PowerFlex® 6000 Medium Voltage Variable Frequency Drive
Publication 6000-UM001B-EN-P
Important User Information
IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
6Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preface
Introduction
Who Should Use This Manual
What Is Not in This Manual
This document provides procedural information for managing daily or recurring
tasks involving PowerFlex 6000 medium voltage variable frequency drives.
This manual is intended for use by personnel familiar with operating medium
voltage and solid-state variable speed drive equipment. The manual contains
material that enables operation and regular maintenance of the drive system.
This manual provides information specific to maintaining the PowerFlex 6000
medium voltage variable frequency drive. It does not include topics such as:
• Dimensional and electrical drawings generated for each customer’s order
• Spare parts lists compiled for each customer’s order
Please refer to the following documents for additional product detail or
instruction relating to PowerFlex 6000 drives:
• PowerFlex 6000 Medium Voltage Variable Frequency Drive Shipping,
Handling, and Installation Instructions (6000-IN006_-EN-P
document provides procedural information for physically unloading,
moving, and installing PowerFlex 6000 medium voltage drives.
• PowerFlex 6000 Medium Voltage Variable Frequency Drive
Commissioning Manual (6000-IN007_-EN-P
information for commissioning PowerFlex 6000 medium voltage drives.
). This document provides
). This
Additional Resources
Rockwell Automation provides the site- and installation-specific electrical and
design information for each drive during the order process cycle. If they are not
available on site with the drive, contact Rockwell Automation.
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Product Certifications website, http://www.ab.comProvides declarations of conformity, certificates, and
You can view or download publications at
http:/www.rockwellautomation.com/literature/
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Provides general guidelines for installing a Rockwell
Automation industrial system.
other certification details.
. To order paper copies of
Rockwell Automation Publication 6000-UM001B-EN-P - October 20147
Preface
General Precautions
Service and Support
ATT EN TI ON : This drive contains ESD (Electrostatic Discharge) sensitive parts
and assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with static control
procedures, reference Allen-Bradley publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
ATT EN TI ON : An incorrectly applied or installed drive can result in component
damage or a reduction in product life. Wiring or application errors, such as,
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient
temperatures may result in malfunction of the system.
ATT EN TI ON : Only personnel familiar with the PowerFlex 6000 Adjustable
Speed Drive (ASD) and associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the system. Failure to
comply may result in personal injury and/or equipment damage.
Commissioning Support
After installation, Rockwell Automation is responsible for commissioning
activities for the PowerFlex 6000 product line. Contact your local Rockwell
Automation sales representative to arrange commissioning.
Rockwell Automation support includes, but is not limited to:
• quoting and managing product on-site start-ups
• quoting and managing field modification projects
• quoting and managing customer in-house and on-site product training
The user or its representatives are responsible for pre-commissioning activities to
prepare the drive for commissioning. Failure to complete these activities prior to
the commissioning process will delay the start-up of the drive. Please refer to the
Pre-commissioning Checklist in the PowerFlex 6000 Medium Voltage Variable
Frequency Drive Shipping, Handling, and Installation Instructions
(6000-IN006_-EN-P
).
8Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 1
Introduction
Around the world, Allen-Bradley® PowerFlex® medium voltage drives from
Rockwell Automation have built a reputation for providing efficient and reliable
motor control for industry's most demanding applications. From the hardware
designed to help optimize production to the power of networked control
platforms, users can quickly and easily gain access to valuable information from
their systems. Better information leads to higher asset availability, reduced energ y
and maintenance costs, and asset and personnel protection - all resulting in an
increased return on your investment and real bottom-line savings. No matter
where your applications are located - and whether your requirements are simple
or complex, count on PowerFlex medium voltage drives for the optimal solution.
Safety Considerations
SHOCK HAZARD: Energized industrial control equipment can be dangerous.
Severe injury or death can result from electrical shock, burn, or unintended
actuation of control equipment. Hazardous voltages may exist in the drive
cabinet even with the input circuit breaker in the off position. If it is necessary
to work in the vicinity of energized equipment, the safety related work
practices outlined in Electrical Safety requirements for Employee Work places
must be followed. Before attempting any work, verify the system has been
locked out and tested to have no potential.
Lockout and tagout the device feeding power to the input of the drive before
performing any drive maintenance or component replacements. After the input
device cabinet doors are opened, immediately test the outgoing power cables
feeding the drive with a live-line tool (hot stick) while wearing high voltage
gloves. Repeat the live-line tool (hot stick) testing at the drive incoming line
power cable connections to verify that medium voltage is not present. Pay special
attention to any capacitors connected to medium voltage that can retain a charge
for a period of time. Only after the drive equipment has been verified as isolated
and de-energized can subsequent work be performed. Even though the input to
the drive may be open, it is still possible for hazardous voltage to be present.
Rockwell Automation Publication 6000-UM001B-EN-P - October 20149
Chapter 1Introduction
Refer to national and local safety guidelines for detailed procedures on how to
safely isolate the equipment from hazards.
ATT EN TI ON : The national and local electrical codes outline provisions for safely
installing and working on electrical equipment. Installation must comply with
specifications regarding wire type, conductor sizes, branch circuit protection
and disconnect devices. Failure to do so may result in personal injury and/or
equipment damage.
Environmental Conditions
How it Works
• Elevation above sea level must be less than 1000 m (3250 ft)
• Ambient air temperature must be between 0...40°C (32...104°F)
(1)
.
(2)
.
• Relative humidity must be less than 90%, non-condensing.
• The drive must be installed indoors; there must be no dripping water or
other fluids in the room.
• Cooling air must be clean without significant concentrations of sand,
corrosive or conductive dust (defined by IEC 721-1 as being less than
0.2 mg/m
of dust), or explosive gas.
• Free from significant vibration.
• The drive must be anchored on a level floor. Please refer to the dimension
drawing for the anchor point sizes and locations.
For the equipment to operate in conditions other than those specified, consult
the local Rockwell Automation Sales Office.
Cascaded “H” Bridge (CHB) Topology
The proven CHB topology combines an integrally mounted phase shifting
isolation transformer and series-connected power modules for each phase. In
addition to stepping down the input voltage, the isolation transformer also
provides two other principal functions:
• Mitigate common mode voltage stress so motors with standard insulation
levels can be used.
• Reduce Total Harmonic Distortion (THD), due to the phase shifting of
its secondary windings, so input side harmonics don’t negatively impact
the plant or utility power grid.
(1) Options are available for operation up to 3000 m.a.s.l. However, these must be stated at the time of order and cannot be retrofitte d
in the field.
(2) Options are available for ambient temperatures up to 50 ºC. However, these must be stated at the time of order and cannot be
retrofitted in the field.
10Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
IntroductionChapter 1
Input Power
3 Phase AC
Power Modules
Isolation
Transformer
A number of identical low voltage power modules are series-connected
(cascaded) together to produce the medium voltage levels required to operate the
motor.
The voltage step for each module is relatively small and a Pulse Width
Modulation (PWM) switching pattern is used so output harmonics and torque
pulsations at the motor are minimal, even at lower speeds. This technology is
very motor friendly so standard motors can be used for new applications and it
also is ideal for retrofitting existing motors. This also allows for the motor cable
lengths required for most applications, without the requirement for output
filtering.
This power module concept makes maintenance quick and easy. Each module has
powerful built in diagnostics to identify and isolate a module needing
replacement, in the unlikely event of a failure. This minimizes power module
replacement time, so process uptime is maximized.
Figure 1 - 6/6.6 kV Example Power Structure
Rockwell Automation Publication 6000-UM001B-EN-P - October 201411
GB 3797-2005Electric-driving Control Gear, Part 2: Electric- driving Control Gear Incorporating Electronic
Devices
GB/T 14549-93Quality of Electric Energy Supply Harmonics in Public Supply Network
GB 4208-2008Degrees of Protection Provided by Enclosures (IP Code) (IEC 60529:1989)
GB/T 16935.1-2008Insulation Coordination for Equipment within Low Voltage Systems, Part 1: Principles,
Requirements, and Tests (IEC 60664-1:1992)
GB 156-2007Standard Voltages
GB/T 1980-2005Standard Frequencies
GB/T 2423.10Electric and Electronic Products—Basic Environmental Test Regulations for Electricians—
Guidelines for Vibration (sine)
GB/T 2681Colors of Insulated Conductors Used in Electrical Assembly Devices
GB 2682Colors of Indicator Lights and Push Buttons Used in Electrical Assembly Devices
GB/T 4588.1-1996Specification for Single and Double-sided Printed Boards with Plain Holes
GB/T 4588.2-1996Sectional Specification: Single and Double-sided Printed Boards with Plated-through Holes
Rockwell Automation Publication 6000-UM001B-EN-P - October 201415
Chapter 1Introduction
Standard NumberStandard Description
GB 10233.2005Basic Test Method for Low Voltage Switchgear and Controlgear
GB 12668.4-2006Adjustable Speed Drive Electrical System, Part 4: General Requirement for Voltage up to 35 kV
GB 12668.3-2006Adjustable Speed Drive Electrical System, Part 3: EMC Requirement and Testing Method
GB 12668.701-2013Adjustable Speed Drive Electrical System, Part 701: Communication
GB/T 15139-94General Technical Standard for Electrical Equipment Structure
GB/ 13422-2013Semiconductor Converters—Electrical Test Methods
IEEE 519-1992Practices and Requirements for Harmonic Control in Electrical Power Systems
GB/T 12668.4-2006Adjustable Speed Electrical Power Drive Systems, Part 4: General Requirements. Rating
Specifications for AC Power
GB1094.11-2007Power Transformer, Part 11: Dry-type Transformer
16Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 2
Isolation Transformer CabinetPower Module CabinetLV Control
Cabinet
Drive System Layout
There are two basic power cell configurations offered in the PowerFlex 6000
product line. For a drive amperage rating
design is supplied. Fixed-mounted modules are shipped installed in the drive. For
a drive amperage rating of >200 A, a drawout power module design is supplied.
The PowerFlex 6000 drive is shipped in two sections, the Isolation Transformer
Cabinet and the Power Module/LV Control Cabinet. Refer to PowerFlex 6000
Medium Voltage Variable Frequency Drive Shipping, Handling, and Installation
Instructions (6000-IN006_-EN-P
Isolation Transformer Cabinet18
Power Module Cabinet25
LV C ont ro l Ca bin et29
≤200 A, a fixed-mounted power module
).
