control System R1000 series L20
Electrical installation B0063191 / 1.3
with integrated fieldbus interface
5.2.9 Sensor connection (Connections A and B)
The sensor cable SCL20-S-GG is connected at the control unit by plug. All sensors require this
cable type.
.
Note When using the sensor system LAAS40 the connection of the sensor
system with the sensor cables to the terminals A and B is arbitrary. If the
sensor system LAAS40+ is used, then Sensor A (with beam control) must
be mounted above and connected to the control unit at port A.
Connector enclosure isolated (no contact with shield)
Fig.10: Cable assignment of SCL20S-GG*
*Until October 2015 cables with a different connection, but with IDENTIC functionality have been delivered.
32
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 33
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
5.2.10 Beam control connection (Connection C)
The sensor cable SC5M12S-GG can be connected with the sensor and the control unit.
Electrical installation
Fig.10: Cable assignment of SC5M12S-GG
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
33
Page 34
Manual
Double Sheet Control System R1000 series L20
Electrical installation B0063191 / 1.3
with integrated fieldbus interface
Blank page
34
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 35
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
6 Communication with the PLC
The fieldbus interface contained in the R1000 enables the communication with a fieldbus master.
The data structure of the L20 enables the exclusive use of the cyclical communication data
transmission mode.
6.1 Fieldbus specific messages
The fieldbus messages are combined with other information in an info window.
This message can be recalled in the normal mode by pressing the ENTER key.
1
L20-PR-S
2
SV: 1 HVH: 0 HVA: 0
3
Profibus DP xxx
45 6
Fig. 15: Fieldbus specific messages of the R1000
7
Status messages
• Init: Display after start-up of the L20. This message is displayed until the initializing
process is completed.
• Online: The fieldbus interface is in operation
• Offline: The fieldbus interface is not in operation or displays a fault
Parameter channel messages
• Closed: The parameter channel is closed
• Open: The parameter channel is open
• Conflict: A collision occurred when opening the parameter channel
• Collis.: A collision occurred during parameter transmission
Bus (slave) addresses
• 1... : Possible Slave addresses, which can be adjusted via software depending on the
fieldbus type.
NoteThe messages are regularly updated and enhanced. It is therefore
possible that there are deviations to the messages described here.
Communication with the PLC
1 Control unit name
2 Software version, hardware version motherboard
and hardware version analogue board
3 Bus system message (here with Profibus-DP)
4 Bus status
5 Parameter channel status
6 Bus (slave) address
(only if Fieldbus with node bus address)
7 Fieldbus baud rate (only if Fieldbus with baud rate)
or MAC ID
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
35
Page 36
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.2 Data transmission communication
The L20 uses an IN/OUT configuration for the cyclical data exchange with the master. This means
that for each transmission direction a parameter channel with 8 Bytes as well as a process channel
with 16 Bytes is used.
The R100 is controlled via the process channel and via the parameter channel all system and
application data is available.
The following table shows the layout of the communication facility:
Inputs (PLC L20) Outputs (L20 PLC)
Byte Meaning Byte Meaning
BIN0 Management BOUT0 Management
BIN1 Program index BOUT1 Program index
BIN2 Parameter index BOUT2 Parameter index
BIN3 Application data byte 0 BOUT3 Application data byte 0
BIN4 Application data byte 1 BOUT4 Application data byte 1
BIN5 Application data byte 2 BOUT5 Application data byte 2
BIN6 Application data byte 3 BOUT6 Application data byte 3
Parameter channel
BIN7 Checksum BOUT7 Checksum
BIN8 Control BOUT8 Control signals (0-sheet, 1-sheet, 2-sheet)
BIN9 Program selection 1 – 255 BOUT9 Actual measuring program
BIN10 -- BOUT10 Measuring value, Measuring channel 1 High Byte
Measuring value, Measuring channel 1 High Byte
(identical with BOUT10)
Measuring value, Measuring channel 1 Low Byte
(identical with BOUT11)
6.3 Process channel
The process channel is implemented via the bytes 8 to 23.
36
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 37
Manual
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
B0063191 / 1.3
6.3.1 Process channel – functions and signals
Byte 8 to 11:
Inputs (PLC L20) Ausgänge (L20 PLC)
Byte.Bit Meaning Byte.Bit Meaning
BIN8.0
BIN8.1
BIN8.2
BIN8.3
BIN8.4
BIN8.5
BIN8.6
BIN8.7
BIN9.0
BIN9.1 BOUT9.1
BIN9.2 BOUT9.2
BIN9.3 BOUT9.3
BIN9.4 BOUT9.4
BIN9.5 BOUT9.5
BIN9.6 BOUT9.6
BIN9.7 BOUT9.7
BIN10.0
BIN10.1
BIN10.2
BIN10.3
BIN10.4
BIN10.5
BIN10.6
BIN10.7
BIN11.0
BIN11.1
BIN11.2
BIN11.3
BIN11.4
BIN11.5
BIN11.6
BIN11.7
System test
Measurement start
Calibration 6)
Dummy function 3)
--Clear 2-Blech / clear 0-1-2-outputs
Program switch
Reset function fault
Measuring program number for program
switching
---
---
---
---
---
---
---
---
---
---
---
Dummy Function 3)
Dummy Function 3)
---
---
Range (only L20-3-XX-S)
Explanation of summary output 0-sheet, 1-sheet and 2-sheet:
If the unit is operated in the sequencer mode (program with more sensors e.g. 1+2+3), the measurement result is formed as
summary output. Only the active sensors are included.
2-sheet is issued if at least one sensor detects 2-sheet.
1-sheet is issued if all sensors detect 1-sheet.
0-sheet is issued if no 2-sheet is detected but at least one sensor detects 0-sheet.
If the results of individual sensors are required, then interrogate bytes 12-23.
1)
If a fault occurs at the equipment an operator intervention is required e.g. memory error, low or missing voltage.
2),3), 4)
Footnotes see next chart “Byte 12 to 14”
5)
At R1000 systems with multiple measuring points, these outputs are issued as "summary output" for all measuring points;
as this equipment has only one measuring point available, the result of the measuring point 1 will be outputted.
6)
This function is implemented only in L20-3-XX-S (L20-XX-S in preparation).
This function is implemented only in L20-3-XX-S (L20-XX-S in preparation).
System test Measuring channel 1
(only at L20-3-XX-S)
For the outputs „0V active“ or „24V active“ is selectable in the device configuration. This also affects the I/O outputs.
The „Dummy Function“ sets the output „Function result“ only. This was implemented due to reasons of compatibility.
The output of the measured value is done in dependency of the chosen unit of measure at the fieldbus output and
the type of sensor. The values are displayed as follows:
Sensor type
LAAS10 (in preparation)
(micrometer)
0…15748 x 10-4 inch
(1/10000 inch)
BOUT12.0 Always „0“ (Low)
Sensor type
LAAS40
0…40000 x 10-3 mm
(micrometer)
(1/10000 inch)
High Byte measuring value
Measuring channel 1
Low Byte measuring value
Measuring channel 1
Sensor type
LAAS200 (in preparation)
0…20000 x 10-2 mm
(10 micrometer)
0…7874 x 10-3 inch
(1/1000 inch)
4)
4)
Example at
LAAS40
1000 = 1 mm
1000 = 0.1 inch
38
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 39
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
Bytes 15 to 17:
The following signals are used in the L20-3-XX-S unit version only.
Inputs (PLC L20) Outputs (L20 PLC)
Byte.Bit Meaning Byte.Bit Meaning
For the outputs „0V active“ or „24V active“ is selectable in the device configuration. This has also effect to the I/O
outputs.
3)
The „Dummy Function“ sets the output „Function result“ only. This was implemented due to reasons of compatibility.
4)
The output of the measured value is done in dependency of the chosen unit of measure at the fieldbus output and
the type of sensor:
Measuring unit
(mm or inch)
mm 0…20000 x 10-3 mm
inch 0…7874 x 10-4 inch
5)
This function is implemented only in L20-3-XX-S (L20-XX-S in preparation).
Sensor type
LAAS10 (in preparation)
(micrometer)
(1/10000 inch)
Sensor type
LAAS40
0…40000 x 10-3 mm
(micrometer)
0…15748 x 10-4 inch
(1/10000 inch)
High Byte measuring value
Measuring channel 3
Low Byte measuring value
Measuring channel 3
Sensor type
LAAS200 (in preparation)
0…20000 x 10-2 mm
(10 micrometer)
0…7874 x 10-3 inch
(1/1000 inch)
4)
4)
Example at
LAAS40
1000 = 1 mm
1000 = 0.1 inch
Bytes 21 to 23:
Bytes 21 to 23 are reserved for future extensions.
40
Note In the following timing diagrams all outputs and inputs via the bus are
designated as BOUT and BIN, in contrast, the opto coupler interface
uses OUT or IN.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 41
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
6.3.2 External single measurement via process channel
Communication with the PLC
Fig. 16: Timing diagram for start single measurement via process channel
1)
In case of “Function fault“, “Function result“ is not necessarily set.
2)
The measuring time depends on the time set for averaging.
Start “Measurement start“
wait until
“Function fault“ or “Function result“
In case of “Function fault“ then:
- Pause 100 ms
- Unset “Measurement start”
- Reset “Function fault“
In case of “Function result" then:
- Analyse
- Unset “Measurement start”
Explanation:
• If a fault occurs when initiating the function (for instance a previous function is still active) then
only the “Function fault“ is displayed. The “Function result“ will not be displayed. The other
outputs remain in their current status.
