Installation Instructions 1
Beipackinformation 9
Notice d’utilisation 17
de
en
fr
DIR 10000043408
(Version 00)
Isolator, 3 Way, Monitoring
931S-V1R1D-MC1R
1
1. General notes
• Disconnect power prior to installation
• Installation only by Qualified personnel
• Follow all applicable local and national electrical codes
• Due to potential hazardous voltages in close proximity, use a nonconductive tool and proper PPE when adjusting the potentiometers
on the front panel.
Please observe that applications with high insulation voltages require
sufficient space or insulation to adjoining devices, as well as protection
against accidental contact. Generally speaking, fer rules with plastic collars
are to be used.
Protective measures must be taken against electrostatic
discharges (ESD) when installing and setting the
931S-V1R1D-MC1R
1.1 Notes on EMC
Deviations may occur during disturbances caused by HF radiation. It is possible to reduce these interferences by installing the
electrical equipment into a shielding enclosure, using shielded
cables or cable filters.
WARNINGWARNINGWARNINGWARNING
2
2. Function description
2.1 The 3 Way Monitoring Isolator 931S-V1R1D-MC1R monitors
24Vac/dc to 260Vac/dc voltage in single-phase power supply
systems. This voltage range can be divided into 4 individual ranges.
Power is supplied via the monitoring input. A relay with changeover
contact is used for the switching output. Fundamentally, the device
works on a closed-circuit current principle; that means that the
relay picks up by status OK, and drops out when an alarm is
signalled.The switching point is set via a potentiometer (located
under the front plastic cover).
Functions:
- High Trip: The relay switches when the set operating
point is exceeded
- Low Trip: The relay switches by underflow of the set
operating point
- Memory on: The output alarm status is retained; it can
be reset via an internal pushbutton or
external reset input
- Memory off: The alarm status is not stored
- Hysteresis, small: Pickup and release delay of 5V/8V
depends on the range set
- Hysteresis, large: Pickup and release delay of 10V/16V
depends on the range set
- AC voltage: AC voltage measurement of the input
signal
- DC voltage: DC voltage measurement of the input
signal
3
3. Configuring the module
3.1 Required tool
A screwdriver with a 2.5-mm blade is required to set the
module and to connect the conductors to the terminals.
3.2 To open the module
Remove the connector. Disengage the locking mechanism by
lightly pressing the locks on both
sides of the housing 햲, remove
the upper part of the housing
and the electronics 햳.
1
2
1
4
Input
24Vac/dc...70Vac/dc
70Vac/dc...140Vac/dc
140Vac/dc...210Vac/dc
210Vac/dc...260Vac/dc
Tri p
High Trip
Low Trip
Memory
Memory on
Memory off
Hysteresis
Hysteresis, small
Hysteresis, large
Input voltage
AC voltage
DC voltage
1 2 3 4 5 6 7 8
on
on
on
on
on
on
on
on
3.3 Settings
3.3.1 Table of settings options for 931S-V1R1D-MC1R
50%
100%
Input range
1
0
1
0
Output
1
0
min. 700ms
Reset
Alarm trip with setting Low Trip
(Closed-circuit current principle permanently set)
Operating point
Hysteresis
Times
Relay/Low Trip Memory off
Relay/Low Trip Memory on
Reset for output
4. Settings examples
4.1 Monitoring single-phase undervoltage with 931S-V1R1D-MC1R
No underflow of the setpoint value
Alarm status
The alarm status can be reset, because set-
point value was exceeded
6
5. Electrical connection
5.1 Technical Data
Supply voltage 18 ... 30 Vdc / approx. 1 W
Operating temperature 0 °C ... + 55 °C
931S-V1R1D-MC1R
Terminal
1 + reset (18 Vdc...30 Vdc)
2 nc
3 – reset
4 nc
5 Input (24Vac/dc...260Vac/dc)
6 Input (24Vac/dc...260Vac/dc)
7 nc
8 nc
9 nc
10 Relay contact 11
11 Relay contact 12
12 Relay contact 14
Connection cross-section max. 2.5 mm
2
Multi-wire connection max. 1 mm
2
(two wires with the same cross-section)