Rockwell Automation 599-GR1, 599GR2, 599-GR3 User Manual

Bulletin 599 Service Disconnect Ground Kit Installation Instructions
(Cat. No. 599-GR1, -GR2, -GR3)
AT T E NT I O N: To prevent electrical shock, disconnect from power source before installing or servicing. I nstall in suitable enclosure. K eep free from contaminants.
NOTE:
Use 599-GR1 for starter sizes 0-2 and disconnect sizes 30A-60A. Use 599-GR2 for starter sizes 3-4 and disconnect sizes 100A-200A. Use 599-GR3 for starter sizes 5-6 and disconnect sizes 400A-600A.
INSTALLATION FOR 599-GR1 AND 599-GR2:
Locate ground stud (1) in the lower left corner of enclosure base.
1.
Stack lugs (2) over ground stud.
2.
Install and tighten locknut (3) to torque of 40-60 LB.-INS. (4.5-6.8 N·M)
3.
1
2
3
INSTALLATION: 599-GR3 (50" (H) x 22" (W) ENCLOSURE SIZE)
1 2
TORQUE: 275 LB.-IN.
599-GR3 (56" (H) x 30" (W) ENCLOSURE SIZE)
TORQUE: 90-130 LB.-IN.
1
42052-031-01 (2)
Printed in U.S.A.
TORQUE: 275 LB.-IN.
TORQUE: 90-130 LB.-IN.