Rockwell Automation CompactLogix series, 1768-L45S, 1768-L43S, 1768-L43, 1768-L45 Installation Instructions Manual

Installation Instructions
CompactLogix Controllers
Catalog Numbers 1768-L43, 1768-L43S, 1768-L45, 1768-L45S
Topic Page
Important User Information 2 About CompactLogix Controllers 6 Verify Compatibility 6 Required System Components 7 Clearance Requirements 7 Module Placement 8 Install the Controller 9 Panel Mount the Controller 10 Mount the Controller on a DIN Rail 10 Confirm the Installation 13 Connect to the Controller 14 Configure a Communication Driver 14 Insert or Remove a CompactFlash Card 18 Install Controller Firmware 18 Remove a 1768 or 1769 Module from the DIN Rail 21 Status Indicators 23 Safety Status Indicators (1768-L43S and 1768-L45S Controllers only) 25 Clear a Major Fault 26 Clear a Nonrecoverable Fault 27 Troubleshoot a Nonresponsive Module 27 Troubleshoot System Power 28 Specifications 32 Additional Resources 36
2 CompactLogix Controllers
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
available from your local Rockwell Automation sales office or online at
) describes some important differences between solid state
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Publication
Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.
1768-IN004D-EN-P - December 2009
Environment and Enclosure
CompactLogix Controllers 3
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted as well as radiated disturbances. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, Rockwell
Automation publication 1770-4.1 requirements.
, for additional installation
NEMA Standards 250 and IEC 60529, as applicable, for explanations of
the degrees of protection provided by different types of enclosure.
Publication
1768-IN004D-EN-P - December 2009
4 CompactLogix Controllers
European Hazardous Location Approval
Consider the following if you install a 1768-L43S or 1768-L45S controller in a European Zone 2 location.
European Zone 2 Certification (The following applies when the product bears the EX marking.)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
WARNING
This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Allen-Bradley.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
This equipment is not resistant to sunlight or other sources of UV
radiation.
Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.
General Safety Information for 1768-L43S and 1768-L45S Controllers
ATTENTION
Publication
Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 5
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD -
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Preventing Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
Publication
1768-IN004D-EN-P - December 2009
6 CompactLogix Controllers
About CompactLogix Controllers
CompactLogix 1768-L43 and 1768-L45 controllers are designed to provide a Logix solution for medium-sized applications. Compact GuardLogix controller catalog numbers end in ‘S’. These safety controllers are wider than their standard counterparts.
1768-L43, 1768-L45 1768-L43S, 1768-L45S
Verify Compatibility
IMPORTANT
This table shows the compatible RSLogix 5000 software versions and controller firmware revisions.
Controllers RSLogix 5000 Software
1768-L43 and 1768-L45, Series B
Attempting to use controllers with incompatible software and firmware revisions may result in:
an inability to connect to the series B controller in RSLogix 5000
software.
unsuccessful firmware upgrades in ControlFlash or AutoFlash
utilities.
Controller Firmware
Version or Later
16.03 16.23
Revision or Later
1768-L43S and 1768-L45S, Series B
Publication
1768-IN004D-EN-P - December 2009
18 18
CompactLogix Controllers 7
Required System Components
You need these parts when installing your controller:
1768-L43, 1768-L43S, 1768-L45, or 1768-L45S CompactLogix
controller
1768-PA3 or 1768-PB3 power supply
1769-ECR end cap
Mounting screws (M4 or #8 panhead) or one of these
EN 50 022 DIN rails:
35 x 7.5 mm (1.38 x 0.30 in.)35 x 15 mm (1.38 x 0.59 in.)
1756-CP3 serial cable (or make your own)
Clearance Requirements
Allow for the minimum clearance from enclosure walls, wireways, and other equipment.
105 mm (4.13 in.)
90 mm
(3.54 in.)
IMPORTANT
Power
L1
L2/N
OUT
31609-M
105 mm (4.13 in.)