• If the fault occurs during execution, the “Function fault“ is displayed. The “Function result“ will not
be displayed (if the fault is connected to the function). The outputs remain in their current status.
• If the fault occurs after the result, e.g. by a faulty operation then this has no influence on the
“Function result“.
• If the “Measurement start“ cycle is shorter than the duration of the function then the
“Function result“ will not be displayed. However, the function is nevertheless executed!
For safety reasons the control should not be executed in this style!
• If the “Measurement start“ cycle is longer than the duration of the function then the
“Function result“ will be displayed as shown in the timing diagram.
Note Uncritical faults can be deleted via the process channel with the
“Reset function fault“ command.
Note The measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
systems. The cycle time of the PLC has not been taken into account.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
41
Page 42
Manual
s
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.3.3 External continuous measurement / External special via process channel
Measurement Start
(Warning, 0-sheet, 1-sheet, 2-sheet)
(Warning, 0-sheet, 1-sheet, 2-sheet)
BIN8.1
BOUT8.0
Function result
BOUT8.2
Function fault
BOUT8.3
Ready
BOUT8.4 - 7
OUT 0,1, 2, 4
1)
“1” if fault
“0” if fault
"0" active
"0" active
****
< 15 ms
15 - 250 ms
Fig. 17: Timing diagram for external continuous / external special measurement via process channel
1)
In case of “Function fault“ “Function result“ is not necessarily set.
2)
The measuring time depends on the averaging.
*
The status of the 0 -, 1 -, 2-sheet and warning outputs is refreshed via the fieldbus (BOUT8.4-7) with a refresh rate of
6 ms. Through the I / O outputs (OUT), the rate is 1 ms.
2)
< 15 m
Note The output “Function result“ is set with the appearance of the first
measurement value and then remains set.
NoteIn the “extern special” measurement mode the highest measured value
will be displayed and held at the outputs until a new measurement is
started.
NoteThe measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
systems. The cycle time of the PLC has not been taken into account.
42
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 43
Manual
s
Double Sheet Control System R1000 series L20
B0063191 / 1.3
6.3.4 Program switching
Program switching
Binary measurement program
Binary current measurement program
Function result
BIN8.6
BIN9.0 - 7
BOUT9.0 - 7
BOUT8.0
BOUT8.2
Function fault
BOUT8.3
Ready
with integrated fieldbus interface
Communication with the PLC
1)
“1” if fault
0V if fault
< 10 m
Fig. 18: Timing diagram for program switching
1)
In case of “Function fault“ “Function result“ is not necessarily set.
Note The measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
< 15 ms
systems. The cycle time of the PLC has not been taken into account.
Program no. Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
1 0 0 0 0 0 0 0 0
2 0 0 0 0 0 0 0 1
… … … … … … … … …
255 1 1 1 1 1 1 1 0
not used 1 1 1 1 1 1 1 1
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
43
Page 44
Manual
s
300 ms
s
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.3.5 System test
Note
L20-XX-S: The System test is planned for future extensions.
Currently the sensors are not checked.
L20-3-XX-S with LAAS40: The sensors used in the actual program are checked
for function.
L20-3-XX-S with LAAS40+: The beam control is checked at the sensors used in
the actual program; During the test no sheet is allowed to remain between the
sensors.
BIN8.0
System test
BOUT8.0
Function result
1)
BOUT8.2
Function fault
BOUT8.3
Ready
(Warning, 0-sheet, 1-sheet, 2-sheet)
(0-sheet, 1-sheet, 2-sheet)Warning,
Fig. 19: Timing diagram for system test
1)
In case of “Function fault“ “Function result“ is not necessarily set.
*L20-3-XX-S with LAAS40: 55 ms;
L20-3-XX-S with LAAS40+: 65 ms one measuring channel;
125 ms two measuring channels;
185 ms three measuring channels
BOUT8.4-7
OUT 3
ENABLE
OUT 0, 1, 2, 4
< 15 m
10 -
max. * ms
Note The measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
“1” if fault
0V if fault
< 15 m
systems. The cycle time of the PLC has not been taken into account.
44
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
In case of “Function fault“ “Function result“ is not necessarily set.
Note The measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
systems. The cycle time of the PLC has not been taken into account.
6.3.7 Calibration static (L20-XX-S only)
A static calibration is not possible with L20-3-XX-S. (L20-XX-S is in preparation)
BIN 8.2
Calibration
BOUT 8.0
Function result
BOUT 8.2
Function fault
OUT 8.3
Ready
Fig. 21: Timing diagram for calibration static
1)
In case of “Function fault“ = 1 “Function result“ will sometimes remain at 0.
1)
< 7 s< 15 ms
Note The measured timing periods were determined with 12 Mbit
Profibus. These timing periods can vary with different
transmission rates and bus systems. The cycle time of the PLC
has not been taken into account.
max. ? msmax. ? ms
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
45
Page 46
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.3.8 Calibration dynamic (L20-3-XX-S only)
During the dynamic calibration the sheet must be passed between the sensors.
BIN 8.2 / 12.2 / 15.2 / 18.2
Calibration
BIN 11.7 /14.7 / 17.7 / 20.7
Range
BOUT 8.0
Function result
BOUT 8.2
Function fault
OUT 8.3
Ready
1)
Calibration
Range
Range> 0 ms
> 350 ms
Fig. 22: Timing diagram for Teach-In 1-sheet – dynamic
Note The measured timing periods were determined with
12 Mbit-Profibus. These timing periods can vary with different
< 0.5 s
< 15 ms
transmission rates and bus systems. The cycle time of the PLC
has not been taken into account.
1)
In case of “Function fault“ = 1 “Function result“ will sometimes remain at 0.
Note The thickness of the calibration sheet is set in menu adjustment
parameter in chapter 7.8
46
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 47
Manual
s
s
Double Sheet Control System R1000 series L20
B0063191 / 1.3
6.3.9 Dummy function
BIN8.2 / BIN8.3 / BIN11.3/ ...
BOUT8.0
Function result
Function fault
Fig. 23: Timing diagram for Dummy function
1)
In case of “Function fault“ “Function result“ is not necessarily set.
1)
BOUT8.2
BOUT8.3
Ready
Note The measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
systems. The cycle time of the PLC has not been taken into account.
with integrated fieldbus interface
Communication with the PLC
“1” if fault
0V if fault
< 15 m
< 15 m
6.3.10 Reset Function fault
Fig. 24: Timing diagram for reset function fault
1)
In case of “Function fault“ “Function result“ is not necessarily set.
BOUT8.3 is not reset if a critical systems fault is present. Examples are memory fault, power
failure, or low voltage. Critical faults cannot be reset via the process channel. Theses faults must
be reset via keyboard.
Note The measured timing periods were determined with12 Mbit/s Profibus.
These timing periods can vary with different transmission rates and bus
systems. The cycle time of the PLC has not been taken into account.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
47
Page 48
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.4 Parameter channel
The parameter channel is designed to exchange systems and parameter data of the R1000 with
the master. Primary purpose is the central data backup on the master. In addition, certain
measurement and operating parameters can be extracted from the R1000 and analyzed by the
master.
Note When re-transmitting the system and program parameters, the system
parameters must be re-transmitted first!
Note The configuration of the data format has to be compatible with the PLC for
consistent data transmission!
The data transmission via the parameter channel must be initiated with the service “Open
parameter channel“. The end of data transmission mission via the parameter channel must be
completed with the service “Close parameter channel“.
If the parameter channel is open then it is not possible to issue control commands via the process
channel or via inputs on the keyboard.
6.4.1 Structure of the parameter channel
Inputs (PLC L20) Ausgänge (L20 PLC)
Byte Meaning Byte Meaning
BIN0 Management BOUT0 Management
BIN1 Program index BOUT1 Program index
BIN2 Parameter index BOUT2 Parameter index
BIN3 Application data byte 0 BOUT3 Application data byte 0
BIN4 Application data byte 1 BOUT4 Application data byte 1
BIN5 Application data byte 2 BOUT5 Application data byte 2
BIN6 Application data byte 3 BOUT6 Application data byte 3
Parameter channel
BIN7 Checksum BOUT7 Checksum
Data access control (management)
The management byte (BIN0) is used by the master to select the service (for example writing or
reading) and to confirm the access. The R1000 confirms via the management byte (BOUT0) the
execution of the command. The execution may need up to 100 ms. If an access is not allowed and
therefore, the service cannot be executed, then the R1000 declares this action as a collision.
Services have to be executed only by the master. The R1000 cannot initiate a data transmission as
slave.
Program index
Program index enables the access to one of the 255 programs. The access to the systems
parameters is made via the program index 255.
Parameter index
The parameter index enables the access to the parameters of each program.
Application data bytes
The application data bytes 0 to 3 contain the data which must be transmitted.
Checksum
The checksum is formed of the bytes 1 – 6. The bytes BIN1 to BIN6 respectively BOUT1 to BOUT6
are summed. The least significant is the respective checksum.
48
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 49
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
Inputs (PLC L20) Outputs (L20 PLC)
Byte.Bit Meaning Byte.Bit Meaning
BIN0.0
BIN0.1 BOUT0.1
BIN0.2 BOUT0.2
BIN0.3 BOUT0.3
BIN0.4
BIN0.5 BOUT0.5
BIN0.6
BIN0.7 -- BOUT0.7
Service selection (Bit 32,1,0)
0000 = empty service
0001 = read parameters
0010 = write parameters
0100 = open parameter channel
1000 = close parameter channel
Set Application data length always to
11 (11 = 4 Byte)
Handshake The state is changed with
every new job. It is controlled by the
master only, when a new job is to be
processed by the R1000. The R1000
mirrors the handshake back, once the job
is processed. At a successful job, the
collision bit is set to 0, otherwise the
collision bit is set by the R1000 to 1.
