Rockwell Automation CENTERLINE 2100 Instruction Manual

CENTERLINE 2100 Low Voltage Motor Control Centers
Instruction Manual
2100-xxx
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 Rockwell Automation sales office or online at http://literature.rockwellautomation.com between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local
) describes some important differences
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
CENTERLINE, CENTERLINE 2100, ArcShield, Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

The information below summarizes the changes to this manual since the last printing.
To help you find new and updated information in this release of the manual, we have included change bars as shown to the right of this paragraph.
Topic Page
Addition of ArcShield Throughout document Updated tech support contact information Throughout document Updated product dimensions 26 Updated seismic information 37 Addition of temperature measurement
techniques for preventative maintenance
95
3Publication 2100-IN012C-EN-P - April 2009 3
Summary of Changes
Notes:
4 Publication 2100-IN012C-EN-P - April 2009
General Information

Table of Contents

Preface
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Purchased Components and Additional Instruction Sheets. . . 10
Chapter 1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Nameplate Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
MCC Sequence Numbering . . . . . . . . . . . . . . . . . . . . . . . . . 14
UL/CSA Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Short-circuit Rating Label. . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Series Number and Series ID as Manufactured in the
United States. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Series Lettering - Units and Sections. . . . . . . . . . . . . . . . . . . 20
Receiving, Handling and Storage . . . . . . . . . . . . . . . . . . . . . 22
Receiving. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Storage and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installation Procedures
Installing Conduit and Cable
Chapter 2
Location Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Height Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Securing an MCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Seismic Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Joining & Splicing New MCCs . . . . . . . . . . . . . . . . . . . . . . . 38
Joining & Splicing Existing MCCs . . . . . . . . . . . . . . . . . . . . . 38
Installing and Joining Pull Boxes . . . . . . . . . . . . . . . . . . . . . 38
Joining and Splicing NEMA Type 12 MCCs . . . . . . . . . . . . . . 39
Joining & Splicing NEMA Type 3R and Type 4 MCCs . . . . . . 39
Bus Torque Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Chapter 3
Installing Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Bottom Entry Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Top Entry Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Installing Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Incoming Line Compartment . . . . . . . . . . . . . . . . . . . . . 43
Main Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Cable Bracing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Incoming Line Brace . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Chapter 4 Installing and Removing Plug-in Units
5Publication 2100-IN012C-EN-P - April 2009 5
Installing Plug-in Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Remove a Plug-in Unit with a Vertical Operating Handle
from a Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table of Contents
Arc Flash Protection Marking as Required by the National Electrical Code
Operator Handle and Unit Interlock
Remove a Plug-in Unit with a Horizontal Operating Handle
from a Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Remove the Support Pan. . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Chapter 5
Flash Protection Marking Requirement . . . . . . . . . . . . . . . . . 59
110.16 Flash Protection . . . . . . . . . . . . . . . . . . . . . . . . . 59
Arc Flash Marking Clarification . . . . . . . . . . . . . . . . . . . . . . 60
Rockwell Automation Services . . . . . . . . . . . . . . . . . . . . . . . 60
Chapter 6
Defeating the Unit Door Interlock . . . . . . . . . . . . . . . . . . . . 61
Open the Door when the Operating Handle is in the
ON/I Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Defeating the Unit Interlock Lever . . . . . . . . . . . . . . . . . . . . 63
Energize a Unit with the Unit Door Open . . . . . . . . . . . . 63
Locking Provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Lock Vertical Operating Handles in the OFF/O Position . 64 Lock Horizontal Operating Handles in the OFF/O
Position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Lock Units with Operating Handles in the ON/I Position . 66
Unit Interlocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Final Check List Before Energizing
Energizing the Equipment
Maintenance
Maintenance After Fault Condition
Renewal Parts
Chapter 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Pre-Energizing Check Procedure . . . . . . . . . . . . . . . . . . . . . 73
Perform the Pre-energizing Check Procedure . . . . . . . . . . . . 74
Chapter 8
Energize the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Chapter 9
Maintain the MCC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Disconnect the Switch and Contact Lubrication . . . . . . . . . . 94
Use Thermal Infrared or Other Temperature Measurement
Techniques for Preventive Maintenance . . . . . . . . . . . . . . . . 95
Inspect the Units for Signs of Overheating . . . . . . . . . . . 96
Chapter 10
Maintain the MCC After a Fault Condition . . . . . . . . . . . . . . 99
Chapter 11
Order Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
6 Publication 2100-IN012C-EN-P - April 2009
Parts Illustrations
Table of Contents
Chapter 12
Typical Section Construction . . . . . . . . . . . . . . . . . . . . . . . 103
Typical Construction of a Unit with a Vertical Operating
Handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Typical Construction of a Half Space Factor Unit with a Horizontal Operating Handle and Door Mounted Pilot
Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Typical Construction of a Unit with a Horizontal Operating
Handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Index
Publication 2100-IN012C-EN-P - April 2009 7
Table of Contents
8 Publication 2100-IN012C-EN-P - April 2009