These minimum clearances keep the modules cool enough in most situations. See Specifications on page 32
for the acceptable temperature range.
90 mm
(3.54 in.)
Publication
1768-IN004D-EN-P - December 2009
8 CompactLogix Controllers
Module Placement
1768 Backplane (local) 1768 Controller, Power
Supply, and I/O Modules
Remote Bank
1769 Power Supply and
I/O Modules
1769 Backplane
IMPORTANT
CompactLogix System Distance Ratings
Because the 1768 CompactLogix power supply works with the controller to power a 1768 system, the distance rating in a 1768 CompactLogix system differs from that in a 1769 CompactLogix system. In the 1768 system, the distance rating is the distance between 1769 I/O modules and the controller. In the 1769 system, the distance rating is the distance between 1769 I/O modules and the power supply.
Follow these requirements to determine proper placement of your 1768 controller, power supply, 1768 I/O modules, and 1769 I/O modules:
Place the 1768-L4xx controller so that it is the last module
(furthest away from the power supply) in the 1768 backplane.
The 1768 CompactLogix power supply distributes power from
the right side of the supply and must be the leftmost module in the system.
Up to eight 1769 I/O modules can reside in the local bank.
The local bank is powered by a 1768 power supply.
Up to two remote banks of 1769 I/O modules may be
connected by using 1769-CRLx extension cables.
Remote banks are powered by a standard 1769 power supply.
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 9
Up to eight 1769 Compact I/O modules can reside on each
side of a 1769 power supply in a remote bank. Consult the module’s specifications for its distance rating.
IMPORTANT
Never place a 1769 power supply in a local bank with a 1768 controller or a major fault will occur.
The type of controller determines the maximum number of
1768 modules that can reside in the local bank and the maximum number of 1769 I/O modules that can reside in one local and up to two remote banks.
Controller Max Local 1768
Modules
1768-L43, 1768-L43S 2 16 1768-L45, 1768-L45S 4 30
Max 1769 I/O Modules (local and remote)
Install the Controller
Follow these steps to install your controller.
1. Mount the controller to a panel or on a DIN rail.
IMPORTANT
Do not use screws if using a DIN rail to mount the controller. You can break the mounting tabs if you screw the controller to a panel while it is on a DIN rail.
2. Confirm the installation.
3. Connect the controller.
4. Configure a serial or Ethernet driver.
5. Install a CompactFlash card (optional).
6. Download and install controller firmware.
Publication
1768-IN004D-EN-P - December 2009
10 CompactLogix Controllers
Panel Mount the Controller
Follow these steps to mount your controller by using the panhead screws.
1. Connect the CompactLogix modules together as shown in
Mount the Controller on a DIN Rail
on page 10.
2. Use the controller as a template and mark pilot holes on your panel.
3. Drill the pilot holes for M4 or #8 screws.
ATTENTION
During mounting of all devices, be sure that all debris (such as metal chips or wire strands) is kept from falling into the controller or I/O modules. Debris that falls into the controller or modules could cause damage while the controller is energized.
4. Use M4 or #8 screws to mount the controller to your panel with 1.16 N•m (10 lb•in) of torque.
5. Ground the module on a ground bus with a dedicated earth ground stake.
6. Connect the ground bus to a functional earth ground on the panel or a DIN rail.
Mount the Controller on a DIN Rail
ATTENTION
Publication
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum and plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to the mounting surface approximately every 200 mm (7.87 in.) and use end anchors appropriately.
1768-IN004D-EN-P - December 2009
Mount 1768 Components
Follow these steps to mount the controller.
1. Mount the controller on the DIN rail.
CompactLogix Controllers 11
a.
31595-M
b.
31596 -M
2. Mount additional 1768 modules to the left of the controller.
a.
c.
b.
a.
3. Mount the 1768 power supply and other 1768 modules.
31597-M
Publication
c.
