Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
10Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Product Overview
Chapter 1
Overview
The E300™ Electronic Overload Relay is a microprocessor-based electronic
overload relay designed to protect three-phase or single-phase AC electric
induction motors rated from 0.5…65,000 A. Its modular design, communication
options, diagnostic information, simplified wiring, and integration into Logix
makes this the ideal overload for motor control applications in an automation
system. The E300 Electronic Overload Relay provides flexibility, reduces
engineering time, and maximizes uptime for important motor starter
applications.
Modular Design
Users can select the specific options needed for their motor starter application.
The E300 Electronic Overload Relay consists of three modules: sensing, control
and communications. Users have choices in each of the three with additional
accessories to tailor the electronic motor overload for their application’s exact
needs.
Users can select from multiple communication options which integrate with
Logix based control systems. Developers can easily add the E300 Electronic
Overload Relay to Logix based control systems using Integrated Architecture
tools such as Add-on Profiles, Add-on Instructions, and Faceplates.
• EtherNet/IP (DLR)
• DeviceNet
Rockwell Automation Publication 193-UM015B-EN-P - June 201411
Chapter 1 Product Overview
Diagnostic Information
The E300 Electronic Overload Relay provides a wide variety of diagnostic
information to monitor motor performance, proactively alert users to possible
motor issues, or identify the reason for an unplanned shut down. Information
includes:
• Voltage, Current, & Energy
• Tri p / Warni ng His to ri es
• % Thermal Capacity Utilization
• Time to Trip
• Time to Reset
• Operational Hours
• Number of Starts
• Tri p S nap sh ot
Simplified Wiring
The E300 Electronic Overload Relay provides an easy means to mount to both
IEC and NEMA Allen-Bradley contactors. A contactor coil adapter is available
for the 100-C contactor, which allows the user to create a functional motor
starter with only two control wires.
12Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Product Overview Chapter 1
193 - ESM - VIG - 30A - C23
592
Module Type
ESM Sensing Module
Sensing Module Type
VIG Current, Ground Fault Current,
Voltage, & Power
IG Current & Ground Fault Current
ICurrent
Sensing Module Mounting Style
C23 Mounts to 100-C09…-C23 Contactor
C55 Mounts to 100-C30…-C55 Contactor
C97 Mounts to 100-C60…-C97 Contactor
D180 Mounts to 100-D115…-D180 Contactor
S2Mounts to Bulletin 500 NEMA Size 0-2 Contactor
S3Mounts to Bulletin 500 NEMA Size 3 Contactor
S4Mounts to Bulletin 500 NEMA Size 4 Contactor
TDIN Rail / Panel Mount with Power Terminals
E3TReplacement DIN Rail / Panel Mount with Power Terminals for an E3 Plus Panel Mount Adapter
PDIN Rail / Panel Mount with Pass-thru Power Conductors
CTDIN Rail / Panel Mount with Pass-thru Power Conductors (used with External CTs)
SCS Starter Control Station
SDS Starter Diagnostic Station
Bulletin Number
193 IEC Overload Relay
193 - EXP - PS - AC
Module Type
EXP Expansion Module
Func tion Type
PS Expansion Bus Power Supply
Bulletin Number
193 IEC Overload Relay
Supply Voltage
AC 110-240V AC, 50/60Hz control voltage
DC 24V DC control voltage
Digital Expansion Module
Analog Expansion Module
Operator Station
Power Supply
14Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Product Overview Chapter 1
Module Description
The E300 Electronic Overload Relay is comprised of three modules. All three
modules are required to make a functional overload relay.
• Sensing Module
• Control Module
• Communication Module
Sensing Module
Figure 1 - Sensing Module
The sensing module electronically samples the current, voltage, power, and
energy data consumed by the electric motor internal to the module. Users can
pick from one of three varieties of the sensing modules depending on the motor
diagnostic information that is needed for the motor protection application:
rrent Sensing
• Cu
• Current and Ground Fault Current Sensing
• Current, Ground Fault Current, Voltage, and Power Sensing
T
current ranges for each of three varieties of sensing module are shown below:
he
• 0.5…30 A
• 6…60 A
• 10…100 A
• 20…200 A
Users can choose how the sensing module mechanically mounts inside the
rical enclosure. The following mounting mechanisms are available for the
elect
sensing module.
• Mount to the load side of an Allen-Bradley Bulletin 100 IEC Contactor
• Mount to the load side of an Allen-Bradley Bulletin 500 NEMA
Cont
actor
• DIN Rail / Panel Mount with power terminals
• Replacement DIN Rail / Panel Mount with power terminals for an
Al
len-Bradley E3 Plus panel mount adapter
• DIN Rail / Panel Mount with pass-thru power conductors
Rockwell Automation Publication 193-UM015B-EN-P - June 201415
Chapter 1 Product Overview
Control Module
Figure 2 - Control Module
The control module is the heart of the E300 Electronic Overload Relay and can
attach to any sensing module. The control module performs all of the protection
and motor control algorithms and contains the native I/O for the system. The
control module has two varieties:
• I/O only
• I/O and prote
ction (PTC & External Ground Fault Current Sensing)
The control module is offered in three control voltages:
• 110…120V AC, 50/60Hz
• 220…240V AC, 50/60Hz
• 24V D
Ext
ernal control voltage is required to power the E300 Electronic Overload Relay
and
activate the digital inputs.
C
Communication Module
Figure 3 - Communication Module
The communication module allows the E300 Electronic Overload Relay to be
integrated into an automation system, and it can attach to any control module.
All communication modules allow the user to set the node address with rotary
16Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Product Overview Chapter 1
turn dials, and it provides diagnostic LEDs to provide system status at the panel.
The E300 Electronic Overload Relay supports two network protocols:
• EtherNet/IP
• DeviceNet
The
E300 EtherNet/IP Communication Module has two RJ-45 connectors that
funct
ion as a switch. Users can daisy chain multiple E300 Electronic Overload
Relays with Ethernet cable, and the module supports a Device Level Ring (DLR).
Optional Add-On Modules
Optional Expansion I/O
The E300 Electronic Overload Relay allows the user to add additional digital and
analog I/O to the system via the E300 Electronic Overload Relay Expansion Bus
if the native I/O count is not sufficient for the application on the base relay. Users
can add up to four additional Digital I/O Expansion Modules that have 4 inputs
(120V AC, 240V AC, or 24V DC) and 2 relay outputs.
Users can also add up to four additional Analog I/O Expansion Modules, which
have three independent universal analog inputs and one isolated analog output.
The independent universal analog inputs can accept the following signals:
• 4…20 m
• 0…20 mA
• 0…10V DC
• 1…5V DC
• 0…5V DC
• RTD Sensors (Pt, Cu, Ni, & NiFe)
• NTC Sensors
o
The is
signa
diagnostic values:
lated analog output can be programmed to reference a traditional analog
l (4…20 mA, 0…20 mA, or 0…10V DC) to represent the following
• Average %FLA
• %TCU
• Ground Fault Current
• Current Imbalance
• Average L-L Voltage
• Voltage Imbalance
• To ta l kW
• To ta l kVA R
• To ta l kVA
• To ta l P ow er Fa cto r
• User Defined Value
A
Rockwell Automation Publication 193-UM015B-EN-P - June 201417
Chapter 1 Product Overview
Control StationDiagnostic Station
Optional Operator Station
Figure 4 - Operator Stations
Power LED
Trip / Warn LED
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Escape
Up
Select
ESC
SELECT
0
RESET
Enter
Down
Stop
LOCAL
REMOTE
Reset
Power LED
Trip / Warn LED
0
RESET
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
LOCAL
REMOTE
Reset
The E300 Electronic Overload Relay offers the user the capability to add one
operator interface to the Expansion Bus. There are two types of operator stations
that the user can chose from: control station or a diagnostic station. Both types of
operator stations mount into a standard 22 mm push button knockout, and they
provides diagnostic LEDs which allow the user to view the status of the E300
Electronic Overload Relay from the outside of an electrical enclosure. Both
operator stations provide push buttons which can be used for motor control
logic, and they both can be used to upload and download parameter
configuration data from the base relay. The diagnostic station contains a display
and navigation buttons that allows the user to view and edit parameters in the
base relay.
Optional Expansion Bus Power Supply
Figure 5 - Expansion Bus Power Supply
The E300 Electronic Overload Relay expansion bus provides enough current to
operate a system that has (1) Digital Expansion Module and (1) Operator
Station. An E300 Electronic Overload Relay system that contains more
expansion modules will need supplemental current for the Expansion Bus. The
E300 Electronic Overload Relay offers users two types of Expansion Bus Power
Supplies: AC (110…240V AC, 50/60 Hz) and DC (24V DC). One Expansion
Bus Power Supply supplies enough current for a fully loaded E300 Electronic
18Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Product Overview Chapter 1
Overload Relay Expansion Bus (four Digital Expansion Modules, four Analog
Expansion Modules, and one Operator Station).
Protection Features
Standard Current-Based Protection
All versions of the E300 Electronic Overload Relay provide the following motor
protection functions:
• Thermal Overload (51)
• Phase Loss
• Current Imbalance (46)
• Undercurrent – load loss (37)
• Overcurrent – load jam (48)
• Overcurrent – load stall
• Start Inhibit (66)
Ground Fault Current Based Protection
The E300 Electronic Overload Relay sensing modules and control modules with
a ground fault current option provides the following motor protection function:
• Ground Fault – zero sequence method (50N)
Voltage and Power Based Protection
The E300 Electronic Overload Relay sensing modules with voltage sensing
provides the following motor protection functions:
• Undervoltage (27)
• Overvoltage (59)
• Phase Reversal (47) – voltage based
• Over and Under Frequency (81) – voltage based
• Voltage Imbalance (46)
• Over and Under Power (37)
• Over and Under Leading/Lagging Power Factor (55)
• Over and Under Reactive Power Generated
• Over and Under Reactive Power Consumed
• Over and Under Apparent Power
Rockwell Automation Publication 193-UM015B-EN-P - June 201419
Chapter 1 Product Overview
Applications:
The E300 Electronic Overload Relay can be used with the following across the
line starter applications:
• Non-Reversing Starter
• Reversing Starter
• Wye (Star) / Delta Starter
• Two -s pe ed Motors
• Low and Medium Voltage with 2 or 3 Potential Transformers
• With or Without Phase Current Transformers
• With or Without Zero-sequence Core Balanced Current Transformer
20Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring
Chapter 2
Introduction
Receiving
Unpacking/Inspecting
Storing
This chapter provides instructions for receiving, unpacking, inspecting, and
storing the E300™ Electronic Overload Relay. Assembly, installation, and wiring
instructions for common applications are also included in this chapter.
It is the responsibility of the user to thoroughly inspect the equipment before
accepting the shipment from the freight company. Check the item(s) received
against the purchase order. If any items are damaged, it is the responsibility of the
user not to accept delivery until the freight agent has noted the damage on the
freight bill. Should any concealed damage be found during unpacking, it is again
the responsibility of the user to notify the freight agent. The shipping container
must be left intact and the freight agent should be requested to make a visual
inspection of the equipment.
Remove all packing material from around the E300 Electronic Overload Relay.
After unpacking, check the item’s nameplate catalog number against the purchase
order.
The E300 Electronic Overload Relay should remain in its shipping container
prior to installation. If the equipment is not to be used for a period of time, it
must be stored according to the following instructions in order to maintain
warranty coverage:
• Store in a clean, dry location.
• Store within an ambient temperature range
-40…+85 °C (-40…+185
of
• Store within a relative humidity range of 0…95%, non-condensing.
• Do not store where the device could be exposed to a corrosive atmosphere.
• Do not store in a construction area.
°F).
Rockwell Automation Publication 193-UM015B-EN-P - June 201421
Chapter 2 Installation and Wiring
General Precautions
If the E300 Electronic Overload Relay is being deployed in an environment with
an ambient temperature greater than 30 °C (86 °F), please refer to the
Environmental Specifications on page 325
derating. In addition to the specific precautions listed throughout this manual,
the following general statements must be observed.
ATT EN TI ON : The E300 Electronic Overload Relay contains electrostatic
discharge (ESD) sensitive parts and assemblies. Status control precautions are
required when installing, testing, servicing, or repairing this assembly.
