Rockwell Automation 931S-F1C2D-DC User Manual [en, de, fr]

Installation Instructions 1 Beipackinformation 15 Notice d’utilisation 28
de
en
fr
DIR 10000043403 (Version 00)
10000043403
1
1. General instructions
• Disconnect power prior to installation
• Installation only by Qualified personnel
• Follow all applicable local and national electrical codes
For applications with high isolation voltages, take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices!
Appropriate safety measures against electrostatic discharge (ESD) should be taken during assembly and adjustment work on the 931S-F1C2D-DC.
2. Application
The 3 Way Frequency Converters 931S-F1C2D-DC are used for galvanic isolation and conversion of frequency signals. Input and output signals can be calibrated/switched via DIP switches. It is not necessary to adjust the pre-settable measurement ranges. The output signal is linear to the frequency.
WARNINGWARNINGWARNINGWARNING
2
3. Configuration
3.1 Equipment
A screwdriver with a width of 2.5 mm is required to adjust the unit and to connect the wires to the terminals.
3.2 Opening the unit
Disconnect the plugs. Disengage the top part of the housing by carefully pressing the latches on both sides (1). Pull out the top part of the hou­sing and the electronics section until they lock (2).
3.3 Settings
Set input and output ranges, minimum input values and measuring span via the DIP switches SW1 and SW2. Set the input range via the DIP switches (no frequency generator required): 2 cases are to be distinguished:
1. below measurement frequency = 0 Hz – Select operating mode "0...fmax". S2.3 = 0 and S2.4 = 0 – Set upper measurement frequency via the DIP switches
S1 and S2.1, S2.2 (see table).
– Ready!
2. Lower measurement frequency ≠ 0 Hz – First, the lower measurement frequency has to be saved.
Select operating mode "save from fmin". S2.3 = 1 and S2.4 = 0
1
1
2
SW2
SW1
3
Set upper measurement frequency via the DIP switches S1 and S2.1, S2.2 (see table). Connect the module to the power supply to save the frequency. – Select operating mode "fmin...fmax". S2.3 = 0 and S2.4 = 1 – Set upper measurement frequency via the DIP switches S1
and S2.1, S2.2 (see table).
– Ready!
Setting the input range using a frequency generator: – Select the switch setting for saving the min. frequency
S2.1=0; S2.2=1; S2.3=1 and S2.4=1 – Apply min. frequency to the module – Connect the module to the power supply. – The LED lights up when the input frequency is measured.
The frequency has been saved when the LED goes out;
the module can be disconnected from the power supply. – Repeat the process with the max. frequency: S2.1=1;
S2.2=0; S2.3=1 and S2.4=1. – Select special range: S2.1=1; S2.2=1; S2.3=1 and S2.4=1 – Ready!
4
Selecting the frequency
Switch 2
C12
X1 0 0 X10 0 1 X100 1 0 X1000 1 1
Selecting the frequency
Switch 1
B 5 678
0.0 0 0 0 0
0.1 0 0 0 1
0.2 0 0 1 0
0.3 0 0 1 1
0.4 0 1 0 0
0.5 0 1 0 1
0.6 0 1 1 0
0.7 0 1 1 1
0.8 1 0 0 0
0.9 1 0 0 1
Selecting the frequency
Switch 1
A 1234
0 0000 1 0001 2 0010 3 0011 4 0100 5 0101 6 0110 7 0111 8 1000
9 1001 10 1010 11 1011 12 1100 13 1101 14 1110 15 1111
Selecting the operating mode
Switch 2
Operating mode 3 4
0...fmax 0 0 fmin...fmax 0 1 save from fmin 1 0
f=(A+B)xC
55
Special range (frequency generator is required)
Switch 2
123 4
Save min. frequency 0 1 1 1 Save max. frequency 1 0 1 1 Select special range 1 1 1 1
Selecting the output
Switch 2
Output 5 6 7 8
0...10 V 1 0 1 1
0...20 mA 0 0 0 0
4...20 mA 0 1 0 0
0...5 V 1 1 1 1
