Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WA RN I NG : Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
2Rockwell Automation Publication 875-UM001A-EN-P - March 2021
4Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Preface
This manual is a reference guide for Bulletin 875F and 875L capacitive
proximity sensors with IO-Link. It describes how to install, configure, and use
the device.
Who Should Use This
Manual?
Ter mi nol ogy
This manual contains important information regarding installation. Qualified
personnel familiar with proximity capacitive sensors must be read and
understand this manual completely. We recommend that you read the manual
carefully before installation of the sensor. Save the manual for future use.
Te rmD ef in it i on
I/OInput/output
PDProcess data
PLCProgrammable logic controller
SIOStandard input/output
SPSetpoints
IODDI/O device description
IECInternational Electrotechnical Commission
N.O.Normally open contact
N.C.Normally closed contact
NPNPull load to ground
PNPPull load to V+
Push-PullPull load to ground or V+
QoRQuality of run
QoTQuality of teach
UARTUniversal asynchronous receiver-transmitter
SOSwitching output
SSCSwitching signal channel
Download Firmware, AOP,
EDS, and Other Files
Additional Resources
Download firmware, associated files (such as AOP, EDS, and DTM), and access
product release notes from the Product Compatibility and Download Center at
rok.auto/pcdc
.
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
EtherNet/IP Network Devices User Manual, ENET-UM006
Ethernet Reference Manual, ENET-RM002
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications
.Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at rok.auto/literature
Rockwell Automation Publication 875-UM001A-EN-P - March 20215
Describes how to configure and use EtherNet/IP™ devices to communicate on the EtherNet/
IP network.
Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
.
Notes:
6Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Product Overview
Status Indicator
Sensitivity
Max
Min
Sensitivity
Adjustment AC Models
Programmable N.O. or N.C.
)by selector switch back view)
(2-wire device back view)
Max
Min
Sensitivity
Non-IO-Link Sensors875L AC Cylindrical Cap
•Capacitive proximity switches with either sensing distance:
- M18 housing: 8 mm (0.31 in.) flush mounted in metal or sensing
distance 12 mm (0.47 in.) non-flush mounted. Gray M18 polyester
housing with 2 m (6.6 ft) PVC cable or M12 plug.
- M30 housing: 16 mm (0.63 in.) flush mounted or 25 mm (0.98 in.)
sensing distance non-flush mounted. Gray M30 polyester housing
with 2 m (6.6 ft) PVC cable or plug.
•2-wire AC output with make (N.O.) or break (N.C.) switching. Ideal for
use in level and plastic machinery applications.
•SCR output
•Make or break switching function
•Status indicators
•High noise immunity
•Flush and non-flush types
•Plug and cable versions
Chapter 1
Housing
Figure 1 - M18 Housing
Figure 2 - M30 Housing
Rockwell Automation Publication 875-UM001A-EN-P - March 20217
Chapter 1 Product Overview
Catalog Number Explanation
875L-F8N18A2
ab c d ef
ab c
Housing StyleShieldingSensing Distance
CodeDescriptionCodeDescriptionCodeDescription
Cylindrical housing
L
with threaded barrel
de f
Output FunctionBarrel DiameterOutput Type
CodeDescriptionCodeDescriptionCodeDescription
NNormally open (N.O.)1818 mm (0.71 in.)A22 m (6.6 ft) PVC cable
CNormally closed (N.C.)3030 mm (1.18 in.)R3AC micro connector
BN.O./N.C.
FShielded 88 mm (0.31 in.)
GUnshielded 1212 mm (0.47 in.)
1616 mm (0.63 in.)
2525 mm (0.98 in.)
875F DC Flat Cap
•Detection of water-based fluids inside a container or tube without direct
contact with the fluids.
•The sensor detects the liquids reliably while compensating for residue
film, moisture, or foam build-up from liquids such as water, milk, bodily
fluids (blood), acid, or alkaline solutions with conductivity as high as
50 mS/cm inside or outside the container wall.
•Flexible and fast universal mounting bracket.
•The sensing principle detects only the level of the liquids while ignoring
foam, film, or build-up that would cause standard capacitive sensors to
detect faultily.
Features
•Compact housing
•Supply voltage: 10…30V DC
•Output: 100 mA, NPN or PNP preset
•Make or break switching function
•Status indication for output and power ON
•Protection: reverse polarity, short circuit, and transients
•Cable and pigtail M8 plug versions
•Excellent EMC performance
•IP65, IP66, IP67, IP68, and IP69K for hose-down applications
•c-UL-us
•Ecolab
8Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 1 Product Overview
D
BA
C
E
Housing
Item Description
AYellow status indicator (output)
BGreen status indicator (power ON)
CTwo M3 mounting holes
DRecessed area for cable strips, 5 mm wide (max)
ESensing surface
Table 1 - Status Indicators
Green Status Indicator Yellow Status IndicatorOutput
— Flashes three times 1 HzSuccessful full calibration
—Flashes three times 1 HzSuccessful empty calibration
—Flashes ten times 4 HzUnsuccessful calibration (canceled or error) (>12 s)
Catalog Number Explanation
875F-M10NP34A2
ab c d ef
ab c
Housing StyleMountingSensing Distance
CodeDescriptionCodeDescriptionCodeDescription
FRectangular housingMFlush 1010 mm (0.39 in.)
de f
Output FunctionHousing LengthOutput Type
CodeDescriptionCodeDescriptionCodeDescription
NPN.O. PNP3434 mm (1.34 in.)A22 m (6.6 ft) PVC cable
NNN.O. NPN
CPN.C. PNP
CNN.C. NPN
FP02
0.2 m (0.66 ft) PVC
cable 4-pin DC pico
Rockwell Automation Publication 875-UM001A-EN-P - March 20219
Chapter 1 Product Overview
D
D
A
B
C
M18 Housing
M30 Housing
A
B
C
IO-Link Sensors875L DC Cylindrical Cap
•The sensor can be operated in IO-Link mode once it is connected to an
IO-Link master or in standard I/O mode.