Further jobs can only be done by
withdrawal of the faulty service.
with integrated fieldbus interface
Communication with the PLC
BOUT0.0
BOUT0.4
BOUT0.6
Service selection (Bit 3,2,1,0)
0000 = empty service
0001 = read parameters
0010 = write parameters
0100 = open parameter channel
1000 = close parameter channel
Set Application data length always to
11 (11 = 4 Byte)
Handshake The state is changed with every
new job. It is controlled by the master only,
when a new job is to be processed by the
R1000. The R1000 mirrors the handshake
back, once the job is processed. At a successful
job, the collision bit is set to 0, otherwise the
collision bit is set by the R1000 to 1. Further
jobs can only be done by withdrawal of the
faulty service.
Collision
0 = Fault free access, 1 = Faulty access.
"1" is set by the R1000 only if a service is
invalid or not executable. In this case the
master must reset the service to end the faulty
condition. See also the section "Reset faulty
access" within this chapter.
BIN1.0-7
BIN2.0-7
BIN3.0-7 Application data byte 0 (MSB) BOUT3.0-7 Application data byte 0 (MSB)
BIN4.0-7 Application data byte 1 BOUT4.0-7 Application data byte 1
BIN5.0-7 Application data byte 2 BOUT5.0-7 Application data byte 2
BIN6.0-7 Application data byte 3 (LSB) BOUT6.0-7 Application data byte 3 (LSB)
BIN7.0-7 Checksum BOUT7.0-7 Checksum
Program index
Back reflexion
0 = Program 1, 255 = System parameter
Parameter index
0...255,
Assignment see section 11.1
“Parameter channel commands"
BOUT1.0-7
BOUT2.0-7
Program index
0 = Program 1, 255 = System parameter
Parameter index
1 ... 18 at program parameter
1 ... 24 at system parameter
Assignment see section 11.1
“Parameter channel commands"
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
49
Page 50
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.4.2 Service "Open parameter channel"
The service open parameter channel is initiated by the master with the selection of the service. The
content of the index bytes BIN1, BIN2 and the application data bytes 0 to 3 are not relevant. The
checksum of bytes 1 to 6 is calculated and inserted into byte 7. To initiate the service the master
changes the handshake bit. To avoid data fault the following sequence is mandatory:
1. Service selection, program index, parameter index
2. Switch handshake
In addition a consistent data transmission from the master is necessary.
Note For the service “Open parameter channel“ the index bytes BIN1, BIN2
and the application data bytes BIN3... BIN6 are not relevant.
The R1000 checks the data with the checksum and mirrors the application data, the service
selection and the index selection into BOUT1, BOUT2. The R1000 sets the handshake bit in
BOUT 0.0 only in the last step and signals thereby that the data is valid. This sequence is
observed by the R1000 in order to avoid data faults.
The slave ensures a consistent data transmission.
Note If reading cannot be executed the collision bit is set. The fault number is
transmitted instead of application data bit , see section “6.4.8. Reset faulty
access“. The collision bit can be deleted by one of the following services:
“Close parameter channel”, “Empty service” or “Reset parameter channel”.
6.4.3 Service "Close parameter channel"
This service is initiated by the master by selecting the service. The content of the index bytes BIN1,
BIN2 and the application data bytes 0 to 3 is not relevant. The checksum of bytes 1 to 6 is
calculated and inserted into byte 7. To initiate the service the master changes the handshake bit.
To avoid data fault the following sequence is mandatory:
1. Service selection, program index, parameter index
2. Switch handshake
In addition consistent data transmission from master is necessary.
Note For the service “Open parameter channel“ the index bytes BIN1,
The R1000 checks the data with the checksum and mirrors the application data bytes, the service
selection and the index selection in BOUT1 and BOUT2. The R1000 sets the handshake bit in
output BOUT0.0 only in the last step and signals thereby that the data is valid. This sequence is
observed by the R1000 in order to avoid data faults.
The slave ensures a consistent data transmission.
Note If the checksum is correct then the closing of the parameter
channel is always executed. A set collision bit is thereby deleted.
BIN2 and the application data bytes BIN3... BIN6 are irrelevant.
50
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 51
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
6.4.4 Service "Read parameters"
The master initiates the service “Read parameter“ by selecting the service, and index bytes BIN1
and BIN2. The content of the application data bytes 0 to 3 is not relevant. The checksum of byte 1
to 6 is calculated and inserted into byte 7. To initiate the service the master changes the
handshake bit. In order to avoid data faults the following sequence is mandatory:
1. Service selection, program index, parameter index
2. Switch handshake
In addition consistent data transmission from master is necessary.
Note The application data bytes BIN3 - BIN6 of the service “Read
The R1000 checks the data with the checksum and makes the content of the respective
parameters available in the application data bytes of parameter channel BOUT3... BOUT6.
In addition the R1000 mirrors the service “Read parameter“ and the index adjustment in BOUT1,
BOUT2. Only in the last step the R1000 sets the handshake bit intoBOUT0.0 and indicates thereby
that the data is valid. This sequence is observed by the R1000 in order to avoid data faults.
The slave should ensure a consistent data transmission.
Note A collision bit is et if reading cannot be executed. Instead of
application data the default number is transmitted, see “6.4.8 Reset
faulty access“.
parameter“ are not relevant.
Communication with the PLC
6.4.5 Service "Write parameters"
Initiate the master with the setting of the service selection, the index bytes BIN1 and BIN2. The
content of the application data bytes 0 to 3 is also stored. The checksum of byte 1 to 6 is calculated
and inserted in byte 7. To initiate the service the master changes the handshake bit.
In order to avoid data faults the following sequence is mandatory:
1. Service selection, program index, parameter index, application data byte 0 to 3
2. Switch handshake
In addition consistent data communication from the master is necessary.
The R1000 checks the data with the checksum and transfers the content of the application data
bytes of the parameter channel BIN3…BIN6 into its own parameter memory. Afterwards the R1000
mirrors the index adjustment in BOUT1, BOUT2 and the application data in BOUT3…BOUT6. Only
in the last step inserts the R1000 the handshake bit in BOUT0.0 and indicates thereby that the data
has been completely accepted. The same sequence applies here also, in order to avoid data faults.
The slave ensures a consistent data transmission.
Note If writing cannot be executed, the collision bit is et. In place of the
application data a fault number is transmitted, see section “6.4.8
Reset faulty access“.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
51
Page 52
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.4.6 Service "Empty service"
The master initiates the service “Empty service“ with the setting of the service selection. The
content of the index bytes BIN1, BIN2 and the application data bytes 0 to 3 are not relevant. The
checksum of byte 1 through 6 is calculated and inserted in byte 7. To initiate the service the master
switches the handshake bit. In order to avoid data faults the following sequence is mandatory:
1. Service selection, program index, parameter index, application data byte 0 to 3
2. Switch handshake
In addition consistent data communication from the master is necessary.
The R1000 checks the data with the checksum and mirrors the index adjustment in BOUT1,
BOUT2 and the application data in BOUT3…BOUT6. A possibly set collision bit is set back. Only in
the last step inserts the R1000 the handshake bit in BOUT0.0 and indicates thereby that the data
has been completely accepted. The same sequence applies here also, in order to avoid data faults.
The slave ensures a consistent data transmission.
Note If the service “Empty service“ cannot be executed, the collision bit
is set (remains set). In place of the application data a fault code is
transmitted, see section “6.4.8 Reset faulty access“.
6.4.7 Service "Reset parameter channel"
The service “Rest parameter channel“ initiates the master by transferring a zero string. The service
was added for safety reasons during the start-up of the system or in case a fault occurs in the bus.
The R1000 closes the parameters channel and mirrors "parameters channel closed"
(38 00 00 00 00 00 00 00 Hex). The handshake bit remains set to 0. The collision bit is also
set to 0.
Note If the fieldbus is off-line the service “Reset parameter channel“ is
automatically executed.
52
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 53
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
6.4.8 Reset faulty access
For the following reasons a service cannot be executed:
• The current operating conditions do not allow the execution of the selected service.
• The collision bit in the management byte has not been reset.
• The index register address invalid parameters.
• The service cannot be applied to this parameter.
• The application data contains inadmissible values.
• The service is unknown.
The reasons above can prevent the service execution during reading or writing. The R1000
indicates this problem by the collision bit. In order to prevent an additional uncontrolled access
procedure, the R1000 expects the reset of the called service by the master. In addition the master
executes an “Empty service“ with the confirmation of a handshake. After receipt of this empty
order, the R1000 puts the collision bit back and confirms the service with a handshake. Thus the
fault condition can be reset and the R1000 is available for further orders.
Note If necessary the collision bit can be reset by the service “Close
with integrated fieldbus interface
Communication with the PLC
parameter channel“ and by the service “Reset parameter channel“.
However the parameter channel is thereby closed.
6.4.9 Listing of parameter channel commands
A list with all parameter channel commands is specified in chapter 11 “Technical records".
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
53
Page 54
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.4.10 Example: Remote control with parameter adjustment for the L20
H is the handshake bit and switched by the master and with each data transmission via the
parameter channel (see section of “6.4.1 Layout of the parameters channel - data access control“)
1. Terminate current activities via I/O or process channel
2. Open parameter channel with service “Open parameter channel“
- In case of collision: Undo the collision with the service “Empty service“, remove the cause of the collision
and open again. If necessary evaluate fault number in application data bytes.