31599-M
31598 -M
1768-IN004D-EN-P - December 2009
12 CompactLogix Controllers
Mount 1769 I/O Modules
Follow these steps to mount 1769 I/O modules to the right of the controller.
1. Align the upper and lower tongue-and-groove slots and slide the module back toward the DIN rail until the bus levers line up.
2. Close the DIN rail latches.
3. Slide the bus lever to the left to lock the modules together.
ATTENTION
Publication
1768-IN004D-EN-P - December 2009
When attaching I/O modules, it is very important that the bus connectors are securely locked together for proper electrical connection.
CompactLogix Controllers 13
4. Attach the end cap by using the tongue and groove slots (a) and locking the bus lever (b).
a.
b.
a.
Confirm the Installation
After you have installed the controller and applied power, check that the PWR and I/O PWR status indicators are solid green.
Power
L1
L2/N
OUT
If the indicators are in any other state, see Troubleshoot System
Power on page 28.
Publication
1768-IN004D-EN-P - December 2009
14 CompactLogix Controllers
Connect to the Controller
WARNING
If you connect or disconnect the serial cable with power applied to this module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Connect the 1756-CP3 serial cable to the controller’s serial port and to your workstation.
If you make your own cable, follow these guidelines.
Wire the connectors as
shown.
Limit the cable length
to 15.2 m (50 ft).
Attach the shield to
both connectors.
Workstation Controller
1 DCD 2 RDX 3 TXD
4 DTR
COMMON
6 DSR 7 RTS 8 CTS
1 DCD 2 RDX
3 TXD 4 DTR
COMMON
6 DSR 7 RTS 8 CTS
9
9
Configure a Communication Driver
Before you update controller firmware or use the controller in your network, you must configure a communication driver specific to your network.
See Configure a Serial Driver
Driver on page 17.
on page 15 or Configure an EtherNet/IP
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 15
Configure a Serial Driver
Use RSLinx software to configure the driver for serial communication.
1. From the Communications menu, choose Configure Drivers.
2. From the Available Driver Types pull-down menu, choose the RS-232 DF1 devices driver.
3. Click Add New.
4. Type a name for the driver and click OK.
Publication
1768-IN004D-EN-P - December 2009
16 CompactLogix Controllers
5. From the Comm Port pull-down menu on the Configure Devices dialog box, choose the serial port on the workstation
to which your cable is connected.
6. From the Device pull-down menu, choose Logix5550/CompactLogix.
7. Click Auto-Configure. a. Click OK if the Auto Configuration Successful dialog box
appears.
b. If the dialog box does not appear, go back to step 5
verify that you selected the correct comm port.
8. Click Close.
and
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 17
Configure an EtherNet/IP Driver
For EtherNet/IP communication, you must use a 1768-ENBT or 1768-EWEB module. If your controller is a 1768-L4xS, you must use a series B 1768-ENBT or 1768-EWEB module. You can install up to two of these modules to the left of the controller in the 1768 backplane. Before you can load controller firmware via the EtherNet/IP network, you must set the EtherNet/IP module’s IP address. You can set the IP address by using the BootP-DHCP Utility on the Tools menu in RSLogix 5000 software.
For more information, refer to the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001
Set the Communication Path to the Controller
1. Open an RSLogix 5000 project for the controller.
2. From the Communications menu, choose Who Active.
3. Expand the communication driver to the level of the controller.
4. Select the controller.
.
5. Complete the desired action.
To Cli ck
Monitor the project in the controller Go Online Transfer a copy of the project from the controller to RSLogix 5000 software Upload Transfer the open project to the controller Download
Publication
1768-IN004D-EN-P - December 2009
18 CompactLogix Controllers
Insert or Remove a CompactFlash Card
WARNING
When you insert or remove the CompactFlash card while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Follow these steps to insert or remove a CompactFlash card.