Preface

Additional Resources

The following publications supplement this manual. For more information and further reference, please use these available publications.
Publication Name Publication No.
Arc-Flash Resistant Low Voltage Motor Control Center Designs White Paper
Power Factor Correction Capacitors for Bulletin 2100 MCC Starter Units Application Techniques
CENTERLINE 2100 Motor Control Centers Joining and Splicing Vertical Sections Instructions
CENTERLINE 2100 Motor Control Centers (MCC) Units with Vertical Operating Handles Installation Instructions
CENTERLINE Motor Control Centers NEMA Type 12 Sealing Instructions
Receiving, Handling, and Storing Motor Control Centers 2100-IN040 MCC Instantaneous Trip Motor Circuit Protectors (MCP) in
Combination NEMA Starter, Soft Starter (SMC), and Variable Frequency AC Drive Units Technical Data
MCC Inverse Time Circuit Breakers in Combination NEMA Starter, Soft Starter (SMC), and Variable Frequency AC Drive Units Technical Data
CENTERLINE Motor Control Centers Power Fuses Product Data 2100-TD003 DeviceNet Motor Control Centers (MCC) Technical Data 2100-TD019
2100-AP003
2100-AT001
2100-IN010
2100-IN014
2100-IN037
2100-TD001
2100-TD002
CENTERLINE 2100 Motor Control Center End Closing Plates Installation Instructions
CENTERLINE 2100 Motor Control Center (MCC) Units with Horizontal Operating Handles Installation Instructions
CENTERLINE Motor Control Centers Mains and Incoming Lines Reference Document Update
CENTERLINE Motor Control Centers Installing a Pull Box on a Bulletin 2100 Vertical Section Instructions
Safety Guidelines for the Application, Installation, and Maintenance of Solid-state Control
2100-IN069
2100-IN060
2100-TD018
2100-IN029
SGI-IN001
You can view or download publications at
http://literature.rockwellautomation.com
. To order paper copies of technical documents, contact your local Rockwell Automation distributor or sales representative.
9Publication 2100-IN012C-EN-P - April 2009 9
Preface
The documents in the following table are referenced in this document and can be obtained from their respective organizations.
Resource Website
National Electrical Manufacturer’s Association (NEMA)
NEMA ICS 1-2000 Industrial Control and Systems: General Requirements
NEMA ICS 2.3-1995, Instructions for Handling, Operation and Maintenance of Motor Control Centers Rated Not More Than 600V
National Fire Protection Association (NFPA)
NFPA 70 - National Electrical Code
NFPA 70A - Recommended Practice for Electrical Equipment
Maintenance
NFPA 70E - Standard for Electrical Safety in the Workplace
Institute of Electrical and Electronic Engineers (IEEE) IEEE standard C37.20.7 - IEEE Guide for Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults
www.nema.org
www.nfpa.org
www.ieee.org
Purchased Components and
When equipment such as transformers, metering, PLCs, or drives are supplied with the motor control center (MCC), specific manuals and
Additional Instruction Sheets
data sheets are also supplied. These documents should be read and understood before installing and operating the MCC. Refer to the unit locations of these devices for their manuals and/or data sheets.
10 Publication 2100-IN012C-EN-P - April 2009
General Information
Chapter
1