Elevation Drawings
Figure 7 - Fixed-mounted Power Module Drive Configuration
Rockwell Automation Publication 6000-UM001B-EN-P - October 201417
Chapter 2Drive System Layout
Isolation Transformer CabinetPower Module CabinetLV C ont ro l Ca bin et
Figure 8 - Drawout Power Module Drive Configuration
Isolation Transformer
Cabinet
Isolation Transformer20
Isolation Transformer Temperature Monitor21
Isolation Transformer Auxiliary Cooling Fans22
Top-mounted Main Cooling Fan(s)22
Incoming Line Power Cable Connections22
Outgoing Motor Cable Connections22
Door Position Limit Switch23
Voltage Sensing Board24
18Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Rockwell Automation Publication 6000-UM001B-EN-P - October 201419
Chapter 2Drive System Layout
PRIMARY WINDING INPUT
SECONDARY WINDING OUTPUT
C (L3)B (L2)A (L1)
U
V
W
Isolation Transformer
The primary winding of the isolation transformer is rated for the voltage of the
distribution system. It is connected to the distribution system by the incoming
line power cables. The secondary windings of the isolation transformer are
connected to the inputs of the power modules. The secondary winding voltage is
typically 690V, to feed the low voltage power modules.
There are between 9 and 27 three-phase secondary side windings, dependent on
the motor voltage requirements. The phase relationship between the secondary
windings are optimized to provide the highest reduction of line side harmonics.
The isolation transformer’s three-phase primary coils are oriented C, B, and A
from left to right, as viewed from the front. The secondary windings are also
divided into three principal sections from top to bottom. The upper third are to
feed the power modules in the U output phase. The middle third are to feed the
power modules in the V output phase. The bottom third are to feed the power
modules in the W output phase (Figure 11
Figure 11 - Isolation Transformer Primary and Secondary Winding Orientation
).
The secondary windings are brought out to corresponding vertical isolated standoffs on the body of the transformer (orientated C, B, and A from left to right as
viewed from the front).
20Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Drive System LayoutChapter 2
For drives with fixed-mounted power modules, the U and W phase
interconnections to the isolation transformer secondary windings are on the
front of the isolation transformer and the connections to the V phase are on the
rear of the isolation transformer. The power cable connections to the power
modules are made at the factory. Therefore, the field power cable connections
need to be made at the isolation transformer secondary winding termination
points (see 6000-IN006_-EN-P
).
For drives with drawout power modules, all of the interconnections between the
isolation transformer secondary windings and the power modules are made in the
rear of the isolation transformer and the connection to the power modules are
also in the rear. The power cable connections to the isolation transformer
secondary winding termination point are made at the factory. Therefore, the field
power cable connections must be made at the power module input points (see
6000-IN006_-EN-P
).
Isolation Transformer Temperature Monitor
A discrete transformer temperature monitor is mounted on the LV door in the
isolation transformer cabinet. Three temperature sensors are embedded in the
isolation transformer. The monitor can be set to indicate an alarm condition or a
trip condition, dependent on the temperature detected.
Figure 12 - Isolation Transformer Temperature Monitor
A separate user manual from the manufacturer is included in the documentation
package.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201421
Chapter 2Drive System Layout
Isolation Transformer Auxiliary Cooling Fans
Six fans are mounted directly underneath the isolation transformer to force air
directly through the windings - to ensure reliable cooling. A baffle structure
surrounds the periphery of the transformer structure to ensure the cooling air
does not bypass the interior of the transformer windings. These fans are powered
by a tertiary winding in the isolation transformer. Separate fan control power is
not required.
Top-mounted Main Cooling Fan(s)
The top mounted cooling fan(s) work with the auxiliary cooling fans to ensure
reliable cooling of the isolation transformer. They ensure the air is exhausted
from the cabinet by creating an induced draft.
Incoming Line Power Cable Connections
The incoming line cables connect to the line side terminals on the isolation
transformer. Incoming line cables can be brought in through the top or bottom of
the isolation transformer cabinet. Generous working space is provided, if stress
cones are required. See publication 6000-IN006_-EN-P
for additional details.
Outgoing Motor Cable Connections
The outgoing motor cables connect to a cable stand-off assembly on the cabinet
side sheet (Fixed-mounted Power Module configuration) or to the cable standoffs mounted on the Isolation Transformer (Drawout Power Module
configuration).
The outgoing motor cables connect to output phase of the power module array.
Outgoing motor cables can be brought in through the top or bottom of the
isolation transformer cabinet. Generous working space is provided. See
publication 6000-IN006_-EN-P
for additional details.
22Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Drive System LayoutChapter 2
Door Position Limit Switch
Door Position Limit Switch
Each cabinet door that allows access to medium voltage components is lockable
and also has a Guardmaster® safety limit switch. If the cabinet door is opened
when the input switching device feeding power to the drive is closed, the input
device will be tripped off.
ATT EN TI ON : The door position interlock is a safety feature. It must not be used
solely as a part of the plant operation process to ensure the drive has been
disconnected from input medium voltage. Keep the medium voltage doors
locked as standard practice. If access to the medium voltage rated cabinets is
required, always go to the input device feeding the drive to verify if it is open.
Lock out and tagout the input device before performing any work on the drive
or bypass units.
Figure 13 - Door Position Limit Switch Location
Rockwell Automation Publication 6000-UM001B-EN-P - October 201423
Chapter 2Drive System Layout
L11
L12
L13
A1
B1
C1
A2
B2
C2
A3
B3
C3
A4
B4
C4
A5
B5
C5
A6
B6
C6
A7
B7
C7
A8
B8
C8
A9
B9
C9
U
V
W
PC A1
PC A2
PC A3
PC B1
PC B2
PC B3
PC C1
PC C2
PC C3
U
V
W
Input power
3-phase AC
any voltage
Isolation Transformer
Motor
Volt age Sens ing
Board
Isolation Transformer CabinetPower Module/LV Control Cabinet
Voltage Sensing Board
The Voltage Sensing Board (VSB) is connected to the drive output terminals that
connect to the motor. The VSB converts motor voltage to low voltage levels
which allows the drive to monitor the output voltage to the motor.
Figure 14 - Voltage Sensing Board
Figure 15 - Power Cabling Overview (3.3 kV Fixed-mounted Power Module Configuration)
24Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Power Module Cabinet
Drive System LayoutChapter 2
Power Modules26
Hall Effect Current Sensors (HECs)28
Top-mounted Main Cooling Fan(s)28
Figure 16 - Fixed-mounted Power Module Configuration
Figure 17 - Drawout Power Module Configuration
Rockwell Automation Publication 6000-UM001B-EN-P - October 201425
Chapter 2Drive System Layout
Input U
Input V
Input W
Fuse 1
Fuse 2
Three-phase Diode
Rectifier Bridge
DC Bus
Capacitor Network
Single Phase IGBT
Inverter Network
IGBT 1IGBT 2
Output AOutput B
D1D2D3
D4D5D6
C1R1
C2R2
C3R3
Power Modules
Power Modules are available in a wide variety of amperage ratings relating to the
required motor current. Power Modules rated up to and including 200 A are
fixed-mounted in the drive and ship already installed.
Drawout power modules are supplied for a drive current rating of >200 A. The
power modules are shipped separately and must be installed in the cabinet. A
Power Module lift cart is included and shipped together with the other
components.
Basic Principle of Power Module
The Power Module combines a three phase rectifier and an “H” bridge inverter,
powered from the secondary side windings of the Isolation Transformer. After
rectifying and filtering, it outputs AC current with variable frequency and
variable voltage under the control of four IGBTs using a PWM switching pattern.
Several Power Modules, after being connected in series and superposed, can
output three-phase AC current with adjustable frequency and voltage to control
an AC motor.
Figure 18 - Low Voltage Power Module
Control signals to the Power Module and the feedback signals from the Power
Module are transmitted by fiber optic cables which provide electrical isolation
between the medium voltage and low voltage sections of the drive, and protects
against electromagnetic interference.
Although the voltage produced by each power unit is typically less than 690V, the
voltage-to-ground can reach the VFD rated output voltage, if operating at rated
frequency.
The control signals from the main control unit, through the optical-electrical
converter, are sent to the Power Module control board for further processing and
to the corresponding gate drive circuits to turn the IGBTs on or off.
26Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Drive System LayoutChapter 2
Line Terminals
Fuse
Optic Fiber Socket
and Status Indicator
Output Terminal
The status information of the Power Module is transmitted through the
electrical-optical converter and sent to the main control unit. When there is a
fault, the main control unit sends control signals to lockout or bypass the affected
Power Module.
The Power Module cabinet consists of Power Modules, current transformers and
high-voltage cable.
The Power Modules are divided evenly into three phases (U, V, and W). The
units in each phase are connected end-to-end at the output terminals. Then
individual phases are formed, using a star connection. Current transformers are
installed into the U phase and W phase.
Different models of Power Modules are used for VFDs of different power ratings
(Figure 19
Figure 19 - Typical Fixed-mounted Power Module
).
Rockwell Automation Publication 6000-UM001B-EN-P - October 201427
Chapter 2Drive System Layout
Table 1 - Power Module Ratings
Catalog NumberSpare Part NumberCurrent Rating (Amps)
TPUxx/030-AC3HTPUXX/030-AC3-R30
TPUxx/040-AC3
TPUxx/050-AC3HTPUXX/050-AC3-R50
TPUxx/060-AC3HTPUXX/060-AC3-R60
TPUxx/075-AC3HTPUXX/075-AC3-R75
TPUxx/080-AC3
TPUxx/100-AC3HTPUXX/100-AC3-R100
TPUxx/120-AC3HTPUXX/120-AC3-R120
TPUxx/150-AC3
TPUxx/180-AC3HTPUXX/180-AC3-R180
TPUxx/200-AC3HTPUXX/200-AC3-R200
TPUxx/300-AC3
TPUxx/380-AC3HTPUXX/380-AC3-R380
TPUxx/420-AC3HTPUXX/420-AC3-R420
HTPUXX/040-AC3-R40
HTPUXX/080-AC3-R80
HTPUXX/150-AC3-R150
HTPUXX/300-AC3-R300
Hall Effect Current Sensors (HECs)
The Hall Effect Current Sensors are current transformers capable of measuring
current throughout the output frequency range of the drive. They monitor the
current waveform in each of the phases going to the motor and provide feedback
to the control system.
Top-mounted Main Cooling Fan(s)
The Top-mounted Cooling Fans ensure reliable cooling of the Power Modules.
They draw cool air in through the vents in the Power Module Cabinet doors,
through the Power Modules, and exhaust the heated air out through the top of
the cabinet.
28Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Drive System LayoutChapter 2
Control Unit
PLC
LV C irc uit B rea ker s
LV Control Relays
UPS
LV Control Cabinet
Control Unit (all modules)30
PLC32
HMI32
UPS32
The LV Control Cabinet consists of the Control Unit, the human-machine
Interface (HMI), PLC, AC/DC power supplies, contactors and relays.