3. Set nominal thickness to the desired program index (e.g. program number 7, 1.00 mm)
- In case of collision: Undo the collision with the service “Empty service“, remove the cause of the collision
and open again. If necessary evaluate fault number in application data byte.
4. Set the lower limit to the desired program index (e.g. program number 7, 80%)
- In case of collision: Undo the collision with the service “Empty service“, remove the cause of the collision
and open again. If necessary evaluate fault number in application data byte.
5. Set the upper limit to the desired program index (e.g. program number 7, 120%)
- In case of collision: Undo the collision with the service “Empty service“, remove the cause of the collision
and open again. If necessary evaluate fault number in application data byte.
6. Set the time for averaging to the desired program index (e.g. program number 7; 25ms)
- Transfer: 0H110010b 06h 10h 00h 00h 00h 03h 19h
- Answer: 0H110010b 06h 10h 00h 00h 00h 03h 19h
- In case of collision: Undo the collision with the service “Empty service“, remove the cause of the collision
and open again. If necessary evaluate fault number in application data byte.
- In case of collision: Undo the collision with service “Empty service“, remove the cause of the collision
(normally only wrong content or checksum are possible) and close.
If necessary evaluate fault number in application data bytes.
8. Switch program number via the process channel (e.g. switch to program number 7)
- Transfers: byte 9: 06h, byte 8: 40h
- Answer: byte 8: 01h, byte 9: 06h
- Transfer: byte 8: 00h
- Answer: byte 8: 00h
- In case of malfunctioning the “Function fault“ is returned (see also section “6.3 Process channel“)
9. Open, if necessary, the parameters channel again and read the internal program parameter (1-11) of the
selected programs and store the data backup in the PLC. Then close the parameters channel again.
54
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 55
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
6.5 External I/O control
The system is normally controlled via the process channel. The exception is the signal
"Measurement start", which, for fast procedures, can also be controlled via the Optocoupler inputs
(IN). A mixed operation is also possible. The control cannot, however, be made simultaneously by
both signal sources.
The “Measurement start“ signals can be initiated via the process channel or the opto couplers. The
“Measurement start“ signals can be initiated via the process channel or the opto couplers.
Simultaneous initiation leads to an error message.
Signal Meaning Notes
IN0 Measurement start input 1 Optocoupler input 1, 24 V active
IN1 Measurement start input 2 Optocoupler input 2 24 V active
IN2 Measurement start input 3 Optocoupler input 3 24 V active
The “Measurement start“ inputs are linked in different combinations via AND. The following
configuration can be selected in the control unit:
• IN0
• IN0 and IN1
• IN0 and IN1 and IN2
In addition the signals “0-, 1-, 2-sheet”, “ENABLE” and “Warning” are available for further
processing via Optocoupler (OUT).
Signal Meaning Notes
OUT0 Output 0-sheet 1. Optocoupler output Standard 0 V active (selectable in unit configuration)
OUT1 Output 1-sheet 2. Optocoupler output Standard 0 V active (selectable in unit configuration)
OUT2 Output 2-sheet 3. Optocoupler output Standard 0 V active (selectable in unit configuration)
OUT3 Output ENABLE 4. Optocoupler output Standard 24 V active (not selectable for safety reasons)
OUT4 Warning 5. Optocoupler output Standard 0 V active (selectable in unit configuration)
Attention If the external outputs or inputs are used, then the supply voltage for
with integrated fieldbus interface
Communication with the PLC
the outputs / inputs needs to be connected.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
55
Page 56
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.5.1 Signal "Enable"
The signal “ENABLE“ corresponds with the two process channel signals BOUT “Ready“ and BOUT
“Function fault“ according to the following boolean function:
ENABLE = BOUT Ready BOUT Function fault
BOUT
Ready
BOUT
Function fault
Fig. 25: Boolean function “ENABLE”
&
ENABLE
If the signal BOUT “Ready“ is reset, then a fault has occurred, which requires a user intervention at
the control unit. Possible causes: memory faults, missing or too low voltages.
NoteThe timing diagrams in the sections “6.5.3“ and “6.5.4“ do not contain an
explicit chart of the signal “ENABLE“.
6.5.2 Signal "Warning"
The “Warning“ signal is an additional output signal with fixed evaluation thresholds.
The signal becomes activated if the measurement result is below 80% or above 120% of the preset
nominal value.
NoteThe signal will also be activated if measurements without a sheet
(measurement value below 80%) are performed.
56
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 57
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
6.5.3 External single measurement via external inputs
Communication with the PLC
Fig. 26: Timing diagram for external single measuring via external inputs
1)
At "function error" the "function result" not set mandatory.
2)
The measuring time depends on the time set for averaging.
NoteThe operation of the individual measurement, which is initiated via the
external input, can be controlled via the process channel, see section
“6.3.2 Start single measurement via process channel“. If no control is
done via the process channel, then the measurement operation must be
controlled by the signal “ENABLE“, see section “6.5.1 Signal ENABLE“.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
57
Page 58
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.5.4 External continuous measurement / External special via external inputs
Fig. 27: Timing diagram for external continuous measurement / external special via external inputs
1)
At "function error" the "function result" not set mandatory.
2)
The measuring time depends on the time set for averaging.
The status of the 0-,1-,2-sheet and warning outputs are updated via the Fieldbus (BOUT) with a refresh rate of 6 ms.
*
The refresh rate via I/O Outputs is 1 ms.
NoteThe output “function result” is set with the arrival of the first measured
value and remains set.
NoteIn the “extern special” measurement mode the highest measured value
will be displayed and held at the outputs until a new measurement is
started.
58
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 59
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
6.6 Fieldbus configuration file
The configuration files for the respective fieldbus systems are located on the supplied CD.
6.6.1 GSD file for Profibus-DP
The GSD file contains the specific configuration data of the slave. The data must be known to the
Profibus master.
The manufacturers of the Profibus master supply the tools for the integration of the GSD file into
the Profibus network. Suitable are for example the Siemens step 7 tools. Roland Electronic does
not supply such tools, because they have to be compatible with the interface design of the master.
The GSD file is supplied on a CD or can be downloaded from the Roland homepage.
Note 24 Bytes I/O must be set.
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
LED 1 --- --- ---
LED 2 Fieldbus
Online
LED 3 Fieldbus
Offline
LED 4 Fieldbus
Diagnostics
Communication with the PLC
Status Indicators
Green Bus online, data exchange possible
Off Bus not online (or no power)
Red Bus offline
Off Bus not offline (or no power)
Off No diagnostics present (or no power)
Red, flashing (1 Hz) Error in Configuration Data
Red, flashing (2 Hz) Error in Parameter Data
Red, flashing (4 Hz) Error in initialization of the PROFIBUS
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
59
Page 60
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.6.2 EDS file for DeviceNet
The EDS file contains the specific configuration data of the slaves. The data must be known to the
DeviceNet master.
The manufacturers of the DeviceNet master supply the tools for the integration of the EDS file into
the DeviceNet network. Suitable are for example the Allen-Bradley DeviceNet manager. Roland
Electronic does not supply such tools, because they have to be compatible with the interface
design of the master.
The EDS file is supplied on a CD or can be downloaded from the Roland homepage.
Note 24 Bytes I/O must be set.
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
Status Indicators
LED 1 --- --- Not used
LED 2 Network
Status
(NS)
LED 3 Module
Status
(MS)
LED 4 --- --- Not used
Off Not powered, not on line
Green On line, one or more connection established
Green, flashing On line, no connection established
Red Critical link failure
Red, flashing One or more connections timed out
Alternating
Red / Green
Off No power
Green Normal operation
Green, flashing Auto Baud in progress
Red Major fault
Red, flashing Minor fault
Alternating
Red / Green
Device self-test in progress
Device self-test in progress
60
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 61
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
6.6.3 EDS file for CanOpen
The EDS file contains the specific configuration data of the slaves. The data must be known to the
master.
The manufacturers of the master supply the tools for the integration of the EDS file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the master.
The EDS file is supplied on a CD or can be downloaded from the Roland homepage.
Note 3 PDOs with 8 Bytes each are set.
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
LED 1 STATUS Off Normal operation
LED 2 RUN Off Module not powered
LED 3 ERROR Off No error
LED 4 POWER Off Module not powered
with integrated fieldbus interface
Communication with the PLC
Status Indicators
Red Unrecoverable fault detected
Green Module is in the OPERATIONAL state
Green, single flash Module is in the STOPPED state
Green, blinking Module is in the PRE-OPERATIONAL state
Red, blinking Bus initialisation fault
Red Bus off
Red, single flash Warning limit reached
Red, double flash Error Control Event
Red, triple flash Sync Error
Green Module powered
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
61
Page 62
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.6.4 GSD file for ProfiNet IO
The GSD file contains the specific configuration data of the device. The data must be known to the
Profibus controller.
The manufacturers of the controller supply the tools for the integration of the GSD file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the controller.
The GSD file is supplied on a CD or can be downloaded from the Roland homepage.
Note 24 Bytes I/O must be set.
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
Status Indicators
LED 1 Link /
Activity
LED 2 Communi-
cation
Status
LED 3 Module
Status
LED 4 --- --- ---
Green Link established
Green, flashing Receiving/Transmitting data
Off No link or power off
Green On line, Run
- Connection with IO Controller established
- IO Controller is in RUN state
Green, 1 flash On line, STOP
- Connection with IO Controller established
- IO Controller in STOP state
Off Off line
- No connection to IO Controller
Green Initialized, no error
Green, 1 flash Diagnostic data available
Green, 2 flashes Blink. Used by an engineering tool to identify the
Anybus module
Red , 1 flash Configuration error
- Too many modules / submodules
- IO size derived from IO Controller too large
- Configuration mismatch ( no module, wrong module)
Red, 3 flashes No Stations Name or no IP-Address assigned
Red, 4 flashes Internal error
Off No power or not initialized
62
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 63
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
6.6.5 CSP file for CC-Link
The CSP file contains the specific configuration data of the device. The data must be known to the
controller.