•Adjustable parameters via IO-Link interface: Sensing distance and
hysteresis.
- Sensing modes: single-point, two-point, or window mode.
- Timer functions like: on-delay, off-delay, one shot leading edge, or
trailing edge.
- Logic functions such as: AND, OR, XOR, and SR-FF.
-External input.
- Logging functions: Maximum temperatures, minimum temperatures,
operating hours, operating cycles, power cycles, minutes above
maximum temperature, minutes below minimum temperature, and
so on.
Features
•A complete family. Availability in M18 in a robust PBT housing with an
operation of 2…10 mm (0.08…0.39 in.) flush or 3…15 mm (0.12…0.59 in.)
non-flush.
•The output can be operated either as a switching output or in IO-Link
mode.
•Fully configurable via output IO-Link v 1.1. Electrical outputs can be
configured as PNP/NPN/Push-pull/External input, normally open or
normally closed.
•Timer functions can be set, such as on-delay, off-delay, and one shots.
•Logging functions: temperatures, detection counter, power cycles, and
operating hours.
•Detection modes: single-point, two-point, and window mode.
•Analog output: In IO-Link mode, the sensor generates 16-bit analog
process data output that represents the dielectric value that the sensor
measures.
Housing
ItemDescription
ASensitivity adjustment
10Rockwell Automation Publication 875-UM001A-EN-P - March 2021
BYellow status indicator
CGreen status indicator
DSensing face
Catalog Number Explanation
875L-M8NP18A2
ab c d ef
ab c
Housing StyleMountingSensing Distance
CodeDescriptionCodeDescriptionCodeDescription
Cylindrical housing
L
with threaded barrel
de f
Output FunctionBarrel DiameterOutput Type
CodeDescriptionCodeDescriptionCodeDescription
NPN.O. PNP1818 mm (0.71 in.)A22 m (6.6 ft) PVC cable
NNN.O. NPN3030 mm (1.18 in.)D4DC micro connector
CPN.C. PNP
CNN.C. NPN
Chapter 1 Product Overview
MFlush 88 mm (0.31 in.)
NNon-flush 1212 mm (0.47 in.)
1616 mm (0.63 in.)
2525 mm (0.98 in.)
Rockwell Automation Publication 875-UM001A-EN-P - March 202111
Chapter 1 Product Overview
Notes:
12Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 2
Configure with IO-Link
Bulletin 875 sensors offer five different tabs (shown in Table 2) to describe the
device functionality and operations.
Table 2 - Tab Descriptions
TabDescription
Common
(page 14
Identification
(page 15
Observation
(page 15)
Parameter
(page 16
Diagnosis
(page 17
Provides general product information about sensor specifications and IO-Link IODD information.
)
Provides sensor catalog number, series letter, product firmware, and hardware revisions.
)
Displays real-time measurement information, including distance measurement value, switching
outputs, and operation conditions.
Allows you to configure sensors by modifying parameter settings.
)
Provides information of operation status and sensor health diagnosis, and enables you to restore
)
factory default settings and physically locate the sensor for troubleshooting.
Rockwell Automation Publication 875-UM001A-EN-P - March 202113
Chapter 2 Configure with IO-Link
Common Tab
The Common tab contains the following device information:
ParameterDescription
VendorProvides the vendor name of the product.
Vendor TextField that is used to describe additional product information.
Vendor ID
URLDisplays the vendor URL.
DeviceProvides the specific catalog number of the product.
DescriptionDescribes the sensor features and range performance.
Device IDDisplays the unique device ID as defined in the IO-Link specifications.
IO-Link RevisionDisplays the current IO-Link version that the device supports.
Hardware RevisionDisplays the latest sensor hardware information.
Firmware RevisionDisplays the latest sensor Firmware information.
Bitrate
SIO Mode
IODDDisplays the complete file name of the IODD that is assigned to the product.
Document VersionDisplays the version control for the IODD.
Date of CreationDisplays when the IODD file was creation.
Describes the vendor ID of the manufacturer of the product as designated in the
IO-Link Consortium.
Displays the supported bitrate for communications as defined in the IO-Link 1.1
standard.
Describes whether the sensor is also designed to operate without and IO-Link
connection.
14Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Identification Tab
Chapter 2 Configure with IO-Link
The Identification tab contains the following device information:
ParameterDescription
Device Information
Vendor NameThe vendor name of the product.
Product NameThe product catalog number information.
Product IDProduct catalog number information with series letter.
Product TextProduct description.
Serial NumberSerial number of the device as unique numeric value.
User-Specific Information
Application-Specific
Tag
Revision Information
Hardware VersionHardware version of the 875 sensor that is provided as alphanumeric value
Firmware VersionFirmware revision of the875 sensor that is provided as numeric value.
Device-specific name that is assigned to device for device identification. This tag is a
unique identity of each device. You can customize this read/write field.
Observation TabThe Observation tab displays real-time device status. For more information,
see Appendix B on page 37
Rockwell Automation Publication 875-UM001A-EN-P - March 202115
.
Chapter 2 Configure with IO-Link
Parameter TabThe Parameter tab allows you to configure the sensor. For more information,
see Appendix B on page 37
.
16Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 2 Configure with IO-Link
Diagnosis TabThe Diagnosis tab provides information on operation status and sensor health
diagnosis. For more information, see Appendix B on page 37
.
ParameterDescription
Operating hours
Number of power cycles
Event configurationsSee Event Configuration on page 30
Maximum temperature -
all-time high [°C]
Minimum temperature -
all-time low [°C]
Maximum temperature
since last power-up [°C]
Minimum temperature
since last power-up [°C]
Current temperature [°C] The current temperature of the sensor.