1. Press the memory-card door latch on the controller front panel and pivot the door down toward you.
2. Insert or remove the card from the slot.
3. Close the memory card door.
Install Controller Firmware
The controller ships without functioning firmware, so you must obtain and install the firmware before you can use your controller.
IMPORTANT
When installing or updating controller firmware, do not interrupt the update process in any way. Interrupting the firmware update may result in an inoperable controller. Inoperable controllers must be returned to Rockwell Automation.
Firmware revisions are available with RSLogix 5000 programming software, or you can download them from the support website at:
http://support.rockwellautomation.com
. Be prepared to enter the
serial number of your RSLogix 5000 software. To install firmware, you can use any of the following.
Method Page
ControlFlash, version 8 or later, software that ships with RSLogix 5000 software 19 AutoFlash software that runs within RSLogix 5000 software 20 A 1784-CF64 or 1784-CF128 CompactFlash card with valid firmware already loaded 21
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 19
Updating your controller firmware via ControlFlash or AutoFlash software requires either a serial or other network connection to the controller.
Updating via an Ethernet connection is faster, but you must first install a 1768-ENBT Ethernet module to connect to the controller via the Ethernet network.
For information on installing, configuring, and operating a 1768-ENBT module, refer to the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001
.
Install Firmware via ControlFlash Software
1. Make sure the network is connected.
2. Start ControlFlash software.
3. When the Welcome dialog box appears, click Next.
4. Select the catalog number of the controller and click Next.
5. Expand the network until you see the controller.
TIP
6. Select the controller and click OK.
7. Select the desired revision level and click Next.
If the required network is not shown, first configure a driver for that network in RSLinx software.
8. To start the update, click Finish and then Yes.
The OK status indicator flashes red to show that the update is in progress. The status box indicates when the update is complete and the OK status indicator is solid green.
9. Click OK.
10. Click Cancel and then Yes to close ControlFlash software.
Publication
1768-IN004D-EN-P - December 2009
20 CompactLogix Controllers
Install Firmware via AutoFlash Software
1. Make sure the network is connected.
2. Using RSLogix 5000 software, attempt a download to a controller project.
AutoFlash software launches if the required firmware is not loaded on the controller.
3. Select the catalog number of the controller and click Next.
4. Expand the network until you see the controller.
TIP
5. Select the controller and click OK.
If the required network is not shown, first configure a driver for that network in RSLinx software.
6. Select the desired revision level and click Next.
7. To start the update, click Finish and then Yes.
The OK status indicator flashes red to show that the update is in progress. The status box indicates when the update is complete and the OK status indicator is solid green.
8. Click OK.
9. Click Cancel and then Yes to close AutoFlash software.
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 21
Install Firmware via a CompactFlash Card
Follow these steps to use RSLogix 5000 software to store the controller program and firmware of an already-configured controller to the CompactFlash card. The firmware is automatically stored on your CompactFlash card when you store the program.
1. With the CompactFlash card installed on the configured controller, on the Controller Properties dialog box, click the Nonvolatile Memory tab.
2. Click Load Image On Powerup to save to the card.
3. Remove the card and insert it into the controller onto which you want to load the firmware and user program.
4. Start the new controller and the image stored on the CompactFlash card loads.
Remove a 1768 or 1769 Module from the DIN Rail
If you need to remove a module from the DIN rail, follow these steps.
1. Remove power from the controller and wait for all status indicators on the power supply and controller to turn off.
Off
Power
L1
L2/N
OUT
IMPORTANT
If you disconnect any part of the system while the controller is still writing its program to memory, you will lose your program.
Publication
1768-IN004D-EN-P - December 2009
22 CompactLogix Controllers
2. Remove the 1768 module.
a.
Power
L1
L2/N
OUT
b.
a.
c.
Powe r
L1
L2/N
OUT
d.
c.
31607-M
3. Remove the 1769 module by unlocking the bus lever (a) and DIN rail latches (b).
b.
Power
L1
L2/N
OUT
b.
a.