General Description

Allen-Bradley CENTERLINE Motor Control Centers (MCCs) consist of one or more vertical sections containing electromagnetic and/or solid state control devices that are prewired and tested within modular (plug-in) or frame mounted (hard-wired) units.
CENTERLINE MCCs are designed in standard widths of 20 in. (508 mm), 25 in. (635 mm), 30 in. (762 mm), 35 in. (789 mm), and 40 in. (1016 mm). The standard front-mounted depths of an MCC are 15 in. (381 mm) and 20 in. (508 mm), in addition back-to-back mounted depths of 30 in. (762 mm) and 40 in. (1016 mm) are also offered. The standard height of an MCC is 90 in. (2286 mm). A 70.5 in. (1791 mm) high section is also available. All MCC sections are supplied with top and bottom horizontal wireways. Sections which are designed to accommodate plug-in units include a vertical wireway. Each 90 in. (2286 mm) vertical section can accommodate up to 6.0 space factors or 78 in. (1981 mm) for units.
Units (buckets) are designed in increments of 0.5 space factors. Each
0.5 space factor is approximately 6.5 in. (165.1 mm) high. Units are designed as either removable (plug-in) or frame-mounted (non-plug-in).
Individual units house a wide variety of power and logic devices. Plug-in units are mounted on unit support pans within the section. Stab assemblies located on the back of the unit plug onto the vertical bus. A mechanical interlock prevents the unit door from being opened when the disconnect is not in the OFF position. An additional mechanical interlock prevents the unit from being plugged-in or unplugged when the disconnect is not in the OFF position.
Line power is distributed throughout the MCC via an isolated bus work structure. The main horizontal bus is located in the center of each section. Standard, center-fed, 300 A rated vertical bus supplies power to the individual units above and below the horizontal bus for an effective 600 A capacity, allowing virtually unrestricted unit arrangement. An optional 600 A vertical bus provides 1200 A effective rating.
11Publication 2100-IN012C-EN-P - April 2009 11
Chapter 1 General Information
The CENTERLINE MCC is also available with ArcShield. ArcShield includes arc resistant features which are intended to help provide enhanced protection to you during internal arcing faults (when compared to MCCs which are only designed to meet UL 845 requirements). Arcing faults can be caused, for example, by accidental touching, closing into faulted lines, or loose connections. Depending on the application, ArcShield can provide up to Type 2 accessibility per IEEE standard C37.20.7, which helps protect you when you are located at the front, sides, and rear of the enclosure in the unlikely event of an arcing fault.
A label on the MCC with ArcShield provides information in regard to the accessibility level and arc fault ratings.
For more information about accessibility levels, performance, and testing requirements, refer to IEEE standard C37.20.7, IEEE Guide for Testing Metal-Enclosed Switchgear Rated up to 38 kV for Internal Arcing Faults.
ArcShield provides a reinforced MCC structure and arc-containment latches on all doors. To help protect you during an arc-fault, arc-containment latches, when closed and latched properly, allow pressure relief and help keep the doors from unlatching or detaching from the structure.
12 Publication 2100-IN012C-EN-P - April 2009
General Information Chapter 1

Nameplate Data

Catalog Number/Serial Number
UL and cUL Certification Marking
Section Number
Each MCC section has a nameplate located on the enclosure or vertical wireway door. The nameplate includes:
catalog number/serial number.
series letter of section.
bus bar voltage and current rating.
section number.
UL and cUL certification marking.
UL registration number.
enclosure type.
Section Nameplate
Series Letter of Section
Bus Bar Voltage and Current Rating
UL Registration Number
Enclosure Type
Catalog Number / Serial Number
cUL Certification Marking
Each plug-in and frame mounted unit also has an identification label. The unit label is located on the interior of the bottom plate of plug-in units or on the interior right-hand side plate of the frame mounted units. The unit label for each plug-in or frame mounted unit includes:
catalog number/serial number.
series letter of the unit.
voltage rating.
unit location.
UL and cUL certification marking.
device type and size.
Unit Label
Series Letter of Unit
Device Type and Size
Unit Location
Voltage Rating
The catalog number or serial number and series letter are required to properly identify the equipment to sales or factory personnel.
Publication 2100-IN012C-EN-P - April 2009 13
Chapter 1 General Information

MCC Sequence Numbering

Identifies Vertical Section Sequence Numbering
CENTERLINE MCCs are designed so functionality is not affected by the section installation order, for example, vertical section-numbering sequence order.
All MCC sections carry a serial plate, which identifies vertical section sequence numbering. For example, MCC section 1 of 1, 1 of 5, and so on.
Section Nameplate
Sections are numbered to match factory-supplied MCC elevation drawings. Numbering each section helps installers and users easily identify MCCs, sections, and units. If there are questions about section numbering during field installation, inspection, or operation, the following information can provide guidance on equipment acceptability, listing, and certification.
CENTERLINE MCC sections can be installed or added as follows:
In non-sequential order
Addition of a single section (add-on section)
Addition of multiple sections (add-on lineup of sections)
Addition of single section or multiple section between MCC
sections
If sections are added to an existing lineup and not installed in sequential order, the installation should not be considered a misapplication or in conflict with Underwriter Laboratories (UL) listing and Canadian Standards Association (CSA) certification.
The paramount criteria for additions of sections to existing MCCs is matching the horizontal bus electrical and ingress protection (enclosure type) ratings for the total MCC line up. For example, the voltage, current rating, short circuit withstand, and NEMA enclosure type (IP rating) for all sections must match.
14 Publication 2100-IN012C-EN-P - April 2009
General Information Chapter 1
Non-sequential numbering may not create a functional or listing/certification issue. However, MCCs should be installed in sequential order. Installing MCCs in sequential order helps ensure proper installation and ensures that factory-supplied documentation matches the equipment.
You can rearrange MCC sections. However, if a section that uses a right-hand side sheet with integral, internal mounting flanges is located on the outside of a lineup, an additional closing kit plate is required. Refer to CENTERLINE 2100 Motor Control Center End Closing Plates Installation Instructions, publication 2100-IN069 that contain contain arc resistant features cannot use a section with integral mounting flanges on the outside of a lineup.
. MCCs