Component damage may result if ESD control procedures are not followed. If
you are not familiar with static control procedures, refer to Allen-Bradley
publication 8000-SB001_-en-p, “Guarding Against Electrostatic Damage”, or
any other applicable ESD protection handbook.
ATT EN TI ON : An incorrectly applied or installed E300 Electronic Overload Relay
can result in damage to the components or reduction in product life. Wiring or
application errors (e.g., incorrectly figuring the FLA setting, supplying incorrect
or inadequate supply voltage, connecting an external supply voltage to the
thermistor terminals, or operating or storing in excessive ambient
temperatures) may result in malfunction of the E300 Electronic Overload Relay.
for the appropriate temperature
Base Relay Assembly
ATT EN TI ON : Only personnel familiar with the E300 Electronic Overload Relay
and associated machinery should plan to install, start up, and maintain the
system. Failure to comply may result in personal injury or equipment damage.
ATT EN TI ON : The purpose of this user manual is to serve as a guide for proper
installation. The National Electrical Code (NEC) and any other governing
regional or local code will overrule this information. Rockwell Automation
cannot assume responsibility for the compliance or proper installation of the
Electronic Overload Relay or associated equipment. A hazard of personal
E300
injury and/or equipment damage exists if codes are ignored during installation.
ATT EN TI ON : The earth ground terminal of the E300 Electronic Overload Relay
shall be connected to a solid earth ground via a low-impedance connection.
The following section illustrates the E300 Electronic Overload Relay base relay
assembly instructions.
22Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring Chapter 2
Control Module to Sensing
Module Assembly
1
Any E300 Control Module can connect to any E300 Sensing Module. The
illustrations below show the steps required to make this connection.
Figure 6 - Control Module to Sensing Module Assembly\
2
3
Rockwell Automation Publication 193-UM015B-EN-P - June 201423
Chapter 2 Installation and Wiring
1
3
2
Communication Module to
Control Module Assembly
Any E300 Communication Module can connect to any E300 Control Module.
The illustrations below show the steps required to make this connection.
Figure 7 - Communication Module to Control Module Assembly
24Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring Chapter 2
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
Reset
Start Forward / Speed 1
Start Reverse / Speed 2
Local / Remote
Stop
Up
Down
Reset
Escape
Power LED
Trip / Warn LED
Power LED
Trip / Warn LED
Enter
Select
0
RESET
LOCAL
REMOTE
0
RESET
SELECT
ESC
REMOTE
LOCAL
Control StationDiagnostic Station
Expansion Bus Peripherals
Panel Mount
Hole
DIN Rail Mount
Panel Mount Hole
Expansion Bus Out
Expansion Bus In
The E300 Electronic Overload Relay offers a range of Expansion Digital and
Analog I/O modules that simply connect to the E300 Electronic Overload
Relay’s Expansion Bus.
Figure 8 - Expansion Bus Peripherals
Removable I/O Terminals
3
2
4
4T
1
3T
1T
2T
Color
Blinking Green
GreenModule OK and active
Module Number Selector
Number
1 - 4
1T - 4T
Note: If the expansion bus does not have an operator station, then the
last expansion module number must be set to terminated.
Status LED
Description
O
No power applied
Module OK with no connection
RedError Detected
Description
Module number
Module number with
expansion bus terminating
resistor applied
Users can also add one of the two available operator stations to the end of the
Expansion Bus.
Figure 9 - Expansion Operator Stations
The following illustrations show how to mount and connect the E300 Electronic
Overload Relay expansion bus I/O modules, expansion power supplies, and
operator stations.
Rockwell Automation Publication 193-UM015B-EN-P - June 201425
Chapter 2 Installation and Wiring
1
2
Click
2
1
1.7 N.m
(15 lb-in)
0
RESET
SELECT
ESC
REMOTE
LOCAL
800F-AW2
3
22 mm
Expansion Bus Digital &
Analog I/O Modules and
Power Supply Installation
Figure 10 - Expansion Bus Digital& Analog I/O Modules and Power Supply
Expansion Bus Operator
Figure 11 - Expansion Bus Operator Station
Station Installation
Expansion Bus Network
Installation
26Rockwell Automation Publication 193-UM015B-EN-P - June 2014
The E300 Electronic Overload Relay will support up (4) Expansion Digital I/O
modules, (4) Expansion Analog I/O modules, and (1) Operation Station. The
E300 Base Relay can supply enough power for (1) Expansion Digital I/O module
and (1) Operator Station. Any other combination of E300
Expansion Bus
Installation and Wiring Chapter 2
0
RESET
SELECT
ESC
REMOTE
LOCAL
Click
1
2
peripherals will require an Expansion Bus Power Supply which connects as the
first module on the Expansion Bus.
Users will set the address dial of the Expansion Digital Module to a unique digital
module address number (1-4). If the Expansion Digital Module is the last device
on the Expansion Bus, set the address to the address value that enables in the
internal terminating resistor (1T-4T). A power cycle is required when changes
are made to the address dial.
Users will set the address dial of the Expansion Analog Module to a unique
analog module address number (1-4). If the Expansion Analog Module is the last
device on the Expansion Bus, set the address to the address value that enables in
the internal terminating resistor (1T-4T). A power cycle is required when
changes are made to the address dial.
Users will connect the E300 Base Relay to the Expansion Module’s Input Port
using the supplied Expansion Bus cable. Users will add the next Expansion
Module by connecting the supplied Expansion Bus cable to the Output Port of
the previous Expansion Module and into the Input Port of the additional
Expansion Module. The Operator Stations is the last device on the E300
Expansion Bus; it only has an Input Port with an internal Expansion Bus
terminating resistor.
If the user supplied Expansion Bus cable is not long enough for the installation,
1-meter (Cat. No. 193-EXP-CBL-1M) and 3-meter (Cat. No.
193-EXP-CBL-3M) Expansion Bus cables are available as accessories. The E300
expansion bus can support a maximum distance of 5 meters (16 ft.).
Figure 12 - Expansion Bus Network Installation
Rockwell Automation Publication 193-UM015B-EN-P - June 201427
Chapter 2 Installation and Wiring
Starter Assembly
5 - 7 lb-in
IN1
The following illustrations show how to assemble an E300 Electronic Overload
Relay as a motor starter with an Allen-Bradley Bulletin 100-C contactor.
100-C09…-C55 Starter Assembly Installation
The starter assembly installation instructions are for use with E300 Sensing
Module catalog numbers 193-ESM-___-___-C23 and 193-ESM-___-___-C55
34Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Control Module
193-EIOGP-42- _ _ _
193-EIOGP-22- _ _ _
Sensing Module Latch
Power / PTC
Terminals
Expansion Bus Connector
Relay / Ground Fault
Terminals
R13
R14
S1
S2
A1
A1
A2
IN2
IN3
IT1
IT2
R13
R14
S1
S2
193-EIO-63- _ _ _
193-EIO-43- _ _ _
R13
R14
R23
R24
A1
A1
A2
IN2
IN3
IN4
IN5
R13
R14
R23
R24
A1
A1
A2
IN2
IN3
A1
A1
A2
IT1
IT2
Input / Output
Terminals
Communication
Module Latch
IN1
IN0
A2
A1
R04
R03
Figure 25 - E300 Control Module Terminal Designations
Installation and Wiring Chapter 2
Rockwell Automation Publication 193-UM015B-EN-P - June 201435
Chapter 2 Installation and Wiring
R24R23
RELAY 2RELAY 1
R14R13
IN3
IN2
Additional Inputs for 193-EIO-63-_ _ _
IN0
IN1
A2
PE
A1A1
A1
R03
R04
A2
IN5
IN4
(+)
(-)
RELAY 0
S2S1
RELAY 1
R14R13
IN3
IN2
IN0
IN1
A2
A1A1
A1
R03
R04
A2
IT2
IT1
(+)
(-)
RELAY 0
193-EIOGP-_ _-_ _ _193-EIO-_ _-_ _ _
PE
Ground
Fault
PTC
Additional Inputs for 193-EIOGP-42-_ _ _
+
t
Table 2 - E300 Control Module Wire Size and Torque Specifications
Cat. No.
Wire TypeConductor Torque
193-EIO-_ _-_ _ _
193-EIOGP-_ _-_ _ _
Single24...12 AWG
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule
Metric
Coarse-Stranded/Solid Metric
Multiple
(stranded only)
24...16 AWG
5 lb-in
Single0.25…2.5 mm
Multiple
0.5...0.75 mm
0.55 N•m
Single0.2...2.5 mm
Multiple
0.2...1.5 mm
0.55 N•m
2
2
2
2
Figure 26 - Control Module Wiring
36Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Expansion Digital Module
IN0 IN1 INC
IN2 IN3
RS2
R04 R14 RC3
Figure 27 - E300 Expansion Digital Module Terminal Designations
Installation and Wiring Chapter 2
Table 3 - E300 Expansion Digital Module Wire Size and Torque Specifications
Wire TypeConductor Torque
Single24...12 AWG
Stranded/Solid [AWG]
Multiple
(stranded only)
Single0.25…2.5 mm
Flexible-Stranded with Ferrule Metric
Multiple
Single0.2...2.5 mm
Coarse-Stranded/Solid Metric
Multiple
Cat. No.
193-EXP-DIO-42-_ _ _
24...16 AWG
5 lb-in
0.5...0.75 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
Rockwell Automation Publication 193-UM015B-EN-P - June 201437
Chapter 2 Installation and Wiring
R04R14RC3
IN0INCIN1IN2IN3
Source
+
-
IN1+ IN1- RS1
IN2+ IN2- RS2
OUT+OUT-
IN0+ IN0- RS0
Figure 28 - E300 Expansion Digital Module Wiring Diagram
Expansion Analog Module
Figure 29 - E300 Expansion Analog Module Terminal Designations
38Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring Chapter 2
Analog Current InputAnalog Voltage Input
24V DC
Power
Supply
INx+
IN
x
-
+
-
Current
Input
Device
INx+
-
V
+V
INx-
Analog Voltage or Current Output
+
Out
-
Out+
Device
-
2 Wire RTD
INx+
INx-
INx-
3 Wire RTD
INx+
RS
x
Table 4 - E300 Expansion Analog Module Wire Size and Torque Specifications
Wire TypeConductor Torque
Single24...12 AWG
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule Metric
Coarse-Stranded/Solid Metric
Multiple
(stranded only)
Single0.25…2.5 mm
Multiple
Single0.2...2.5 mm
Multiple
Figure 30 - E300 Expansion Analog I/O Modules 193-EXP-AIO-__
Cat. No.
193-EXP-AIO-31
24...16 AWG
5 lb-in
0.5...0.75 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
Rockwell Automation Publication 193-UM015B-EN-P - June 201439
Chapter 2 Installation and Wiring
A1 A2
A1A2
Source
+
-
Expansion Power Supply
Figure 31 - E300 Expansion Power Supply Terminal Designations
Table 5 - E300 Expansion Power Supply Wire
Wire TypeConductor Torque
Stranded/Solid [AWG]
Flexible-Stranded with Ferrule Metric
Coarse-Stranded/Solid Metric
Size and Torque Specifications
Single24...12 AWG
Multiple
(stranded only)
Single0.25…2.5 mm
Multiple
(stranded only)
Single0.2...2.5 mm
Multiple
(stranded only)
Figure 32 - E300 Expansion Power Supply Wiring Diagram
Cat. No.
193-EXP-PS-_ _
24...16 AWG
5 lb-in
0.5...0.75 mm
0.55 N•m
0.2...1.5 mm
0.55 N•m
2
2
2
2
40Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring Chapter 2
Grounding
Short-Circuit Ratings
The following grounding recommendations are provided to ensure EMC
requirements during installation
.
• The earth ground terminal of the E300 Electronic Overload Relay shall be
connected to a solid earth ground via a low-impedance connection.
• Wire the green shield wire of the Cat. No. 193-ECM-ETR into the earth
ound terminal of the E300 control module.
gr
• Installations employing an external ground fault sensor shall ground the
cable shield
at the sensor with no connection made at the E300 Electronic
Overload Relay.
• The PTC thermistor cable shield shall be grounded at the E300 Electronic
Ov
erload Relay with no connection made at the opposite end.