The manufacturers of the controller supply the tools for the integration of the CSP file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the controller.
The CSP file is supplied on a CD or can be downloaded from the Roland homepage.
Three „occupied Stations“ with 36 Byte are used. 12 Byte are Bit Data Area and 24 Byte Word Data
*1) Remote Ready: after Roland R1000 is ready for Data exchange the signal Remote READY is set. If Remote READY is
off the Data in the user area are not valid.
System area
word 5
Remote
Ready *1)
System area
word 5
with integrated fieldbus interface
Communication with the PLC
Word Data area
word 0 to 3
Roland L20
Parameter channel
(see Chapter 6.4)
Word Data area
word 0 to 3
Parameter channel
(see Chapter 6.4)
Word Data area
word 4 to 11
Roland L20 Process channel (see Chapter 6.3)
Word Data area
word 4 to 11
Roland L20 Process channel (see Chapter 6.4)
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
Status Indicators
LED 1 RUN Green On Normal operation
Green Off Network non-participating or timeout status
LED 2 ERRL Red On CRC Error detected
Red Off Normal Operation
LED 3 RDLED Green On Data being received
LED 4 SDLED Green On Data being transferred
Green Off No data reception
Green Off No data transmission
No power on the module
Illegal station number or illegal baudrate detected
No power on the module
No power on the module
No power on the module
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
63
Page 64
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
6.6.6 EDS file for EtherNet/IP
The EDS file contains the specific configuration data of the device. The data must be known to the
controller.
The manufacturers of the controller supply the tools for the integration of the EDS file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the controller.
The EDS file is supplied on a CD or can be downloaded from the Roland homepage.
Note 24 Bytes I/O must be set.
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
Status Indicators
LED 1 Link (Activity) LED configuration 1 (Default)
Off Link not sensed
Green Link sensed
LED 2 Module
Status
LED 3 Network
Status
LED 4 Activity
Status
LED configuration 3 (Default)
Off No power
Green Controlled by a scanner in Run state
Green, flashing Not controlled, or scanner in Idle state
Red, flashing A minor recoverable fault has been detected
Red A major unrecoverable fault has been detected
Alternating
Red / Green
LED configuration 3 (Default)
Off No power or no IP address
Green On line, one or more connections established
Green, flashing On line, no connections established
Red Duplicate IP address, fatal error
Red, flashing One or more connections timed out
Alternating
Red / Green
Green, flashing The activity led flashes green each time a packet
Self test in progress
(CIP Class 1 or 3)
(CIP Class 1 or 3)
Self-test in progress
is received or transmitted
64
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 65
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
6.6.7 Device Description file for EtherCAT
The Device Description file contains the specific configuration data of the device. The data must be
known to the controller. The manufacturers of the controller supply the tools for the integration of
the Device Description file into the network. Roland Electronic does not supply such tools, because
they have to be compatible with the interface design of the controller.
The Device Description file is supplied on a CD or can be downloaded from the Roland homepage.
Note 24 Bytes I/O must be set.
By pressing the key “
Nr. LED State Description
▼” status indicators are shown on the display.
Status Indicators
LED 1 Link/Activity 1 Off No link sensed on Ethernet port 1
Green Link sensed on Ethernet port 1
Green flickering Exchanging packets on Ethernet port 1
LED 2 RUN Off The device is in INIT state
Green, blinking The device is in PRE-OPERATIONAL state
Green, single
flash
LED 3 ERR Off EtherCAT is in communication condition
LED 4 Link/Activity 2 Off No link sensed on Ethernet port 2
Green The device is in OPERATIONAL state
Red, flashing General configuration error
Red single flash Slave device application has changed the EtherCAT
Red double
flash
Red Application watchdog timeout
Green Link sensed on Ethernet port 2
Green, flashing Exchanging packets on Ethernet port 2
Communication with the PLC
The device is in SAFE-OPERATIONAL state
state autonomously: Parameter „Change“ in the AL
status register is set to 01 (change/error).
Sync manager watchdog timeout
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
65
Page 66
Manual
Double Sheet Control System R1000 series L20
Communication with the PLC B0063191 / 1.3
with integrated fieldbus interface
Leerseite
66
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 67
Manual
3
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
7 Start-up
7.1 Initially applying power to the system
The L20 is designed for an operating voltage of 24 VDC (+6 V / -4 V). This voltage is to be checked
before applying power. The control unit is automatically switched on by applying the power.
After applying power, the type of system and the version number are briefly displayed.
If the system does not react, check the fuse.
7.2 Start screen
After applying the supply voltage to the system, the start screen will be shown.
ROLAND ELECTRONIC
L20
SV: 2
ROLAND ELECTRONIC
L20 SV: 2
or
Fig. 28: Start screen
The start screen shows the type of system and the software version.
After the control unit is fully operational, the Start screen is replaced by the operations screen.
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
67
Page 68
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
7.3 Operation
Note Units with CanOpen bus module:
Note The system is factory adjusted for “external continuous measurement“.
After applying power to the system and the version number are briefly displayed. Afterwards the
system switches into that measurement menu which was active before the unit was switched off.
require approx. 30 seconds to reach the operational status after applying
power to the system.
Therefore the system functions only if the signal “measurement start“ is
activated via the fieldbus. The modification of the configuration is
described in the following sections.
1 LED functions
2 Pushbutton functions
3 Program number
Fig. 29: Frontal view of the L20 with enlarged display detail
4 Nominal thickness
5 State of measurement
6 Lower limit value
7 Upper limit value
8 Measured value of measuring channel 1
9 Measured value of measuring channel 2*
10 Measured value of measuring channel 3*
LED functions (symbols above the keys)
<
Norm
>
Enable
ON, if the measured value reaches (or falls short of) the lower limit value.
ON, if the measured value is within the lower and upper limit values.
ON, if the measured value reaches (or exceeds) the upper limit value.
- blinks, if a fault is present
- ON, if the equipment is in measurement mode
- OFF, during parameter programming with the keyboard
Key functions (symbols below the keys)
▲
▼
ENTER
MENU
Changes the parameters forward / greater.
Changes the parameters backward / smaller.
Selects a parameter for changing and confirming the change
Activates the menu level, for deleting a fault message and exiting the menu level.
68
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 69
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
7.4 Configuration menu
7.4.1 Main menu structure
with integrated fieldbus interface
Start-up
Fig. 30: Main structure of configuration menu
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
69
Page 70
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
7.4.2 Sub structure “program parameters” (details in 7.7)
Fig. 31: Sub structure „program parameters“
70
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 71
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
7.4.3 Sub structure “system adjustment” (details in 7.8)
Start-up
Fig. 32: Sub structure „system adjustment“
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
71
Page 72
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
7.4.4 Sub structure “system parameters” (details in 7.9)
number of active channels
number of active channels
72
internal communication diagnostic
Fig. 33: Sub structure „system parameters“
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 73
Manual
Double Sheet Control System R1000 series L20
with integrated fieldbus interface
B0063191 / 1.3
7.5 General information regarding the configuration
Note The correct configuration depends on the communication with the PLC,
The following rules apply to the operation in the configuration mode:
• The configuration mode is activated (while in measurement mode) by pressing the MENU
key.
• The configuration mode is terminated or cancelled by pressing the MENU key.
• The selected / set parameters can be changed when the items are blinking in the display.
• The selected / set parameters are activated by pressing the ENTER key.
Note The systems info and bus info is displayed by pressing the ENTER key in
the base menu (also see system parameter 27).
NoteIn the base menu the LED of the fieldbus coupler is displayed when
pressing the
on the measurement task and the connected components.
▼ key, see chapter 6.6 “Fieldbus configuration files”.
Start-up
7.6 Changing, setting-up or checking the configuration
In order to select, set-up or check the system / program parameters, press the MENU key.
Here either reviewing or changing the configuration can be selected.
Configuration review:No changings can be performed. The measurement mode is not interrupted.
configuration
review
Fig. 34: Indication after calling-up the menu
Configuration change: After entering the password it is possible to perform changings.
The following menu option is shown.
configuration
change
Fig. 35: Setting the configuration mode
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
73
Page 74
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
For changing parameters, the password must be entered.
password
xxxx
Fig. 36: Password request
Each blinking digit can be changed with the arrow keys and confirmed with ENTER. After having
entered the correct password, the following menu appears for the selection of sub structure items.
The password is factory set to “0000”.
If the entered password is incorrect then the cursor returns to the first digit of the password and the
input must be repeated. The input of the password can be aborted by pressing the MENU button.
Note After exiting the configuration mode the password remains active for five
Note A fault is generated if PLC commands are executed while entering the
minutes. Thus other configuration adjustments can be made, without reentering the password. If no key is pressed for five minutes while in the
menu level, the unit will return to the default state.
password or changing parameters.
Selection of sub structure items:
configuration
program parameter
Fig. 37: Selecting the sub structure items
Available sub structure items are:
• Configuration program parameter
• Configuration adjustment parameters
• Configuration system adjust
• Data backup
• Firmware update
Program parameters are application specific adjustments (e.g. input of nominal sheet thickness).
Adjustment parameters are parameter, which are only valid for this individual system; they cannot
be transferred to other systems.