UL/CSA Marking

CENTERLINE MCCs are listed by Underwriter’s Laboratories, Inc. (UL), Standard for Safety UL 845, and certified by the Canadian Standards Associate (CSA), Standard C22-2, No. 14.
Due to standards harmonization, a MCC may also carry the cUL designation. cUL is comparable to CSA certification.
Vertical sections and units are labeled independently. It is possible to have combinations of labeled and non-labeled sections and units in the same MCC.
Vertical sections and structure options that are UL listed and CSA/cUL certified are marked accordingly. All components in a UL or CSA listed section must be UL listed and cUL/CSA certified. The UL and/or CSA/cUL designation is an integral part of the section nameplate as shown on page 14
Units and unit options that are UL listed and CSA/cUL certified are marked accordingly. All options and components in a UL and/or cUL/CSA listed unit must be UL listed or recognized and/or cUL/CSA certified. The UL designation is located on the interior of the bottom plate of plug-in units or on the interior right-hand side plate of frame mounted units.
.
UL Label Designation for Units
Publication 2100-IN012C-EN-P - April 2009 15
Chapter 1 General Information

Short-circuit Rating Label

MCC vertical sections that are UL listed and/or CSA/cUL certified will carry a short-circuit rating label. The short-circuit rating label for a vertical section is located on the inside of the vertical wireway door of standard sections or on the interior right-hand side plate of a section that contains a unit that occupies the full section and does not contain a vertical wireway.
Short Circuit Label for Sections
MCC units that are UL listed and/or CSA/cUL certified will carry a short-circuit rating label located on the bottom plate of plug-in units or on interior right-hand side plate of frame mounted units.
Short Circuit Label for Units
16 Publication 2100-IN012C-EN-P - April 2009
Series Number and Series
General Information Chapter 1
ID as Manufactured in the United States
Sections
Series Letter
Scope Description of Change Date
(1)
A
(1)
B
(1)
C
(1)
D
(1)
E
(1)
F
Original design
All Changed terminal blocks
All Elimination of external mounting channels
All Reverse fed 2192 and 2193
All Redesign gasketing
All Modified top horizontal wireway pan to accept units with handle interlock in topmost space
factor
(1)
G
(1)
G
42K 42 k bracing-incorporates new bus support & cover
65K 65 k bracing-incorporates new bus support & cover
ATTENTION
Read tables through before adding new sections or units to an existing CENTERLINE MCC.
Implemented in the U.S.
February 1971
November 1976
June 1979
April 1981
October 1982
October 1983
January 1985
July 1985
H All New hinge design January 1986 J All Changed handle, operating mechanism, and circuit breaker to Cutler-Hammer series C, 150 A,
250 A, 400 A frame
October 1986
K All Changed to new unit grounding system May 1990
L All Changed to new 600 A...1200 A circuit breaker operating mechanism February 1996
M All Changed to serpentine DeviceNet cabling system May 2001
(1)
Replacement and renewal parts are no longer supported. For more information, contact Rockwell Automation LV MCC Technical Support at 1.440.646.5800 and follow the prompts to Allen-Bradley>Low Voltage Motor Control Centers>Post Shipment Support.
2100 Units
Series Letter
A
B
C
D
E
Scope Description of Change Date Implemented
in U.S.
(1)
(1)
(1)
(1)
(1)
Original design
All sizes Changed terminal blocks
All sizes Changed handle mechanism to Cutler-Hammer MCPs
Size 5 Changed from ITE to A-B 400A disconnect
All sizes Changed from Bulletin 709 series K starters to Bulletin 500 line starters
February 1971
November 1976
June 1979
April 1981
April 1981
Publication 2100-IN012C-EN-P - April 2009 17
Chapter 1 General Information
2100 Units
Series Letter
(1)
F
(1)
G
(1)
H
(1)
J
K
L
M
N
P
Q
Scope Description of Change Date Implemented
in U.S.
All sizes Redesign of gasketing, wraparound and unit support pan for Bulletin 700 line
All sizes Redesign of gasketing, wraparound and unit support pan for Bulletin 500 line
All sizes Changed to new door, circuit breaker mechanism and control station
October 1982
October 1982
April 1984
Size 5 Changed to Bulletin 500 series L October 1984 Size 3 Changed to new PCP 100A disconnect December 1988 Size 6 Changed to Bulletin 500 series B starters October 1988
Size 1-5 CB
units and size
Changed handle, operating mechanism and circuit breaker to Cutler-Hammer series C, 150 A, 250 A, 400 A frame October 1986
1-2 disc units
21A through
54A
All sizes Changed to new unit grounding system and 600 A, 800 A, 1200 A bolted pressure
All sizes Changed to PCP 200 A and 400 A disconnect, rerated vacuum Bulletin 2112 and
0.5 SF CB units 2103L, 2113,
Changed to Bulletin 100 line contactors in 21 A, 30 A, 45 A SMC units and original design 24 A, 35 A, 54 A SMC units
switch
2113 and new pilot device offerings External auxiliary on circuit breakers
November 1989
May 1990
January 1993
April 1994
2193
All sizes and
ratings
New disconnect external auxiliary contacts and new 600 A...1200 A circuit breaker operating mechanism
May 1996
SMC units Redesign and upgrade of ratings for 24 A...500 A SMC-2 and SMC-PLUS units.
Original design of SMC Dialog Plus units
R
1200A 2193 Redesign of 1200A, 2193F and 2193M units November 1997
August 1997
800A 2193 Changed circuit breakers to MDL Frame November 1998