Detection counter
[cycles]
Minutes above maximum
temperature [min]
Minutes below minimum
temperature [min]
The sensor has a built-in counter that logs every full hour that the sensor has been operational, the maximum hours that can be recorded is
2,147,483,647 hours, this value can be read from an IO-Link master.
The sensor has a built-in counter that logs every time that the sensor has been powered-up, the value is saved every hour, the maximum
numbers of power cycles that can be recorded is 2,147,483,647 cycles, this value can be read from an IO-Link master.
.
The sensor has a built-in function that logs the highest temperature that the sensor has been exposed to during the full operational lifetime.
This parameter is updated once per hour and can be read from an IO-Link master.
The sensor has a built-in function that logs the lowest temperature that the sensor has been exposed to during the full operational lifetime.
This parameter is updated once per hour and can be read from an IO-Link master.
The maximum registered temperature has been since startup. This value is not saved in the sensor.
The minimum registered temperature has been since startup. This value is not saved in the sensor.
The sensor logs every time the SSC1 change state. This parameter is updated once per hour and can be read from an IO-Link master.
The sensor logs how many minutes the sensor has been operational above the maximum temperature for the sensor, the maximum number of
minutes to be recorded is 2,147,483,647. This parameter is updated once per hour and can be read from an IO-Link master.
The sensor logs how many minutes the sensor has been operational below the minimum temperature for the sensor, the maximum number of
minutes to be recorded is 2,147,483,647. This parameter is updated once per hour and can be read from an IO-Link master.
Rockwell Automation Publication 875-UM001A-EN-P - March 202117
Chapter 2 Configure with IO-Link
Notes:
18Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 3
Switch Output Configuration
The sensor measures five different physical values. These values can be
independently adjusted and used as source for the Switching Output 1 or 2, in
addition to those an external input can be selected for SO2. After selecting one
of these sources, it is possible to configure the output of the sensor with an
IO-Link master following the steps that are shown in the Switching Output
configuration (Figure 3
Once the sensor has been disconnected from the master, it switches to the SIO
mode and keeps the last configuration setting.
Figure 3 - Switch Output Configuration
123456
).
Sensor frontSelector
S.P., Two P.
Window,
1. SSC1
Adj. Hyst.
S.P., Two P.
Window,
2. SSC2
Adj. Hyst.
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
One of
1 to 6
Selector
B
One of
1 to 6
ItemDescription
1Sensor front (see page 20
2Input selector (see page 21)
3Logic function block (see page 21
4Timer (see page 23
)
5Output inverter (see page 24)
6Output stage mode (see page 24
A
B
A
B
AND, OR,
XOR, S-R
AND, OR,
XOR, S-R
)
Logic
A - B
divider
Logic
A - B
divider
)
)
Time
delay
ON, OFF
One-shot
Time
delay
ON, OFF
One-shot
Output
inverter
N.O., N.C.NPN, PNP,
Output
inverter
N.O., N.C.NPN, PNP,
Sensor
output
Push-Pull
Sensor
output
Push-Pull
EXT-Input
Out 1
Out 2
EXTInput
Rockwell Automation Publication 875-UM001A-EN-P - March 202119
Chapter 3 Switch Output Configuration
Sensor
Sensing distance
ONOFF
SP1
Hysteresis
Sensor FrontWhen an object (solid or liquid) approaches the face of the sensor, the
capacitance of the detecting circuit is influenced and the sensor output
changes its status.
SSC (Switching Signal Channel)
For presence (or absence of presence) detection of an object in front of the face
of the sensor, the following settings are available: SSC1 or SSC2.
The setpoints can be set from 0…10,000 units that represent the change of
capacitance of the detecting circuit. The higher value, the closer the target
appears to the sensing face of the sensor, also a higher dielectric value of the
target increases the value. For example, a metal target has a higher dielectric
value than a plastic target.
Switchpoint Mode
The switchpoint mode setting can be used to create more advanced output
behavior. The following switchpoint modes can be selected for the switching
behavior of SSC1 and SSC2.
ModeDescription
Disabled
Single-point mode
Two-point mode
SSC1 or SSC2 can individually be disabled, which also disables the output if it is
selected in the input selector (the logic value is always 0).
The switching information changes, when the measurement value passes the
threshold that is defined in setpoint SP1, with rising or falling measurement values,
considering the hysteresis.
The switching information changes when the measurement value passes the threshold
that is defined in setpoint SP1. This change occurs only with rising measurement
values. The switching information also changes when the measurement value passes
the threshold that is defined in setpoint SP2. This change occurs only with falling
measurement vales. Hysteresis is not considered in this case.
Hysteresis
Sensor
ONOFF
SP2
SP1
Sensing distance
The switching information changes, when the measurement value passes the
thresholds that are defined in setpoint SP1 and setpoint SP2, with rising or falling
measurement values, considering the hysteresis.
Hyst
Hyst
Window mode
Sensor
OFFOFF
SP2
20Rockwell Automation Publication 875-UM001A-EN-P - March 2021
ON
window
Sensing distance
SP1
Chapter 3 Switch Output Configuration
Hysteresis Settings
In SSC1 and SSC2 - single point mode and in windows mode the hysteresis can
be set 1…100% of the actual switching value.
The safe limit between when the sensing output is switching and the value at
where the sensor can detect safely even with a slight buildup of dust can be set.
Temperature Alarm (TA)
The sensor constantly monitors the internal temperature in the front part of
the sensor. With the temperature alarm setting, it is possible to get an alarm
from the sensor if temperature thresholds are exceeded.
The temperature alarm has two separate values, one for setting the maximum
temperature and one for setting the minimum temperature.