The E300 Electronic Overload Relay is suitable for use on circuits capable of
delivering not more than the RMS symmetrical amperes listed in the following
tables.
Table 6 - Standard Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1
Overload Relay using Sensing Module Cat. No.Max. Available Fault Current [A] Maximum Voltage [V]
193-ESM-___-30A-C23
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
5,000600
Table 7 - Short Circuit Ratings per EN60947-4-1
Overload Relay using Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55
193-ESM-___-30A-E3T
193-ESM-___-30A-P
193-ESM-___-30A-T
193-ESM-VIG-30A-CT
592-ESM-___-30A-S2
193-ESM-___-60A-C55
193-ESM-___-60A-E3T
193-ESM-___-60A-P
193-ESM-___-60A-T
592-ESM-___-60A-S2
Rockwell Automation Publication 193-UM015B-EN-P - June 201441
Prospective Short-
Circuit Current, Ir [A]
3,000100,000690
Conditional Short-Circuit
Current, Iq [A]
Maximum Voltage [V]
Chapter 2 Installation and Wiring
Table 8 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul.
100-C and 100-D IEC contactors protected by fuses
Overload Relay using
Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55,
193-ESM-___-60A-C55
Overload Relay using
Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C23
193-ESM-___-30A-C23
Contactor Cat. No.Max. Starter FLC[A]
100-C099
100-C121220
100-C161630
100-C232330
100-C303050
100-C373750
100-C434370
100-C555580
Max. Available Fault
Current [A]
100,000600
Max. Voltage [V]Class C or JJ fuse [A]
Table 9 - Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with Bul. 100-C IEC
contactors protected by Bul. 140U-D circuit breakers
Contactor Cat. No.Max. Starter FLC[A]
100-C099
100-C1212
100-C1616
100-C2323
100-C099
100-C1212
100-C1616
100-C2323
100-C099
100-C1212
100-C1616
100-C2323
Max. Available Fault
Current [A]
65,000480Y/277VC30 (30 A)
35,000600Y/347VC30 (30 A)
5,000600Y/347VC30 (30 A)
Max. Voltage [V]
20
Max. Circuit Breaker
Cat. No. 140U-D6D3-
Table 10 - High Fault Short Circuit Ratings per UL60947-4-1 and CSA 22.2 No. EN60947-4-1 with
Bul. 500 line NEMA contactors protected by fuses
Overload Relay using Sensing Module
Cat. No.
592-ESM-___-30A-S2009
592-ESM-___-30A-S2018
592-ESM-___-30A-S2127
592-ESM-___-60A-S2245
Fuse Coordination
Contactor SizeMax. Starter FLC[A]
The following tables list Type I and Type II Fuse Coordination when used in
conjunction with Bulletin 100-C & 100-D and Bulletin 500 NEMA Size 00… 2
Contactors.
ATT EN TI ON : Select the motor branch circuit protection that complies with the
NEC and any other governing regional or local codes.
Max. Available Fault
Current [A]
100,000
Max. Voltage
[V]
600—20
2403030
6003030
24060100
6003050
240100200
60060100
Max. UL Fuse [A]
RJ
42Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring Chapter 2
Table 11 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors per
EN60947-4-1
Overload Relay using
Sensing Module Cat. No.
193-ESM-___-30A-C23
193-ESM-___-30A-C55,
193-ESM-___-60A-C55
Contactor Cat.
No.
100-C099
100-C12122020
100-C16163030
100-C2323
100-C30305050
100-C37375050
100-C43437070
100-C55558080
Max. Starter
FLC[A]
Prospective Short-Circuit
Current, Ir [A]
1000
3000
Conditional Short-
Circuit Current, Iq [A]
100,000600
Max. Voltage
[V]
Type I C lass J or
CC Fuse [A]
2015
4040
Type II Class J
or CC Fuse [A]
Table 12 - Type 1 and Type II fuse coordination with Bul. 100-C and 100-D contactors
per EN60947-4-1
Overload Relay using Sensing
Module Cat. No.
592-ESM-___-30A-S2018
592-ESM-___-30A-S21273030
592-ESM-___-60A-S22456060
Contactor SizeMax. Starter FLC[A]
Prospective Short-
Circuit Current, Ir [A]
3000100,000600
Conditional Short-
Circuit Current, Iq
[A]
Max. Voltage
[V]
Type I C lass J
Fuse [A]
3030
Type II Class J
Fuse [A]
Typical Motor Connections
ATT EN TI ON : When working on energized circuits, DO NOT rely on voltage and
current information provided by the E300 Electronic Overload Relay for personal
safety. Always use a portable voltage or current measurement device to
measure the signal locally.
Three-Phase Direct On-Line (DOL) & Single-Phase Full Voltage
The following wiring diagram illustrates the E300 Electronic Overload Relay
typical motor connections in a three-phase DOL and Single-Phase Full Voltage
applications.
Rockwell Automation Publication 193-UM015B-EN-P - June 201443
Chapter 2 Installation and Wiring
Figure 33 - E300 DOL and Single-Phase Full Voltage Connections
Three-Phase Direct-On-Line
S.C.P.D.
L1
2/T1
T1T2T3
L2
E300
4/T2
M
L3
6/T3
Single-Phase Full-Voltage
S.C.P.D.
L1
2/T1
T1
E300
T2
M
L2
4/T2
6/T3
External Line Current
Transformer Application
Current Transformer Ratio
The following E300 Electronic Overload Relay sensing module catalog numbers
can be used with step down current transformers:
• 193-
• 193-ESM-IG-30A-T
• 193-ESM-IG-30A-P
• 193-ESM-I-30A-E3T
• 193-ESM-I-30A-T
• 193-ESM-I-30A-P
• 193-ESM-VIG-30A-CT
CT Primary (Parameter 263) and CT Secondary (Parameter 264) allows the user
to identify the turns ratio of the step down current transformers in use. The E300
Electronic Overload Relay will automatically adjust the measured current based
on these two configuration parameters. Users will use the primary current for
their FLA settings.
Table 13 - CT Primary (Parameter 263)
CT Primary (Parameter 263)
Default Value5
Minimum Value1
Maximum Value65535
ESM-IG-30A-E3T
44Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Param eter TypeUINT
IMPORTANT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Table 14 - CT Secondary (Parameter 264)
CT Secondary (Parameter 264)
Default Value5
Minimum Value1
Maximum Value65535
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
ATT EN TI ON : Improper configuration of the CT Ratio parameters can result in
the E300 Electronic Overload Relay reporting inaccurate motor operational data
and possible motor damage.
Installation and Wiring Chapter 2
The E300 Electronic Overload Relay will trip on a configuration fault when the
FLA setting is outside of the legal range of the selected CT Ratio settings. The
TRIP/WARN LED status indicator will flash red 3-long, 8-short blinking pattern.
The installer shall (1) provide one CT for each motor phase and shall (2) connect
the CT’s secondary leads to the appropriate sensing module power terminals.
The CTs shall be selected to be capable of providing the required VA to the
secondary load, which includes the E300 Sensing Module burden of 0.1 VA at
the rated secondary current and the wiring burden. Finally, the CT shall (1) be
rated for Protective Relaying to accommodate the high inrush currents associated
with motor startup and shall (2) have an accuracy of ≤±2% over its normal
operating range. Typical CT ratings include:
• ANSI USA
• CSA (Canada)
• IEC (Europe)
• Class C5 BO.1
• Class 10L5
• 5 VA Class SP10
ATT EN TI ON : The improper selection of a current transformer can result in the
E300 Electronic Overload Relay reporting inaccurate motor operational data and
possible motor damage. The selected current transformer must be rated for
protective relaying applications.
Rockwell Automation Publication 193-UM015B-EN-P - June 201445
Chapter 2 Installation and Wiring
NEMA
L1L2
L3
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
M
T1
T2
T3
IEC
L1L2
L3
K1
L1/1 L2/3 L3/5
T1/2 T2/4 T3/6
E300
M
Primary
Current
Transformers
Primary
Current
Transformers
E300
Figure 34 - External Current Transformer Connection
The E300 Electronic Overload Relay voltage based sensing modules support a
wide variety of power systems. Listed below are the power systems supported by
the specific sensing module.
Table 15 - Supported Power Systems
Catalog NumberConnection TypePower System
Single Phase
193-ESM-VIG-__-__
592-ESM-VIG-__-__
193-ESM-VIG-30A-CT
Direct
Direct
3 PT
2 PT
Delta
Wye
Grounded B Phase Delta
Single Phase
Delta
Wye
Grounded B Phase Delta
Delta
Wye
Single Phase
Open Delta
Voltage Mode
Voltage Mode (Parameter 252) determines the method for how voltage is
monitored E300 Electronic Overload Relay. The user selects the connection type
for the appropriate power system.
46Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Installation and Wiring Chapter 2
Table 16 - Voltage Mode (Parameter 352)
Default Value0 = Delta direct or with PTs
0 = Delta direct or with PTs
1 = Wye direct or with PTs
Range
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
Units
2 = Delta with Delta to Wye PTs
3 = Wye with D elta to Wye PTs
4 = Delta with Wye to Delta PTs
5 = Wye with Wye to De lta PTs
Potential (Voltage) Transformer Ratio
The E300 Electronic Overload Relay sensing module catalog number 193-ESMVIG-30A-CT can be used with step down potential (voltage) transformers. PT
Primary (Parameter 353) and PT Secondary (Parameter 354) allows the user to
identify the turns ratio of the step down potential (voltage) transformers in use.
The E300 Electronic Overload Relay will automatically adjust the measured
voltage based on these two configuration parameters. Users will use the primary
voltage for their voltage protection settings.
Table 17 - PT Primary (Parameter 353)
Default Value480
Minimum Value1
Maximum Value65535
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Table 18 - PT Secondary (Parameter 354)
Default Value480
Minimum Value165535
Maximum Value
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsAmps
Rockwell Automation Publication 193-UM015B-EN-P - June 201447
Chapter 2 Installation and Wiring
Control Circuits
ATT EN TI ON : Do not exceed the ratings of the E300 Electronic Overload Relay’s
output and trip relay. If the coil current or voltage of the contactor exceeds the
overload relay’s ratings, an interposing relay must be used.
ATT EN TI ON : When the power is applied to the E300 Electronic Overload Relay’s
A1 and A2 terminals, the N.O. relay contact assigned as a Trip Relay will close
after approximately 2 seconds if no trip condition exists.
ATT EN TI ON : Additional control circuit protection may be required. Refer to the
applicable electrical codes.
The E300 Electronic Overload relay is capable of providing motor control logic
for many different type of motor starters (refer to Chapter 4 for more
information on Operating Modes). By default, the E300 is configured for the
Overload-Network operating mode in which Relay 0 (terminals R03 and R04) is
configured to be a normally closed Trip Relay. The following wiring diagrams are
typical control circuits for Non-Reversing and Reversing Motor starters that use
the Overload-Network operating mode.
Rockwell Automation Publication 193-UM015B-EN-P - June 201449
Chapter 2 Installation and Wiring
Figure 38 - CENELEC Nomenclature
L1
Relay 0
Configured as a
Trip Relay
R03
2
R04
Relay 1
K2
R13
R14
Relay 2
R23
R24
K1
A1A1
K1
A2
N
K2
A2
2
Contact shown with supply voltage applied.
50Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration
Chapter 3
Introduction
Device Modes
This chapter provides instructions for operating and configuring an E300
Electronic Overload Relay system. Settings for Device Modes, Option Match,
Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an
introduction to Operating Modes are included in this chapter.
The E300 Electronic Overload Relay has five device modes to validate
configuration of the device and limit when a user can configure the E300
Electronic Overload Relay, perform a firmware update, and issue commands.
• Administration Mode
• Operation Mode
• Run Mode
• Te st Mo de
• Invalid Configuration Mode
Administration Mode
Administration Mode is a maintenance mode for the E300 Electronic Overload
Relay which allows users to configure parameters, modify security policies, enable
web servers (see page 286
firmware upgrades, and issue commands.
to enable the EtherNet/IP web server), perform
Follow these steps to enter into Administration Mode:
1. Set the rotary dials on the E300 Communication Module to the following
values
– For EtherNet/IP set the rotary dials to 0-0-0
– For DeviceNet set the rotary dials to 7-7
2. Cycle power on the E300 Electronic Overload Relay
Af
ter commissioning activities and maintenance tasks are completed, return the
E300 Ele
rotary dials of the E300 communication module back to its previous positions
and cycle power.