225A 2193F Changed circuit breakers from J Frame to F Frame October 1999
2000A 2193 Changed to flange mounted operating handle November 2000
T
U
All sizes Changed the Bulletin 800MR and Bulletin 800T-PS pilot devices to Bulletin 800Es November 2000
All 1.5 space
factor units
All except 2100-SD1
Changed unit bottom plate
Changed to new Bulletin 1497 control circuit transformer
November 2000
July 2001
2100-SD1 Changed smoke detector head and base components November 2001
18 Publication 2100-IN012C-EN-P - April 2009
2100 Units
General Information Chapter 1
Series Letter
Scope Description of Change Date Implemented
in U.S.
2162Q, 2163Q, 2164Q, 2165Q
2162R, 2163R,
2164R, 2165R
Redesign of 240-480V PowerFlex 70 and release of 600V PowerFlex 70
Original release of PowerFlex 700
April 2002
July 2002
2154H, 2155H Original release of SMC-3 November 2002
V
2154J, 2155J Original release of SMC Flex April 2004
2112, size 3, 4
and 5
Redesign to reduced space factor with Class J fuse clip
April 2004
2162T, 2163T Original release of PowerFlex 40 September 2004
2107, 2113,
size 3
Reduced space factor
April 2005
2162Q, 2163Q Reduced space factor, changed CCT with integral fuses April 2005
X
All sizes 800F pilot devices August 2005
2154J, 2155J,
Y
108 A and 135
Redesign to change units from frame mounted to plug-in
March 2006
A
(1)
Replacement and renewal parts are no longer supported. For more information contact, Rockwell Automation LV MCC Technical Support at 1.440.646.5800 and follow the prompts to Allen-Bradley>Low Voltage Motor Control Centers>Post Shipment Support.
2400 Units
Series
Scope Description of Change Date
Letter
A Original design June 1990 B 18A, 24A, 30A Changed to series B, Bulletin 194R, 30 A disconnect March 1992 C 18A, 24A, 30A Changed to three Bulletin 800E pilot devices on 0.5 space factor units July 1992
All sizes New disconnect external auxiliary contacts and new 600 A...1200 A circuit breaker
D
operating mechanism
16A-85A Original design of units with a Bulletin 100-C contactor September 1999
Implemented in U.S.
February 1996
Publication 2100-IN012C-EN-P - April 2009 19
Chapter 1 General Information
Series Lettering - Units and
When using sections in conjunction with units of different series letters, consult the table below.
Sections
MCC Modifications for Unit and Structure Compatibility
If Mounted in this Type of
(1),(2)
Section
NEMA Type 1 Series A...D
NEMA Type 1 Series E...J
(4)
NEMA Type 1 Series K or later
NEMA Type 1 w/gasket or Type 12 Series A...D
NEMA Type 1 w/gasket or Type 12
Series E...J
(7)
NEMA Type 1 w/gasket or Type 12 Series K or later
Plug-in Units No
Space Factor
1.0 or
(4)
larger
Series 2100H-UAJ1 2100H-UA1
A-E
F-L M or
later
(2)
N or
0.5
1.0 or
later
A-E
larger
F-L M or
later
(2)
0.5
N or later
1.0 or
A-L
larger
M or later
1.0 or
A-E
larger
F-L M or
later
(2)
0.5
N or later
1.0 or
A-E
larger
F-L M or
later
(2)
0.5
N or later
1.0 or
A-L
larger
M or later
Additional Parts Required
(4)
(4)
——
——
(6)
——— ——
(4)
(4)
—— ———
——— — — ——
(6)
(4)
(4)
(4)
—— ———
——
——
——— ——
(4)
(4)
—— ———
——— — — ——
(4)
—— ———
Requires Style 1 Unit Support Pan
——— — ———
——— — ———
——— — ———
——— — ———
——— — ———
——— — ———
——— — ———
——— — ———
Requires Style 3 Unit Support Pan
2100H-UJ1
Requires Style 3 Unit Support Pan w/ Bushing
2100H-USPA1 2100H-USPJ1
Requires Alternate Top Horizontal Wireway Pan
2100H-NA4A1 2100H-NA4J1 2100H-NA4A2 2100H-NA4J2
(5)
(5)
(5)
(5)
Requires Door Gasketing Kit
2100-GJ10 2100H-R1
Requires Retrofit
Kit
2100H-R2
Requires Ground
(3)
Bus Kit
2100H-GS1
———
——
(8)
(8)
——
(8)
(8)
20 Publication 2100-IN012C-EN-P - April 2009
General Information Chapter 1
(1)
When installing unit in topmost location in vertical sections, care must be taken to comply with the National Electric Code 6.7 ft (2000 mm) unit handle-to-floor height limitation. A unit operating handle extender (catalog number 2100-NE1) is available which provides 3 in. (76.2 mm) added height flexibility.
(2)
When CENTERLINE 2100, 0.5 space factor or Space Saving NEMA Starter plug-in units are ordered unassembled or ordered for existing sections, a centralized wiring diagram holder kit (catalog number 2100H-WDH) should be ordered.
(3)
Permits installation of 0.5 space factor or Space Saving NEMA Starter plug-in units in existing series E...J CENTERLINE 2100 vertical sections.
(4)
Replacement and renewal parts are no longer supported. Contact Rockwell Automation LV MCC Technical Support at 1.440.646.5800 and follow the prompts to Allen-Bradley>Low Voltage Motor Control Centers>Post Shipment Support.
(5)
Required only if series F or later, 1.0 space factor or larger CENTERLINE 2100 unit is installed in topmost location of series A...E vertical sections.
(6)
For more information regarding possible door hinge requirements, contact Rockwell Automation LV MCC Technical Support at 1.440.646.5800 and follow the prompts to Allen-Bradley>Low Voltage Motor Control Centers>Post Shipment Support.
(7)
Series E...J sections cannot accommodate 0.5 space factor or Space Saving NEMA Starter plug-in units in bottom-most unit location.
(8)
A ground strap can be used to ground units rather then installing a ground bus. Refer to the CENTERLINE 2100 Motor Control Centers (MCC) Units with Vertical Operating Handles Installation Instructions, publication 2100-IN014
.
Publication 2100-IN012C-EN-P - April 2009 21
Chapter 1 General Information