The HMI is located on the front door of the LV Control Cabinet, where an
operator can setup, monitor, and control the drive.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201429
Chapter 2Drive System Layout
Tra ns ce iv er
Indicators
PWM Board A
PWM Board B
PWM Board C
CPU Board
Analog Signal
Processor Board
(AT)
Digital Signal
Processor Board
(DT)
Status Indicators
Interface Terminals
Fiber Optic Sockets
Board
Handle
Board
Mounting
Screw
HMI
Commu nication
Interface
Power Indication
Status
DB Board
Control Unit (all modules)
The control unit provides the core functionality of the variable frequency drive.
This includes controlling the power modules to produce the required output
voltage and frequency, monitoring the power modules, motor voltage, and motor
current to provide alarm and trip signals based on the information.
Figure 20 - PowerFlex 6000 Interface
The CPU Board accepts external inputs through the connected communication
network, hard-wired control devices or user interactions via the HMI to
determine the actions required of the drive. The CPU Board also monitors
motor voltage and current as well as internal inputs from the PLC, analog and
digital signal processor boards and Power Modules. It uses these inputs in its
motor control and protection algorithms to determine the necessary actions to
be taken and outputs to be set. In combination with the PWM Boards, the CPU
board sends the necessary optical PWM control signals to the Power Modules to
allow the Power Modules to output the required voltage and frequency to the
motor
30Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Figure 21 - Control Unit Layout
HMI
PWM Board A
DCS
Phase A
Power Module s
Fieldbus
VSB
HECS
PLC
Communication
Board
PWM Board BPWM Board C
Phase C
Power Modules
DT
AT
DB
CPU Board
Phase B
Power Modules
RJ45 Modbus TCP/IP
RS-485
Modbus
Modbus
Drive System LayoutChapter 2
Table 2 - Control Unit description
Board Function
PWM Board A, B, COutput PWM and control signals to Power Modules
CPU BoardProcess analog input signals, switch and fault information, control DA and switch signal output,
Analog Signal
Processor Board (AT)
Digital Signal
Processor Board (DT)
DB BoardActs as a base board in the Control Unit and interfaces the digital and analog signal cables
Connector
HMI Communication
Interface
Fiber Optic SocketConnection between Power Modules and Control Unit (two per module)
Interface TerminalsConnects external inputs, outputs and the CPU Board
Status Indicators
Phase control board
transceiver indicator
light
CPU Board Indicator Lights
5V5V power supply indicator
3.3V3.3V power supply indicator
FPGAFPGA healthy indicator
DSP1DSP1 healthy indicator
DSP2DSP2 healthy indicator
Collect and process fault and state information from Power Modules to CPU board
Each phase PWM board can control up to nine power cells
realize V/F algorithm, set and change parameters in communication with HMI
Collect and process analog input signals to CPU Board, output analog signals processed by DT
board
Collect and output digital signals, digital to analog conversion function
Connection between HMI and Control Unit. Provides inputs from the HMI and PLC to the CPU
Board
B: board healthy indicator
T: transmit data to power module indicator
R: receive data from power module indicator
Rockwell Automation Publication 6000-UM001B-EN-P - October 201431
Chapter 2Drive System Layout
Power Input
Extend I/OExtend I/OPlug inPLCPlug inPlug in
EtherNet/IP Port
Digital Signal Processor Board Indicator Lights
HVENAllow High voltage switching on indicator
RUNDrive Running indicator
FaultDrive is in fault state
TripDrive is in trip state; any fault can result in trip
AlarmDrive in alarm state
Reserved
PLC
The PowerFlex 6000 uses a Micro850 PLC to perform many of its internal
control functions. The PLC controls and monitors the cooling fans, input and
bypass switching devices, door switch status, etc. The PLC is also responsible for
interfacing with the user's automation control system via many optional
communication protocols. Standard communication protocols are EtherNet/IP,
Modbus/TCP Server and Modbus RTU. Optional communication modules are
available to support other communication protocols.
Figure 22 - PLC Location
HMI
The PowerFlex 6000 HMI is a PanelView Plus 700 series, catalog number 2711PT7C4D9.
The HMI is connected to the Master Control board through a communication
interface (standard RJ45 EtherNet/IP connection). The HMI configures
operating parameters and input operation commands, and displays the operation
status, operation parameters, and fault messages.
UPS
32Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
The UPS supplies power to the LV Control cabinet using internal batteries if the
customer-supplied control power and isolation transformer control power is off.
The UPS provides control power in the event of transient power loss to ensure
the drive control can operate without interruption.
Setup and Operation
User
Setup
R&D
Set Several
P Parameters
Set Several
P Parameters
Set All
P Parameters
Set All
T Parameters
View K
Parameters
Settings
Default
Select
Language
Select
Bypass Mode
Operation
No
Bypass
Manual
Bypass
Auto
Bypass
Local/
Remote
Switch
Status
Open/Close
Switch
Local /
Remote
Local/
Remote
Switch
Status
Switch
Status
Tre nd s
V
I
Act. Freq.
Alarm
Alarm Status
Alarm History
Set Frequency
Start/Stop/Reset
Accel/Decel
Main Operation
Data Display
Set Frequency
Actual Frequenc y
Motor Voltage
Motor Current
Status Info.
Version Info.
Home
Main Interface
1
2
3
5
6
7
Screen Layout
1Top Menu Bar
2Status Bar
3Set and Monitor Box
4Actual Frequency Display Box
5Version Information Box
6Actual Date and Time
7Operation Bar
4
Chapter 3
Overview
Main Interface
The structure of the touchscreen operation is shown in Figure 23.
Figure 23 - HMI Overview
The Main Interface Screen contains configuration and operation controls,
monitoring parameters and actual speed.
Figure 24 - Main Interface Screen
Rockwell Automation Publication 6000-UM001B-EN-P - October 201433
Chapter 3Setup and Operation
Drive Setup and Configuration Controls
There are five buttons in the Top Menu Bar. A description of the functionality is
described in Ta b l e 3
Table 3 - Setup and Configuration Controls
.
• Return to Main Interface screen
• Check warnings
• Check faults
• Reset alarm status
• Show alarm history
• Check voltage trends
• Check current trends
• Check frequency trends
• Pause tre nding
• Confirm/change bypass configuration
• Change from local to remote control
• Close/open drive contactors (auto bypass)
• Access System Settings
– Change Language
– Change Bypass Mode
• Access P and T Parameters
Status Indicators
There are eight status indicators on Status Bar.
Table 4 - St atus Indi cators
AllowedThe drive is in a state that will allow MV to be applied
MVClosdIndicates that the input switching device feeding MV power to the drive is closed
ReadyDrive is ready to start
ConnectBeing connected with medium voltage
RunningThe drive is running
Warn ingThe system has faults or warnings
LocalThe system is under Local Control
RemoteThe system is under Remote Control
34Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Setup and OperationChapter 3
Operation Bar
Table 5 - Operation Bar Buttons
StartStarts the drive only if no fault is found during self test at startup; otherwise, this button is invalid
AccelIncreases the frequency by the set step
DecelDecreases the frequency by the set step
StopStop output of the drive
(1)
Reset
(1) The drive must not be running to complete this operation.
Resets the drive (under fault conditions) once
Setup and Monitor Box
Main Interface Controls
The set frequency field is the only one which is user-configurable. See Set
Frequency (Hz) for instruction on how to set the frequency.
Table 6 - Monitoring Parameters
Set FrequencyFrequency set for the drive (Hz)
Actual Frequenc yActual frequency of the drive (Hz)
Motor SpeedSpeed of the motor (%)
Motor VoltageVoltage of the motor stator (V)
Motor CurrentCurrent of the motor stator (A)
From the Main Interface screen, you can:
Set Frequency (Hz)36
Drive Operation Controls37
View Version Information38
Rockwell Automation Publication 6000-UM001B-EN-P - October 201435
Chapter 3Setup and Operation
Numpad
Cancel
Backspace
Enter
Set Frequency (Hz)
1. Press the Set Frequency: input field.
2. Press the Set Freq: input field.
3. Enter desired frequency and press .
4. Press to accept or to cancel.
36Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Setup and OperationChapter 3
Drive Operation Controls
Press the desired Drive Operation Control button, and to accept or
to cancel.
ATT EN TI ON : Drive Operation Controls will only function if using Local Control,
otherwise the following dialog appears.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201437
Chapter 3Setup and Operation
Will always
appear blue
The number of
Power Modu les in
the drive will
appear as blue; the
rest appear as grey
Fields show the
firmware version,
where applicable
View Version Information
Press under Ve r s i on Inf o. to view the currently installed Firmware.
The Version Information screen shows the most current firmware installed for
the applicable devices.
38Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Alarm
List of Active
Alarms
Alarm Code
Quantity
Accumulated Time
Alarm
CodeAlarm code. Codes beginning with W indicates a warning, codes beginning
with F indicates a fault.
QTYHow many times the alarm has occurred
Acc TimeTime which has elapsed since the alarm
MessageDescription of the warning or fault
Reset Status
Scroll to Top or
Bottom of List
Scroll Alarm
by Entry
Page Up /
Page Down
Shows Alarm History
Setup and OperationChapter 3
If the drive encounters and alarm or warnings, will blink,
indicating an active alarm.
Press the button in the Top Menu Bar to see the active alarms.
Active Alarms Controls
Reset Status
will reset just the quantity and accumulated time of the alarms. This
function does not reset the drive.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201439
Chapter 3Setup and Operation
TIP
Alarm History
Press to see a detailed listed of all warnings and faults on the drive.
The controls to scroll through the alarms are the same.
Sort Alarms
Press once to sort once to sort by time. Press again to sort by message.
Current alarms appear as red; past alarms appear as gray.
40Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
62Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
T Parameters
Parameter
Number
T01Fault-To -Bypass
T02Fault-To -Bypass Delay3ON060
T03Fault-To-Bypass Delay When Starting
T04Fault-To-Bypass Minimum Frequency
T05Auto Restart After Input Sup ply Power Loss
T06Input Supply Power Loss Time for
T07Local Frequency Command Selection
T08Remote Frequency Command Selection
T09Frequency Step For Accel or Decel1ON1Rated
T10Exit Config Environment Password555OFF
T11Automatic Bypass-To-Drive or
T12PID Parameter Settings
T134-Step Variable Speed
DescriptionDefault
Value
0ON01
0: Disable
1: Enable
60ON060
the Motor (0...60s)
5ON0Rated
0...Rated Frequency (Hz)
0ON01
0: Disable
1: Enable
20ON020
Auto Restart (0...20s)
0ON01
0: Digital
1: Analog
1ON14
1: Analog
2: 4-Step Speed
4: Communication Port
Drive-To-Bypass Selection
P0.01ON032767
I0.01ON032767
D0ON032767
D Gain0ON032767
(available only when T8=2)
Speed 110ON0Rated
Speed 220ON0Rated
Speed 330ON0Rated
Speed 440ON0Rated
Modify
Root
Lower
Limit
Upper
Limit
Frequenc y
Frequenc y
Frequenc y
Frequenc y
Frequenc y
Frequenc y
Rockwell Automation Publication 6000-UM001B-EN-P - October 201463
Chapter 4Parameters and Function Codes
Alarm List
CodeAlarm
F0000IGBT Set #1 Over Current In Power Cell #1
F0001IGBT Set #2 Over Current In Power Cell #1
F0002Input Over Voltage In Power Cell #1
F0004Communication Error In Power Cell #1
F0005No PWM1 Pulse For IGBT Set #1 In Power Cell #1
F0006No PWM2 Pulse For IGBT Set #2 In Power Cell #1
F0007IGBT Set #1 Failed To Turn On In Power Cell #1
F0008IGBT Set #2 Failed To Turn On In Power Cell #1
F0009Power Cell #1 Bypassed
F0010Over Temperature In Power Cell #1
F0011Power Cell #1 Failed To Bypass
F0012One Phase Lost In Power Cell #1
F0013Two Phases Lost In Power Cell #1
F0100IGBT Set #1 Over Current In Power Cell #2
F0101IGBT Set #2 Over Current In Power Cell #2
F0102Input Over Voltage In Power Cell #2
F0104Communication Error In Power Cell #2
F0105No PWM1 Pulse For IGBT Set #1 In Power Cell #2
F0106No PWM2 Pulse For IGBT Set #2 In Power Cell #2
F0107IGBT Set #1 Failed To Turn On In Power Cell #2
F0108IGBT Set #2 Failed To Turn On In Power Cell #2
F0109Power Cell #2 Bypassed
F0110Over Temperature In Power Cell #2
F0111Power Cell #2 Failed To Bypass
F0112One Phase Lost In Power Cell #2
F0113Two Phases Lost In Power Cell #2
F0200IGBT Set #1 Over Current In Power Cell #3
F0201IGBT Set #2 Over Current In Power Cell #3
F0202Input Over Voltage In Power Cell #3
F0204Communication Error In Power Cell #3
F0205No PWM1 Pulse For IGBT Set #1 In Power Cell #3
F0206No PWM2 Pulse For IGBT Set #2 In Power Cell #3
F0207IGBT Set #1 Failed To Turn On In Power Cell #3
F0208IGBT Set #2 Failed To Turn On In Power Cell #3
F0209Power Cell #3 Bypassed
F0210Over Temperature In Power Cell #3
F0211Power Cell #3 Failed To Bypass
F0212One Phase Lost In Power Cell #3
F0213Two Phases Lost In Power Cell #3
64Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
CodeAlarm
F0300IGBT Set #1 Over Current In Power Cell #4
F0301IGBT Set #2 Over Current In Power Cell #4
F0302Input Over Voltage In Power Cell #4
F0304Communication Error In Power Cell #4
F0305No PWM1 Pulse For IGBT Set #1 In Power Cell #4
F0306No PWM2 Pulse For IGBT Set #2 In Power Cell #4
F0307IGBT Set #1 Failed To Turn On In Power Cell #4
F0308IGBT Set #2 Failed To Turn On In Power Cell #4
F0309Power Cell #4 Bypassed
F0310Over Temperature In Power Cell #4
F0311Power Cell #4 Failed To Bypass
F0312One Phase Lost In Power Cell #4
F0313Two Phases Lost In Power Cell #4
F0400IGBT Set #1 Over Current In Power Cell #5
F0401IGBT Set #2 Over Current In Power Cell #5
F0402Input Over Voltage In Power Cell #5
F0404Communication Error In Power Cell #5
F0405No PWM1 Pulse For IGBT Set #1 In Power Cell #5
F0406No PWM2 Pulse For IGBT Set #2 In Power Cell #5
F0407IGBT Set #1 Failed To Turn On In Power Cell #5
F0408IGBT Set #2 Failed To Turn On In Power Cell #5
F0409Power Cell #5 Bypassed
F0410Over Temperature In Power Cell #5
F0411Power Cell #5 Failed To Bypass
F0412One Phase Lost In Power Cell #5
F0413Two Phases Lost In Power Cell #5
F0500IGBT Set #1 Over Current In Power Cell #6
F0501IGBT Set #2 Over Current In Power Cell #6
F0502Input Over Voltage In Power Cell #6
F0504Communication Error In Power Cell #6
F0505No PWM1 Pulse For IGBT Set #1 In Power Cell #6
F0506No PWM2 Pulse For IGBT Set #2 In Power Cell #6
F0507IGBT Set #1 Failed To Turn On In Power Cell #6
F0508IGBT Set #2 Failed To Turn On In Power Cell #6
F0509Power Cell #6 Bypassed
F0510Over Temperature In Power Cell #6
F0511Power Cell #6 Failed To Bypass
F0512One Phase Lost In Power Cell #6
F0513Two Phases Lost In Power Cell #6
F0600IGBT Set #1 Over Current In Power Cell #7
Rockwell Automation Publication 6000-UM001B-EN-P - October 201465
Chapter 4Parameters and Function Codes
CodeAlarm
F0601IGBT Set #2 Over Current In Power Cell #7
F0602Input Over Voltage In Power Cell #7
F0604Communication Error In Power Cell #7
F0605No PWM1 Pulse For IGBT Set #1 In Power Cell #7
F0606No PWM2 Pulse For IGBT Set #2 In Power Cell #7
F0607IGBT Set #1 Failed To Turn On In Power Cell #7
F0608IGBT Set #2 Failed To Turn On In Power Cell #7
F0609Power Cell #7 Bypassed
F0610Over Temperature In Power Cell #7
F0611Power Cell #7 Failed To Bypass
F0612One Phase Lost In Power Cell #7
F0613Two Phases Lost In Power Cell #7
F0700IGBT Set #1 Over Current In Power Cell #8
F0701IGBT Set #2 Over Current In Power Cell #8
F0702Input Over Voltage In Power Cell #8
F0704Communication Error In Power Cell #8
F0705No PWM1 Pulse For IGBT Set #1 In Power Cell #8
F0706No PWM2 Pulse For IGBT Set #2 In Power Cell #8
F0707IGBT Set #1 Failed To Turn On In Power Cell #8
F0708IGBT Set #2 Failed To Turn On In Power Cell #8
F0709Power Cell #8 Bypassed
F0710Over Temperature In Power Cell #8
F0711Power Cell #8 Failed To Bypass
F0712One Phase Lost In Power Cell #8
F0713Two Phases Lost In Power Cell #8
F0800IGBT Set #1 Over Current In Power Cell #9
F0801IGBT Set #2 Over Current In Power Cell #9
F0802Input Over Voltage In Power Cell #9
F0804Communication Error In Power Cell #9
F0805No PWM1 Pulse For IGBT Set #1 In Power Cell #9
F0806No PWM2 Pulse For IGBT Set #2 In Power Cell #9
F0807IGBT Set #1 Failed To Turn On In Power Cell #9
F0808IGBT Set #2 Failed To Turn On In Power Cell #9
F0809Power Cell #9 Bypassed
F0810Over Temperature In Power Cell #9
F0811Power Cell #9 Failed To Bypass
F0812One Phase Lost In Power Cell #9
F0813Two Phases Lost In Power Cell #9
F0900IGBT Set #1 Over Current In Power Cell #10
F0901IGBT Set #2 Over Current In Power Cell #10
66Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
CodeAlarm
F0902Input Over Voltage In Power Cell #10
F0904Communication Error In Power Cell #10
F0905No PWM1 Pulse For IGBT Set #1 In Power Cell #10
F0906No PWM2 Pulse For IGBT Set #2 In Power Cell #10
F0907IGBT Set #1 Failed To Turn On In Power Cell #10
F0908IGBT Set #2 Failed To Turn On In Power Cell #10
F0909Power Cell #10 Bypassed
F0910Over Temperature In Power Cell #10
F0911Power Cell #10 Failed To Bypass
F0912One Phase Lost In Power Cell #10
F0913Two Phases Lost In Power Cell #10
F1000IGBT Set #1 Over Current In Power Cell #11
F1001IGBT Set #2 Over Current In Power Cell #11
F1002Input Over Voltage In Power Cell #11
F1004Communication Error In Power Cell #11
F1005No PWM1 Pulse For IGBT Set #1 In Power Cell #11
F1006No PWM2 Pulse For IGBT Set #2 In Power Cell #11
F1007IGBT Set #1 Failed To Turn On In Power Cell #11
F1008IGBT Set #2 Failed To Turn On In Power Cell #11
F1009Power Cell #11 Bypassed
F1010Over Temperature In Power Cell #11
F1011Power Cell #11 Failed To Bypass
F1012One Phase Lost In Power Cell #11
F1013Two Phases Lost In Power Cell #11
F1100IGBT Set #1 Over Current In Power Cell #12
F1101IGBT Set #2 Over Current In Power Cell #12
F1102Input Over Voltage In Power Cell #12
F1104Communication Error In Power Cell #12
F1105No PWM1 Pulse For IGBT Set #1 In Power Cell #12
F1106No PWM2 Pulse For IGBT Set #2 In Power Cell #12
F1107IGBT Set #1 Failed To Turn On In Power Cell #12
F1108IGBT Set #2 Failed To Turn On In Power Cell #12
F1109Power Cell #12 Bypassed
F1110Over Temperature In Power Cell #12
F1111Power Cell #12 Failed To Bypass
F1112One Phase Lost In Power Cell #12
F1113Two Phases Lost In Power Cell #12
F1200IGBT Set #1 Over Current In Power Cell #13
F1201IGBT Set #2 Over Current In Power Cell #13
F1202Input Over Voltage In Power Cell #13
Rockwell Automation Publication 6000-UM001B-EN-P - October 201467
Chapter 4Parameters and Function Codes
CodeAlarm
F1204Communication Error In Power Cell #13
F1205No PWM1 Pulse For IGBT Set #1 In Power Cell #13
F1206No PWM2 Pulse For IGBT Set #2 In Power Cell #13
F1207IGBT Set #1 Failed To Turn On In Power Cell #13
F1208IGBT Set #2 Failed To Turn On In Power Cell #13
F1209Power Cell #13 Bypassed
F1210Over Temperature In Power Cell #13
F1211Power Cell #13 Failed To Bypass
F1212One Phase Lost In Power Cell #13
F1213Two Phases Lost In Power Cell #13
F1300IGBT Set #1 Over Current In Power Cell #14
F1301IGBT Set #2 Over Current In Power Cell #14
F1302Input Over Voltage In Power Cell #14
F1304Communication Error In Power Cell #14
F1305No PWM1 Pulse For IGBT Set #1 In Power Cell #14
F1306No PWM2 Pulse For IGBT Set #2 In Power Cell #14
F1307IGBT Set #1 Failed To Turn On In Power Cell #14
F1308IGBT Set #2 Failed To Turn On In Power Cell #14