Rockwell Automation Publication 193-UM015B-EN-P - June 201451
ctronic Overload Relay back to Operation or Run Mode by setting the
Chapter 3 System Operation and Configuration
Bit
1514131211109876543210Function
Operation Mode
Operation Mode is a standby mode for the E300 Electronic Overload Relay in
which the E300 is ready to protect an electric motor and no electrical current has
been detected. Users can modify configuration parameters, upgrade firmware,
and issue commands if the appropriate security policies are enabled. The Power
LED on the Communication Module and Operator Stations will be flashing
green and bit 14 in Device Status 0 (Parameter 20) is set to 1 when the device is in
Operation Mode.
Table 19 - Operation Mode Bit Function Detail — Device Status 0 (Parameter 20)
X Trip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
Run Mode
Run Mode is an active mode for the E300 Electronic Overload Relay in which
the E300 is sensing electrical current and is actively protecting an electric motor.
Only non-motor protection configuration parameters can be modified if the
appropriate security policies are enabled. The Power LED on the
Communication Module and Operator Stations will be solid green and bits 3, 4,
and/or 5 in Device Status 0 (Parameter 20) are set to 1 when the device is in Run
Mode.
52Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Table 20 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20)
Bit
1514131211109876543210Function
X Trip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
Test Mode
Test Mode is used by installers of motor control centers who are testing and
commissioning motor starters with an automation system. A digital input of the
E300 Electronic Overload Relay is assigned to monitor the motor control center
enclosure’s Test Position. The Input Assignments (Parameters 196-201) are
described later in this chapter.
Users commissioning motor starters in an automation system can put their motor
control center enclosure into the Test Position to activate Test Mode and verify
that the digital inputs and relay outputs of the E300 Electronic Overload Relay
are operating properly with the motor starter without energizing power to the
motor. If the E300
Electronic Overload Relay senses current or voltage in Test
Mode, the E300 Electronic Overload Relay will generate a Test Mode Trip.
Invalid Configuration Mode
Invalid Configuration Mode is an active mode for the E300 Electronic Overload
Relay in which the E300 is in a tripped state due to invalid configuration data.
Invalid Configuration Parameter (Parameter 38) indicates the parameter number
that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies
the reason for Invalid Configuration Mode.
Rockwell Automation Publication 193-UM015B-EN-P - June 201453
Chapter 3 System Operation and Configuration
Bit
1514131211109876543210Function
Table 21 - Invalid Configuration Cause (Parameter 39)
CodeDescription
0No Error
1Value over maximum value
2Value under minimum value
3Illegal value
4L3 Current detected (for single-phase applications)
5CopyCat error
The Trip/Warn LED on the Communication Module and Operator Stations will
be flashing a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device
Status 0 (Parameter 20) are set to 1 when the device is in Invalid Configuration
Mode.
Table 22 - Invalid Configuration Mode Bit Function Detail — Device Status 0 (Parameter 20)
X Trip Present
XWarning Present
XInvalid Configuration
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved
To return to Operation/Run Mode, place a valid configuration value in the
parameter identified by Invalid Configuration Parameter (Parameter 38) and
Invalid Configuration Cause (Parameter 39). Reset the trip state of the E300
Electronic Overload Relay by pressing the blue reset button on the
Communication Module, via network communications, with the internal web
server of the EtherNet/IP communications module, or by an assigned digital
input.
Option Match
Due to the modular nature of the E300 Electronic Overload Relay, a user can
enable the Option Match feature to ensure that the options that were expected
for the motor protection application are the ones that are present on the E300
54Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Electronic Overload Relay system. Users can configure an option mismatch to
cause a protection trip or provide a warning within the E300.
Enable Option Match Protection Trip (Parameter 186)
To enable the E300 Electronic Overload Relay’s Option Match feature to cause a
protection trip in the event of an option mismatch, place a (1) in bit position 8 of
Parameter 186 (Control Trip Enable). Users can select the specific option match
features to cause a protection trip in Parameter 233 (Option Match Action).
Table 23 - Enable Option Match Protection Trip Bit Function Detail— Control Trip Enable
(Parameter 186)
Bit
1514131211109876543210Function
XTest Trip Enable
XPTC Trip Enable
XDeviceLogix Trip Enable
XOperator Station Trip Enable
XRemote Trip Enable
XBlocked Start Trip Enable
XHardware Fault Trip Enable
XConfiguration Trip Enable
XOption Match Trip Enable
XFeedback Timeout Trip Enable
XExpansion Bus Trip Enable
Reserved
Reserved
XNon-Volatile Memory Trip Enable
XReady
Reserved
Rockwell Automation Publication 193-UM015B-EN-P - June 201455
Chapter 3 System Operation and Configuration
Bit
1514131211109876543210Function
Enable Option Match Protection Warning (Parameter 192)
To enable the E300 Electronic Overload Relay’s Option Match feature to cause a
warning in the event of an option mismatch, place a (1) in bit position 8 of
Parameter 192 (Control Warning Enable). Users can select the specific option
match features to cause a warning in Parameter 233 (Option Match Action).
Table 24 - Enable Option Match Protection Warning Bit Function Detail— Control Warning
Enable (Parameter 192)
Reserved
Reserved
XDeviceLogix Warning Enable
Reserved
Reserved
Reserved
Reserved
Reserved
XOption Match Warning Enable
XFeedback Timeout Warning Enable
XExpansion Bus Warning Enable
XNumber Of Starts Warning Enable
XOperating Hours Warning Enable
Reserved
Control Module Type (Parameter 221)
The E300 Electronic Overload Relay offers six different control modules. Place
the value of the expected control module into Parameter 221. A value of (0)
disables the Option Match feature for the control module.
Table 25 - Control Module Type (Parameter 221)
Code DescriptionControl Module Cat. No.
0Ignore—
16 Inputs, 24V DC / 3 Relay Outputs193-EIO-63-24D
24 Inputs, 110-120V AC 50/60Hz / 3 Relay Outputs193-EIO-43-120
34 Inputs, 220-240V AC 50/60Hz / 3 Relay Outputs193-EIO-43-240
56Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Sensing Module Type (Parameter 222)
The E300 Electronic Overload Relay offers 12 different sensing modules. Place
the value of the expected sensing module into Parameter 222. A value of (0)
disables the Option Match feature for the sensing module.
Table 26 - Sensing Module Type (Parameter 222)
CodeDescriptionSensing Module Cat. No.
0Ignore—
1Voltage / Current 0.5…30 A / Ground Fault193-ESM-VIG-30A-__ or 592-ESM-VIG-30A-__
2Voltage / Current 6…60 A / Ground Fault193-ESM-VIG-60A-__ or 592-ESM-VIG-60A-__
3Voltage / Current 10…100 A / Ground Fault 193-ESM-VIG-100A-__ or 592-ESM-VIG-100A-__
4Voltage / Current 20…200 A / Ground Fault193-ESM-VIG-200A-__ or 592-ESM-VIG-200A-__
5Current 0.5…30 A / Ground Fault 193-ESM-IG-30A-__ or 592-ESM-IG-30A-__
6Current 6…60 A / Ground Fault 193-ESM-IG-60A-__ or 592-ESM-IG-60A-__
7Current 10…100 A / Ground Fault 193-ESM-IG-100A-__ or 592-ESM-IG-100A-__
8Current 20…200 A / Ground Fault193-ESM-IG-200A-__ or 592-ESM-IG-200A-__
9Current 0.5…30 A 193-ESM-I-30A-__ or 592--ESM-I-30A-__
10 Current 6…60 A193-ESM-I-60A-__ or 592--ESM-I-60A-__
11Current 10…100 A 193-ESM-I-100A-__ or 592--ESM-I-100A-__
12Current 20…200 A193-ESM-I-200A-__ or 592--ESM-I-200A-__
Communication Module Type (Parameter 223)
The E300 Electronic Overload Relay offers two different communication
modules. Place the value of the expected communication module into Parameter
223. A value of (0) disables the Option Match feature for the communication
module.
Table 27 - Communication Module Type (Parameter 223)
CodeDescriptionCommunication Module Cat. No.
0Ignore—
1EtherNet/IP with Dual Port Switch supporting DLR 193-ECM-ETR
2DeviceNet193-ECM-DNT
Rockwell Automation Publication 193-UM015B-EN-P - June 201457
Chapter 3 System Operation and Configuration
Operator Station Type (Parameter 224)
The E300 Electronic Overload Relay offers two different types of operator
stations. Place the value of the expected operator station into Parameter 224. A
value of (0) disables the Option Match feature for the operator station. A value of
(1), “No Operator Station”, makes the operator station not available to the
Expansion Bus and prevents a user from connecting an operator station to the
E300 Electronic Overload Relay system.
Table 28 - Operator Station Type (Parameter 224)
CodeDescriptionOperator Station Cat. No.
0Ignore—
1No Operator Station (Operator Station Not Available)—
2Control Station193-EOS-SCS
3Diagnostic Station with LCD 193-EOS-SDS
Digital I/O Expansion Module 1 Type (Parameter 225)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module at Digital Module Address 1. There are three
different types of Digital I/O expansion modules. Place the value of the expected
Digital I/O expansion module at Digital Module Address 1 into Parameter 225.
A value of (0) disables the Option Match feature for this Digital I/O expansion
module. A value of (1), “No Digital I/O Expansion Module at Digital Module Address 1”, makes the Digital I/O expansion module at Digital Module Address 1
not available to the Expansion Bus and prevents a user from connecting a Digital
I/O expansion module at Digital Module Address 1 to the E300 Electronic
Overload Relay system.
Table 29 - Digital I/O Expansion Module 1 Type (Parameter 225)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Available)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
58Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Digital I/O Expansion Module 2 Type (Parameter 226)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module at Digital Module Address 2. There are three
different types of Digital I/O expansion modules. Place the value of the expected
Digital I/O expansion module at Digital Module Address 2 into Parameter 226.
A value of (0) disables the Option Match feature for this Digital I/O expansion
module. A value of (1),“No Digital I/O Expansion Module at Digital Module Address 2”, makes the Digital I/O expansion module at Digital Module Address 2
not available to the Expansion Bus and prevents a user from connecting a Digital
I/O expansion module at Digital Module Address 2 to the E300 Electronic
Overload Relay system.
Table 30 - Digital I/O Expansion Module 2 Type (Parameter 226)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Available)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
Digital I/O Expansion Module 3 Type (Parameter 227)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module at Digital Module Address 3. There are three
different types of Digital I/O expansion modules. Place the value of the expected
Digital I/O expansion module at Digital Module Address 3 into Parameter 227.
A value of (0) disables the Option Match feature for this Digital I/O expansion
module. A value of (1),“No Digital I/O Expansion Module at Digital Module Address 3”, makes the Digital I/O expansion module at Digital Module Address 3
not available to the Expansion Bus and prevents a user from connecting a Digital
I/O expansion module at Digital Module Address 3 to the E300 Electronic
Overload Relay system.
Table 31 - Digital I/O Expansion Module 3 Type (Parameter 227)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Available)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
Rockwell Automation Publication 193-UM015B-EN-P - June 201459
Chapter 3 System Operation and Configuration
Digital I/O Expansion Module 4 Type (Parameter 228)
The E300 Electronic Overload Relay supports up to four additional Digital I/O
expansion modules. This parameter configures the Option Match feature for the
Digital I/O expansion module at Digital Module Address 4. There are three
different types of Digital I/O expansion modules. Place the value of the expected
Digital I/O expansion module at Digital Module Address 4 into Parameter 228.
A value of (0) disables the Option Match feature for this Digital I/O expansion
module. A value of (1), “No Digital I/O Expansion Module at Digital Module Address 4”, makes the Digital I/O expansion module at Digital Module Address 4
not available to the Expansion Bus and prevents a user from connecting a Digital
I/O expansion module at Digital Module Address 4 to the E300 Electronic
Overload Relay system.