Receiving, Handling and Storage

Refer to the following sections for information on receiving, handling, and storage of MCC units.

Receiving

As standard, CENTERLINE MCCs are shipped upright in shipping blocks of one to three front-mounted sections or two to six back-to-back sections. Each shipping block of an MCC is provided with a lifting angle. The lifting angle is optional on NEMA Type 3R and Type 4 MCCs. Each vertical section in a shipping block is bolted to the shipping skid and covered with clear plastic wrap. Equipment that extends from the structures is also protected. Protection is for upright shipping and is not waterproof or watertight. If necessary, other types of packaging are available.
Refer to publication 2100-IN040 instructions. This publication is shipped with each MCC, attached to the outside of the MCC within the layer of clear plastic wrap. For additional information about the handling, installation, operation and maintenance of MCCs rated more then not 600V, consult NEMA ICS
2.3-1995.
for receiving, handling, and storage
Export Packaging
A maximum of three vertical sections standing upright can be shipped with export packaging together in one block. The MCC is bolted to a skid and wrapped in poly wrap suitable for occasional water-spray; a wooden frame and chipboard surround the sections. Export packaging is not watertight, waterproof or intended for long-term storage. Extended storage may require space heaters and other considerations. Export packing adds extra weight and dimensions to the shipping block.
Handling and Receiving MCCs
Lifting Angle
Shipping Skid
22 Publication 2100-IN012C-EN-P - April 2009
General Information Chapter 1