F1309Power Cell #14 Bypassed
F1310Over Temperature In Power Cell #14
F1311Power Cell #14 Failed To Bypass
F1312One Phase Lost In Power Cell #14
F1313Two Phases Lost In Power Cell #14
F1400IGBT Set #1 Over Current In Power Cell #15
F1401IGBT Set #2 Over Current In Power Cell #15
F1402Input Over Voltage In Power Cell #15
F1404Communication Error In Power Cell #15
F1405No PWM1 Pulse For IGBT Set #1 In Power Cell #15
F1406No PWM2 Pulse For IGBT Set #2 In Power Cell #15
F1407IGBT Set #1 Failed To Turn On In Power Cell #15
F1408IGBT Set #2 Failed To Turn On In Power Cell #15
F1409Power Cell #15 Bypassed
F1410Over Temperature In Power Cell #15
F1411Power Cell #15 Failed To Bypass
F1412One Phase Lost In Power Cell #15
F1413Two Phases Lost In Power Cell #15
F1500IGBT Set #1 Over Current In Power Cell #16
F1501IGBT Set #2 Over Current In Power Cell #16
F1502Input Over Voltage In Power Cell #16
F1504Communication Error In Power Cell #16
68Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
CodeAlarm
F1505No PWM1 Pulse For IGBT Set #1 In Power Cell #16
F1506No PWM2 Pulse For IGBT Set #2 In Power Cell #16
F1507IGBT Set #1 Failed To Turn On In Power Cell #16
F1508IGBT Set #2 Failed To Turn On In Power Cell #16
F1509Power Cell #16 Bypassed
F1510Over Temperature In Power Cell #16
F1511Power Cell #16 Failed To Bypass
F1512One Phase Lost In Power Cell #16
F1513Two Phases Lost In Power Cell #16
F1600IGBT Set #1 Over Current In Power Cell #17
F1601IGBT Set #2 Over Current In Power Cell #17
F1602Input Over Voltage In Power Cell #17
F1604Communication Error In Power Cell #17
F1605No PWM1 Pulse For IGBT Set #1 In Power Cell #17
F1606No PWM2 Pulse For IGBT Set #2 In Power Cell #17
F1607IGBT Set #1 Failed To Turn On In Power Cell #17
F1608IGBT Set #2 Failed To Turn On In Power Cell #17
F1609Power Cell #17 Bypassed
F1610Over Temperature In Power Cell #17
F1611Power Cell #17 Failed To Bypass
F1612One Phase Lost In Power Cell #17
F1613Two Phases Lost In Power Cell #17
F1700IGBT Set #1 Over Current In Power Cell #18
F1701IGBT Set #2 Over Current In Power Cell #18
F1702Input Over Voltage In Power Cell #18
F1704Communication Error In Power Cell #18
F1705No PWM1 Pulse For IGBT Set #1 In Power Cell #18
F1706No PWM2 Pulse For IGBT Set #2 In Power Cell #18
F1707IGBT Set #1 Failed To Turn On In Power Cell #18
F1708IGBT Set #2 Failed To Turn On In Power Cell #18
F1709Power Cell #18 Bypassed
F1710Over Temperature In Power Cell #18
F1711Power Cell #18 Failed To Bypass
F1712One Phase Lost In Power Cell #18
F1713Two Phases Lost In Power Cell #18
F1800IGBT Set #1 Over Current In Power Cell #19
F1801IGBT Set #2 Over Current In Power Cell #19
F1802Input Over Voltage In Power Cell #19
F1804Communication Error In Power Cell #19
F1805No PWM1 Pulse For IGBT Set #1 In Power Cell #19
Rockwell Automation Publication 6000-UM001B-EN-P - October 201469
Chapter 4Parameters and Function Codes
CodeAlarm
F1806No PWM2 Pulse For IGBT Set #2 In Power Cell #19
F1807IGBT Set #1 Failed To Turn On In Power Cell #19
F1808IGBT Set #2 Failed To Turn On In Power Cell #19
F1809Power Cell #19 Bypassed
F1810Over Temperature In Power Cell #19
F1811Power Cell #19 Failed To Bypass
F1812One Phase Lost In Power Cell #19
F1813Two Phases Lost In Power Cell #19
F1900IGBT Set #1 Over Current In Power Cell #20
F1901IGBT Set #2 Over Current In Power Cell #20
F1902Input Over Voltage In Power Cell #20
F1904Communication Error In Power Cell #20
F1905No PWM1 Pulse For IGBT Set #1 In Power Cell #20
F1906No PWM2 Pulse For IGBT Set #2 In Power Cell #20
F1907IGBT Set #1 Failed To Turn On In Power Cell #20
F1908IGBT Set #2 Failed To Turn On In Power Cell #20
F1909Power Cell #20 Bypassed
F1910Over Temperature In Power Cell #20
F1911Power Cell #20 Failed To Bypass
F1912One Phase Lost In Power Cell #20
F1913Two Phases Lost In Power Cell #20
F2000IGBT Set #1 Over Current In Power Cell #21
F2001IGBT Set #2 Over Current In Power Cell #21
F2002Input Over Voltage In Power Cell #21
F2004Communication Error In Power Cell #21
F2005No PWM1 Pulse For IGBT Set #1 In Power Cell #21
F2006No PWM2 Pulse For IGBT Set #2 In Power Cell #21
F2007IGBT Set #1 Failed To Turn On In Power Cell #21
F2008IGBT Set #2 Failed To Turn On In Power Cell #21
F2009Power Cell #21 Bypassed
F2010Over Temperature In Power Cell #21
F2011Power Cell #21 Failed To Bypass
F2012One Phase Lost In Power Cell #21
F2013Two Phases Lost In Power Cell #21
F2100IGBT Set #1 Over Current In Power Cell #22
F2101IGBT Set #2 Over Current In Power Cell #22
F2102Input Over Voltage In Power Cell #22
F2104Communication Error In Power Cell #22
F2105No PWM1 Pulse For IGBT Set #1 In Power Cell #22
F2106No PWM2 Pulse For IGBT Set #2 In Power Cell #22
70Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
CodeAlarm
F2107IGBT Set #1 Failed To Turn On In Power Cell #22
F2108IGBT Set #2 Failed To Turn On In Power Cell #22
F2109Power Cell #22 Bypassed
F2110Over Temperature In Power Cell #22
F2111Power Cell #22 Failed To Bypass
F2112One Phase Lost In Power Cell #22
F2113Two Phases Lost In Power Cell #22
F2200IGBT Set #1 Over Current In Power Cell #23
F2201IGBT Set #2 Over Current In Power Cell #23
F2202Input Over Voltage In Power Cell #23
F2204Communication Error In Power Cell #23
F2205No PWM1 Pulse For IGBT Set #1 In Power Cell #23
F2206No PWM2 Pulse For IGBT Set #2 In Power Cell #23
F2207IGBT Set #1 Failed To Turn On In Power Cell #23
F2208IGBT Set #2 Failed To Turn On In Power Cell #23
F2209Power Cell #23 Bypassed
F2210Over Temperature In Power Cell #23
F2211Power Cell #23 Failed To Bypass
F2212One Phase Lost In Power Cell #23
F2213Two Phases Lost In Power Cell #23
F2300IGBT Set #1 Over Current In Power Cell #24
F2301IGBT Set #2 Over Current In Power Cell #24
F2302Input Over Voltage In Power Cell #24
F2304Communication Error In Power Cell #24
F2305No PWM1 Pulse For IGBT Set #1 In Power Cell #24
F2306No PWM2 Pulse For IGBT Set #2 In Power Cell #24
F2307IGBT Set #1 Failed To Turn On In Power Cell #24
F2308IGBT Set #2 Failed To Turn On In Power Cell #24
F2309Power Cell #24 Bypassed
F2310Over Temperature In Power Cell #24
F2311Power Cell #24 Failed To Bypass
F2312One Phase Lost In Power Cell #24
F2313Two Phases Lost In Power Cell #24
F2400IGBT Set #1 Over Current In Power Cell #25
F2401IGBT Set #2 Over Current In Power Cell #25
F2402Input Over Voltage In Power Cell #25
F2404Communication Error In Power Cell #25
F2405No PWM1 Pulse For IGBT Set #1 In Power Cell #25
F2406No PWM2 Pulse For IGBT Set #2 In Power Cell #25
F2407IGBT Set #1 Failed To Turn On In Power Cell #25
Rockwell Automation Publication 6000-UM001B-EN-P - October 201471
Chapter 4Parameters and Function Codes
CodeAlarm
F2408IGBT Set #2 Failed To Turn On In Power Cell #25
F2409Power Cell #25 Bypassed
F2410Over Temperature In Power Cell #25
F2411Power Cell #25 Failed To Bypass
F2412One Phase Lost In Power Cell #25
F2413Two Phases Lost In Power Cell #25
F2500IGBT Set #1 Over Current In Power Cell #26
F2501IGBT Set #2 Over Current In Power Cell #26
F2502Input Over Voltage In Power Cell #26
F2504Communication Error In Power Cell #26
F2505No PWM1 Pulse For IGBT Set #1 In Power Cell #26
F2506No PWM2 Pulse For IGBT Set #2 In Power Cell #26
F2507IGBT Set #1 Failed To Turn On In Power Cell #26
F2508IGBT Set #2 Failed To Turn On In Power Cell #26
F2509Power Cell #26 Bypassed
F2510Over Temperature In Power Cell #26
F2511Power Cell #26 Failed To Bypass
F2512One Phase Lost In Power Cell #26
F2513Two Phases Lost In Power Cell #26
F2600IGBT Set #1 Over Current In Power Cell #27
F2601IGBT Set #2 Over Current In Power Cell #27
F2602Input Over Voltage In Power Cell #27
F2604Communication Error In Power Cell #27
F2605No PWM1 Pulse For IGBT Set #1 In Power Cell #27
F2606No PWM2 Pulse For IGBT Set #2 In Power Cell #27
F2607IGBT Set #1 Failed To Turn On In Power Cell #27
F2608IGBT Set #2 Failed To Turn On In Power Cell #27
F2609Power Cell #27 Bypassed
F2610Over Temperature In Power Cell #27
F2611Power Cell #27 Failed To Bypass
F2612One Phase Lost In Power Cell #27
F2613Two Phases Lost In Power Cell #27
F2700Output Short Circuit
F2701Output Over Current
F2702Motor Over Temperature
F2703Output Over Voltage
F2704Abnormal Output Voltage
F2705Ground Fault
F2706Over Speed Fault
F2707Motor Stalled
72Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
CodeAlarm
F2900Cabinet Door Opened While Drive Energized
F2901E-Stop Trip
F2902Input Circuit Breaker Opened (Not Initiated By The Drive)
F2903Non-Zero Frequency Command Exists Upon Start
F2904Flying Start Failed
F2905Input Circuit Breaker Tripped
F2909System Locked
F2910CPU Board In Wrong Position
F2911AT Board In Wrong Position
F29125V Power Supply Fault
F291315V Power Supply Fault
F291424V DCS Power Supply Fault
F291524V PLC Power Supply Fault
F3000PWMA Board In Wrong Position
F3001PWMB Board In Wrong Position
F3002PWMC Board In Wrong Position
F3003DT Board In Wrong Position
F3100PWMA Board Not Compatible With PUA1 Board
F3101PWMA Board Not Compatible With PUA2 Board
F3102PWMA Board Not Compatible With PUA3 Board
F3103PWMA Board Not Compatible With PUA4 Board
F3104PWMA Board Not Compatible With PUA5 Board
F3105PWMA Board Not Compatible With PUA6 Board
F3106PWMA Board Not Compatible With PUA7 Board
F3107PWMA Board Not Compatible With PUA8 Board
F3108PWMA Board Not Compatible With PUA9 Board
F3109PWMA Board Not Compatible With PUA10 Board
F3110PWMA Board Not Compatible With PUA11 Board