Table 32 - Digital I/O Expansion Module 4 Type (Parameter 228)
No Digital I/O Expansion Module (Digital I/O Expansion
1
Module Not Available)
24 Inputs, 24V DC / 2 Relay Outputs193-EXP-DIO-42-24D
34 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
44 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs193-EXP-DIO-42-240
—
Analog I/O Expansion Module 1 Type (Parameter 229)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module at Analog Module Address 1. There are three
different types of Analog I/O expansion modules. Place the value of the expected
Analog I/O expansion module at Analog Module Address 1 into Parameter 229.
A value of (0) disables the Option Match feature for this Analog I/O expansion
module. A value of (1), “No Analog I/O Expansion Module at Analog Module Address 1”, makes the Analog I/O expansion module at Analog Module Address 1
not available to the Expansion Bus and prevents a user from connecting a Analog
I/O expansion module at Analog Module Address 1 to the E300 Electronic
Overload Relay system.
Table 33 - Analog I/O Expansion Module 1 Type (Parameter 229)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Available)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
60Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Analog I/O Expansion Module 2 Type (Parameter 230)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module at Analog Module Address 2. There are three
different types of Analog I/O expansion modules. Place the value of the expected
Analog I/O expansion module at Analog Module Address 2 into Parameter 230.
A value of (0) disables the Option Match feature for this Analog I/O expansion
module. A value of (1), “No Analog I/O Expansion Module at Analog Module Address 2”, makes the Analog I/O expansion module at Analog Module Address 2
not available to the Expansion Bus and prevents a user from connecting a Analog
I/O expansion module at Analog Module Address 2 to the E300 Electronic
Overload Relay system.
Table 34 - Analog I/O Expansion Module 2 Type (Parameter 230)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Available)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
Analog I/O Expansion Module 3 Type (Parameter 231)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module at Analog Module Address 3. There are three
different types of Analog I/O expansion modules. Place the value of the expected
Analog I/O expansion module at Analog Module Address 3 into Parameter 231.
A value of (0) disables the Option Match feature for this Analog I/O expansion
module. A value of (1), “No Analog I/O Expansion Module at Analog Module Address 3”, makes the Analog I/O expansion module at Analog Module Address 3
not available to the Expansion Bus and prevents a user from connecting a Analog
I/O expansion module at Analog Module Address 3 to the E300 Electronic
Overload Relay system.
Table 35 - Analog I/O Expansion Module 3 Type (Parameter 231)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Available)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
Rockwell Automation Publication 193-UM015B-EN-P - June 201461
Chapter 3 System Operation and Configuration
Analog I/O Expansion Module 4 Type (Parameter 232)
The E300 Electronic Overload Relay supports up to four additional Analog I/O
expansion modules. This parameter configures the Option Match feature for the
Analog I/O expansion module at Analog Module Address 4. There are three
different types of Analog I/O expansion modules. Place the value of the expected
Analog I/O expansion module at Analog Module Address 4 into Parameter 232.
A value of (0) disables the Option Match feature for this Analog I/O expansion
module. A value of (1), “No Analog I/O Expansion Module at Analog Module Address 4”, makes the Analog I/O expansion module at Analog Module Address 4
not available to the Expansion Bus and prevents a user from connecting a Analog
I/O expansion module at Analog Module Address 4 to the E300 Electronic
Overload Relay system.
Table 36 - Analog I/O Expansion Module 4 Type (Parameter 232)
No Analog I/O Expansion Module (Analog I/O Expansion
1
Module Not Available)
23 Universal Analog Inputs / 1 Analog Output193-EXP-AIO-31
—
Option Match Action (Parameter 233)
The Option Match feature for the E300 Electronic Overload Relay allows the
user to specify an action when there is an option mismatch – Protection Trip or
Warning. Place a (0) in the appropriate bit position for a warning, and place a
(1) in the appropriate bit position to cause a protection trip if there is an option
mismatch.
Table 37 - Option Match Action (Parameter 233) Bit Function Detail
Bit
1514131211109876543210Function
XControl Module Mismatch Action
XSensing Module Mismatch Action
X
XOperator Station Mismatch Action
XDigital Module 1 Mismatch Action
XDigital Module 2 Mismatch Action
XDigital Module 3 Mismatch Action
XDigital Module 4 Mismatch Action
XAnalog Module 1 Mismatch Action
XAnalog Module 2 Mismatch Action
XAnalog Module 3 Mismatch Action
XAnalog Module 4 Mismatch Action
Communication Module Mismatch
Action
62Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Security Policy
The E300 Electronic Overload Relay has a security policy that can be used to
prevent users with malicious intent to potentially damage a motor or piece of
equipment. By default, the user can only modify the security policy when the
E300 Electronic Overload Relay is in Administration Mode (see page 51
how to enable Administration Mode).
Table 38 - Security Policy (Parameter 211) Bit Function Detail
Bit
1514131211109876543210Function
XDevice Configuration Enable
XDevice Reset Enable
XFirmware Update Enable
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
XSecurity Policy Config Enable
to learn
Device Configuration Policy
The Device Configuration Policy allows users to send external message
instructions via a communications network to write values to configuration
parameters. When this policy is disabled, all external message instructions with
configuration data will return a communications error when the E300 Electronic
Overload Relay is in Operation Mode or Run Mode.
Device Reset Policy
The Device Reset Policy allows users to send external message instruction via a
communications network to perform a soft device reset when the E300
Electronic Overload Relay is in Operation Mode. When this policy is disabled,
all external reset message instructions will return a communications error when
the E300 Electronic Overload Relay is in Operation Mode or Run Mode.
Rockwell Automation Publication 193-UM015B-EN-P - June 201463
Chapter 3 System Operation and Configuration
Firmware Update Policy
The Firmware Update Policy allows users to update the internal firmware of the
communication module and control module via ControlFlash when the E300
Electronic Overload Relay is in Operation Mode. When this policy is disabled,
firmware updates will return a communications error when the E300 Electronic
Overload Relay is in Operation Mode or Run Mode.
Security Configuration Policy
The Security Configuration Policy allows users to modify the Security Policy of
the E300 Electronic Overload Relay in Operation Mode. When this policy is
disabled, the Security Policy can only be modified when the E300 Electronic
Overload Relay is in Administration Mode.
I/O Assignments
The E300 Electronic Overload Relay has native digital inputs and relay outputs
in the Control Module. This I/O can be assign to dedicated functions. Listed
below are the function assignments for the available Control Module I/O.
Input Pt00 Assignment (Parameter 196)
Input Pt00 Assignment (Parameter 196) allows the user to assign this digital
input for the following functions:
Table 39 - Input Pt00 Assignment (Parameter 196)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss ArmActivate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current based
protection algorithms
64Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Input Pt01 Assignment (Parameter 197)
Input Pt01 Assignment (Parameter 197) allows the user to assign this digital
input for the following functions:
Table 40 - Input Pt01 Assignment (Parameter 197)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms
Input Pt02 Assignment (Parameter 198)
Input Pt02 Assignment (Parameter 198) allows the user to assign this digital
input for the following functions:
Table 41 - Input Pt02 Assignment (Parameter 198)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms
Rockwell Automation Publication 193-UM015B-EN-P - June 201465
Chapter 3 System Operation and Configuration
Input Pt03 Assignment (Parameter 199)
Input Pt03 Assignment (Parameter 199) allows the user to assign this digital
input for the following functions:
Table 42 - Input Pt03 Assignment (Parameter 199)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms
Input Pt04 Assignment (Parameter 200)
Input Pt04 Assignment (Parameter 200) allows the user to assign this digital
input for the following functions:
Table 43 - Input Pt04 Assignment (Parameter 200)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Star t command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms
66Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Input Pt05 Assignment (Parameter 201)
Input Pt05 Assignment (Parameter 201) allows the user to assign this digital
input for the following functions:
Table 44 - Input Pt05 Assignment (Parameter 201)
ValueAssignmentDescription
0NormalFunction as a digital input
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
6Test ModeEnable Test Mode monitoring
7L1 Line Loss ArmActivate L1 Line Loss Protection
8L2 Line Loss ArmActivate L2 Line Loss Protection
9L3 Line Loss ArmActivate L3 Line Loss Protection
10L1 L2 Line Loss ArmActivate L1 and L2 Line Loss Protection
11L2 L3 Line Loss ArmActivate L2 and L3 Line Loss Protection
12L1 L3 Line Loss ArmActivate L1 and L3 Line Loss Protection
13L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Use the value in FLA2 Setting (Parameter 177) for the current based protection
algorithms
Rockwell Automation Publication 193-UM015B-EN-P - June 201467
Chapter 3 System Operation and Configuration
Output Pt00 Assignment (Parameter 202)
Output Pt00 Assignment (Parameter 202) allows the user to assign this relay
output for the following functions:
Table 45 - Output Pt00 Assignment (Parameter 202)
ValueAssignmentDescription
0NormalFunction as a relay output
1Trip Relay
2Control Relay
3Trip Alarm
4Warning Alarm
Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.
Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.
Output Pt01 Assignment (Parameter 203)
Output Pt01 Assignment (Parameter 203) allows the user to assign this relay
output for the following functions:
Table 46 - Output Pt01 Assignment (Parameter 203)
ValueAssignmentDescription
0NormalFunction as a relay output
1Trip Relay
2Control Relay
3Trip Alarm
4Warning Alarm
Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.
Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.
68Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Output Pt02 Assignment (Parameter 204)
Output Pt02 Assignment (Parameter 204) allows the user to assign this relay
output for the following functions:
Table 47 - Output Pt02 Assignment (Parameter 204)
ValueAssignmentDescription
0NormalFunction as a relay output
1Trip Relay
2Control Relay
3Trip Alarm
4Warning Alarm
Function as a normally closed contact until the E300 is in a tripped state in which the relay
opens. The Trip Relay remains open until a trip reset is issued.
Function as a combination Normal and Trip Relay. The Control Relay is in a normally open
state until the relay is commanded to close by communications or via a DeviceLogix
program. When the E300 enters into a tripped state the Control Relay opens and remains
open until a trip reset is issued.
Function as a normally open contact until the E300 is in a tripped state in which the relay
closes. The Trip Alarm remains closed until a trip reset is issued.
Function as a normally open contact until the E300 is in a protection warning state in which
the relay closes. The Warning Alarm remains closed until the protection warning clears.
Activate FLA2 with Output Relay (Parameter 209)
Expansion Bus Fault
Activate FLA2 with Output Relay (Parameter 209) allows a user to activate the
value in FLA2 Setting (Parameter 177) for the current based protection
algorithms when the assigned output relay is in an energized state.
Table 48 - Activate FLA2 with Output Relay (Parameter 209)
ValueDescription
0Disable
1Pt00 Output
2Pt01 Output
3Pt02 Output
The E300 Electronic Overload Relay’s expansion bus can be used to expand the
I/O capabilities of the E300 Electronic Overload Relay with the addition of
digital and analog expansion I/O modules. The Expansion Bus Fault allows a user
to have the E300 Electronic Overload Relay go into a Trip or Warning state when
established Expansion Bus communications is disrupted between the Control
Module and any digital and analog expansion I/O modules.
The Expansion Bus Fault is used when the Option Match feature is not enabled
for the digital and/or analog expansion I/O modules. The Expansion Bus Fault
only monitors for communication disruptions between the Control Module and
digital and/or analog expansion I/O modules. Expansion bus communication
disruptions between the Control Module and Operator Station do not affect the
Expansion Bus fault.
Rockwell Automation Publication 193-UM015B-EN-P - June 201469
Chapter 3 System Operation and Configuration
Bit
1514131211109876543210Function
Expansion Bus Trip
Expansion Bus Trip is enabled by setting Control Trip Enable (Parameter 186)
bit 10 to 1. When communications is disrupted between the Control Module
and digital and/or analog expansion I/O modules, the E300 Electronic Overload
Relay will go into a tripped state in which the Trip/Warn LED on the
Communication Module and Operator station will blink a red 3 long and 11
short blinking pattern.