Handling

Lifting with a forklift, overhead lifting, sling lifting, and pipe or rod rolling are methods that can be used to handle vertical sections. See the following tables for typical weights and dimensions for standard 20 in. (508 mm) wide and 15 in. (381 mm) or 20 in. (508 mm) deep sections. For sizes not listed consult your local Rockwell Automation Sales Office.
Shipping Weights and Dimensions - Standard Packaging
Standard Packing
(1)
Front mounted 1-section block
Front mounted 2-section block
Front mounted 3-section block
Back-to-back 2-section block
Back-to-back 4-section block
Back-to-back 6-section block
(1)
Standard packing for shipments in the United States and Canada. The MCC shipping block is mounted on a skid and covered in clear plastic wrap. This packaging is not watertight or waterproof.
Weight kg (lb), approx.
Height in. (cm), approx.
Depth in. (cm), approx.
Width in. (cm), approx.
227 (500) 96 (244) 36 (91) 43 (109)
454 (1000) 96 (244) 36 (91) 43 (109)
680 (1500) 96 (244) 36 (91) 63 (160)
454 (1000) 96 (244) 42 (107) 43 (109)
816 (1800) 96 (244) 42 (107) 43 (109)
998 (2200) 96 (244) 42 (107) 63 (160)
Publication 2100-IN012C-EN-P - April 2009 23
Chapter 1 General Information
Shipping Weights and Dimensions - Export Packaging
Export Packing (below deck)
Front mounted 1-section block
Front mounted 2-section block
Front mounted 3-section block
Back-to-back 2-section block
Back-to-back 4-section block
Back-to-back 6-section block
(1)
Export packing for below deck is required for all international shipments. The MCC shipping block is mounted on a skid and covered in clear plastic wrap. This packaging is not watertight or waterproof. Additional packing materials surround the shipping block. The export packing adds extra weight and increases the dimension of the shipping block.
Weight
(1)
kg (lb), approx.
295 (600) 99 (252) 37 (94) 44 (112)
522 (1150) 99 (252) 37 (94) 44 (112)
748 (1650) 99 (252) 37 (94) 64 (163)
544 (1200) 99 (252) 43 (109) 44 (112)
907 (2000) 99 (252) 43 (109) 44 (112)
1111 (2450) 99 (252) 43 (109) 64 (163)
Height in. (cm), approx.
Depth in. (cm), approx.
Width in. (cm), approx.
ATTENTION
MCCs are top and front heavy. To avoid personal injury or structural damage, never attempt to lift or move the MCC by any means other than the methods outlined in Receiving, Handling and Storing Motor Control Centers, publication
2100-IN040
.

Storage and Operation

CENTERLINE MCCs conform to NEMA standard ICS 1-2000 for service and storage conditions. All MCCs should operate in an ambient
temperature above 0 95% non-condensing humidity. If the equipment is stored, the ambient
temperature should remain above -30
o
(149
F). In addition, MCCs have an altitude class of 2 km (1 km for MCCs that contain variable frequency drives). The altitude class of 2 km designates equipment for installation where the altitude does not exceed 2000 m (6600 ft). For installation above 2000 m (6600 ft), contact Rockwell Automation LV MCC Technical Support at
1.440.646.5800 and follow the prompts to Allen-Bradley>Low Voltage Motor Control Centers>Post Shipment Support.
o
C (32 oF) but not exceeding 40 oC (104 oF) at
o
C (-22 oF) but not exceed 65 oC
24 Publication 2100-IN012C-EN-P - April 2009
Installation Procedures
Chapter
2

Location Planning

Height Considerations

When planning the location for your CENTERLINE MCC, consider the following:
Conduits
Busways
Overall height of installation area
Alignment with other equipment
Future needs
Ambient temperature
The area must be level and the environment must be compatible with the NEMA enclosure rating of the equipment
Documentation packages shipped with assembled MCCs include an MCC elevation drawing and an MCC floor plan layout.
If the MCC is equipped with optional external mounting channels or is mounted on a pad, the height from the floor to the center of the top handles must be checked for compliance with NFPA 70 National Electrical Code (NEC) Article 404.8 and UL Standard 845. If the distance from the floor to the center of the highest handle is greater then 6.7 ft (2042.16 mm) a unit operating handle extender should be added (catalog number 2100H-NE1).
Height Planning Dimensions
Height of Handle
6.7 ft (2042.16 mm) Maximum
Cement Pad
Floor Line
25Publication 2100-IN012C-EN-P - April 2009 25
Chapter 2 Installation Procedures