4. Slide the module away from the DIN rail along the tongue and groove slots.
Publication
1768-IN004D-EN-P - December 2009
Status Indicators
Controller Status Indicators
Indicator State Description
Green The controller is providing power to 1768 modules in
PWR
the system.
CompactLogix Controllers 23
I/O PWR
RUN
FORCE
MEM SAVE
Off or red See Troubleshoot System Power Off Replace the controller. Green The controller is operating properly. Flashing red/green
or solid red Off The controller is in PROG or Test mode. Green The controller is in RUN mode. Off No tags contain I/O force values or I/O forces are
Amber I/O forces are active (enabled). I/O force values may or
Flashing amber One or more input or output addresses have been
Off The user program and configuration data are not
See Troubleshoot System Power
inactive (disabled).
may not exist.
forced to an On or Off state, but the forces have not been enabled. Enable forces or remove the individual I/O from being forced.
actively being saved to flash memory.
on page 28.
on page 28.
Green The use program and configuration data are being
I/O Off There are no devices in the I/O configuration of the
Green The controller is communicating with all of the devices
Flashing green One or more devices in the controller’s I/O configuration
Flashing red The controller is not communicating with any of the
saved to flash memory.
controller or the controller does not contain a project.
in its I/O configuration.
are not responding. See Troubleshoot a Nonresponsive Module
devices in its I/O configuration. See Troubleshoot a Nonresponsive Module
Publication
1768-IN004D-EN-P - December 2009
on page 27.
on page 27.
24 CompactLogix Controllers
Controller Status Indicators
Indicator State Description
OK Off No power is applied. If MEM SAVE indicator is green,
the user program and configuration data are being saved to flash memory.
Flashing red The controller requires a firmware update or a
firmware update is in progress.
A recoverable major fault occurred on the
controller.
A nonrecoverable major fault occurred on the
controller.
See Clear
Red The controller detected a nonrecoverable major fault so
it cleared the project from memory.
See Clear a Nonrecoverable Fault Green Controller is OK. Flashing green The controller is storing or loading a project to or from
nonvolatile memory.
CF Off There is no CompactFlash card activity.
Flashing green The controller is reading from or writing to the
CompactFlash card.
IMPORTANT: Do not remove the CompactFlash card
while the controller is reading from or writing to the
card. Removing the card during a read or write could
corrupt data on the card, data in the controller, and
firmware installed on the controller. Flashing red The CompactFlash card does not have a valid file
system and must be replaced.
a Major Fault on page 26.
on page 27.
DCH0 Off Channel 0 is configured differently than the default
Green Channel 0 has the default serial configuration.
CH0 Off No RS-232 activity.
Green RS-232 activity.
Publication
1768-IN004D-EN-P - December 2009
serial configuration.
CompactLogix Controllers 25
Safety Status Indicators (1768-L43S and 1768-L45S Controllers only)
Indicator State Description
Off The user safety task or safety outputs are disabled.
The controller is in PROG mode, Test mode, or the safety task is faulted.
Green The user safety task and safety outputs are enabled.
SAFE RUN
SAFETY TASK
Flashing green The user safety task and safety outputs are enabled.
Off No partnership established. Green Safety controller status is OK. The coordinated
Flashing green Safety controller status is OK. The coordinated
The safety task is executing. Safety signature is present.
The safety task is executing. Safety signature is not present.
system time (CST) is synchronized and safety I/O connections are established.
system time (CST) is not synchronized.
SAFETY LOCK
SAFETY OK
Red Safety partnership was lost. Flashing red Safety task is inoperable. Off Safety task is not locked. Green Safety task is locked. Off No power is applied. Green The safety partner is OK. Flashing green The safety partner is storing or loading a project to
or from nonvolatile memory.
Red The safety partner detected a nonrecoverable major
fault, so it cleared the project from its memory.
Flashing red The internal safety partner requires a firmware
update or a firmware update is in progress.
