Rockwell Automation PowerFlex 700S, PowerFlex 700H Installation Instructions Manual

Installation Instructions
PowerFlex® 700S and 700H Frame 14 Replacement Power Structures
Introduction
frame 14 drives are matched at the factory and cannot be paired with any other Power Modules. Therefore, when a Power Module fails, you must replace both power structures on a frame 14 drive.
Use this document to install replacement power structures on a frame 14 drive. This document covers the following replacement power structures:
Voltage Class
400/480V AC (540/650V DC)
600/690V AC (810/932V DC)
PowerFlex Spare Module Catalog String
SK-H1-PWRMOD-D1K7 20CC1K7 20CH1K7 na na
SK-H1-PWRMOD-D2K1 20CC2K1 20CH2K1 na na
SK-H1-PWRMOD-D2K7 20CC2K7 20CH2K7 na na
SK-H1-PWRMOD-E1K5 20CE1K5 20CK1K5 20DE1K5 20DK1K5
SK-H1-PWRMOD-E1K9 20CE1K9 20CK1K9 na na
SK-H1-PWRMOD-E2K2 20CE2K2 20CK2K2 na na
700H AC
Input
20CD1K7 20CJ1K7 na na
20CD2K1 20CJ2K1 na na
20CD2K7 20CJ2K7 na na
20CF1K5 20CM1K5 20DF1K5 20DM1K5
20CF1K9 20CM1K9 na na
20CF2K2 20CM2K2 na na
PowerFlex 700H DC Input
PowerFlex 700S AC Input
PowerFlex 700S DC Input
What You Need to Do
Step 1: Remove power from the drive
Step 2: Remove the old power structures
Step 3: Install the new power structures
Step 4: Connect the new power structures to the components in the
drive
Step 5: Install the product identification label on the new power
structures
Step 6: Start the drive
2 PowerFlex® 700S and 700H Frame 14 Replacement Power Structures
Power Structure Locations in Frame 14 Drives
Above 1500A Drive 1500A Drive
Rectifying Structure
Power Structure
Step 1: Removing Power from the Drive
Power Structure
Note: Shown with doors and control frames removed for clarity only.
Rectifying Structure
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before servicing
!
the drive. Check the DC bus voltage at the Power Terminal Block by measuring between the +DC and -DC terminals, between the +DC terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all three measurements.
Remove power before making or breaking cable connections. When you remove or insert a cable connector with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your system’s field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
Rectifying Structure
Power Structure
Power Structure
PowerFlex® 700S and 700H Frame 14 Replacement Power Structures 3
1. Turn off and lock out input power. Wait five minutes.
2. Verify that there is no voltage at the drive’s input power terminals.
3. Measure between the +DC and -DC terminals, between the +DC
terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all three measurements.
Step 2: Removing the Old Power Structures
L1 L2 L3
I
O
Before you can remove the old power structures from the drive, you must remove the protective screens, protective covers and air flow plates from the drive.
Note: The following steps must be completed for both power structures in the drive.
Removing the Protective Screens and Covers
1. For NEMA/UL Type 1 enclosures, remove the screws that secure the
protective screens to the enclosures and remove the screens.
2. Remove the four M5 POZIDRIV screws that secures each of the three
pairs of protective covers to the drive power structures and remove the protective covers.
1
2
Three covers
DC BUS CONDUCT
!
OPERATE AT HIGH AND W
DAN
AIT 5 MINUTES BEFORE SERVICING
GER
ORS AND CAPACITORS VOLTAGE. REMO
VE POWER
4 PowerFlex® 700S and 700H Frame 14 Replacement Power Structures
Removing the Air Flow Plates
3. Remove the four T8 Torx-head screws that secure each airflow plate to
the drive.
4. Slide each airflow plate off of the drive.
4
3
DC Bus Terminals
PowerFlex® 700S and 700H Frame 14 Replacement Power Structures 5
Important:Mark all connections and wires before removal to avoid
incorrect wiring during assembly.
5. Remove the motor connections from the output power terminals on both
of the power structures. Note: The terminals are located in different positions, depending on whether du/dt filters are installed or not.
6. Remove the ground connections from the bottom of the power structure
enclosures.
7. Remove the input connections from the incoming DC bus terminals at
the top of both power structures.
DC– (Front Terminals)
Output Power Terminals without du/dt Filters
DC+ (Back Terminals)
Power Supply Voltage Feedback Board Assembly
ASIC Board Assembly
U/T1
V/T2 W/T3
Output Power Terminals with du/dt Filters
U/T1
V/T2 W/T3
Side View
Ground Terminals
6 PowerFlex® 700S and 700H Frame 14 Replacement Power Structures
8. Remove the four screws that secure the cover to the ASIC assembly on
each power structure and remove the -DC bus connection from the cover.
Remove –DC bus connection
PowerFlex® 700S and 700H Frame 14 Replacement Power Structures 7
9. Disconnect the cable to the cooling fan, mounted on the ASIC assembly
cover, from connector X1 on the ASIC board and remove the ASIC assembly cover from each power structure.
10. Disconnect the fiber optic cables (H1 - H7) from each ASIC board.
11. Disconnect the cable from connector H903 on each ASIC Feedback
board.
12. For drives with 700H control, disconnect the +24V supply cable from
connector X10 on ASIC board #1.
13. For drives with DC input, disconnect the external precharge circuitry
from connectors X9 and X15 from each ASIC board.
X10
H7
Disconnect fiber optic cables (H1 - H7)
X3X4X5
X1
H4H5H6 H1H2H3
H11H12H13
X15
H8
H9H10
Disconnect cables
X2
DC precharge connections
X9
8 PowerFlex® 700S and 700H Frame 14 Replacement Power Structures
14. Pull the rubber grommet, through which the ASIC board and Power
Supply Voltage Feedback board wire bundles are routed, out of the drive frame and secure the wire bundles away from the frame of the power structures.
Rubber grommet and wire bundles
Precharge cables ­Shown disconnected
Fan control cables ­Shown disconnected
15. Disconnect the fan control cables and, for drives with AC input,
disconnect the precharge cable from the Rectifying modules located to the left of the ASIC board.
Loading...