System parameters are general adjustments (e.g. language).
74
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 75
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
7.7 Program parameters
The program parameters contain the information required for the various measurement programs.
For accessing the program parameters, select the mode “configuration program parameter“ and
confirm with ENTER.
Program parameter 1: Selecting the measuring program to be configured.
Program Parameter: 1
Program Number
1
Fig. 38: Selecting the program to be configured
At this point select the measuring program (1-255) that needs to be configured. All following
adjustments apply to the selected program.
Program parameter 2:
For L20-XX-S not available.
For L20-3-XX-S:
with integrated fieldbus interface
Start-up
Programmparameter: 2
active meas.channel
1
Fig. 39: Selecting the active measuring channel
At this point select the active measuring channel used during the measuring operation.
Possible choices are: 1 / 2 / 3 / 1+2 / 1+3 / 2+3 / 1+2+3
(in function of selected measuring channels in the substructure „system parameter“, item 11)
Program parameter 3: Specifying the nominal thickness and material of the sheet to be
measured (in mm/inch).
Program Parameter: 3
nominal thickness
0.900 mm
Fig. 40: Adjusting the nominal thickness
The minimum and maximum adjustable nominal dimension (thickness of the sheet) is depending
on sensor type:
- LAAS10 / LAAS10+: from 0.1 mm to 5 mm / from 0.004 inch to 0.196 inch
- LAAS40 / LAAS40+: from 0.3 mm to 15 mm / from 0.012 inch to 0.59 inch
- LAAS200 / LAAS200+: from 1.5 mm to 99 mm / from 0.06 inch to 3.93 inch
Program parameter 4: not available
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
75
Page 76
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
Program parameter 5: Setting the lower limit value.
Program Parameter: 5
lower threshold
80% 0.720 mm
Fig. 41: Adjusting the lower limit
Value range: between 1% and 100% of the nominal value, with simultaneously displaying the
absolute limit value.
Program parameter 6: Setting the upper limit value.
Program Parameter: 6
upper threshold
120% 1.080 mm
Fig. 42: Adjusting the upper limit
Value range: between 100% and 180% of the nominal value, with simultaneously displaying the
absolute limit value.
Program parameter 7: Adjusting the time for average value.
Program Parameter: 7
average value
25ms
Fig. 43: Adjusting the time for average value
Possible choices are:
• 8 / 15 / 25 / 50 / 100 / 250 ms
Generally, the „desired value“ should be set to fit to the transportation speed and to the sheet
length.
NoteFast transportation and short sheets require a smaller averaging
time, see chapter 8.3.
76
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 77
Manual
m
0
Double Sheet Control System R1000 series L20
B0063191 / 1.3
7.8 Adjustment parameters
Adjustment parameters are parameters, which are only valid for this individual system; they cannot
be transferred to other systems.
Adjustment parameter 1:Measuring channel calibration
This is required before operating a new system, to replace a sensor or a control unit. Start by
placing a calibration sheet between the sensors. The thickness of the calibration sheet is stored in
the unit.
Depending on the sensor type, following sensor distances are allowed:
• LAAS10 / LAAS10+: 10 mm
• LAAS40 / LAAS40+: 40 mm
• LAAS200 /LAAS200+: 200 mm
• The measuring channel calibration is valid to all programs.
Note LAAS10 / LAAS10+ and LAAS200 /LAAS200+ are in preparation.
with integrated fieldbus interface
Start-up
± 1 mm
± 2.5 mm
± 10 mm
adjust parameter: 1
measuring channel
calibration
ok
Fig. 44: Selection of measuring channel
Display:
• missing: Measuring channel calibration at one measuring channel has not
been performed yet.
• ok: Measuring channel calibration at one measuring channel has been
performed.
To perform measuring channel calibration press the ENTER key.
Following possibilities can be selected:
• no: Do not perform measuring channel calibration.
Perform (again) measuring channel calibration at selected channels.
(for L20-3-XX-S and depending on selected sensors).
L20-XX-S L20-3-XX-S
adjust parameter: 1
thickness of
calibration sheet
0.500m
Fig. 45: Enter the thickness of calibration sheet
Enter the thickness of the calibration sheet at measuring channel calibration.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
adjust parameter: 1
thickness of
calibration sheet
.500mm ENTER start
77
Page 78
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
L20-XX-S L20-3-XX-S
adjust parameter: 1
feed calibration
sheet at channel
push ENTER
adjust parameter: 1
feed calibration
active
push ENTER to finish
Fig. 46: Feed the calibration sheet
L20-XX-S: At this point place the calibration sheet in the measuring station. The calibration is
performed punctual. During the calibration a sheet must be between the sensors.
L20-3-XX-S: Now the calibration sheet is placed in the measuring station or passed through the
measuring station. Confirm by pressing the ENTER key.
Attention For L20-3-XX-S dynamic calibration is advantageous because
localized thickness variations or fluctuations in the calibration piece
will have less impact on the calibration.
Now the rated sensor range is shown. The margin areas must be avoided.
adjust parameter: 1
rated sensor range
37.5 ... 42.5mm
AB1 active: 41mm
Fig. 47: Showing of the rated sensor range
If several measuring points have been calibrated, the ABs will be listed consecutively in the last
row. The measuring channel calibration is completed by pressing the ENTER key.
Adjustment parameter 2:Controlling the sensor gaps with the calibration sheet.
adjust parameter: 2
control with
calibration sheet
no
Fig. 48: Select the control with the calibration sheet
To perform a control press the ENTER key.
Selection options:
• no: Do not perform control.
• yes: Perform control (At L20-XX-S)
• measuring channel: 1 / 2 / 3 / 1+2 / 1+3 / 2+3 / 1+2+3
perform controls at selected measuring channels
(At L20-3-XX-S and depending on connected sensors)
78
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 79
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
Fig. 49: Prompt for placing the calibration sheet
The thickness of the calibration sheet is now displayed.
L20-XX-S: At this point place the calibration sheet in the measuring station. The calibration is
performed on one selected point. During the calibration a sheet must be between the sensors.
L20-3-XX-S: Now the calibration sheet is placed in the measuring station or passed through the
measuring station. Confirm by pressing the ENTER key.
L20-XX-S L20-3-XX-S: The deviation is shown as a result.
Fig. 50: Select control with the calibration sheet Fig. 50: Display of the deviation
adjust parameter: 2
feed sheet 0.500 mm
for calibration
Push ENTER to start
NoteFor L20-3-XX-S, the dynamic calibration is advantageous because
localized thickness variations or fluctuations in the calibration piece
will have less impact on the calibration.
adjust parameter: 2
control with
calibration sheet
ok
with integrated fieldbus interface
Start-up
adjust parameter: 2
max. deviation
+/- 0.31mm
AB1 Ist: +0.01mm
L20-XX-S:
If the control with the calibration
sheet was successful the message
above will be displayed.
The control is completed by pressing
the ENTER key.
Adjustment parameter 3: not available.
L20-3-XX-S:
Deviations may occur due to thermal expansions of the
mechanic components.
The measured fault is taken in consideration in the
measuring result.
By large or in the case of large deviations a re-calibration
will be necessary.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
79
Page 80
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
For L20-XX-S:
Adjustment parameter 4: Calibration deviation
adjust parameter: 4
show calibration
deviation distance
Fig. 51: Selection of the calibration deviation
The measured deviation of the calibration sheet thickness (in mm / inch) is displayed by pressing
the ENTER key. This requires that the calibration sheet has to be inserted.
adjust parameter: 4
AB1:-0.005 mm
Fig. 52: Display of the calibration deviation
Pressing the ENTER key will close the display of the calibration deviation.
For L20-3-XX-S:
Adjustment parameter 4: System test / Alignment
According to the type of sensor used, the device performs the following check:
A)
When connecting the sensor type LAAS40+, LAAS10+ (in preparation) and LAAS200+
(in preparation) the alignment and function control of all activated sensors in the system settings
is performed.
80
adjust parameter: 4
system test/
alignment
no
Fig. 53: Display of system test / alignment
Possible selections:
yes
no
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 81
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
Sensor alignment:
Hereby no sheet is allowed to be placed between the sensors. The sensor LAS40+ has an
incorporated photo element which determines the alignment of the actual used pair of sensors.
The result will be shown:
Fig. 54: Display of the sensor alignment
control and XC3 means measuring channel 3 beam control.
The following classifications are outputted:
Additionally
B)
At connection of sensor types LAAS40, LAAS10 (in preparation) and LAAS200 (in preparation), the
sensor control of all activated sensors in the system setup will be performed.
with integrated fieldbus interface
sensor alignment
XC1: good 200
XC2: good 190
XC3: good 202
XC1 means measuring channel 1 beam control, XC2 means measuring channel 2 beam
good (255...51)
Explanation: optimal alignment of the sensors.
borderline (50...21)
Explanation: the alignment of the sensors should be verified because it is not optimal.
Remove any contamination from sensors if necessary.
bad (20...0)
Explanation: the alignment of the sensors must be verified.
sheet?
Explanation: there is a sheet in the measuring gap. A control cannot be performed.
interfering light
Explanation: interfering light makes a control impossible. Avoid direct light irradiation.
A/B mismatched
Explanation: The sensor connections of measuring channel A and B are mismatched.
Start-up
adjust parameter: 4
system test/
sensor control
no
Fig. 55: Display of system test / alignment
Possible selections:
yes
no
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
81
Page 82
Manual
D
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
Function control:
When the function is correct, the following is displayed:
with integrated fieldbus interface
adjust parameter: 4
meas.station: 1+2
function: OK
Push ENTER
Fig. 56:Display of function control
Adjustment parameter 5: Individual diagnostics of sensors.
adjust parameter: 5
individual diagnos tic of sensors
Fig. 57: Individual diagnostics of the laser sensors
If more measuring channels are present, press the ▲ and ▼ key to change to the next measuring
channel.