F3111PWMA Board Not Compatible With PUA12 Board
F3112PWMA Board Not Compatible With PUA13 Board
F3113Primary FPGA Not Compatible With PWMA Board
F3114Primary FPGA Not Compatible With PWMB Board
F3115Primary FPGA Not Compatible With PWMC Board
F3200PWMB Board Not Compatible With PUB1 Board
F3201PWMB Board Not Compatible With PUB2 Board
F3202PWMB Board Not Compatible With PUB3 Board
F3203PWMB Board Not Compatible With PUB4 Board
F3204PWMB Board Not Compatible With PUB5 Board
F3205PWMB Board Not Compatible With PUB6 Board
F3206PWMB Board Not Compatible With PUB7 Board
Rockwell Automation Publication 6000-UM001B-EN-P - October 201473
Chapter 4Parameters and Function Codes
CodeAlarm
F3207PWMB Board Not Compatible With PUB8 Board
F3208PWMB Board Not Compatible With PUB9 Board
F3209PWMB Board Not Compatible With PUB10 Board
F3210PWMB Board Not Compatible With PUB11 Board
F3211PWMB Board Not Compatible With PUB12 Board
F3212PWMB Board Not Compatible With PUB13 Board
F3213Primary FPGA Not Compatible With DT Board
F3214Primary DSP Not Compatible With Primary FPGA
F3215Primary DSP Not Compatible With Secondary DSP
F3300PWMC Board Not Compatible With PUC1 Board
F3301PWMC Board Not Compatible With PUC2 Board
F3302PWMC Board Not Compatible With PUC3 Board
F3303PWMC Board Not Compatible With PUC4 Board
F3304PWMC Board Not Compatible With PUC5 Board
F3305PWMC Board Not Compatible With PUC6 Board
F3306PWMC Board Not Compatible With PUC7 Board
F3307PWMC Board Not Compatible With PUC8 Board
F3308PWMC Board Not Compatible With PUC9 Board
F3309PWMC Board Not Compatible With PUC10 Board
F3310PWMC Board Not Compatible With PUC11 Board
F3311PWMC Board Not Compatible With PUC12 Board
F3312PWMC Board Not Compatible With PUC13 Board
F3313Versions Of System Not Compatible
F3400Primary DSP Not Compatible With PLC
F3401HMI Not Compatible With PLC
F3402Primary DSP Not Compatible With HMI
FCOM1DSP Communication Fault
FCOM2PLC Communication Fault
FP006Transformer Over Temperature Trip
FP007Auxiliary Power Off
FP008Cabinet Door Open
W0003DC Bus Under Voltage In Power Cell #1 Warning
W0014Input Over Voltage In Power Cell #1 Warning
W0103DC Bus Under Voltage In Power Cell #2 Warning
W0114Input Over Voltage In Power Cell #2 Warning
W0203DC Bus Under Voltage In Power Cell #3 Warning
W0214Input Over Voltage In Power Cell #3 Warning
W0303DC Bus Under Voltage In Power Cell #4 Warning
W0314Input Over Voltage In Power Cell #4 Warning
W0403DC Bus Under Voltage In Power Cell #5 Warning
74Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Parameters and Function CodesChapter 4
CodeAlarm
W0414Input Over Voltage In Power Cell #5 Warning
W0503DC Bus Under Voltage In Power Cell #6 Warning
W0514Input Over Voltage In Power Cell #6 Warning
W0603DC Bus Under Voltage In Power Cell #7 Warning
W0614Input Over Voltage In Power Cell #7 Warning
W0703DC Bus Under Voltage In Power Cell #8 Warning
W0714Input Over Voltage In Power Cell #8 Warning
W0803DC Bus Under Voltage In Power Cell #9 Warning
W0814Input Over Voltage In Power Cell #9 Warning
W0903DC Bus Under Voltage In Power Cell #10 Warning
W0914Input Over Voltage In Power Cell #10 Warning
W1003DC Bus Under Voltage In Power Cell #11 Warning
W1014Input Over Voltage In Power Cell #11 Warning
W1103DC Bus Under Voltage In Power Cell #12 Warning
W1114Input Over Voltage In Power Cell #12 Warning
W1203DC Bus Under Voltage In Power Cell #13 Warning
W1214Input Over Voltage In Power Cell #13 Warning
W1303DC Bus Under Voltage In Power Cell #14 Warning
W1314Input Over Voltage In Power Cell #14 Warning
W1403DC Bus Under Voltage In Power Cell #15 Warning
W1414Input Over Voltage In Power Cell #15 Warning
W1503DC Bus Under Voltage In Power Cell #16 Warning
W1514Input Over Voltage In Power Cell #16 Warning
W1603DC Bus Under Voltage In Power Cell #17 Warning
W1614Input Over Voltage In Power Cell #17 Warning
W1703DC Bus Under Voltage In Power Cell #18 Warning
W1714Input Over Voltage In Power Cell #18 Warning
W1803DC Bus Under Voltage In Power Cell #19 Warning
W1814Input Over Voltage In Power Cell #19 Warning
W1903DC Bus Under Voltage In Power Cell #20 Warning
W1914Input Over Voltage In Power Cell #20 Warning
W2003DC Bus Under Voltage In Power Cell #21 Warning
W2014Input Over Voltage In Power Cell #21 Warning
W2103DC Bus Under Voltage In Power Cell #22 Warning
W2114Input Over Voltage In Power Cell #22 Warning
W2203DC Bus Under Voltage In Power Cell #23 Warning
W2214Input Over Voltage In Power Cell #23 Warning
W2303DC Bus Under Voltage In Power Cell #24 Warning
W2314Input Over Voltage In Power Cell #24 Warning
W2403DC Bus Under Voltage In Power Cell #25 Warning
Rockwell Automation Publication 6000-UM001B-EN-P - October 201475
Chapter 4Parameters and Function Codes
CodeAlarm
W2414Input Over Voltage In Power Cell #25 Warning
W2503DC Bus Under Voltage In Power Cell #26 Warning
W2514Input Over Voltage In Power Cell #26 Warning
W2603DC Bus Under Voltage In Power Cell #27 Warning
W2614Input Over Voltage In Power Cell #27 Warning
W2800Motor Over Temperature Warning
W2801Abnormal Output Voltage Warning
W2802Ground Fault Warning
W2803Output Frequency Deviation Warning
W3314Version Fault Identification Code Error
WP001Control Power Switch Warning
WP002Transformer Cabinet Fan Fault
WP003Power Module Cabinet Fan Fault
WP004Transformer Over Temperature Warning
WP005Analog Loss Warning
WP009Power Module Cabinet Fan Circuit Breaker Open
WP010Transformer Cabinet Fan Circuit Breaker Open
76Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Safety
Chapter 5
Preventative Maintenance and
Component Replacement
ATT EN TI ON : Servicing energized Medium Voltage Motor Control Equipment
can be hazardous. Severe injury or death can result from electrical shock, bump,
or unintended actuation of controlled equipment. Recommended practice is to
disconnect and lockout control equipment from power sources, and release
stored energy, if present.For countries following NEMA standards, refer to
National Fire Protection Association Standard No. NFPA70E, Part II and (as
applicable) OSHA rules for Control of Hazardous Energy Sources (Lockout/
Tagout) and OSHA Electrical Safety Related Work Practices safety related work
practices, including procedural requirements for lockout/tagout, and
appropriate work practices, personnel qualifications and training requirements,
where it is not feasible to de-energize and lockout or tagout electric circuits and
equipment before working on or near exposed circuit parts.For countries
following IEC standards, refer to local codes and regulations.
Introduction
ATT EN TI ON : Use suitable personal protective equipment (PPE) per local codes
or regulations. Failure to do so may results in severe burns, injury, or death.
ATT EN TI ON : Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device that
all circuits are voltage free. Failure to do so may result in severe burns, injury, or
death.
ATT EN TI ON : These tasks require person(s) skilled in this type of detailed work.
Read and understand this manual thoroughly before commencing. Contact
Rockwell Automation with any questions or for clarification.
The drive can experience reduced service life if operated outside of its design
parameters. Ensure the operating environment is within specifications. Daily
inspection and regular maintenance will maximize the service life of the
equipment.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201477
Chapter 5Preventative Maintenance and Component Replacement
IMPORTANT
Daily Inspection
Check the following items during normal operation of the drive:
• abnormal noise or vibration in the drive or motor
• abnormal temperature in the drive or motor
• ambient temperature in the control room above nominal
• accumulation of dust or particulate on control room floor or surfaces
• abnormal load current above nominal
Regular Maintenance Intervals
The annual maintenance requirements are summarized on page 123 as a
guideline. Detailed procedures referred to in the Preventative Maintenance
Schedule are described beginning on page 81.
Medium Voltage Motor control equipment should be inspected periodically.
Inspection intervals should be based on environmental and operating conditions
and adjusted as indicated by experience. An initial comprehensive inspection,
within 3 to 4 months after installation, is suggested. Refer to the following
standards for general guidelines for setting-up a periodic maintenance
program.For countries following NEMA standards, refer to National Electrical
Manufacturers Association (NEMA) Standard No. ICS 1.1 (Safety Guidelines
for the Application, Installation, and Maintenance of Solid-Sate Control) for
MV Drives and ICS 1.3 (Preventive Maintenance of Industrial Control and
Systems Equipment) for MV Controllers. For countries following IEC standards,
refer to IEC 61800-5-1 Sec. 6.5 for MV Drives and IEC 60470 Sec. 10, IEC
62271-1 Sec. 10.4 for MV Controllers.
If inspection reveals that dust, dirt, moisture or other contamination has reached
the control equipment, the cause must be eliminated. This could indicate
unsealed enclosure openings (conduit or other) or incorrect operating
procedures. Replace any damaged or embrittled seals, and repair or replace any
other damaged or malfunctioning parts. Replace dirty, wet, or contaminated
control devices unless they can be cleaned effectively by vacuuming or wiping.