A recoverable major fault occurred on the
safety partner.
A nonrecoverable major fault occurred on the
safety partner.
Publication
1768-IN004D-EN-P - December 2009
26 CompactLogix Controllers
Clear a Major Fault
If the OK status indicator flashes red because of a recoverable major fault, clear the fault by following these steps.
1. Turn the controller keyswitch from PROG to RUN and back to PROG.
2. Go online with RSLogix 5000 software.
3. On the Controller Properties dialog box, click the Major Faults tab to find information about the fault.
If the OK status indicator is flashing red because of a nonrecoverable major fault, the controller:
initially displayed a solid red OK indicator.
reset itself.
cleared the project from its memory.
set the OK indicator to flashing red.
produced a major recoverable fault and generated a
corresponding fault code in the RSLogix 5000 project.
Fault code 60 means the CompactFlash card is not installed.Fault code 61 means the CompactFlash card is installed.
Follow these steps to recover from fault code 60 or 61.
1. Turn the controller keyswitch from PROG to RUN and back to PROG.
2. Go online with RSLogix 5000 and download the project.
3. Change to REM RUN or RUN mode.
If the issue persists, record the status of the OK and RS-232 indicators before cycling power and contacting Rockwell Automation support.
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 27
Clear a Nonrecoverable Fault
If the OK status indicator is solid red, follow these steps to clear the fault.
1. Cycle power.
2. Download the project.
3. Change to REM RUN or RUN mode.
If the issue persists, record the status of the OK and RS-232 indicators before cycling power and contacting Rockwell Automation support.
Troubleshoot a Nonresponsive Module
Follow these steps to determine why a device may not be responding.
1. Verify that all I/O modules in your project are installed in the same order.
2. Verify that all devices have been updated to the latest major and minor firmware revisions.
3. Use RSLogix 5000 software’s online help to determine which module is not responding.
Publication
1768-IN004D-EN-P - December 2009
28 CompactLogix Controllers
Troubleshoot System Power
The CompactLogix power supply works with the CompactLogix controller to provide power to the system. You must consider both when attempting to troubleshoot system power.
IMPORTANT
Before you disconnect, reconnect, or replace any component, make sure you have turned off power and allowed all system status indicators to turn off.
To troubleshoot system power issues, use the CompactLogix power supply PWR status indicator and the CompactLogix controller PWR and I/O PWR indicators. If the power supply is not operating properly, the controller will not operate properly either. You must first diagnose and correct any issues with the power supply before troubleshooting the controller.
1. Examine the power supply PWR status indicator.
2. If the power supply is operating properly and the power supply PWR status indicator is green, examine the controller PWR indicator.
3. If the controller PWR status indicator is green, examine the I/O PWR status indicator.
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 29
Examine the Power Supply PWR Status Indicator
Power Supply PWR Indicator Status
Off Verify that the power supply is turned on and that adequate input
Green The power supply is operating properly.
Red The power supply is not producing valid 24V power to the 1768
Recommended Action
power is properly connected. Replace the power supply.
Check the controller PWR and I/O PWR status indicators to make sure the entire system is operating properly.
modules. Follow the corrective action below.
1. Remove power and wait for all status indicators to turn off.
2. Disconnect all modules from the system, including the controller.
3. Reapply power.
4. Check the PWR status indicator on the power supply. a. If the status indicator remains red, replace the power
supply.
b. If the status indicator is green, one of the other modules in
the system is causing the red indicator.
5. Remove power and wait for all status indicators to turn off.
6. Reinstall the controller and check the power supply’s PWR indicator.
a. If green, remove power, wait for all status indicators to turn
off and reinstall 1768 modules one at a time until you identify the module causing the red indicator.
b. If red, replace the controller.
Publication
1768-IN004D-EN-P - December 2009
30 CompactLogix Controllers
Examine the Controller PWR Indicator
This task assumes that the power supply PWR indicator is green.