66
Selecting the frequency
Switch 1
B 5 678
0.5 0 101
Selecting the frequency
Switch 2
C12
x1000 1 1
Selecting the output
Switch 2
Output 5 6 7 8
0...10 V 1 0 1 1
ready
Selecting the frequency
Switch 1
A 1234
10 1010
Selecting the operating mode
Switch 2
Operating mode
34
0...fmax 0 0
3.4 Example 1
Input frequency: 0...10.5 kHz Output: 0...10 V
Set max. frequency
77
Selecting the output
Switch 2
Output 5 6 7 8
0...20 mA 0 0 0 0
ready
Selecting the frequency
Switch 2
C12
x100 1 0
Selecting the frequency
Switch 1
B 5 678
0.1 0 001
Selecting the frequency
Switch 1
A1234
81000
Selecting the operating mode
Switch 2
Operating mode
34
fmin...fmax 0 1
Selecting the frequency
Switch 2
C12
x1 0 0
Selecting the frequency
Switch 1
B 5 678
0.6 0 110
Selecting the frequency
Switch 1
A 1234
3 0011
Selecting the operating mode
Switch 2
Operating mode
34
save from fmin
10
Set max. frequency
3.5 Example 2
Input frequency: 3,6...810 Hz Output: 0...20 mA
Set min. frequency
The module must be briefly con­nected to the power supply (5s) in order to save the min. frequency.
88
Special range
(frequency generator is required)
Switch 2
Operating mode 1234
Special range 1111
Special range
(frequency generator is required)
Switch 2
Operating mode 1234
Save min. frequency 0111
3.6 Example 3
Input frequency: 20 kHz...50 kHz Output: 4...20mA
Special range min. frequency
Special range
(frequency generator is required)
Switch 2
Operating mode 1234
Save max. frequency 1011
Special range max. frequency
Selecting the special range
Selecting the output
Switch 2
Output 5678
4…20 mA 0100 ready
• Apply min. frequency to the module.
• Connect the module to the power supply.
• The LED lights up when the min. input frequency is measured. The frequency has been saved when the LED blinks; the module can be disconnected from the power supply.
Apply max. frequency to the module.
• Connect the module to the power supply.
• The LED lights up when the max. input frequency is measured. The frequency has been saved when the LED blinks; the module can be disconnected from the power supply.
99
3.7 Application
Namur activated: not activated:
Power
N-
N+
<= 1,2mA
>= 2,1 mA
78
56
12
34
Registering motor revolutions using Namur sensor
PLC
0…20 mA
1010
4. Mounting
The signal conditioners are mounted on standard TS 35 rails.
5. Electrical connection
5.1 Technical Data
Supply voltage 18 ... 30 Vdc/approx. 1 W Operating temperature 0 °C ... +55 °C Voltage supply via plug-in jumper. Operating carrying capacity of cross-connection ^ 2 A
Terminal assignments
1 +15 V power supply for sensor 2 Input PNP 3 Input NPN / Namur 4 Input GND 5 Output (0...10 V; 0/4...20 mA) 6 Output GND 7 Supply voltage + 24 Vdc (cross-connected) 8 Power supply GND (cross-connected)
Wire cross-section max. 2.5 mm
2
Multi-wire conncection max. 1 mm
2
(two wires with same cross-section)
7
8
5
6
2
1
4
3
1111
Push-pull output stage
5.2 Wiring diagram
3-wire initiator with PNP output
2-wire inititiator
(residual current <1 mA)
N+ N-
Namur initiator
U= 24 V
U= 24 V
U= 24 V
3-wire initiator with NPN output
3-wire initiator with PNP output and external power supply
(1) +15V (2) PNP (3) NPN / Namur (4) GND
(1) +15V (2) PNP (3) NPN / Namur (4) GND
3-wire initiator with NPN output and external power supply
(1) +15V (2) PNP (3) NPN / Namur (4) GND
(1) +15V (2) PNP (3) NPN / Namur (4) GND
(1) +15V (2) PNP (3) NPN / Namur (4) GND
(1) +15V (2) PNP (3) NPN / Namur (4) GND
(1) +15V (2) PNP (3) NPN / Namur (4) GND
Loading...
+ 29 hidden pages