Securing an MCC

Anchor bolts [1/2 in. (13 mm)] may be pre-located and embedded in the foundation prior to installation. Two bolts per vertical section fasten the MCC through its internal mounting angle to the foundation [corner sections require three bolts and 40 in. (1016 mm) wide sections require four bolts]. See the following illustrations and tables for general dimensions. Dimensions matching your equipment can be found on the elevation drawings shipped with your MCC.
Mounting Dimensions for 15 in. and 20 in. Sections
26 Publication 2100-IN012C-EN-P - April 2009
Installation Procedures Chapter 2
(2) Mounting Slots
0.56 in. x 1.13 in. in Slots (14 mm x 29 mm) Slots
A
Standard Ground Bus
C
Rear
0.25 in. (6.35 mm)
B
7.38 in. (187 mm)
For seismic bolt-down applications: first section of the MCC lineup.
D
Front
E
For seismic bolt-down applications: last section of the MCC lineup, extra bolt-down locations (2 bolts).
D
E
The optional external mounting channels add 1.5 in. (38.1 mm) to the height.
15 in. Deep 20 in. Deep
Dimensions approx.
20 in.
Wide
in. (mm)
25 in. Wide
in. (mm)
30 in. Wide
in. (mm)
35 in. Wide
in. (mm)
20 in. Wide
in. (mm)
25 in. Wide
in. (mm)
30 in. Wide
in. (mm)
35 in. Wide
in. (mm) A 20.00 (508) 25.00 (635) 30.00 (762) 35.00 (889) 20.00 (508) 25.00 (635) 30.00 (762) 35.00 (889) B 15.00 (381) 15.00 (381) 15.00 (381) 15.00 (381) 20.00 (508) 20.00 (508) 20.00 (508) 20.00 (508) C 11.56 (294) 11.56 (294) 11.56 (294) 11.56 (294) 16.56 (421) 16.56 (421) 16.56 (421) 16.56 (421) D 10.00 (254) 12.50 (318) 15.00 (381) 17.50 (445) 10.00 (254) 12.50 (318) 15.00 (381) 17.50 (445)
(1)
E
(1)
Applies to first and last sections that require seismic ratings.
Publication 2100-IN012C-EN-P - April 2009 27
9.13 (232) 9.13 (232) 9.13 (232) 9.13 (232) 14.13 (359) 14.13 (359) 14.13 (359) 14.13 (359)
Chapter 2 Installation Procedures
Mounting Dimensions for 30 in. and 40 in. Deep Back-to-Back Section
Dimensions approx.
7.38 in. (187 mm)
0.25 in. (6 mm)
B
0.25 in. (6 mm)
7.38 in. (187 mm)
20 in. Wide
in. (mm)
1.69 in. (43 mm)
C
3.19 in. (81 mm)
C
Front
Rear Rear
Front
A
D
D
20 in. Deep 40 in. Deep
25 in. Wide
in. (mm)
30 in. Wide
in. (mm)
35 in. Wide
in. (mm)
20 in. Wide
in. (mm)
25 in. Wide
in. (mm)
(4) Mounting Slots
0.56 in. x 1.13 in. in Slots (14 mm x 29 mm) Slots
Standard Ground Bus
30 in. Wide
35 in. Wide
in. (mm)
in. (mm) A 20.00 (508) 25.00 (635) 30.00 (762) 35.00 (889) 20.00 (508) 25.00 (635) 30.00 (762) 35.00 (889) B 30.00 (762) 30.00 (762) 30.00 (762) 30.00 (762) 40.00 (1016) 40.00 (1016) 40.00 (1016) 40.00 (1016) C 11.56 (294) 11.56 (294) 11.56 (294) 11.56 (294) 16.56 (421) 16.56 (421) 16.56 (421) 16.56 (421) D 10.00 (254) 12.50 (318) 15.00 (381) 17.50 (445) 10.00 (254) 12.50 (318) 15.00 (381) 17.50 (445)
28 Publication 2100-IN012C-EN-P - April 2009
Installation Procedures Chapter 2
Mounting Dimensions for 25 in. Wide Section with 9 in. (228.6 mm) Wireway [90 in. (2286 mm) high]
The optional external mounting channels add 1.5 in. (38.1 mm) to the height.
Publication 2100-IN012C-EN-P - April 2009 29
Chapter 2 Installation Procedures
Mounting Dimensions for 10 in. Wide Section with 10 in. (254 mm) Incoming Line Section
A (L1)
A (L2)
A (L3)
7.5 in. (191 mm)
1.25 in. (32 mm) 10 in. (254 mm)
Power Wires
Section Depth
Dimension,
approx.
15 in. (381 mm) Deep
20 in. (508 mm) Deep
in. (mm A 12.75 (324) 17.75 (451) B 14.75 (375) 19.75 (502)
in. (mm
1.12 in. (28 mm)
A
B
30 Publication 2100-IN012C-EN-P - April 2009
Loading...
+ 78 hidden pages