Controller PWR Indicator Status
Off Make sure all of the modules in the system are installed
Green The controller is providing power to 1768 modules in the
Red Either the controller or 1768 modules in the system need to
Recommended Action
properly and are fully engaged with one another. If the indicator remains off, follow the corrective action below.
system. Check the controller I/O PWR status indicator to make sure the entire system is operating properly.
be replaced. Follow the corrective action below.
1. Remove power and wait for all status indicators to turn off.
2. Disconnect all 1768 modules from the system, except for the controller.
3. Reapply power.
4. Check the controller PWR indicator. a. If the status indicator remains red, replace the controller. b. If the status indicator is green, one of the 1768 modules is
causing the red indicator.
5. Remove power.
6. Reinstall the 1768 modules one at a time, removing and reapplying power and checking the controller PWR indicator each time.
7. If the controller PWR indicator turns red, the most-recently installed module is causing the red indicator.
To troubleshoot 1768 modules, see their respective installation instructions.
Publication
1768-IN004D-EN-P - December 2009
CompactLogix Controllers 31
Examine the I/O PWR Indicator
This task assumes that the power supply and controller PWR indicators are green and that you have 1769 I/O modules in your system.
Controller I/O PWR Indicator Status
Off Replace the controller. Green The controller is operating properly. No action required. Flashing red and green Make sure the 1769 I/O modules or end cap are properly
Red A 1769 power supply may be installed in the local bank, or
(1) When the controller powers up, the I/O PWR status indicator is momentarily red and then changes to
green if there are no issues. If the indicator remains red, use the table above to troubleshoot the issue.
(1)
Recommended Action
attached and cycle power.
there may be an issue with the controller or 1769 I/O in the system. Follow the corrective action below.
1. If there is a 1769 power supply installed in the local bank, remove it and reapply power.
If the I/O PWR indicator remains red, go to the next step.
2. Remove power and wait for all status indicators to turn off.
3. Disconnect the 1769 I/O modules from the system.
4. Reapply power.
5. Check the controller I/O PWR indicator. a. If the indicator is red, replace the controller. b. If the indicator is green, one of the 1769 I/O modules is
causing the red indicator. To troubleshoot 1769 I/O modules, see their respective
installation instructions.
Publication
1768-IN004D-EN-P - December 2009
32 CompactLogix Controllers
Specifications
1768-L43, 1768-L43S, 1768-L45, 1768-L45S Controllers
Attribute 1768-L43 1768-L43S 1768-L45 1768-L45S
1768 backplane module
24
support Backplane current 1.3 A @ 24V 1.4 A @ 24V 2.0 A @ 24V 2.1 A @ 24V 1769 backplane current
2.0 A @ 5.2V 2.0 A @ 5.2V
output 1768 backplane current
2.8 A @ 5.2V 5.6 A @ 5.2V
output Total 1768 and 1769
4.8 A @ 5.2V 7.6 A @ 5.2V
backplane current output Power dissipation
6.3 W
(2)
7.5 W
(2)
8.3 W
(2)
9.5 W
(2)
Power consumption 31.3 W 33.6 W 48.0 W 50.4 W Number of 1769-series I/O
16 30
modules, max Number of I/O banks, max 2 3 Number of 1768 modules
(3)
2
4
(3)
available, max Isolation voltage 30V (continuous)
Functional Insulation Type Type Tested @ 500V AC for 60 s, RS-232 to system
Wiring category North American
(1)
2 - on communication ports T4
temperature code IEC temperature code Not
Applicable
Mounting screw torque 1.16 N
Publication
1768-IN004D-EN-P - December 2009
m (10 lbin), using M4 or #8 screws
T4 Not
Applicable
T4
CompactLogix Controllers 33
1768-L43, 1768-L43S, 1768-L45, 1768-L45S Controllers
Attribute 1768-L43 1768-L43S 1768-L45 1768-L45S
Dimensions (HxWxD), approx.