It is possible to read the temperature of the sensor via the acyclic IO-Link
parameter data.
External Input
The output 2 (SO2) can be configured as an external input that allows external
signals to be feed into the sensor from a second sensor, a PLC, or directly from
machine output.
Input SelectorThis function block allows you to select any of the signals from the sensor front
to the Channel A or B.
Channel A and B: Can select between SSC1, SSC2, margin alarm 1, margin
alarm 2, temperature alarm, and external input.
Logic Function BlockIn the logic function block, the selected signals from the input selector can be
added a logic function directly without using a PLC - which makes decentral
decisions possible.
The logic functions available are AND, OR, XOR, and gated SR-FF.
Rockwell Automation Publication 875-UM001A-EN-P - March 202121
Chapter 3 Switch Output Configuration
A
B
Q
&
2-input AND Gate
A
B
Q
≥1
2-input OR Gate
A
B
Q
=1
2-input XOR Gate
A
B
Q
&
≥1
SR
Flip-Flop
AND Function
Boolean Expression Q = A.BRead as A AND B gives Q
OR Function
Boolean Expression Q = A + BRead as A OR B gives Q
Symbol
Symbol
Truth Table
ABQ
000
010
100
111
Truth Table
ABQ
000
011
101
111
XOR Function
Symbol
Boolean Expression Q = A + BA OR B but NOT BOTH gives Q
ABQ
000
011
101
110
Truth Table
Gated SR-FF Function
The function is designed to function as filling or emptying function with only
two interconnected sensors.
Symbol
ABQ
000
01
10
Truth Table
(1)
X
(1)
X
111
(1) X = No changes to the output.
22Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 3 Switch Output Configuration
N.O.
ToffToffToffToff
Presence of target
N.O.
To nTo nTo n
Toff
Toff
Presence of target
Presence of target
TimerThis parameter can be set individually for Out1 and Out2.
The Timer allows you to introduce different timer functions by editing the
three timer parameters:
•Timer mode
•Timer scale
•Timer value
Timer Mode
Selects which type of timer function is introduced on the Switching Output.
Any one of the following is possible:
ModeDescription
Disabled
This option disables the timer function no matter how timer scale and timer delay are
configured.
The activation of the switching output is generated after the actual sensor actuation.
Presence of target
Turn On delay (T-on)
Turn Off delay (T-off)
Turn ON and Turn Off
and T
delay (T
on
off
N.O.
To nTo nTo n
The deactivation of the switching output is delayed compared to the time of removal
of the target in the front of the sensor.
When selected both the T
and the T
on
delays are applied to the generation of the
off
switching output.
)
Each time a target is detected in front of the sensor the switching output generates a
pulse of constant length on the leading edge of the detection.
Rockwell Automation Publication 875-UM001A-EN-P - March 202123
One shot leading edge
Chapter 3 Switch Output Configuration
Presence of target
ModeDescription
Similar in function to the one shot leading edge mode, but in this mode the switching
output is changed on the trailing edge of the activation.
One shot trailing edge
Timer scale
Timer value
Parameter defines if the delay specified in the Timer delay should be in milliseconds,
seconds, or minutes.
Parameter defines the actual duration of the delay. The delay can be set to any integer
value from 1… 32,767.
Output InverterThis function allows you to invert the operation of the switching output
between normally open and normally closed.
IMPORTANT
The recommended function is found in the parameters under 64 (0x40)
sub index 8 (0x08) for SO1 and 65 (0x40) sub index 8 (0x08) for SO2 does
not have any negative influence on the Logic functions or the timer
functions of the sensor as it is added after those functions.
ATTENTION: We do not recommend using the Switching logic function that is
found under 61 (0x3D) sub index 1 (0x01) for SSC1 and 63 (0x3D) sub index 1
(0x01) for SSC2 as they have a negative influence on the logic or timer
functions.
For example, this function turns an ON-delay into an OFF-delay as it is added
for the SSC1 and SSC2 and not only for the SO1 and SO2.
Output Stage ModeIn this function block, you can select how the switching outputs operate:
•SO1: Disabled, NPN, PNP, or Push-Pull configuration.
24Rockwell Automation Publication 875-UM001A-EN-P - March 2021
External Teach
(Teach-by-wire)
Chapter 4
Teach Procedure
IMPORTANT
The Teach-by-wire must be first configured with an IO-Link master:
1. Select 2=Teach by wire in the Selection of local/remote adjustment
parameters 68 (0x44).
2. Select 1=Single Point Mode is already selected in SSC1 Configuration
61(0x3D), “Mode 1” 2(0x02) (this value should already be set as default).
3. Select 6=Teach-In (Active High) in Chanel 2 (SO2) 65 (0x41) sub index 1
(0x01).
Teach-by-wire Procedure
This function works in single point mode and only for SP1 in SSC1.
1. Place the target in front of the sensor and connect the teach-by-wire
input (pin 2 white wire) to V+ (pin 1 Brown wire). The yellow status
indicator flashes at a 1 Hz rate (ON 100 ms and OFF 900 ms).
2. Within 3…6 seconds the wire must be disconnected, and the yellow status
indicator flashes at a 1 Hz rate (ON 900 ms and OFF 100 ms).
3. After a successful teach, the yellow status indicator flashes at a 2 Hz rate
(ON 250 ms and OFF 250 ms).
IMPORTANTIf the Teach procedure is to be canceled, do not remove the wire after
3…6 second. Keep the connection for 12 sec until the yellow status
indicator flashes at a 10 Hz rate (On 50 ms and off 50 ms).
Teach from IO-Link MasterTo enable teach from IO-Link master, first disable the trimmer input:
1. Select 0=Disabled in the Selection of local/remote adjustment
parameters 68 (0x44).