The measured distance between the laser sensors is displayed. This makes a diagnostic possible.
L20-XX-S L20-3-XX-S
adjust parameter: 5
A1: 70.199mm
B1: 89.205mm
Fig. 58: Measured distance between the laser sensors
At the L20-3-XX-S the thickness D1/2/3 of the inserted sheet is displayed additionally.
Press the ENTER key to exit from this parameter.
Adjustment parameter 6: Display of the measuring area
L20-XX-S L20-3-XX-S
adjust parameter: 6
measuring window
1: +-19.8mm
Fig. 59: Display of the measuring area
For measurement the sheet must be located in the measurement in a specified area.
The thickness of the sheet cannot be determined outside this area.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 83
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
Adjustment parameter 7:Sensor alignment aid
Fig. 60: Display of the sensor alignment aid
The sensor alignment aid is activated by pressing the ENTER key. During this procedure the laser
sensors flash alternately.
The congruence of the laser beam path can be verified with a piece of non-reflective piece of
paper. For verification place the paper between the sensors in the laser beam at different positions.
A larger displacement or an angular deviation of the laser beam causes at inclined positions of the
sheet measurement deviations.
At L20-3-XX-S the first pair of sensors flashes alternately 30 x per minute. The second pair of
sensors flashes alternately blinks 60 x per minute and the third pair of sensors flashes alternately
approx. 100x per minute.
This allows to check if the sensors are connected correctly to the appropriate cables.
Press the ENTER key to exit from this parameter.
adjust parameter: 7
sensor alignment
Safety instructions for handling of laser sensors!
Attention! Laser radiation!
Do not look stare the beam!
Do not stare into the specular reflected beam.
with integrated fieldbus interface
Start-up
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
83
Page 84
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
7.9 System parameters
Note The selected system configuration should be documented in the form
The general adjustments are specified by configuring the system parameters.
For accessing, select the “system parameter configuration“ mode and confirm with ENTER.
System parameter 1:Setting the dialogue language.
system parameter: 1
language
english
Fig. 61: Selecting the language
Selectable languages:
• English
• German
• Italian (in preparation)
• French (in preparation)
• Spanish (in preparation)
System parameter 2:Determine the type of system.
“System configuration“ at the end of this manual or in the equipment
documentation. This information is required in case a system needs to be
exchanged.
system parameter: 2
system type
standard
Fig. 62: System type
The type of the system cannot be modified
System parameter 3:Selecting the dimensions for the display (mm / inch).
When changing the measurement units, the sheet metal thicknesses of the stored program
parameters are also converted into the new dimension.
system parameter: 3
display value in
mm
Fig. 63: Selecting the dimensions for the display
84
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 85
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
System parameter 4:Selecting the dimensions for output via fieldbus (mm / inch).
Fig. 64: Selecting the dimensions for the fieldbus output
The multiplication factor of the output is determined by the type of sensors being used.
LAAS10, LAAS10+, LAAS200, LAAS200+ are in preparation
System parameter 5:Setting the display time
Fig. 65: Setting the display time
The maximal measured values (peak values) for the specified time are displayed here(holding
time). This time is for the display only. Values between 0.0 seconds and 2.0 seconds can be set.
System parameter 6:Setting the bus address.
with integrated fieldbus interface
system parameter: 4
bus readout value in
mm
*0.001 (LAAS10/..40)
Sensor types Multiplication factor (at inch resp. mm)
LAAS10, LAAS10+,
LAAS40 and LAAS40+
LAAS200 and LAAS200+ 0,001 inch or 0,01mm
0,0001 inch or 0,001mm
system parameter: 5
display time
2.0 s
Start-up
system parameter: 6
bus address
1
Fig. 66: Setting the fieldbus address
• Profibus: 1 - 125
• DeviceNet: 0 - 63
• CanOpen: 1 - 127
• ProfiNet IO: ---
• CC-Link: 1 – 63
• EtherNet/IP: ---
• EtherCAT: ---
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
85
Page 86
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
This system parameters are only for EtherNet/IP
system parameter: 6
EthernetIP DHCP: no
When DHCP is switched on, the IP-setting will be
done via DHCP. When DHCP is switched off, the IPaddress, SubNet and Gateway must be selected.
Fig. 67: Setting DHCP
The IP-address can be selected here.
system parameter: 6b
IP: 192.168. 0. 10
Fig. 68: Setting IP-Address
The SubNet can be selected here.
system parameter: 6c
Snet: 255.255.255. 0
Fig. 69: Setting SubNet
The Gateway can be selected here.
system parameter: 6d
GWay: 0. 0. 0. 0
Fig. 70: Setting Gateway
System parameter 7: Indicating of the the Bus baud rate.
system parameter: 7
busbaudrate
500kb
Fig. 71: Indicating of the Bus baud rate
Setting the Bus baud rate depends on the Bus type:
Profibus: up to 12Mbps/s; selection at master
DeviceNet: 125/250/500/kBit
CanOpen: 10/20/50/125/250/500/800/1000 kbps
ProfiNet IO: ---CC-Link: 125/625kbps 2,5/5/10Mbps
EtherNet/IP: – –
EtherCAT: – –
86
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 87
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
System parameter 8:Deleting all program parameters (measuring programs).
Fig. 72: Deleting of all program parameters
Selectable options:
• yes
• no
System parameter 9:Switching the password function on / off.
Fig. 73: Switching the password on / off
Selectable options:
• yes
• no
system parameter: 8
clear prog. param.
no
Attention The deletion cannot be undone.
system parameter: 9
password active
no
with integrated fieldbus interface
Start-up
Attention If password protection is not activated, then all parameters can be
accessed at any time. This is recommended only during starting-up
System parameter 10:Assigning a password.
the system. For daily operation the password function should be
activated.
system parameter: 10
set password L20
0000
Fig. 74: Assigning a password
To change the password, press the ENTER key. The first digit flashes. Set the desired digits by
pressing the ▲ ▼ keys.
Press ENTER to move to the next digit. After setting the last digit, press ENTER and the password
is stored.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
87
Page 88
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
System parameter 11:Specifying the number of active channels.
system parameter: 11
number of
active channels
1
Fig. 75: Specifying the number active channels
For L20-XX-S the number of measuring channels cannot be changed.
For L20-3-XX-S it is possible to set the number of the measuring stations between 1 and 3.
Note When using one pair of sensors connect these to channel 1.
When using two pairs of sensors connect these to channel 1 and 2.
System parameter 12: Specifying the type of sensor.
system parameter: 12
sensor type
LAAS40
Fig. 76: Specifying the type of sensor
Selectable options:
• LAAS10 (in preparation)
• LAARS10 (do not use)
• LAAS10+ (in preparation, only for L20-3-XX-S)
• LAAS40
• LAAS40+ (only for L20-3-XX-S)
• LAARS40 (do not use)
• LAAS200 (in preparation)
• LAAS200+ (in preparation, only for L20-3-XX-S)
• LAARS200 (do not use)
88
Note The connected sensor type and the selected sensor type is
checked each time the unit starts. If the sensors do not match, an
error will be reported.
System parameter 13:Specifying the moving average.
system parameter: 13
default moving average
50 ms
Fig. 77: Specifying the moving average
The moving average value which is set in "clear program parameters" as default for for all programs
must be entered here. This value will be used in case the existing program parameters are deleted
and therefore no appropriate moving average value exists.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 89
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
System parameter 14:Adjusting the measuring mode.
Fig. 78: Adjusting the measuring mode
Possible measurement modes:
System parameter 15:Specifying the system reaction when 2-sheet is detected.
with integrated fieldbus interface
Start-up
system parameter: 14
measuring mode
external continuous
• external single: The system measures once if the “Measurement start“ signal is applied.
Each measurement must be initiated separately. The notes in chapter
6.3.2 „timing diagram single measurement“ must be observed.
• demonstration:This mode of operation is intended for equipment demonstrations, but
not for normal process operation. The system executes measurements
continuously.
• external continuous: The system executes measurements, as long as
the “Measurement start“ signal is applied.
external special:As for “external continuous”, but: The highest value reached during a
measurement cycle is displayed and maintained at the outputs until a
new measurement is started.
This also applies for the outputs 0-1-2-Warning.
system parameter: 15
stop if 2-sheet
no
Fig. 79: Adjusting the 2-sheet reaction
Selectable options:
• no: The outputs (0-sheet, 1-sheet and 2-sheet) are activated according to the number of
sheets between the sensors. The equipment does not block operation if double
sheet is encountered.
• yes: The outputs (0-sheet, 1-sheet and 2-sheet) are activated according to the number of
sheets between the sensors. If double sheet is detected, the output “2-sheet“ is
activated and the equipment is blocked until the 2-sheet condition is cleared.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
89
Page 90
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
System parameter 16: Programming the “Measurement start“ inputs under external control.
system parameter: 16
external meas. start
IN0
Fig. 80: Adjusting the measurement start inputs
Selectable operating conditions:
• IN0: If 24 VDC is applied to IN0, then the measurement is executed.
If 0 VDC is applied to this input then the measurement is stopped.
• IN0 + IN1: The measurement is performed only, if 24 VDC is applied
simultaneously to IN0 and IN1.
• IN0 + IN1 + IN2: The measurement takes place only, if 24 VDC is applied
simultaneously to IN0 and IN1 and IN2.