Compressed air is not recommended for cleaning because it may displace dirt,
dust, or debris into other parts or equipment, or damage delicate parts.
78Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
Physical Checks (No Medium
Voltage or Control Power)
Power Connection Inspection
• Inspect PowerFlex 6000 drive, input/output/bypass sections, and all
associated drive components for loose power cable connections and
ground cable connections: torque them based on the required torque
specifications.
• Inspect the bus bars and check for any signs of overheating / discoloration
and tighten the bus connections to the required torque specifications.
• Clean all cables and bus bars that exhibit dust build-up.
• The torques of incoming / outgoing cable screws of the power unit shall be
check if they are in the specified range.
• Use torque sealer on all connections. Carry out the integrity checks on the
signal ground and safety grounds.
Physical Inspection
• Check for any visual/physical evidence of damage or degradation of
components in the low voltage compartments.
– This includes Relays, Contactors, Timers, Terminal connectors, Circuit
breakers, Ribbon cables, Control Wires, UPS, AC/DC Power Supplies
etc.; Causes could be corrosion, excessive temperature, or
contamination.
• Check for any visual/physical evidence of damage or degradation of
components in the medium voltage compartments (cables, contactors,
circuit breakers, isolation disconnecting blades, power units, etc.).
– This includes main cooling fan, power devices, heat sinks, circuit
boards, insulators, cables, capacitors, current transformers, potential
transformers, fuses, wiring, etc.; Causes could be corrosion, excessive
temperature, or contamination.
• Clean all contaminated components using a vacuum cleaner (DO NOT
use a blower), and wipe clean components where appropriate.
• Carry out the physical inspection and verification for the proper operation
of the contactor/isolator interlocks, and door interlocks.
• Carry out the physical inspection and verification for the proper operation
of the key interlocks.
• Carry out the cleaning of the fans and ensure that the ventilation passages
are not blocked and the impellers are freely rotating without any
obstruction.
• Carry out the insulation megger test on the transformer, motor, and
associated cabling.
• Check all bolts for fastening and adjust them as necessary.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201479
Chapter 5Preventative Maintenance and Component Replacement
Medium Voltage Testing
Medium voltage insulation resistance (IR) or dielectric withstanding voltage
(megger) tests should not be used to check solid-state control equipment. When
meggering electrical equipment, such as transformers or motors, solid-state
devices must be bypassed before performing the test. Even though no damage
may be readily apparent after a megger test, the solid-state devices are degraded
and repeated application of high voltage can lead to failure.
Maintenance after a Fault Condition
Opening of the short circuit protective device (such as fuses or circuit breakers)
in a properly coordinated motor branch circuit is an indication of a fault
condition in excess of operating overload. Such conditions can cause damage to
medium voltage motor control equipment. Before restoring power, the fault
condition must be corrected and any necessary repairs or replacements must be
made to restore the medium voltage motor control equipment to good working
order. Refer to NEMA Standards Publication No. ICS-2, Part ICS2-302 for
procedures. Use only replacement parts and devices recommended by Rockwell
Automation to maintain the integrity of the equipment. Ensure the parts are
properly matched to the model, series and revision level of the equipment. After
maintenance or repair of the equipment, always test the control system for proper
functioning under controlled conditions (that avoid hazards in the event of a
control malfunction). For additional information, refer to NEMA ICS 1.3,
PREVENTIVE MAINTENANCE OF INDUSTRIAL CONTROL AND
SYSTEMS EQUIPMENT, published by the National Electrical Manufacturers
Association, and NFPA70B, ELECTRICAL EQUIPMENT
MAINTENANCE, published by the National Fire Protection Association.
Final Report
80Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
A complete, detailed report on all steps in the Preventive Maintenance
procedures should be recorded to identify changes.
A detailed description of all adjustments and measurements that were taken
during the process must be recorded (Interlock Adjustments, Loose Connections,
Voltage Readings, Megger Results, Parameters, etc.).
Isolation Transformer
Cabinet
Preventative Maintenance and Component ReplacementChapter 5
Periodically remove and clean, or remove and replace, the air filters according to
the Preventative Maintenance table on page 124
. The frequency with which you
renew the filters depends on the cleanliness of the available cooling air.
The cabinet door filters are installed in six locations, including four locations on
the Power Module Cabinet, and two locations on the Isolation Transformer
Cabinet. However, the method to remove or clean the air filters is the same. The
screens may be replaced while the drive is operating, but the procedure is easier to
perform while the drive is shut down.
If the drive is running, you must replace the filter as soon as possible to prevent
foreign material from entering into the drive.
Recommended Cleaning Method of Filters:
• Vacuum Cleaner – A vacuum cleaner on the inlet side of the filter will
remove accumulated dust and dirt.
• Blow with Compressed Air – point compressed air nozzle in opposite
direction of operating air flow (Blow from exhaust side toward intake side)
• Cold Water Rinse – Under normal conditions the foam media used in the
filters, require no oily adhesives. Collected dirt is washed away quickly and
easily using just a standard hose nozzle with plain water.
ATT EN TI ON : The filter must be completely dry before reinstalling.
• Immersion in Warm Soapy Water – Where stubborn air-borne dirt is
present, the filter may be dipped in a solution of warm water and mild
detergent. Rinse in clear clean water, let stand until completely dry and free
of moisture.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201481
Chapter 5Preventative Maintenance and Component Replacement
IMPORTANT
Use only Rockwell Automation-supplied or -approved replacement filters (see
Spare Parts List
removal. Check that there are no openings to allow foreign matter to enter the
drive.
1. Unlatch and open the cabinet filter door more than 90°.
on page 127). Replace the filters in the reverse order of its
2. Remove the screens by pulling up out of the door.
When removing the filter, prevent accumulated dirt on the inlet side of the
filter from being sucked into the drive. It may be difficult to remove the filter
material without tearing due to the suction at the air inlet.
3. Re-install the cleaned or new air filter using reverse order of removal.
Ensure the door is fully closed and locked.
Inspect Top Mounted Main Cooling Fans
Inspect fans used for forced air cooling. Replace any that have bent, chipped, or
missing blades, or if the shaft does not turn freely. Apply power momentarily to
check operation. If unit does not operate, check and replace wiring, fuse, or fan
motor as appropriate. Clean or change air filters as recommended in the Users
Manual. Ensure the aviation plug has a proper hand-tight connection. Ensure that
the ventilation passages are not blocked and the impellers can rotate freely
without any obstruction.
82Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
M6 x 12 Bolt (4)
Lock wash er (4)
Washer (4)
Tap pin g S crew ( 4)
M6 x 12 Bolt (8)
Washer (16)
Washer (16)
Lock wash er (8)
Fan H ousi ng Li d
Fan Support Bracket
Fan Housing Assembly
Fan Assembly
Wiring Cover
Aviation Plug
Replace Top Mounted Main Cooling Fans
The top fan housing consists of a motor and impeller assembly. To replace the
fan, it is necessary to remove the Fan Housing Lid.
ATT EN TI ON : Fan replacement requires working at a significant height from the
floor. Complete this procedure on a safe, stable platform.
ATT EN TI ON : Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device that
all circuits are voltage free. Failure to do so may result in severe burns, injury, or
death.
1. Remove and retain four tapping screws around the Fan Housing Lid, and
remove the Lid.
2. Remove and retain eight M6 x 12 bolts from the Fan Housing Assembly
which connect to the Fan Support Bracket.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201483
Chapter 5Preventative Maintenance and Component Replacement
3. Remove and retain four M6 x 12 bolts from the top of the Fan Support
4. Remove the Wiring Cover and disconnect the wiring.
5. Install the fan in the reverse order of its removal. Rotate the impeller by
Fan Balance
Fan impellers are statically and dynamically balanced within acceptable
tolerances at the factory. Damage in shipping or from incorrect handling or
installation may upset the balance. An improperly balanced impeller can lead to
excessive vibration causing undue wear on the entire unit.
Bracket, and remove the bracket from the Fan Assembly.
hand to ensure that there is no contact with the Fan Housing Assembly.
ATT EN TI ON : The fan must be handled with extreme care. Failure to do so can
alter the fan balance and will negatively impact performance and life span.
If vibration is excessive, shut down the fan and determine the cause. Common
causes of excessive vibration include:
• Drive support structure not sufficiently rigid or level
• Loose mounting bolts
• Loose impeller or bushing
84Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
When the drive is running, verify that each of the coil temperatures are the same
on the Isolation Transformer Temperature Monitor display. If there is more than
a 5 °C difference between the highest and lowest temperature, check the Isolation
Transformer Auxiliary Cooling Fans.
Test the Isolation Transformer Auxiliary Cooling Fans:
ATT EN TI ON : Verify that all circuits are voltage-free, using a hot stick or
appropriate high voltage-measuring device. Failure to do so may result in injury
or death.
1. Open the LV Control Door on the Isolation Transformer Cabinet.
Locate the correct circuit breaker(s).
2. Disconnect the wires from the load side of the Isolation Transformer
Auxiliary Cooling Fan circuit breaker. Refer to Electrical Drawings.
Figure 25 - Circuit Breaker Location on LV Control Door
3. Connect 380V power to the wires to verify operation of the fans.
If a fan is not operational, see Replace Isolation Transformer Auxiliary
Cooling Fans on page 86.
4. Remove the power source and reconnect the wires to the circuit breaker.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201485
Chapter 5Preventative Maintenance and Component Replacement
5. Install the new fan in reverse order of removal.
If necessary, install new tie straps around the a, b, c, and o cables through
the fan vent.
Inspect Isolation Transformer
1. Verify the fan is rotating in the proper direction.
2. Verify the incoming and outgoing power cable connections are torqued to
specifications.
SeeTorque Requirements
3. Check the cabinet interior and Isolation Transformer windings and
remove any foreign material. Vacuum dust or debris from the Isolation
Tra ns fo rm er c ab in et .
4. Check for any physical evidence of damage or degradation of components.
on page 129.
86Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
Nylon M10 Nut (x8)
Nylon M10 Bolt (x8)
Inspect Voltage Sensing Board
The input VSB cable connections and output VSB wire connectors must be
firmly fastened and show no signs of damage or accumulation of dirt, dust, or
debris.
Replace Voltage Sensing Board
ATT EN TI ON : To prevent electrical shock, disconnect the main power before
working on the Voltage Sensing Board. Verify that all circuits are voltage-free,
using a hot stick or appropriate high voltage-measuring device. Failure to do so
may result in injury or death.
1. Remove the Voltage Sensing Board input and output cables.
2. Remove the eight nylon nuts to remove the Insulation Board from the
cabinet side sheet.