2. The individual team commands can be written to index 2.
Single-point Mode Procedure
Select the Switching channel to be taught:
1. Select: 1=SSC1 or 2=SSC2 in the Teach-in Select 58(0x3A) or 255 = All SSC.
2. Change the Hysteresis if requested for SSC1 or SSC2.
• SSC1 configuration 61(0x3D) Hysteresis 3(0x03).
• SSC2 configuration 62(0x3D) Hysteresis 3(0x03).
Rockwell Automation Publication 875-UM001A-EN-P - March 202125
Chapter 4 Teach Procedure
Command Sequence
1) “SP1 Single value Teach”
2) “Teach Apply”
Sensing distance
Sensor
SSC
Command Sequence
1) “SP1 Two value Teach TP1”
2) “SP1 Two value Teach TP2”
3) “Teach Apply”
Sensing distance
Sensor
SSC
Command Sequence
1) “SP1 Two value Teach TP1”
2) “SP1 Two value Teach TP2”
3) “Teach Apply”
4) “SP2 Two value Teach TP1”
5) “SP2 Two value Teach TP2”
6) “Teach Apply”
Sensing distance
Sensor
SSC
Sensing distance
SSC
Command Sequence
1) “SP1 Dynamic Teach Start”
2) “SP2 Dynamic Teach Stop”
3) “Teach Apply”
Sensor
IMPORTANTIt is not recommended to change the hysteresis below the values stated
in the SSC parameter list (see page 38
).
Tea ch Command
Sequence
Single-value
Dynamic
Two-value
Description
1. #65 SP1 Single value teach
2. #64 Teach apply (optional command)
1. #71 SP1 dynamic teach start
2. #72 SP1 dynamic teach stop
3. #64 Teach apply (optional command)
1. #67 SP1 two value teach TP1
2. #68 SP1 two value teach TP2
3. #64 Teach apply (optional command)
Two-point Mode Procedure
Tea ch Command
Sequence
Two-value
Dynamic teach
Description
1. #67 SP1 two value teach TP1
2. #68 SP1 two value teach TP2
3. #64 Teach apply (optional command)
4. #69 SP2 two value teach TP1
5. #70 SP2 two value teach TP2
6. #64 Teach apply (optional command)
1. #71 SP1 dynamic teach start
2. #72 SP1 dynamic teach stop
3. #73 SP2 dynamic teach start
4. #74 SP2 dynamic teach stop
5. #64 Teach apply (optional command)
26Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Windows Mode Procedure
Command Sequence
1) “SP1 Single value Teach”
3) “Teach Apply”
2) “SP2 Single value Teach”
3) “Teach Apply”
Sensing distance
Sensor
SSC
Command Sequence
1) “SP1 Dynamic Teach Start”
2) “SP2 Dynamic Teach Stop”
3) “Teach Apply”
Sensing distance
Sensor
SSC
Chapter 4 Teach Procedure
Tea ch Command
Sequence
Single-value
Dynamic
Description
1. #65 SP1 Single value teach
2. #66 SP2 Single value teach
3. #64 Teach apply (optional command)
1. #71 SP1 dynamic teach start
2. #72 SP1 dynamic teach stop
3. #73 SP2 dynamic teach start
4. #74 SP2 dynamic teach stop
5. #64 Teach apply (optional command)
Rockwell Automation Publication 875-UM001A-EN-P - March 202127
Chapter 4 Teach Procedure
Notes:
28Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 5
Sensor-specific Adjustable Parameters
Besides the parameters that are directly related to output configuration, the
sensor also has various internal parameters useful for setup and diagnostics.
Local or Remote
Adjustment Selection
It is possible to select how to set of the sensing distance by either select the
Trimmer, Teach-by-wire using the external input of the sensor, or to disable
the potentiometer to make the sensor tamper-proof.
Process Data and VariablesWhen the sensor is operated in IO-Link mode, you have access to the cyclic
Process Data Variable.
By default the process data shows the following parameters as active: 16-bit
Analog value, Switching Output1 (SO1), and Switching Output 2 (SO2).
The following parameters are set as Inactive: SSC1, SSC2, DA1, DA2, TA, SC.
However, by changing the Process Data Configuration parameter, you can also
decide to enable status of the inactive parameters. This way several states can
be observed in the sensor at the same time.
Byte 0
Byte 1
Byte 2
Byte 3
3130292827262524
MSB
2322212019181716
LSB
15141312111098
SCTADA2DA1SSC2SSC1
76543210
SO2SO1
Sensor Application SettingThe sensor has three presets depending on the application:
PresetDescription
Full scale range
Liquid level
Plastic pellets
Rockwell Automation Publication 875-UM001A-EN-P - March 202129
The setpoints of the sensor can be adjusted at full scale and the sensing speed are set to
maximum.
This preset is used for slow-moving objects with a high dielectric value such as detection of
water-based liquids. When this function is selected, the teach and potentiometer settings are
optimized to high-range scaling. In this mode, the Filter Scaler is set to 100.
This preset is used for slow-moving objects with a low dielectric value such as detection of
plastic pellets. When this function is selected, the teach and potentiometer settings are
optimized to low-range scaling. In this mode, the Filter Scaler is set to 100.
Chapter 5 Sensor-specific Adjustable Parameters
Temperature Alarm
Threshold
The temperature where the temperature alarm activates can be changed for
the maximum and minimum temperature. This setting means that the sensor
gives an alarm in the maximum or minimum temperature is exceeded. The
temperatures can be set between -50…+150 °C (-58…+302 °F). The default
factory settings are:
•Low threshold = -30 °C (-22 °F)
•High threshold = +120 °C (+248 °F)
Safe LimitsThe sensor has a built-in safety margin that helps adjust the sensing up to the
setpoints with an additional safe margin. The factory settings are set to two
times the standard hysteresis of the sensor.