System parameter 17: Setting the output logic
(0-sheet, 1-sheet, 2-sheet and warning outputs).
system parameter: 17
output 0-1-2-warning
24V active
Fig. 81: Setting the output logic
Selectable options:
• 0 V: As shown in the timing diagrams and the wiring diagrams
• +24 V: The outputs 0-sheet, 1-sheet, 2-sheet and warning are inverted, i.e. the respective
signals in the timing diagrams and wiring diagrams must be seen inverted.
Note The output “Enable“ is not affected thereby.
90
System parameter 18: Storing the active program number.
system parameter: 18
storage of active
program number
no
Fig. 82: Storing the active program number
Selectable options:
• no: When the program is switched via Fieldbus or I/O, the program number will not be
stored. So the system always starts up at “Power up” with the program 255.
• yes: When the program is switched via Fieldbus or I/O, the program number will be
stored. So the system always starts up at “Power up” with the last selected program
by keyboard.
AttentionIf the program is often stored, the memory becomes loaded with
frequent writing cycles and thus will be destroyed in the course of
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
time (lifetime is approx. 1.000.000 write cycles).
In this case „no“ should be selected here.
Page 91
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
System parameter 19:Setting the monitoring of the PLC voltage.
Fig. 83: Setting the monitoring of the PLC voltage
Selectable options:
• no monitoring
• monitoring
If the parameter is set to “monitoring“ and the PLC voltage is not connected, a respective fault
message will be indicated.
Remedy: connect the voltage and then confirm the fault message.
System parameter 20:Deactivating / activating the external adjust via fieldbus.
Fig. 84: Deactivating / activating the external adjust
This setting has no influence..
Selectable options:
• yes
• no
System parameter 21:Monitoring the obstruction and measuring position
system parameter: 19
IN/OUT PLC voltage
no monitoring
system parameter: 20
external adjust
no
with integrated fieldbus interface
Start-up
system parameter: 21
check for obstruction
or wrong sheetpos.
no
Fig. 85: Setting the internal system zeroing
Selectable options:
• no
• yes
When the option "yes" was selected, the unit monitors the laser sensors. A fault message will
appear when the L20 receives a signal from only one sensor. This fault condition will also arise
when the "measuring mode external continuous" detects more than 10 ms and all other measuring
modes more than 50 ms. This ensures that a contamination of the sensor is detected.
Attention If the edge of the sheet stops between the sensors this can cause the
error to be triggered-displayed.
System parameter 22: This parameter is not available.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
91
Page 92
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
System parameter 23:Display of the MAC ID for ProfiNet bus systems.
system parameter: 23
unit MAC ID
Fig. 86: MAC-ID
The MAC ID is displayed, when the system is equipped with a Profinet bus system.
System parameter 24:Fieldbus diagnostics
system parameter: 24
fieldbus diagnostic
Fig. 87: Fieldbus diagnostics
This parameter is split into 4 subgroups:
a) Internal Fieldbus information (not displayed here)
b) Parameter channel IN/OUT
c) Process channel OUT
d) Process channel IN
line Display of the versions of Software (SV) and Hardware (Processor board and analog
rd
line: Display of the Fieldbus version (here: Profibus-DP), the bus baud rate (only if Fieldbus
3
th
line: Display of bus condition (bus status, parameter channel status, slave address if
4
This info field can also be displayed during the regular operation by pressing the ENTER key.
board).
with baud rate).
Fieldbus with slave address).
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
93
Page 94
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
7.10 Data backup
For better prevention off loss of data, a data backup procedure is available for the system
configuration and the parameter sets.
The backup is made via the upper USB interface on the front panel. The secured data can then for
example be transferred to an exchange-substituted unit after a unit failure. The data backup is
accomplished with the RPP7 software available from ROLAND ELECTRONIC.
The data backup procedure can be selected in the menu configuration. The following menu is
displayed during the data backup.
Parameter backup
Parameter backup
mode active
Connect upper USB
Fig. 90: Backup of data via USB interface
For backup of data, the upper USB slot on the front panel must be used.
Parameter backup
Parameter backup
mode active
Fig. 91: Display at active connection to PC.
For further information see chapter 10.4.
94
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 95
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
7.11 Firmware update
Roland Systems are continuously further developed. In order to use new functions, firmware
update is required.
Note The firmware update must be performed by qualified personnel only.
For performing a firmware update connect the lower front panel USB slot with the PC.
Then select “Firmware Update” in the configuration mode.
FIRMWARE UPDATE
connect USB(FLASH)
Fig. 92: Display for activating the firmware update
After the USB terminal has been connected to the PC, the following message will appear:
with integrated fieldbus interface
Start-up
On the PC used for firmware update, the actual RPP7 software must be
installed, and the desired firmware version (.bin file) must be available.
The RPP7 software can be found on the supplied CD.
FIRMWARE UPDATE
press UP and ENTER
keys simultaneously
Fig. 93: Messages for activating firmware update
By pressing the keys ▲ and ENTER simultaneously, the firmware update will be activated.
FIRMWARE UPDATE
Bootloader active
Fig. 94: Start firmware update
Attention By pressing both keys the program memory is deleted.
The firmware update must then be performed without interruption,
in order to keep the system operational.
The update will then be executed via the RPP7 software.
For operating the RPP7 software please refer to chapter 10, “Maintenance”.
The unit will restart after a successful update.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
95
Page 96
Manual
Double Sheet Control System R1000 series L20
Start-up B0063191 / 1.3
with integrated fieldbus interface
Blank page
96
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Page 97
Manual
Double Sheet Control System R1000 series L20
B0063191 / 1.3
with integrated fieldbus interface
8 Operation
8.1 Quick start guide
After applying power to the unit type and the version number are briefly displayed. Afterwards the
system switches into that measurement menu which was active before the unit was switched off.
The operation is described in chapter 7.2.
In the measuring mode the measured value can be read on the display. The control unit
automatically compares the measured value with the adjusted thresholds. The result is transmitted
via the interface to the PLC and also to the front panel LEDs.
During the normal measurement process no further actions on the control units are necessary with
the following few exceptions. The following situations require action directly at the control unit or an
action via the PLC interface:
• Clear fault and error messages (see chapter 9 “Error messages, causes and remedies“)
8.2 Entering a measurement program
8.2.1 Entering a measurement program for the double sheet detection
• Clearing a 2-sheet condition (if configured)
Operation
1 Push the MENU key, switch to "change" with the keys and confirm with ENTER key.
2 Enter the password (if active).
3 Switch to "program parameter" and confirm with ENTER key.
4 Select the desired program number at the control unit.
5 Enter the nominal dimension (nominal thickness of the sheet to be processed)
(only for system type “standard”).
6 Adjust lower limit (“low“) to 80% (default setting).
7 Adjust upper limit (“up“) to 120% (default setting).
8 Adjust the averaging according to the sheet length.
9 Return into the measurement mode with the MENU key.
8.2.2 Tailor Welded Blanks
At Tailor Welded Blanks (Sheet consists of two or more thicknesses) enter the thickest part of the
sheet as value for nominal thickness.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
97
Page 98
Manual
Double Sheet Control System R1000 series L20
Operation B0063191 / 1.3
with integrated fieldbus interface
8.3 Averaging time ta and Measuring time tm
Averaging time ta
Every measuring program allows to choose a time for averaging. This time is the averaging time t
Possible options for averaging are 8ms, 15ms, 25ms, 50ms 100ms, 250ms.
See also chapter 7.7 „Start-up“, „Program parameter 7“.
Note Basically: A longer time leads because of averaging to more
accurate measuring values.
The selection of the averaging time has influence on the maximal
velocity of the sheets.
Measuring time t
The measuring time t
m
is the time required by the system from "measurement start" to the
m
outputting of the output signal.
Messung Start
Measurement Start
a
.
Ausgangssignal
Output signal
t
m
Fig. 85.: Clarification of the measuring time
The measurement time tm is derived from the sum when operating via I/O inputs: the set time ta for
averaging and an additional delay time of 5 ms for reading the measurement. When operating via
fieldbus the additional delay is 4 ms.
8.3.1 Maximal allowed transport velocity at Double Sheet Control
The maximum allowed transport velocity of the sheet depends on the sheet length and the selected
for averaging. In addition, 4 ms are needed for internal processing.
time t
a
At an upper threshold "up" = 120% (see program parameters) following empiric formula applies:
Max. allowed transport velocity [m/s] <
Length of sheet [mm]
ta [ms] + 4ms
8.3.2 Measuring at standstill
Please notice when performing measurements at standstill:
• The minimum retention period is as long as the measurement time (the selected averaging
time).
• Punctual sheet elevations and contamination, such as dust, leads to wrong measurement
results.
98
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
1 When replacing the sensor you should proceed in concordance with chapter 4.3 "Mounting
of sensors".
2 Press the MENU key, switch to "change" with the ENTER key.
3 Enter the password (if active)
4 Switch to “adjustment parameter” and confirm by pressing the ENTER key.
5 At “measuring channel calibration” choose “yes” and confirm by pressing the ENTER key.
6 Set the sheet thickness for the measuring channel calibration and confirm by pressing the
ENTER key.
7 Place the calibration sheet between the sensors and confirm by pressing the ENTER key.
8 Confirm the completion of the measuring channel calibration by pressing the ENTER key.
9 Return into the measurement mode by pressing the MENU key
▲key and confirm by pressing the
Operation
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
99
Page 100
Manual
Double Sheet Control System R1000 series L20
Operation B0063191 / 1.3
with integrated fieldbus interface
Blank page
100
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.