Weight, approx. 0.34 kg
Enclosure type rating None (open style)
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
(2) See related Power Dissipation chart that follows. (3) Important: You can have any combination of motion and network modules installed in a system.
There is a maximum limit of two network modules that can be installed in a system. Network modules include: 1768-ENBT, 1768-CNB, 1768-CNBR, and 1768-EWEB.
131.6 x 67.4 x 121.8 mm (5.18 x 2.65 x 4.80 in.)
(11.9 oz)
131.6 x 90 x
121.8 mm (5.18 x 3.55 x 4.80 in.)
0.45 kg (15.9 oz)
131.6 x 67.4 x 121.8 mm (5.18 x 2.65 x
4.80 in.)
0.34 kg (11.9 oz)
.
131.6 x 90 x
121.8 mm (5.18 x 3.55 x 4.80 in.)
0.45 kg (15.9 oz)
1768-L43 and 1768-L43S Power Dissipation
7.5 W
6.3 W
Power Dissipated (Watts)
4.0 W
8
6
2.8 W
4
2
510
0
1768 and 1769 Bus 5.2V Load (Watts)
15 20
Publication
1768-IN004D-EN-P - December 2009
25
30
1768-L43S 1768-L43
34 CompactLogix Controllers
1768-L45 and 1768-L45S Power Dissipation
9.5 W
4.0 W
Power
8
6
Dissipated (Watts)
2.8 W
4
2
0
510
1768 and 1769 Bus 5.2V Load (Watts)
Environmental Specifications
Attribute Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...60 °C (32...140 °F)
15 20
25
30
35
40
8.3 W
1768-L45S 1768-L45
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g Emissions CISPR 11: Group 1, Class A ESD immunity IEC 61000-4-2: 6 kV contact discharges
8 kV air discharges
EFT/B immunity IEC 61000-4-4:
±4 kV at 5 kHz on communication ports
Publication
1768-IN004D-EN-P - December 2009
Environmental Specifications
Attribute Value
Radiated RF immunity IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
CompactLogix Controllers 35
Surge transient immunity
Conducted RF immunity
Certifications (when product is marked)
IEC 61000-4-5:
±2 kV line-earth (CM) on communication ports
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
(1)
Certification Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See
UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
Ex 1768-L43S and 1768-L45S only:
European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection ‘n’ II 3 G Ex nA IIC T4 X EN60079-0; General Requirements
Functional
(2)
Safety
1768-L43S and 1768-L45S only: Certified by TÜV: capable of SIL 1 to 3, according to IEC 61508; and PLe/Cat. 4 according to ISO 13849-1
(1) See the Product Certifications link at www.ab.com for Declarations of Conformity, certificates, and
other certification details.
(2) When used with specified software versions.
Publication
1768-IN004D-EN-P - December 2009
Additional Resources
These documents contain additional information concerning related Rockwell Automation http://www.ab.com products.
Resource Description
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication
ENET-UM001
1768 CompactLogix Controllers User Manual, publication 1768-UM001
Compact GuardLogix Controllers User Manual, publication 1768-UM002
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website,
http://www.ab.com
Details how to configure, program, operate, and troubleshoot EtherNet/IP modules, and provides technical specifications.
Details how to configure, program, and operate a 1768 CompactLogix system, and provides technical specifications.
Details how to configure, program, and operate a 1768 Compact GuardLogix system.
Information on the safety requirements for GuardLogix controller systems.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://literature.rockwellautomation.com. To order paper copies of
technical documentation, contact your local Rockwell Automation distributor or sales representative.
Allen-Bradley, Rockwell Automation, Rockwell Software, CompactLogix, GuardLogix, RSLogix 5000, ControlFlash, RSLinx, Logix5000, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1768-IN004D-EN-P - December 2009 PN-48443
Supersedes Publication 1768-IN004C-EN-P - October 2008 Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...