Event ConfigurationTemperature events that are transmitted over the IO-Link interface are turned
off by default in the sensor. If you want to get information about critical
temperatures detected in the sensor application, this parameter allows you to
enable or disable the following events:
EventDescription
Temperature fault event The sensor detects temperature outside specified operating range.
Temperature over-runThe sensor detects temperatures higher than set in Temperature Alarm threshold.
Temperature under-runThe sensor detects temperatures lower than set in Temperature Alarm threshold.
Short-circuitThe sensor detects if the sensor output is short-circuit.
MaintenanceThe sensor detects if maintenance is needed like the sensor need cleaning.
Quality of Run (QoR)The quality of run value informs about the actual sensing performance
compared to the setpoints of the sensor (the higher the value, the better quality
of detection). The value for QoR can vary to any value from 0…255%. The QoR
value is updated for every detection cycle.
Table 3 - QoR Examples
QoR Values Definitions
>150%Excellent sensing conditions, the sensor is not expected to require any maintenance issues.
Good sensing conditions, the sensor performs as well as when the setpoints were taught or setup
100%
50%
0%Poor to not reliable working sensing conditions is expected.
manually with a safety margin of two times the standard hysteresis.
• Long-term reliability is expected for all environmental conditions.
• Maintenance is not expected to be required.
Average sensing conditions.
• Short-term reliability and maintenance are expected due to environmental conditions.
• Reliable detection can be expected with restricted environmental influence.
30Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Chapter 5 Sensor-specific Adjustable Parameters
Quality of Teach (QoT)The quality if teach value informs about how well the actually teach procedure
was done, meaning the margin between the actual setpoints and the
environmental influence of the sensor. The value for QoT can vary to any value
from 0…255%. The QoT value is updated after every teach procedure.
Table 4 - QoT Examples
QoT Value Definitions
> 150%Excellent teach conditions, the sensor is not expected to require any maintenance issues
Good teach conditions, the sensor has been taught with a safety mar- gin of two times the
100%
50%
0%
standard hysteresis.
• Long-term reliability is expected for all environmental conditions.
• Maintenance is not expected to be required.
Average teach conditions.
• Short-term reliability and maintenance are expected due to environmental conditions.
• Reliable detection can be expected with restricted environmental influence.
Poor teach result.
• Not reliable working sensing conditions are expected (for example, too small of a measuring
margin between the target and the surroundings).
Filter ScalerThis function can increase the immunity towards unstable targets and
electromagnetic disturbances. The value can be set from 1…255, the default
factory settings is 1. A filter setting of 1 gives the maximum sensing frequency
and a setting of 255 gives the minimum sensing frequency.
Status IndicationThis parameter allows you to disable status indication in the sensor if you do
not want the status indicators to illuminate in your application.
Rockwell Automation Publication 875-UM001A-EN-P - March 202131
Chapter 5 Sensor-specific Adjustable Parameters
Notes:
32Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Specifications
Non-IO-Link Sensors875L AC Cylindrical Cap
Table 5 - 875L AC Cylindrical Cap Specifications
AttributeValue
Rated operating dist. (Sn)
Sensitivity270° turn potentiometer (adjustable)
Effective operation distance (Sr)0.9 x Sn ≤ Sr ≤ 1.1 x Sn
Usable operation distance (Su) 0.8 x Sr ≤ Su ≤ 1.2 x Sr
Repeat accuracy (R)≤5%
Hysteresis (H)4…20% of sensing distance
Rated operational volt (UB)20…250V AC (ripple included)
Ripple≤10%
Rated operating current (Ie)
Load current, min10 mA
Voltage drop (Ud)≤10V AC (at loads ≥20 mA)
ProtectionTransients
Power ON delay≤100 ms
Frequency of operating cycles (f)10 Hz
Indication for output ONYellow status indicator
Degree of protectionIP67 (NEMA 1, 3, 4, 6, 13)
Tem pera tur e
•875L-F8x18: 3…8 mm (factory set at 8 mm)
•875L-G12x18: 3…12 mm (factory set at 12 mm)
•875L-F16x30: 2…16 mm (factory set at 16 mm)
•875L-G25x30: 4…25 mm (factory set at 25 mm)
• Continuous: ≤500 mA
• Short-time: <2.5 A (20 ms, max)
• Operating: -25…+80 °C (-13…+176 °F)
• Storage: -40…+85 °C (-40…+185 °F)
Appendix A
Rockwell Automation Publication 875-UM001A-EN-P - March 202133
Appendix A Specifications
875F DC Flat Cap