Table 49 - Expansion Bus Trip Bit Function Detail— Control Trip Enable (Parameter 186)
XTest Trip Enable
XPTC Trip Enable
XDeviceLogix Trip Enable
XOperator Station Trip Enable
XRemote Trip Enable
XBlocked Start Trip Enable
XHardware Fault Trip Enable
XConfiguration Trip Enable
XOption Match Trip Enable
XFeedback Timeout Trip Enable
XExpansion Bus Trip Enable
Reserved
Reserved
XNon-Volatile Memory Trip Enable
XReady
Reserved
To return to Operation/Run Mode, verify that the expansion bus cables are
properly plugged into the Bus In and Bus Out ports of all of the expansion
modules. When all of the expansion I/O modules’ status LEDs are solid green,
reset the trip state of the E300 Electronic Overload Relay by pressing the blue
reset button on the Communication Module, via network communications, with
the internal web server of the EtherNet/IP communications module, or by an
assigned digital input.
70Rockwell Automation Publication 193-UM015B-EN-P - June 2014
System Operation and Configuration Chapter 3
Expansion Bus Warning
Expansion Bus Warning is enabled by setting Control Warning Enable
(Parameter 192) bit 10 to 1. When communications is disrupted between the
Control Module and digital and/or analog expansion I/O modules, the E300
Electronic Overload Relay will go into a warning state in which the Trip/Warn
LED on the Communication Module and Operator station will blink a yellow 3
long and 11 short blinking pattern.
Table 50 - Expansion Bus Warning Bit Function Detail— Control Warning Enable (Parameter 192)
Bit
1514131211109876543210Function
Reserved
XP TC Warn ing En able
XDeviceLogix Warning Enable
XOperator Station Warning Enable
Reserved
Reserved
Reserved
Reserved
XOption Match Warning Enable
XFeedback Timeout Warning Enable
XExpansion Bus Warning Enable
XNumber Of Starts Warning Enable
XOperating Hours Warning Enable
Reserved
Emergency Start
To return to Operation/Run Mode, verify that the expansion bus cables are
properly plugged into the Bus In and Bus Out ports of all of the expansion
modules. When all of the expansion I/O modules’ status LEDs are solid green,
the warning state of the E300 Electronic Overload Relay will automatically clear.
In an emergency, it may be necessary to start a motor even if a protection fault or
a communication fault exists. The trip condition may be the result of a thermal
overload condition or the number of starts exceeded its configuration. These
conditions can be overridden using the Emergency Start feature of the E300
Electronic Overload Relay.
To enable the Emergency Start feature in the E300 Electronic Overload Relay set
the Emergency Start Enable (Parameter 216) to Enable.
Table 51 - Emergency Start (Parameter 216)
ValueDescription
0Disable
1Enable
Rockwell Automation Publication 193-UM015B-EN-P - June 201471
Chapter 3 System Operation and Configuration
Configure one of the Ptxx Input Assignments (Parameters 196…201) to
Emergency Start and activate the corresponding digital input.
1Trip ResetReset the E300 when it is in a tripped state
2Remote TripForce a the E300 to go into a tripped state
3Activate FLA2
4Force SnapshotForce the E300 to update its Snapshot log
5Emergency StartIssue an Emergency Start command
Use the value in FLA2 Setting (Parameter 177) for the current based
protection algorithms
The user can also use a network command to activate the Emergency Start
feature. For the EtherNet/IP communications module, the user would set the
Emergency Start bit to 1 in Output Assembly 144. See EtherNet/IP
Communications on page 279 for more information on EtherNet/IP
communications.
When the Emergency Start feature is active, the following actions occur in the
E300 Electronic Overload Relay:
• Protection trips are ignored
• Output relays configured as Trip Relays are put into closed state
• Normal operation resumes with any Normal or Control Relay assigned
put relay
out
he Emergency Start Active bit is set to 1 in Device Status 0
• T
(Paramete
Table 53 - Emergency Start (Parameter 216) Bit Function Detail— Device Status 0 (Parameter 20)
r 20) bit 6
Bit
1514131211109876543210Function
XCurrent Present
XGFCurrent Present
XVoltage Present
XEmergency Start Enabled
XDeviceLogix Enabled
XFeedback Timeout Enabled
XOperator Station Present
XVoltage Sensing Present
XIntern Ground Fault Sensing Present
XExtern Ground Fault Sensing Present
XPTC Sensing
XReady
72Rockwell Automation Publication 193-UM015B-EN-P - June 2014
XTrip Present
XWarning Present
XInvalid Configuration
Reserved
System Operation and Configuration Chapter 3
Introduction to Operating
Modes
The E300 Electronic Overload Relay supports a number of Operating Modes,
which consist of configuration rules and logic to control typical full voltage
motor starters, including :
• Overload
• Non-Reversing Starter
• Reversing Starter
• Wye/Delta (Star/Delta) Starter
• Two-Speed Starter
• Monitor
The default Operating Mode (Parameter 195) for the E300 Electronic Overload
Relay is Overload (Network) in which the E300 Electronic Overload Relay
operates like a traditional overload relay and has one of the output relays assigned
as a Trip Relay. Users can use network commands to control the remaining
output relays that are assigned as Normal output relays. One output relay must be
assigned as a Trip Relay; otherwise, the E300 Electronic Overload Relay will go
into Invalid Configuration Mode and trip on a configuration trip. Operating
Modes on page 75 describes the functionality of all the available Operating
Modes for the E300 Electronic Overload Relay and their associated
configuration rules.
Rockwell Automation Publication 193-UM015B-EN-P - June 201473
Chapter 3 System Operation and Configuration
74Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Operating Modes
Chapter 4
Introduction
Overload (Network)
The E300™ Electronic Overload Relay supports up to 54 Operating Modes which
consist of configuration rules and logic to control typical full voltage motor
starters including :
verload
• O
• Non-Reversing Starter
• Reversing Starter
• Wye/Delta (Star/Delta) Starter
• Two Speed Starter
• Monitoring Device
is chapter explains the configuration rules, logic, and control wiring required
Th
for the
available Operating Modes (Parameter 195). Failure to follow the
configuration rules will cause the E300 Electronic Overload Relay to go into
Invalid Configuration Mode and trip the E300 Electronic Overload Relay on a
configuration trip.
The E300 Electronic Overload Relay’s default Operating Mode (Parameter 195)
is Overload (Network) in which the E300 Electronic Overload Relay operates as
a traditional overload relay with one output relay assigned as a normally closed
Trip Relay. Users can use network commands to control the remaining output
relays that are assigned as Normal output relays.
Rules
1. One output relay must be assigned as a Trip Relay. Set any of the Output
Ptxx Assignments (Parameters 202-204) to Trip Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
Wiring Diagram
The E300 Electronic Overload Relay is wired as a traditional overload relay with
one of the output relays configured as a normally closed Trip Relay. The example
below is a wiring diagram of a Non-Reversing Starter. Relay 0 is configured as a
Trip Relay, and Relay 1 is configured as a normally open Normal Relay which
receives commands from an automation controller to energize the contactor coil.
Rockwell Automation Publication 193-UM015B-EN-P - June 201475
Chapter 4 Operating Modes
Relay 1
Relay 0
Configured as a
Trip Relay
R13 R14
A1
A2
M
R03
R04
1
1
Contact shown with supply voltage applied.
Figure 39 - Wiring Diagram
Timing Diagram
Figure 40 - Timing Diagram
Trip Relay
Monitor (Custom)
Device
Status0.Trip
Present
Trip Reset
The E300 Electronic Overload Relay’s Monitor (Custom) Operating Mode
allows the user to use the E300 Electronic Overload Relay as a monitoring device.
No configuration rules apply in this operating mode if the motor protection
features are disabled.
Rules
1. If any protection trips are enabled (excluding Configuration, NVS, and
Hardware Fault trip), then set any of the Output Ptxx Assignments
(Parameters 202…204) to the appropriate value of Trip Relay, Control
Relay, Monitor Lx Trip Relay, or Monitor Lx Control Relay.
Wiring Diagram
76Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Not Applicable
Timing Diagram
Not Applicable
Protective Trip and Warning Functions
Chapter 5
Introduction
Current Based Protection
The purpose of this chapter is to provide detailed information regarding the
protective trip and warning functions of the E300Electronic Overload Relay.
The protective trip and warning functions are organized into five sections:
rrent Based
• Cu
• Vol ta ge B as ed
• Power Based
• Control Based
• Analog Based
is chapter explains the trip and warning protection features of the E300
Th
ctronic Overload Relay and the associated configuration parameters.
Ele
The E300 Electronic Overload Relay digitally monitors the electrical current
consumed by an electric motor. This electric current information is used for the
following protective trip and warning functions:
• Overload Trip/Warning
• Phase Loss Trip
• Ground Fault Trip/Warning
• Stall Trip
• Jam Trip/Warning
• Underload Trip/Warning
• Current Imbalance Trip/Warning
• Line Under Current Trip/Warning
• Line Over Current Trip/Warning
• Line Loss Trip/Warning
Rockwell Automation Publication 193-UM015B-EN-P - June 201477
Chapter 5 Protective Trip and Warning Functions
Bit
15 14 13 12 11 109876543210Function
X
Current Trip Enable (Parameter 183) and Current Warning Enable (Parameter
189) are used to enable the respective current based protective trip and warning
functions.
Table 54 - Current Trip Enable (Parameter 183)
X
Overload Trip
X
Phase Loss Trip
X
X
X
X
X
X
X
X
X
X
X
X
X
Ground Fault Trip
Stall Trip
Jam Trip
Underload Trip
Current Imbalance Trip
L1 Under Current Trip
L2 Under Current Trip
L3 Under Current Trip
L1 Over Current Trip
L2 Over Current Trip
L3 Over Current Trip
L1 Line Loss Trip
L2 Line Loss Trip
L3 Line Loss Trip
Table 55 - Current Warning Enable (Parameter 189)
Bit
15 14 13 12 11 109876543210Function
X
Overload Warning
Reserved
X
X
X
X
X
X
X
X
X
X
X
X
X
Ground Fault Warning
Reserved
Jam Warning
Underload Warning
Current Imbalance Warning
L1 Under Current Warning
L2 Under Current Warning
L3 Under Current Warning
L1 Over Current Warning
L2 Over Current Warning
L3 Over Current Warning
L1 Line Loss Warning
L2 Line Loss Warning
L3 Line Loss Warning
78Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
Current Trip Status (Parameter 4) and Current Warning Status (Parameter 10)
are used to monitor the respective current based protective trip and warning
functions.
Table 56 - Current Trip Status (Parameter 4)
Bit
15 14 13 12 11 109876543210Function
X
Overload Trip
X
Phase Loss Trip
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Ground Fault Current Trip
Stall Trip
Jam Trip
Underload Trip
Current Imbalance Trip
L1 Under Current Trip
L2 Under Current Trip
L3 Under Current Trip
L1 Over Current Trip
L2 Over Current Trip
L3 Over Current Trip
L1 Line Loss Trip
L2 Line Loss Trip
L3 Line Loss Trip
Table 57 - Current Warning Status (Parameter 10)
Bit
15 14 13 12 11 109876543210Function
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Overload Warning
Reserved
Ground Fault Warning
Reserved
Jam Warning
Underload Warning
Current Imbalance Warning
L1 Under Current Warning
L2 Under Current Warning
L3 Under Current Warning
L1 Over Current Warning
L2 Over Current Warning
L3 Over Current Warning
L1 Line Loss Warning
L2 Line Loss Warning
L3 Line Loss Warning
Rockwell Automation Publication 193-UM015B-EN-P - June 201479
Chapter 5 Protective Trip and Warning Functions
Overload Protection
The E300 Electronic Overload Relay provides overload protection through true
RMS current measurements of the individual phase currents of the connected
motor. Based on the highest current measured, the programmed FLA Setting,
and Trip Class, a thermal model that simulates the actual heating of the motor is
calculated. Percent Thermal Capacity Utilized (Parameter 1) reports this
calculated value and can be read via the communications network.
Overload Trip
The E300 Electronic Overload Relay will trip with an overload indication if:
• No trip currently exists
• Overload trip protection is enabled
• Current is present
• % Thermal Capacity Utilized reaches 100%
the E300 Electronic Overload Relay trips on an overload, the following will
If
occur
:
• The TRIP/WARN LED will flash a red short-1 blink pattern,
• Bit 0 in Current Trip Status (Parameter 4) will set to 1
• Bit 0 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
otection Fault state (if so programmed)
r
P
80Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)
Full Load Amps Setting
FLA (Parameter 171) is one of two parameters that affect the E300 Electronic
Overload Relay’s thermal capacity utilization algorithm. The installer enters the
motor’s full-load current rating into this parameter.