Figure 27 - Remove the Insulation Board
Rockwell Automation Publication 6000-UM001B-EN-P - October 201487
Chapter 5Preventative Maintenance and Component Replacement
Nylon M10 Nut (x9)
Nylon M10 Nut (x9)
Insulation Board
Voltage Sensing Board
3. Remove the nylon nuts which connect the Voltage Sensing Board to the
Figure 28 - Remove the Voltage Sensing Board from the Insulation Board
Insulation Board.
4. Install the new Voltage Sensing Board to the Insulation Board in reverse
order of removal.
5. Reinstall the Insulation Board to the cabinet side sheet in reverse order of
removal.
6. Reconnect the input and output cables according to the Electrical
Drawings.
Inspect Door Position Limit Switch
Check for obvious signs of damage, dust, or foreign material. Remove any dirt or
foreign material. Wipe components with an anti-static cloth, where applicable.
Check the aviation plug has a hand-tight connection.
88Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
Nut
Lock washer
Was her
M4 x 35 Bolt
Aviati on Plug
Replace Door Position Limit Switch
ATT EN TI ON : Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.
1. Open the drive cabinet door.
2. Disconnect the aviation plug from the back of the Limit Switch.
3. Remove two M4 x 35 bolts and hardware from the mounting bracket.
4. Install the new Limit Switch in reverse order of removal.
Figure 29 - Replace Door Position Limit Switch
Rockwell Automation Publication 6000-UM001B-EN-P - October 201489
Chapter 5Preventative Maintenance and Component Replacement
Power Module Cabinet
Inspect, Clean, or Replace Door Mounted Air Filters90
Inspect or Replace Top Mounted Main Cooling Fans90
Inspect Power Modules90
Replace Power Module91
Install Drawout Power Modules95
Replace Power Module Fuses97
Inspect or Replace HECS99
Inspect or Replace Door Position Limit Switch100
Inspect, Clean, or Replace Door Mounted Air Filters
See Replace/Clean Door Mounted Air Filters on page 81.
Inspect or Replace Top Mounted Main Cooling Fans
See Inspect Top Mounted Main Cooling Fans on page 82.
Inspect Power Modules
1. Check for damage or degradation of the Power Modules
a. Inspect the power connections for loose connections or any evidence of
discoloration of connections from heating
b. For Drawout Power Module configurations, remove the back plates
from the Power Module Cabinet and inspect the plug-in connectors on
the back of each Power Module. Look for evidence of discoloration
from overheating.
2. Remove dust or debris from all ventilation openings on the Power Module
3. Inspect the electrolytic capacitors, located in the ventilation openings of
the Power Module.
a. Inspect for signs of discoloration, odor, or leakage.
b. Replace Power Modules if the capacitors have discoloration, odor, or
leakage.
90Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
Fixed-mounted ≤150 A420 x 180 x 615 mm (16.5 x 7.1 x 24.2 in.)20 kg (44.1 lb)
151...200 A420 x 260 x 615 mm (16.5 x 10.2 x 24.2 in.)25 kg (55.1 lb)
Drawout201...380 A575 x 342 x 691 mm (22.6 x 13.5 x 27.2 in.)40 kg (88.2 lb)
381...420 A575 x 342 x 910 mm (22.6 x 13.5 x 35.8 in.)50 kg (110.2 lb)
ATT EN TI ON : Two people are required to handle the Power Modules. Always
handle the drawout Power Modules using the two recessed lifting handles on
both mounting rails (Figure 33
Fixed-mounted Power Module
ATT EN TI ON : The high-voltage power source must be switched off before
replacing a Fixed-mounted Power Module. Wait for 20 minutes before opening
the cabinet doors. Verify that all circuits are voltage-free, using a hot stick or
appropriate high voltage-measuring device. Failure to do so may result in injury
or death.
).
1. Remove the positioning barriers from both sides of the Power Module.
2. Disconnect the Three-phase Input Power Cables.
Figure 30 - Fixed-mounted Power Module Component Location
Rockwell Automation Publication 6000-UM001B-EN-P - October 201491
Chapter 5Preventative Maintenance and Component Replacement
Motor Cable
VSB Cable
Output Copper Bar
Fiber Optic Cables
3. Remove the Output Copper Bars that connect adjacent Power Modules
4. Disconnect the fiber optic cables.
Figure 31 - Close up of Fiber Optic Location and Power Cables
(Figure 31
).
If the Power Module is at the end of a row, remove the VSB and Motor
cable instead of an output copper bus.
ATT EN TI ON : When removing the fiber optic cables, be careful to prevent the
cables from straining or crimping as the resulting loss in light transmission will
impact performance.
ATT EN TI ON : Minimum bend radius permitted for the fiber optic cables is 50
mm (2.0 in.). Any bends with a shorter inside radius can permanently damage
the fiber-optic cable.
5. Carefully withdraw the Power Module.
92Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
6. Install the new Power Module in reverse order of removal.
Preventative Maintenance and Component ReplacementChapter 5
Hand Crank
Foot C rank
Pressure Release Knob
1. Visually inspect the lift cart to ensure it is fully
operational.
2. Turn the Pressure Release Knob clockwise
until tight.
3. Raise the lift tray using the Hand Crank or the
Foot Crank.
4. Lower the lift tray by turning the Pressure
Release Knob counter-clockwise.
TIP
The Foot Crank raises the lift tray faster than
the Hand Crank. Use this to raise the Power
Module to just below the tray assembly in
the drive. Use the Hand Crank for final
precise positioning.
Lift Tray
Release
Pressure in
Cyl ind er
Seal
Pressure in
Cyl ind er
Replace Drawout Power Module
ATT EN TI ON : Only authorized personnel should operate the lift cart. Keep hands
and feet away from the lifting mechanism. Do not stand under the lift tray
when in use. Store the lift cart with the tray fully lowered.
Lift Carts are supplied and shipped separately with drawout power module
configurations. The unit’s hydraulic cylinder can be operated by either a hand or
foot crank. The lifting capacity is 1000 kg (2206 lb).
Figure 32 - Lift Cart Procedure
Rockwell Automation Publication 6000-UM001B-EN-P - October 201493
Chapter 5Preventative Maintenance and Component Replacement
Recessed Lifting Handles
Mounting Rail
Finger Assemblies
Figure 33 - Drawout Power Module Lifting Handles
ATT EN TI ON : Do not use the front mounted positioning handles for lifting the
Power Modules. They are designed to position or withdraw the Power Module
when on the tray assembly.
94Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
Wheels
Tray Assembly Guides
Cam
Mechanism
Actuator
Power Module
Posit ionin g
Handles
Install Drawout Power Modules
1. Place the Power Module module on the lift cart.
Ensure the Power Module is properly oriented; the finger assemblies must
face towards the drive.
2. Position the lift cart in front of the cabinet and raise the Power Module to
the proper height.
3. Align the wheels on the Power Module with the tray assembly guides on
each side of the Power Module tray assembly.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201495
4. Push the Power Module slowly backwards into the cabinet until the cam
mechanism contacts the pin mounted on the tray assembly.
Chapter 5Preventative Maintenance and Component Replacement
Locking Key
Pin
Cam Mechanism
Cabinet
Stab
Assemblies
Finger
Assemblies
SIDE VIEW
Connection to
Motor Phase Bus
Three Phase
Input Power
from Isolation
Transformer
Pin
Cam Mechanism
TOP VIEW
Locking Key
Cam Mechanism Actuator
5. Insert the locking key into the cam mechanism actuator and rotate
clockwise while gently pushing on the face of the Power Module.
The cam mechanism will catch the pin on the tray assembly.
6. Continue rotating the locking key until the Power Module is fully seated.
This ensures the finger assemblies at the back of the Power Module are
fully connected to the stab assemblies at the back of the Power Module
compartment.
96Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
ATT EN TI ON : The Power Module finger assemblies must be fully seated on the
cabinet stab assemblies.
Preventative Maintenance and Component ReplacementChapter 5
Copper Washer
Lock washer
M8 Nut
Fuse
Replace Power Module Fuses
Fixed-mounted Power Module
ATT EN TI ON : Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.
1. Remove the M8 nut, lock washer, and copper washer from the top and
bottom of the fuse.
2. Remove the cables from the top and bottom of the fuse, and remove
another copper washer.
3. Install the new fuse, and replace cables and hardware in reverse order of
removal.
4. Torque all hardware to specifications (see Torque Requirements
page 129).
Figure 34 - Exploded View of Fixed-mounted Power Module Fuse
on
Rockwell Automation Publication 6000-UM001B-EN-P - October 201497
Chapter 5Preventative Maintenance and Component Replacement
Was her
Lock washer
M12 x 30 Bolt
Fuse
Was her
Nut
Power Cabl e
Bus bar
Drawout Power Module
1. Remove and retain the M12 bolt, washer, lock washer, and nut from the
2. Remove the fuse from between the fixed bracket and the power cable and
3. Install the new fuse, and the hardware in reverse order of removal.
ATT EN TI ON : Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.
top and bottom of the fuse.
bus bar.
4. Torque all hardware to specifications (see Torque Requirements
page 129).
ATT EN TI ON : The hardware connecting the Drawout Power Modules MUST be
reinstalled facing up, as shown in Figure 35
. Failure to install the hardware in
this manner will affect clearance distance between bolts and can cause an arc.
Figure 35 - Exploded View of Fixed-mounted Power Module Fuse
on
98Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Preventative Maintenance and Component ReplacementChapter 5
Current Sen sor Connec tion
HECS
Mounting Bracket
Inspect or Replace HECS
ATT EN TI ON : To prevent electrical shock, disconnect the main power before
working on the drive. Verify that all circuits are voltage-free, using a hot stick or
appropriate high voltage-measuring device. Failure to do so may result in injury
or death.
Two current sensors are located at the top inside the Power Module Cabinet.
Verify that the current sensor wire connector is properly seated. Check for
obvious signs of damage.
1. Unplug the Current Sensor Connector from the HECS.
2. Disconnect one end of the power cable that goes through the HECS from
the Power Module.
3. Remove the Mounting Bracket with the HECS still attached.
Rockwell Automation Publication 6000-UM001B-EN-P - October 201499
Chapter 5Preventative Maintenance and Component Replacement
IMPORTANT
M5 x 12 Nut
M5 x 12 Nut
Was her
4. Remove and retain M5 x 12 hardware connecting the HECS to the
Figure 36 - Exploded view of the HECS and Mounting Bracket
Mounting Bracket.
Note the orientation of the HECS on the bracket. The new HECS must be
installed facing the same direction.
5. Install the HECS on the Mounting Bracket using the existing hardware.
ATT EN TI ON : Verify that the current sampling direction is correct. This is
indicated by an arrow symbol on the top of the HECS.
6. Install the Mounting Bracket to the cabinet using existing hardware.
7. Reroute the power cable through the HECS and reattach to the Power
Module.
Inspect or Replace Door Position Limit Switch
See Replace Door Position Limit Switch on page 89.
100Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.