Table 6 - 875F DC Flat Cap Specifications
AttributeValue
• Pipes diameter: Ø8 mm, min
• Wall thickness (factory settings):
Plastic 0.5…6 mm (non-conductive plastic wall)
Glass 0.5…4 mm (non-conductive glass wall)
Detection
Effective operation distance (Sr)0.9 x Sn ≤ Sr ≤ 1.1 x Sn
Usable operation distance (Su) 0.85 x Sr ≤ Su ≤ 1.15 x Sr
Repeat accuracy (R)≤5%
Hysteresis (H)
Rated operational volt (UB)10…30V DC (ripple included)
Ripple≤10%
Output functionsNPN or PNP by sensor type
Output switching functionN.O. and N.C by sensor type
Rated operating current (Ie)≤100 mA
No load supply current (Io)≤13 mA
Rated insulation voltage (UI)75V DC
Power-ON delay (tv)≤300 ms
Voltage drop (Ud)≤1.5V
ProtectionShort circuit, reverse polarity, transients
Degree of protectionIP65, IP66, IP67, IP68 @ 1.3 m and 24 h; IP69K (NEMA 1, 2, 4, 4x, 5, 12)
Tem pera tur e
Humidity rangeOperating and storage: 35…95%
• Wall thickness (manual setup):
≤10 mm plastic wall (best case)
≤10 mm glass wall (best case)
• Liquids: Water-based liquids such as water, milk, syrup, honey, milkshakes,
lubricates, acids, alkaline fluids, body fluids, and other high-conductive liquids
(≤50 ms)
Adjustable by IO-Link (1… 100%)
•875L-M8xx18 Factory settings: Typical 6%
•875L-N12xx18 Factory settings: Typical 15%
•875L-M16xx30 Factory settings: Typical 7%
•875L-N12xx18 Factory settings: Typical 15%
• Operating: -25…+80 °C (-13…+176 °F)
• Storage: -40…+85 °C (-40…+185 °F)
34Rockwell Automation Publication 875-UM001A-EN-P - March 2021
IO-Link Sensors875L DC Cylindrical Cap
3 BU
2WH
4 BK
1 BN
V
V
Table 7 - 875L DC Cylindrical Cap Specifications
AttributeValue
Rated operating distance (Sn)
Sensitivity
Effective operation distance (Sr)0.9 x Sn ≤ Sr ≤ 1.1 x Sn
Usable operation distance (Su) 0.85 x Sr ≤ Su ≤ 1.15 x Sr
Repeat accuracy (R)≤5%
Hysteresis (H)
Rated operational volt (UB)10…40 VDC (ripple included)
Ripple≤10%
Rated operating current (Ie) ≤200 mA (Continuous)
No load supply current (Io)≤20 mA
Rated insulation voltage (UI)50V DC
Power-ON delay (tv)≤300 ms
Operational current (Im), min>0.5 mA
Voltage drop (Ud)≤1.0V DC @ 200 mA DC
ProtectionShort circuit, reverse polarity, transients
Power ON delay≤300 ms
Degree of protectionIP67, IP68/60 min, IP69K (NEMA 1, 2, 4, 4X, 5, 6, 6P, 12)
Tem pera tur e
Humidity rangeOperating and storage: 35…95%
Appendix A Specifications
•875L-M8xx18: 0…8 mm; adjustable distance 2…20 mm (flush type)
•875L-N12xx18: 0…12 mm; adjustable distance 3…15 mm (non- flush type)
•875L-M16xx30: 0…16 mm; adjustable distance 2…20 mm (flush type)
•875L-N25xx30: 0…25 mm; adjustable distance 4…30 mm (non-flush type)
Adjustable by potentiometer, external teach or by IO-Link settings
Rockwell Automation Publication 875-UM001A-EN-P - March 202139
Appendix B Parameter Values
Sensor-specific Adjustable Parameters
Parameter NameIndex Dec (Hex)AccessDefault valueData rangeData TypeLength
Selection of local/remote
adjustment
(1)
68 (0x44)Read/write1 = Trimmer input
Trimmer value69 (0x45)Read-only —10 … 10 000——
Process data configuration70 (0x46)Read/write——RecordT16 bit
Analog value1 (0x01)Read/write1 = Enabled
Switching Output 12(0x02)Read/write1 = Enabled
Switching Output 23 (0x03)Read/write1 = Enabled
Switching Signal Channel 14 (0x04)Read/write0 = Disabled
Switching Signal Channel 25 (0x05)Read/write0 = Disabled
Margin alarm 16 (0x06)Read/write0 = Disabled
Margin alarm 27 (0x07)Read/write0 = Disabled
Temperature alarm8 (0x08)Read/write0 = Disabled
Short-circuit9 (0x09)Read/write0 = Disabled
Sensor Application
Temperature Alarm
Pre-set
Threshold
(2)
(3)
71 (0x47)Read/write0 = Full scale range
72 (0x48)Read/write ——RecordT30 bit
High Threshold1 (0x01)Read/write120-50…+150 °C (-58…+302 °F)IntegerT16 bit
Low Threshold2 (0x02)Read/write-30-50…+150 °C (-58…+302 °F)IntegerT16 bit
Safe ON/OFF Limits
(4)
73 (0x49)Read/write— —RecordT16 bit
SSC 1 - Safe limit1 (0x01)Read/write 2 x standard hysteresis0…100UintegerT8 bit
SSC 2 - Safe limit2(0x02)Read/write 2 x standard hysteresis0…100UintegerT8 bit
Event Configuration
(5)
Maintenance (0x8C30)1 (0x01)Read/write
Temperature fault event
(0x4000)
Temperature over-run
(0x4210)
Temperature under-run
(0x4220)
Short circuit (0x7710)5 (0x05)Read/write
Quality of Teach
Quality of Run
Filter Scaler
LED Indication
(1) See Local or Remote Adjustment Selection on page 29.
(2) See Sensor Application Setting on page 29.
(3) See Temperature Alarm Threshold on page 30.
(4) See Safe Limits on page 30.
(5) See Event Configuration on page 30.
(6) See Quality of Teach (QoT) on page 31.
(7) See Quality of Run (QoR) on page 30.
(8) See Filter Scaler on page 31.
(9) See Status Indication on page 31.