Table 58 - FLA (Parameter 171)
FLA (Parameter 171)
0.50 (0.5…30 A Sensing Modules)
Default Value
Minimum Value0.50
Maximum Value65535.00
Parameter TypeUDINT
Size (Bytes)4
Scaling Factor100
UnitsAmps
FLA2 (Parameter 177) is provided for programming the high-speed FLA value in
two-speed motor applications. Activating FLA2 is described in Chapter 3
6.00 (6…60 A Sensing Modules)
10.00 (10…100 A Sensing Modules)
20.00 (20…200 A Sensing Modules)
.
Rockwell Automation Publication 193-UM015B-EN-P - June 201481
Chapter 5 Protective Trip and Warning Functions
Table 59 - FLA2 (Parameter 177)
FLA2 (Parameter 177)
0.50 (0.5…30 A Sensing Modules)
Default Value
Minimum Value0.50
Maximum Value65535.00
Parameter TypeUDINT
Size (Bytes)4
Scaling Factor100
UnitsAmps
6.00 (6…60 A Sensing Modules)
10.00 (10…100 A Sensing Modules)
20.00 (20…200 A Sensing Modules)
USA & Canada Guidelines
• Motor Service Factor ≥ 1.15: For motors with a service factor rating of
1.15 or greater, program the FLA setting to the printed nameplate’s full
load current rating.
• Motor Service Factor < 1.15: For motors with a service factor rating less
th
an 1.15, program the FLA setting to 90% of the printed nameplate’s full
load current rating.
• Wye-Delta (Y-Δ) Applications: Follow the application’s service factor
in
structions, except divide the printed nameplate’s full-load current rating
by 1.73.
Outside USA & Canada Guidelines
• Maximum Continuous Rated (MCR) Motors: Program the FLA setting
to the printed nameplate’s full-load current rating.
• Star-Delta (Y-Δ) Applications: Follow the MCR instructions, except
divi
de the printed nameplate’s full-load current rating by 1.73.
Trip Class
Trip Class is the second of two parameters that affect the E300 Electronic
Overload Relay’s thermal capacity utilization algorithm. Trip class is defined as
the maximum time (in seconds) for an overload trip to occur when the motor’s
operating current is six times its rated current. The E300 Electronic Overload
Relay offers an adjustable trip class range of 5…30. The user enters the
applications trip class into Trip Class (Parameter 172).
Table 60 - Trip Class (Parameter 172)
Trip Class (Parameter 172)
Default Value10
Minimum Value5
Maximum Value30
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
Units
82Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
1
10
100
1000
100%1000%
Time (seconds)
Trip Class 5
Current (% FLA)
Trip Class 30
1
10
100
1000
10000
100%1000%
Current (% FLA)
Time (seconds)
1
10
100
1000
10000
100%
1000%
Trip Class 20
Time (seconds)
Current (% FLA)
1
10
100
1000
100%1000%
Time (seconds)
Trip Class 10
Current (% FLA)
Cold Trip
Hot Trip
Trip Curves
The following figures illustrate the E300 Electronic Overload Relay’s timecurrent characteristics for trip classes 5, 10, 20, and 30.
Rockwell Automation Publication 193-UM015B-EN-P - June 201483
Trip Class 10
Multiplier
Trip Class
Trip Class 10
Multiplier
Trip Class
Trip Class 10
Multiplier
Chapter 5 Protective Trip and Warning Functions
Automatic/Manual Reset
Overload Reset Mode (Parameter 173) allows the user to select the reset mode
for the E300 Electronic Overload Relay after an overload or thermistor (PTC)
trip. If an overload trip occurs and automatic reset mode is selected, the E300
Electronic Overload Relay will automatically reset when the value stored in %
Thermal Capacity Utilized (Parameter 1) falls below the value stored in
Overload Reset Level (Parameter 174). If manual reset mode is selected, the
E300 Overload Relay can be manually reset after the % Thermal Capacity
Utilized is less than the OL Reset Level.
Table 62 - Overload Reset Mode (Parameter 173)
Overload Reset Mode (Parameter 173)
Default Value0 = Manual
Minimum Value0 = Manual
Maximum Value1 = Automatic
Parameter TypeBOOL
Size (Bytes)1
Scaling Factor1
Units
Table 63 - Overload Reset Level (Parameter 174)
Overload Reset Level (Parameter 174)
Default Value75
Minimum Value0
Maximum Value100
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
Units%TCU
84Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
Overload Reset Level (Parameter 174) is adjustable from 1 to 100% TCU. The
following figures illustrate the typical overload reset time delay when Overload
Reset Level is set to 75% TCU.
Trip Class 5 Trip Class 10 Trip Class 20 Trip Class 30
Time to Reset in Seconds
ATT EN TI ON : In explosive environment applications, Overload Reset Mode
(Parameter 173) must be set to Manual.
ATT EN TI ON : In an explosive environment application Overload Reset Level
(Parameter 174) must be set as low as possible or in accordance with the motor
thermal time constant.
Overload Warning
The E300 Electronic Overload Relay will indicate an overload warning if:
• No warning currently exists
• Overload warning is enabled
• Current is present
• % Thermal Capacity Utilized is equal to or greater than Overload Warning
l
Leve
When the overload warning conditions are satisfied, the:
• TRIP/WARN LED status indicator will flash a yellow short-1 blink
ttern
pa
• Bit 0 in Current Warning Status (Parameter 10) will set to 1
Rockwell Automation Publication 193-UM015B-EN-P - June 201485
Chapter 5 Protective Trip and Warning Functions
• Bit 1 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as Warning Alarm will close
Ov
erload Warning Level (Parameter 175) can be used as an alert for an
imp
ending overload trip and is adjustable from 0…100% TCU.
Table 64 - Overload Warning Level (Parameter 175)
Overload Warning Level (Parameter 175)
Default Value85
Minimum Value0
Maximum Value100
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
Units%TCU
Time to Trip
When the measured motor current exceeds the trip rating of the E300 Electronic
Overload Relay, Overload Time to Trip (Parameter 2) indicates the estimated
time remaining before an overload trip occurs. When the measured current is
below the trip rating, the Overload Time to Trip value is reported as 9,999
seconds.
Table 65 - Overload Time to Trip (Parameter 2)
Overload Time to Trip (Parameter 2)
Default Value9999
Minimum Value0
Maximum Value9999
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsSec
Time To Reset
After an overload trip, the E300 Electronic Overload Relay will report the time
remaining until the device can be reset through Overload Time to Reset
(Parameter 3). When the % Thermal Capacity Utilized value falls to or below the
Overload Reset Level (Parameter 174), the Overload Time to Reset value will
indicate zero until the overload trip is reset. After an overload trip is reset, the
Overload Time to Reset value is reported as 0 seconds.
86Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
Table 66 - Overload Time to Reset (Parameter 3)
Overload Time to Reset (Parameter 3)
Default Value0
Minimum Value0
Maximum Value9999
Param eter TypeUINT
Size (Bytes)2
Scaling Factor1
UnitsSec
Non-Volatile Thermal Memory
The E300 Electronic Overload Relay includes a non-volatile circuit to provide
thermal memory. The time constant of the circuit corresponds to a Trip Class 20
setting. During normal operation, the thermal memory circuit is continuously
monitored and updated to accurately reflect the thermal capacity utilization of
the connected motor. If power is removed, the thermal memory of the circuit
decays at a rate equivalent to the cooling of a Trip Class 20 application. When the
power is re-applied, the E300 Electronic Overload Relay checks the thermal
memory circuit voltage to determine the initial value of % Thermal Capacity
Utilized (Parameter 1).
Phase Loss Protection
A high current imbalance, or phase failure, can be caused by defective contacts in
a contactor or circuit breaker, loose terminals, blown fuses, sliced wires, or faults
in the motor. When a phase failure exists, the motor can experience an additional
temperature rise or excessive mechanical vibration. This may result in a
degradation of the motor insulation or increased stress on the motor bearings.
Rapid phase loss detection helps to minimize the potential damage and loss of
production.
Phase Loss Inhibit Time
Phase Loss Inhibit Time (Parameter 239) allows the user to inhibit a phase loss
trip from occurring during the motor starting sequence. It is adjustable from
0…250 seconds.
Table 67 - Phase Loss Inhibit Time (Parameter 239)
Phase Loss Inhibit Time (Parameter 239)
Default Value0
Minimum Value0
Maximum Value250
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
UnitsSec
Rockwell Automation Publication 193-UM015B-EN-P - June 201487
Chapter 5 Protective Trip and Warning Functions
IMPORTANT
IMPORTANT
The phase loss inhibit timer starts after the maximum phase of load current
transitions from 0 A to 30% of the device’s minimum FLA Setting. The E300
Electronic Overload Relay does not begin monitoring for a phase loss condition
until the Phase Loss Inhibit Time expires.
Phase Loss Trip
The E300 Electronic Overload Relay will trip with a phase loss indication if:
• No trip currently exists
• Phase Loss Protection is enabled
• Current is Present
• Phase Loss Inhibit Time has expired
• Current Imbalance is equal to or greater than 100% for a time period
r
eater than the programmed Phase Loss Trip Delay
g
If the E300 Electronic Overload Relay trips on a phase loss, the:
• TRIP/WARN LED status indicator will flash a red short-2 blink pattern
• Bit 1 in Current Trip Status (Parameter 4) will set to 1
• Bit 0 of Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
r
otection Fault state (if so programmed)
P
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)
88Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
Phase Loss Trip Delay
Phase Loss Trip Delay (Parameter 240) allows the user to define the time period
for which a phase loss condition must be present before a trip occurs. It is
adjustable from 0.1…25.0 seconds.
Table 68 - Phase Loss Trip Delay (Parameter 240)
Phase Loss Trip Delay (Parameter 240)
Default Value1.0
Minimum Value0.1
Maximum Value25.0
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor10
UnitsSec
Ground Fault Current Protection
In isolated or high impedance-grounded systems, core-balanced current sensors
are typically used to detect low level ground faults caused by insulation
breakdowns or entry of foreign objects. Detection of such ground faults can be
used to interrupt the system to prevent further damage or to alert the appropriate
personnel to perform timely maintenance.
The E300 Electronic Overload Relay provides core-balanced ground fault
current detection capability, with the option of enabling Ground Fault Trip,
Ground Fault Warning, or both. The ground fault detection method and range
depends upon the catalog number of the E300 Sensing Module and Control
Module ordered.
Table 69 - Ground Fault Capabilities
Catalog NumberGround Fault Method
193-ESM-IG-__-__
592-ESM-IG-__-__
193-ESM-VIG-__-__
592-ESM-VIG-__-__
193-EIOGP-22-___
193-EIOGP-42-___
Internal0.5…5.0 A
External ➊0.02…5.0 A
Ground Fault Trip/Warning
Range
➊ One of the following Catalog Number 193-CBCT_ Core Balance Ground Fault Sensors must be used:
1 — Ø 20 mm window
2 — Ø 40 mm window
3 — Ø 65 mm window
4 — Ø 85 mm window
Rockwell Automation Publication 193-UM015B-EN-P - June 201489
Chapter 5 Protective Trip and Warning Functions
ATT EN TI ON : The E300 Electronic Overload Relay is not a ground fault circuit
interrupt or for personal protection as defined in Article 100 of the NEC.
ATT EN TI ON : The E300 Electronic Overload Relay is not intended to signal a
disconnecting means to open the faulted current. A disconnecting device must
be capable of interrupting the maximum available fault current of the system
on which it is used.
Ground Fault Type
The E300 Electronic Overload Relay has two options available to measure
ground fault current. Ground Fault Type (Parameter 241) allows the user to
select the internal option or the external option with the appropriate
measurement range.
Table 70 - Ground Fault Type (Parameter 241)
Ground Fault Type (Parameter 241)
Default Value1 = Internal 0.500…5.000 A
1 = Internal 0.500…5.000 A
2 = External 0.020…0.100 A
Range
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
Units
3 = External 0.100…0.500 A
4 = External 0.200…1.000 A
5 = External 1.000…5.000 A
Ground Fault Maximum Inhibit
Ground faults can quickly rise from low-level arcing levels to short circuit
magnitudes. A motor starting contactor may not have the necessary rating to
interrupt a high magnitude ground fault. In these circumstances it is desirable for
an upstream circuit breaker with the proper rating to interrupt the ground fault.
When enabled, Ground Fault Maximum Inhibit (Parameter 248), inhibits a
ground fault trip from occurring when the ground fault current exceeds the
maximum range of the core-balance sensor (approximately 6.5 A).
90Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
Table 71 - Overload Reset Level (Parameter 248)
Overload Reset Level (Parameter 248)
Default Value0 = Disable
Minimum Value0 = Disable
Maximum Value1 = Enable
Parameter TypeBOOL
Size (Bytes)1
Scaling Factor1
Units
Ground Fault Filter
An E300 Electronic Overload Relay has the capability to filter ground fault
currents for High Resistance Grounded (HRG) systems from its current-based
protection trip and warning functions which includes:
• Thermal Overload
• Current Imbalance
• Jam
• Stall
Ground Fault Filter is useful for smaller-sized motors that trip unexpectedly
The
due to
a controlled ground fault current that is significant relative to the current
draw of the electric motor. Ground Fault Filter (Parameter 131) allows the user
to enable this filter.
Table 72 - Ground Fault Filter (Parameter 247
Ground Fault Filter (Parameter 247)
Default Value0 = Disable
Minimum Value0 = Disable
Maximum Value1 = Enable
Parameter TypeBOOL
Size (Bytes)1
Scaling Factor1
Units
This filter only disables the effects of the ground fault current from the current
based motor protection trip and warning functions. Current-based diagnostic
data will be reported unfiltered when this feature is enabled.
Ground Fault Inhibit Time
Ground Fault Inhibit Time (Parameter 242) allows the user to inhibit a ground
fault trip and warning from occurring during the motor starting sequence and is
adjustable from 0…250 seconds. The ground fault inhibit time begins when the
Current Present (bit 3) or Ground Fault Current Present (bit 4) is set in Device
Status 0 (Parameter 20).
Rockwell Automation Publication 193-UM015B-EN-P - June 201491
Chapter 5 Protective Trip and Warning Functions
Bit
15 14 13 12 11 109876543210Function
X
X
X
X
X
X
X
X
X
X
X
XInternal Ground Fault Sensing
XExternal Ground Fault Sensing
X
X
Table 73 - Ground Fault Inhibit Time (Parameter 242
Ground Fault Inhibit Time (Parameter 242)
Default Value0
Minimum Value0
Maximum Value250
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
UnitsSec
Table 74 - Device Status 0 (Parameter 20)
Tri p Pr ese nt
War ning Pres ent
Invalid Configuration
Current Present
Ground Fault Current Present
Voltage Present
Emergency Start Enabled
DeviceLogix Enabled
Feedback Timeout Enabled
Operator Station Present
Voltage Sensing Present
Present
Present
PTC Sensing
Ready
Reserved
Ground Fault Trip
The E300 Electronic Overload Relay will trip with a ground fault indication if:
• No trip currently exists
• Ground fault protection is enabled
• Ground fault current is present
• Ground Fault Inhibit Time has expired
• Ground Fault Current is equal to or greater than the Ground Fault Trip
vel for a time period greater than the Ground Fault Trip Delay
Le
If the E300 Electronic Overload Relay trips on a ground fault, the:
RIP/WARN LED will flash a red 3-short blink pattern
• T
• Bit 2 in Current Trip Status (Parameter 4) will set to 1
92Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
IMPORTANT
• Bit 0 of Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
otection Fault state (if so programmed)
Pr
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)
Ground Fault Trip Delay
Ground Fault Trip Delay (Parameter 243) allows the user to define the time
period a ground fault condition must be present before a trip occurs and is
adjustable from 0.0…25.0 s.
Rockwell Automation Publication 193-UM015B-EN-P - June 201493
Ground Fault Trip Level (Parameter 244) allows the user to define the ground
fault current in which the E300 Electronic Overload Relay will trip and is
adjustable from:
The ground fault inhibit timer starts after the maximum phase load current
transitions from 0 A to 30% of the device’s minimum FLA rating or the ground
fault current is greater than or equal to 50% of the device’s minimum ground
fault current rating. The E300 Electronic Overload Relay does not begin
monitoring for a ground fault condition until the Ground Fault Current Inhibit
Time expires.
Ground Fault Warning
The E300 Electronic Overload Relay will indicate a ground fault warning if:
• No warning currently exists
• Ground Fault Warning is enabled
• Current is present
• Ground Fault Inhibit Time has expired
94Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
• Ground Fault Current is equal to or greater than the Ground Fault
Warning Level for a time period greater than the Ground Fault Warning
Delay.
When the ground fault warning conditions are satisfied, the:
RIP/WARN LED status indicator will flash a yellow 3-short blink
• T
pa
ttern
• Bit 2 in Current Warning Status (Parameter 10) will set to 1
• Bit 1 of Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Warning Alarm will close
Ground Fault Warning Level
Ground Fault Warning Level (Parameter 246) allows the user to define the
ground fault current at which the E300 Electronic Overload Relay will indicate a
warning and is adjustable from 0.20…5.00 A.
Ground Fault Warning Delay (Parameter 245) allows the user to define the time
period (adjustable from 0.0…25.0 s) for which a ground fault condition must be
present before a warning occurs.
Rockwell Automation Publication 193-UM015B-EN-P - June 201495
Chapter 5 Protective Trip and Warning Functions
Stall Protection
A motor stalls when its inrush current lasts for a longer than normal period of
time during its starting sequence. As a result, the motor heats up very rapidly and
reaches the temperature limit of its insulation. Rapid stall detection during the
starting sequence can extend the motor’s life, as well as minimize potential
damage and loss of production. The E300 Electronic Overload Relay can
monitor for this condition with its Stall Trip function and stop the motor before
damage and loss of production can occur.
Stall Trip
The E300 Electronic Overload Relay will trip with a Stall Trip indication when:
• No trip currently exists
• Stall protection is enabled
• Current is present
• The maximum phase current is greater than the Stall Trip Level for a time
riod greater than the Stall Enabled Time
pe
If the E300 Electronic Overload Relay trips on a stall, the:
• TRIP/WARN LED status indicator will flash a red 4-short blink pattern
• Bit 3 in Current Trip Status Parameter 4) will set to 1
• Bit 0 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
r
otection Fault state (if so programmed)
P
96Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
IMPORTANT
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)
Stall Enabled Time
Stall Enabled Time (Parameter 249) allows the user to adjust the time the E300
Electronic Overload Relay monitors for a stall condition during the motor
starting sequence and is adjustable from 0…250 s.
Table 79 - Stall Enabled Time (Parameter 249)
Stall Enabled Time (Parameter 249)
Default Value10
Minimum Value0
Maximum Value250
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
UnitsSec
Stall Trip Level
Stall Trip Level (Parameter 250) allows the installer to define the locked rotor
current and is adjustable from 100…600% of the FLA Setting (Parameter 171).
Rockwell Automation Publication 193-UM015B-EN-P - June 201497
Chapter 5 Protective Trip and Warning Functions
IMPORTANT
IMPORTANT
Table 80 - Stall Trip Level (Parameter 250)
Stall Trip Level (Parameter 250)
Default Value600
Minimum Value100
Maximum Value600
Parame ter TypeUINT
Size (Bytes)2
Scaling Factor1
Units%FLA
Stall Protection is only enabled during the motor starting sequence. If the
maximum phase of load current falls below the programmed Stall Trip Level
before the Stall Enabled Time elapses, the E300 Electronic Overload Relay
disables Stall Protection until the next motor starting sequence.
The E300 Electronic Overload Relay considers a motor to have begun its
starting sequence if the maximum phase of motor current transitions from 0A
to approximately 30% of the device’s minimum FLA Setting.
Jam Protection
A motor goes into a jam condition when a running motor begins to consume
current greater than50% of the motor’s nameplate rating. An example of this
condition could be an overloaded conveyor or jammed gear. These conditions
can result in the overheating of the motor and equipment damage. The E300
Electronic Overload Relay can monitor for this condition with its Jam Trip and
Warning function to detect for a rapid jam fault to minimize damage and loss of
production.
Jam Inhibit Time
Jam Inhibit Time (Parameter 251) allows the installer to inhibit a jam trip and
warning from occurring during the motor starting sequence. It is adjustable from
0…250 s.
Table81‐JamTripInhibitTi me(Parameter251)
Default Value10
Minimum Value0
Maximum Value250
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor1
UnitsSec
98Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Protective Trip and Warning Functions Chapter 5
IMPORTANT
Jam Trip
The E300 Electronic Overload Relay will trip with a jam indication if:
• No trip currently exists
• Jam Trip is enabled
• Jam Inhibit Time has expired
• The maximum phase current is greater than the Jam Trip Level for a time
riod greater than the Jam Trip Delay.
pe
If the E300 Electronic Overload Relay trips on a jam, the:
RIP/WARN LED status indicator will flash a red 5-short blink pattern
• T
• Bit 4 in Current Trip Status (Parameter 4) will set to 1
• Bit 0 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Trip Relay will open
• Any relay outputs configured as a Control Relay will open
• Any relay outputs configured as a Trip Alarm will close
• Any relay outputs configured as a Normal Relay will be placed in their
otection Fault state (if so programmed)
Pr
Jam Trip Delay
The Protection Fault State of Relay 0, Relay 1, Relay 2, Digital Module 1 Output
Relays, Digital Module 2 Output Relays, Digital Module 3 Output Relays, and
Digital Module 4 Output Relays are defined by the respective parameters:
• Output PT02 Protection Fault Value (Parameter 317)
• Output Digital Module 1 Protection Fault Action (Parameter 322)
• Output Digital Module 1 Protection Fault Value (Parameter 323)
• Output Digital Module 2 Protection Fault Action (Parameter 328)
• Output Digital Module 2 Protection Fault Value (Parameter 329)
• Output Digital Module 3 Protection Fault Action (Parameter 334)
• Output Digital Module 3 Protection Fault Value (Parameter 335)
• Output Digital Module 4 Protection Fault Action (Parameter 340)
• Output Digital Module 4 Protection Fault Value (Parameter 342)
Jam Trip Delay (Parameter 252) allows the installer to define the time period a
jam condition must be present before a trip occurs. It is adjustable from
0.1…25.0 s.
Rockwell Automation Publication 193-UM015B-EN-P - June 201499
Chapter 5 Protective Trip and Warning Functions
IMPORTANT
Table 82 - Jam Trip Delay (Parameter 252)
Default Value5.0
Minimum Value0.1
Maximum Value25.0
Parameter TypeUSINT
Size (Bytes)1
Scaling Factor10
UnitsSec
Jam Trip Level
Jam Trip Level (Parameter 253) allows the installer to define the current at which
the E300 Electronic Overload Relay will trip on a jam. It is user-adjustable from
50…600% of the FLA Setting (Parameter 171).
Table 83 - Jam Trip Level (Parameter 253)
Default Value250
Minimum Value50
Maximum Value600
Parame ter TypeUINT
Size (Bytes)2
Scaling Factor1
Units%FLA
The Jam Inhibitor timer starts after the maximum phase of load current
transitions from 0 A to 30% of the device’s minimum FLA setting. The E300
Electronic Overload Relay does not begin monitoring for a jam condition until
the Jam Inhibit Time expires.
Jam Warning
The E300 Electronic Overload Relay will indicate a Jam warning if:
• No warning currently exists
• Jam Warning is enabled
• Current is present
• Jam Inhibit Time has expired
• The maximum phase current is equal to or greater than the Jam Warning
e
l
Lev
When the Jam Warning conditions are satisfied, the:
• TRIP/WARN LED will flash a yellow 5-short blink pattern
• Bit 4 in Current Warning Status (Parameter 10) will set to 1
• Bit 1 in Device Status 0 (Parameter 20) will set to 1
• Any relay outputs configured as a Warning Alarm will close
100Rockwell Automation Publication 193-UM015B-EN-P - June 2014
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.