(6)
(7)
(8)
(9)
74 (0x4A)Read/write——RecordT16 bit
0 = Maintenance
Notification - Inactive
2 (0x02)Read/write
0 = Temperature fault
Error event - Inactive
0 = Temperature
3 (0x03)Read/write
over-run Warning
event - Inactive
0 = Temperature
4 (0x04)Read/write
under-run Warning
event - Inactive
0 = Short circuit Error
event - Inactive
75 (0x4B)Read-only—0…255UintegerT8 bit
76 (0x4D)Read-only—0…255UintegerT8 bit
77 (0x4D)Read/write11…255UintegerT8 bit
78 (0x4E)Read/write1 = Enabled
0 = Disabled
1 = Trimmer input
2 = Teach-by-wire
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = SC Inactive
1 = SC Active
0 = Full scale range
1 = Liquid level
2 = Plastic pellets
0 = Notification event Inactive
1 = Notification event Active
0 = Error event Inactive
1 = Error event Active
0 = Warning event Inactive
1 = Warning event Active
0 = Warning event Inactive
1 = Warning event Active
0 = Error event Inactive
1 = Error event Active
0 = Disabled
1 = Enabled
UintegerT8 bit
— —
— —
— —
— —
— —
— —
— —
— —
— —
UintegerT8 bit
——
——
——
——
——
BooleanT8 bit
40Rockwell Automation Publication 875-UM001A-EN-P - March 2021
Appendix B Parameter Values
Diagnosis Parameters
Parameter NameIndex Dec (Hex)AccessDefault valueData rangeData TypeLength
Operating Hours201 (0xC9)Read-only00…2,147,483,647 [h]IntegerT32 bit
Number of Power
Cycles
Maximum temperature
- All time high
Minimum temperature
- All time low
Maximum temperature
since power up
Minimum temperature
since power up
Current temperature207 (0xCF)Read-only—-50…+150 °C (-58…+302 °F)IntegerT16 bit
Detection counter SSC1210 (0xD2)Read-only—0…2,147,483,647IntegerT32 bit
Minutes above
Maximum Temperature
Minutes below
Minimum Temperature
Maintenance event
counter
Download counter214 (0xD6)Read-only00…65,536UIntegerT16 bit
Event Configuration74 (0x4A)Read/write——RecordT16 bit
Maintenance (0x8C30)1 (0x01)Read/write
Temperature fault
event (0x4000)
Temperature over-run
(0x4210)
Temper ature unde r-
run (0x4220)
Short circuit (0x7710)5 (0x05)Read/write
Quality of Teach75 (0x4B)Read-only—0…255UintegerT8 bit
Quality of Run76 (0x4D)Read-only—0…255UintegerT8 bit
Filter Scaler77 (0x4D)Read/write11…255UintegerT8 bit
LED Indication78 (0x4E)Read/write1 = Enabled
Location Indicator94 (0x5E)Read/write1 = Enabled
202 (0xCA)Read-only00…2,147,483,647IntegerT32 bit
203 (0xCB)Read-only0-50…+150 °C (-58…+302 °F)IntegerT16 bit
204 (0xCC)Read-only0-50…+150 °C (-58…+302 °F)IntegerT16 bit
205 (0xCD)Read-only—-50…+150 °C (-58…+302 °F)IntegerT16 bit
206 (0xCE)Read-only—-50…+150 °C (-58…+302 °F)IntegerT16 bit
211 (0xD3)Read-only—0…2,147,483,647 [min]IntegerT32 bit
212 (0xD4)Read-only—0…2,147,483,647 [min]IntegerT32 bit
213 (0xD5)Read-only00…2,147,483,647IntegerT32 bit
2 (0x02)Read/write
3 (0x03)Read/write
4 (0x04)Read/write
0 = Maintenance
Notification - Inactive
0 = Temperature fault
Error event - Inactive
0 = Temperature
over-run Warning
event - Inactive
0 = Temperature
under-run Warning
event - Inactive
0 = Short circuit Error
event - Inactive
0 = Notification event Inactive
1 = Notification event Active
0 = Error event Inactive
1 = Error event Active
0 = Warning event Inactive
1 = Warning event Active
0 = Warning event Inactive
1 = Warning event Active
0 = Error event Inactive
1 = Error event Active
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
——
——
——
——
——
BooleanT8 bit
BooleanT8 bit
Rockwell Automation Publication 875-UM001A-EN-P - March 202141
Appendix B Parameter Values
Notes:
42Rockwell Automation Publication 875-UM001A-EN-P - March 2021
875F DC flat cap
875L AC cylindrical cap
875L DC cylindrical cap (IO-Link)
IO-Link sensor
20
SSC
parameter
status indication
switch output
configuration
switching signal channel
switchpoint mode
21
25
33
34
33
35
35
38
31
19
20
20
T
TA 21
tab
common
14
29, 40
diagnosis
identification15
observation
parameter
teach
external
IO-Link master
procedure
teach-by-wire 25
temperature
alarm threshold
temperature alarm
terminology
threshold
temperature alarm
timer
23
mode
two-point mode 26
17
15
16
25
25
25
30
21
5
30
23
V
value
29
parameter
variables
37
29
S
safe limit 30
scaler
filter
31
selector
input
21
sensor
application
setting
29
IO-Link
10
IO-Link specifications
non-IO-Link7
specification
sensor front
sensor-specific
sensor-specific adjustable
44Rockwell Automation Publication 875-UM001A-EN-P - March 2021
20
adjustable parameter
parameter
40
35
33
29
W
windows mode 27
wiring diagram
35
X
XOR function 22
Capacitive Sensors User Manual
Rockwell Automation Publication 875-UM001A-EN-P - March 202145
Rockwell Automation Support
Use these resources to access support information.
Technical Support CenterFind help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
KnowledgebaseAccess Knowledgebase articles.rok.auto/knowledgebase
Local Technical Support Phone NumbersLocate the telephone number for your country.rok.auto/phonesupport
Literature LibraryFind installation instructions, manuals, brochures, and technical data publications.rok.auto/literature
Product Compatibility and Download Center
(PCDC)
Download firmware, associated files (such as AOP, EDS, and DTM), and access product
release notes.
rok.auto/pcdc
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our
content, complete the form at rok.auto/docfeedback
.
Waste Electrical and Electronic Equipment (WEEE)
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental information on its website at rok.auto/pec.
Allen-Bradley, expanding human possibility, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur