Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for
the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between
solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended
application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or
application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage, or
economic loss.
available from your local Rockwell
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Rockwell Automation, Allen-Bradley, TechConnect, PanelView, PanelView Component, and MicroLogix are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
2Publication 2711C-QS001F-EN-P - November 20102
Page 3
Where to Start
Chapter 4
Configure Communication
Chapter 1
Review Sample Application
Chapter 2
Make Terminal Connections
Chapter 3
Open a New Application
Chapter 5
Create Tags
Chapter 6
Create the Motor Status Screen
Chapter 7
Create the Motor Speed Screen
Chapter 8
Create Alarms
Chapter 9
Validate and Run Application
3Publication 2711C-QS001F-EN-P - November 20103
Page 4
Browser Configuration to Access the Design Environment
IMPORTANT
Standard Ethernet Cable or
2711P-CBL-EX04 Cable
Ethernet Port
Ethernet Port
USB Port
USB Port
2711C-CBL-UU02 USB Cable
To Ethernet DHCP-enabled Network
Ethernet Cable
PanelView Explorer
Startup Window
PanelView Explorer
Startup Window
The PanelView Explorer design-time environment is accessed through a web browser by connecting your
computer to the PanelView Component terminal over an Ethernet or USB connection.
Before connecting your computer to the USB port of the PanelView Component terminal,
you must first install the "PanelView USB RNDIS Device" driver on a computer with the Windows
XP or Vista operating system. After installing the driver, you can connect the PanelView
Component terminal to your computer. For details on how to install the driver, refer to the
PanelView Component Terminal User Manual, publication 2711C-UM001
.
4Publication 2711C-QS001F-EN-P - November 2010
Page 5
DF1 Runtime Configuration
Ethernet Cable
Ethernet Port
10/100Base-T
Channel 0 Port
RS-232/485
8-pin Mini DIN
1761-CBL-PM02 Cable
RS-232 Serial Port
9-pin D-shell
To Ethernet DHCP-enabled Network
DF1 Connection
Ethernet Port
10/100Base-T
Channel 1 Port
Ethernet 10/100Base-T
Ethernet Cable
Ethernet Cable
To Ethernet DHCP-enabled Network
Standard Ethernet Cable or
2711P-CBL-EX04 Cable
The DF1 configuration shows the PanelView Component C600 terminal connected to the MicroLogix 1100
controller using the 1761-CBL-PM02 cable. One end of the cable connects to the RS-232 serial port of the
terminal and the other end connects to the Channel 0 port of the controller. The terminal and computer
are connected to a DHCP-enabled Ethernet network using an Ethernet switch.
You can substitute another MicroLogix model in place of the MicroLogix 1100 controller. For MicroLogix
controllers with a 9-pin D-shell connector, use the catalog number 1747-CP3 cable.
Ethernet Runtime Configuration
The Ethernet configuration shows the Ethernet port of the PanelView Component C600 terminal
connected to the Channel 1 port of the MicroLogix 1100 controller using a standard Ethernet cable or an
Ethernet crossover CAT5 cable, catalog number 2711P-CBL-EX04. The computer, terminal, and controller
are connected to a DHCP-enabled Ethernet network using an Ethernet switch.
Publication 2711C-QS001F-EN-P - November 20105
Page 6
Notes:
6Publication 2711C-QS001F-EN-P - November 2010
Page 7
Where to Start
Browser Configuration to Access the Design Environment . . . . . . . . . 4
Use this manual to create a sample application to run in a PanelView
Component HMI terminal. You will use the design environment of the
PanelView Explorer software to create the application.
This manual describes the necessary tasks to connect your computer to a
PanelView Component terminal, launch the PanelView Explorer software in
your web browser, create a sample application in the design environment,
validate the application, and run the application while connected to a
Micrologix 1100 controller.
The beginning of each chapter contains the following information.
Read these sections carefully before beginning work in each chapter.
• Before You Begin - This section lists the steps that must be
completed and decisions that must be made before starting that chapter.
The chapters in this quick start do not have to be completed in the order
in which they appear, but this section defines the minimum amount of
preparation required before completing the current chapter.
• What You Need - This section lists the tools that are required to
complete the steps in the current chapter. This includes, but is not
limited to, hardware and software.
• Follow These Steps - This illustrates the steps in the current chapter
and identifies which steps are required to complete the examples.
Audience
This quick start was created to assist application designers on how to create
applications to run in a PanelView Component HMI terminal. The designer
may or may not be familiar with Rockwell Automation HMI software. An
understanding of Rockwell Automation controllers and communication
protocols is helpful but not necessary.
11Publication 2711C-QS001F-EN-P - November 201011
Page 12
Required Software
To complete this quick start, the following software is required:
• PanelView Explorer software, V1.0 or higher
This software is resident on your PanelView Component terminal.
Separate software is not required. After establishing an Ethernet
connection between your terminal and computer, you can launch the
PanelView Explorer software from your web browser by entering the IP
address of the terminal.
• Computer with Windows XP, Vista, or 2000 operating
system and a web browser
Operating SystemWeb Browser
Windows VistaFirefox 2.0 or 3.0
Internet Explorer 7 or 8
Windows XP SP2Firefox 2.0 or 3.0
Internet Explorer 7 or 8
Windows 2000 SP4 or later
(Ethernet only)
(1)
Internet Explorer 6 is supported but not recommended. For optimal
performance, use Internet Explorer 7 or 8, or Mozilla Firefox 2.0 or 3.0.
Firefox 2.0 or 3.0
Internet Explorer 7 or 8
(1)
(1)
The browser is needed to launch the PanelView Explorer software while
connected to a PanelView Component terminal.
• PanelView USB RNDIS Device driver
This driver must be installed on your computer if you intend to connect
your computer to the terminal using the USB port on the terminal. You
can install the driver on a computer with the Windows XP or Vista
operating system, not Windows 2000.
12Publication 2711C-QS001F-EN-P - November 2010
Page 13
Parts List
QuantityCatalog NumberDescription
12711C-T6CPanelView Component C600 touch-screen, color terminal
11763-L16xxxMicroLogix 1100 controller
2 or 3Standard Ethernet cable or
2711P-CBL-EX04
12711C-CBL-UU02USB cable used to connect a computer to the terminal using the USB port of the terminal for
11761-CBL-PM02Cable used to connect the PanelView Component terminal to the MicroLogix 1100 controller
This quick start uses the following hardware.
Standard Ethernet cable or crossover Ethernet cable
This cable is used to connect the terminal to the computer using the Ethernet port of the
terminal for design-time configuration. It is also used to connect the terminal to the
MicroLogix 1100 controller for Ethernet runtime configuration.
design-time configuration.
using a DF1 connection. The 9-pin D-shell connector connects to the RS-232 serial port on
the terminal; the 8-pin mini DIN connector connects to the Channel 0 port of the controller.
Conventions
ConventionMeaningExample
Check or uncheckClick to activate or deactivate a checkbox.Check the Font Italics checkbox.
ClickClick the left mouse button once while the cursor is positioned on
an object or selection.
Double-clickClick the left mouse button twice in quick succession while the
cursor is positioned on an object or selection.
Click the Delete button.
Double-click the object.
ExpandClick the cursor to the left of a tab or panel.Expand the Drawing Tools tab.
Right-clickClick the right mouse button once while the cursor is positioned
on an object or selection.
SelectClick to highlight a row or list choice.Select the write tag from the pull-down
DragHold down the left mouse button while dragging object.Drag the Text tool to the screen.
Right-click the object.
list.
Publication 2711C-QS001F-EN-P - November 201013
Page 14
Additional Resources
ResourceDescription
PanelView Explorer online helpProvides information on how to use the design environment of the PanelView
MicroLogix 1100 Programmable Controller
Instruction Set Reference Manual, publication
1763-RM001
Provides information on how to install, operate, and troubleshoot a MicroLogix
1100 controller.
Provides information on how to mount and wire the MicroLogix 1100 controller.
Provides information on the I/O configuration, controller memory, file types, and
programming instructions for the MicroLogix 1100 controller.
14Publication 2711C-QS001F-EN-P - November 2010
Page 15
Chapter
Review Sample Application
Introduction
In this chapter, you will review the purpose of the sample application and the actual screens in the
application.
TopicPage
Purpose of Application16
Motor Status Screen17
Motor Speed Screen18
Alarm Banner19
Application Tags20
1
Before You Begin
Review the where to start section and preface.
15Publication 2711C-QS001F-EN-P - November 201015
Page 16
Chapter 1 Review Sample Application
page 18
page 19
page 16
Purpose of
Application
Motor Status
Screen
Motor Speed
Screen
page 17
Alarm Banner
page 20
Application
Tags
Follow These Steps
Review the sample application.
Purpose of Application
The sample application contains screens and objects to control and monitor the status of a motor. The
PanelView Component terminal reads and writes data to a MicroLogix controller using:
• DF1 point-to-point communication or
• Ethernet communication.
The sample application uses a MicroLogix 1100 controller but you can substitute another MicroLogix model.
Each chapter provides procedures for creating the sample application on a PanelView Component C600
color, touch-screen terminal.
If you want to create this application on another PanelView Component terminal, consider that:
• touch input is automatically enabled for touch-screen terminals.
• function keys must be assigned to objects on keypad terminals.
• text sizes will vary for different terminal sizes.
• color palette on monochrome terminals, shows only two colors, black and white.
The sample application and ladder logic required to run the application on a MicroLogix 1100 controller are
stored on the CD that ships with your terminal under the names:
• QuickStart_T6C.cha - sample application.
• QuickStart.rss - required ladder logic.
16Publication 2711C-QS001F-EN-P - November 2010
Page 17
Review Sample Application Chapter 1
1
2
3
4
7
5
6
Motor Status Screen
The Motor Status screen is one of two screens in the application. It is the startup screen when the application
is loaded and running in the terminal. The Motor Status screen lets you:
• start and stop a motor.
• set the motor control to auto or manual mode.
• monitor the start/stop status and the auto/manual mode of the motor.
• navigate to the Motor Speed screen.
• navigate to the configuration mode screens of the terminal.
Objects on the Motor Status Screen
#This objectPerforms this function
1List SelectorSets the motor to auto or manual mode by selecting an item in the list. In auto mode,
the controller controls the speed of the motor. You can view the speed of the motor but
cannot change it. In manual mode, you control the speed of the motor by using numeric
entry objects to enter a new speed.
2KeysThe Up key moves the cursor up in the list selector.
The Down key moves the cursor down in the list selector.
The Enter key selects an item in the list selector.
3Momentary Push Button
Normally Open
4Momentary Push Button
Normally Open
5Goto Config ButtonDisplays the runtime configuration screens of the terminal when the button is pressed.
6Goto Screen ButtonDisplays the Motor Speed screen when the button is pressed.
7Multistate IndicatorsOne indicator shows the current mode of the motor; auto or manual. The other indicator
Starts the motor when the push button is pressed.
Stops the motor when the push button is pressed.
shows the current status of the motor; running or stopped.
The screen also contains static text for headings and a border to group objects.
Publication 2711C-QS001F-EN-P - November 201017
Page 18
Chapter 1 Review Sample Application
TIP
1
2
3
4
5
6
Motor Speed Screen
The Motor Speed screen lets you:
• enter a new motor speed.
• increase or decrease the motor speed in increments.
• monitor the motor speed.
• navigate to the Motor Status screen.
Objects on the Motor Speed Screen
#This objectPerforms this function
1Numeric EntryOpens a numeric keypad, when selected, to change the speed of the motor to a value between 0
and 1000 rpm. This object works only in manual mode.
2Numeric
Increment/Decrement
3KeysIncreases or decreases the Motor Speed in incremental steps.
4Goto Screen ButtonDisplays the Motor Status screen when the button is pressed.
5Numeric Data DisplayDisplays the current rpm speed of the motor in a numeric format
6Bar Graph and ScaleDisplays the current rpm speed of the motor in a graphic format.
Increases or decreases the speed of the motor in increments of 1 or 10 rpm depending on the key
pressed. This object works only in manual mode.
Page up key (double-cursor) - increases the speed in 10 rpm increments.
Up key - increases the speed in 1 rpm increments.
Down key - decreases the speed in 1 rpm increments.
Page down key (double-cursor) - decreases the speed in 10 rpm increments.
The screen also contains static text for headings and labels.
Applications typically use a numeric entry or a numeric increment decrement object, not
both. For illustration purposes, the sample application uses both. The numeric entry
object is typically used in PanelView Component C600 and C1000 applications. The
numeric increment decrement object is typically used in C200 and C300 applications.
18Publication 2711C-QS001F-EN-P - November 2010
Page 19
Review Sample Application Chapter 1
1
2
4
3
Alarm Banner
The alarm banner is a global display that pops up over the Motor Status or Motor Speed screen when an
alarm is triggered. The alarm banner lets you:
• read a message associated with a triggered alarm.
• clear the alarm banner from the screen.
• acknowledge an alarm and clear the banner.
• close the banner.
Alarm Banner Objects
#This objectPerforms this function
1Message displayDisplays this message when the motor speed rises to 850 rpm or higher.
MOTOR AT IDEAL OPERATING SPEED!
Displays this message when the motor speed rises to 900 rpm or higher.
MOTOR SPEED NEAR THRESHOLD!
2Ack buttonAcknowledges the alarm message when the button is pressed and closes the
alarm banner.
3Clear buttonClears the alarm from the alarm banner without acknowledging the alarm and
4Close buttonCloses the alarm banner when pressed without performing any action on the
closes the banner.
alarm.
Publication 2711C-QS001F-EN-P - November 201019
Page 20
Chapter 1 Review Sample Application
Application Tags
The sample application uses read and write tags to define how objects interact with addresses in the
MicroLogix 1100 controller. The tags read or write data to a bit or integer file. Objects that do not read or
write to a controller address such as screen buttons or headings do not require a tag.
The same tags are used for DF1 or Ethernet communication.
This objectUses this tagTo
Motor_StartStart the motor by writing the value 1 to the Boolean tag.
Motor_StopStop the motor by writing the value 0 to the Boolean tag.
Motor_AutoManualSet the motor to auto mode or manual mode by writing the
value 0 or 1 to the Boolean tag.
Read the tag value to determine the auto or manual mode of the
motor.
Motor_Status_IndRead the tag value to determine the running or stopped status
of the motor.
Change_SpeedWrite the value of the entered motor speed, 0 to 1000 rpm, to
an unsigned integer address.
Motor_SpeedRead the current value of the motor speed. The bar graph
displays the speed in a graphic format. The numeric display
displays the value in a numeric format.
This tag is also used to trigger an alarm if the motor speed
reaches 850 or 900 rpm.
20Publication 2711C-QS001F-EN-P - November 2010
Page 21
Chapter
IMPORTANT
2
Make Terminal Connections
Introduction
In this chapter, you will connect a PanelView Component C600 terminal to your computer, connect power,
get the IP address of terminal, and launch the PanelView Explorer software.
TopicPage
Connect Terminal to Computer23
Connect Power to Terminal24
Get the IP Address of Terminal25
Launch PanelView Explorer26
Configure Browser Settings27
Before You Begin
Determine if the connection between the PanelView Component terminal and the computer will be through
the Ethernet port or the USB port of the terminal.
• PanelView Component C600 and C1000 terminals support an Ethernet connection using either the
USB port or the Ethernet port.
• All PanelView Component terminals support an Ethernet connection using the USB port. The C200
and C300 terminals support only a USB connection.
The USB device port is for maintenance or programming only, and is not intended for normal
run-time operation.
What You Need
21Publication 2711C-QS001F-EN-P - November 201021
• PanelView Component C600 terminal
• Computer with Windows 2000, Windows XP, or the Vista operating system, and Internet Explorer 7
browser or the Mozilla Firefox 2.0 or 3.0 browser. The Windows 2000 operating system supports only
the Ethernet connection.
• Standard Ethernet cable or 2711P-CBL-EX04 cable for Ethernet port connection
• 2711C-CBL-UU02 USB cable for USB port connection
Page 22
Chapter 2 Make Terminal Connections
page 23
Connect
Terminal to
Computer
Connect Power
to Terminal
page 24
page 25
Get the IP
Address of
Terminal
page 26
Launch
PanelView
Explorer
page 27
Configure
Browser Settings
• Allen-Bradley PanelView USB remote NIDS Network Device driver installed on computer for USB
port connection only. This driver does not work with the Windows 2000 operating system. See the
PanelView Component Terminal User Manual, publication 2711C-UM001, for details on how to install
this driver.
Follow These Steps
Complete these steps to connect your computer to a PanelView Component terminal and launch the
PanelView Explorer software.
22Publication 2711C-QS001F-EN-P - November 2010
Page 23
Make Terminal Connections Chapter 2
Connect Terminal to Computer
For Ethernet Cable Connection
PanelView Component C600 and C1000 terminals support an Ethernet port connection and will require a
computer with the Windows 2000, XP, or Vista operating system.
1. Connect one end of a
standard Ethernet cable to
the Ethernet port on your
PanelView Component
terminal.
2. Connect the other end of the
cable to the Ethernet port
on your computer.
For USB Cable Connection
All PanelView Component terminals support a USB port connection and will require a computer with the
Windows XP or Vista operating system, and the ‘PanelView USB RNDIS Device’ driver installed. The driver
cannot be installed on a computer with the Windows 2000 operating system.
1. Connect one end of a
2711C-CBL-UU02 USB
cable to the mini USB device
port on your PanelView
Component terminal.
2. Connect the other end of the
USB cable to a USB port on
your computer.
Publication 2711C-QS001F-EN-P - November 201023
Page 24
Chapter 2 Make Terminal Connections
DC+
DC-
Functional
Earth Ground
to Ground Bus
Connect Power to Terminal
1. Optionally, remove the
terminal block from the
terminal for ease of wiring.
2. Insert the DC+, DC-, and
the functional-earth ground
wires and tighten terminal
screws.
3. Re-attach terminal block to
terminal.
4. Plug the 3-prong power
connector into a 24V DC
power source.
For power requirements of
the PanelView Component
terminal, refer to the
installation instructions,
2711C-IN001.
The terminal goes through a
series of self-tests and then
displays the configuration
application for the terminal.
24Publication 2711C-QS001F-EN-P - November 2010
Page 25
Get the IP Address of Terminal
For Ethernet Port Connection
1. Press the Communication
button.
2. Write down the IP address.
You will need this IP address
when launching PanelView
Explorer from your Internet
browser.
If you are not using an IP
address from a DHCP
enabled network, then
contact your network
administrator on what static
IP address to use.
Make Terminal Connections Chapter 2
3. Click Main to return to the
Main configuration screen.
Publication 2711C-QS001F-EN-P - November 201025
Page 26
Chapter 2 Make Terminal Connections
Launch PanelView Explorer
Internet Explorer 7 Web Browser, or Mozilla Firefox 2.0 or 3.0 Web Browser
1. Launch your Internet
browser.
2. Type the IP address of your
PanelView Component
terminal in the web address
field.
This establishes a local
Ethernet connection
between your terminal and
computer.
The PanelView Explorer
Startup Window opens.
From here you access the
design environment to create
applications.
26Publication 2711C-QS001F-EN-P - November 2010
Page 27
Make Terminal Connections Chapter 2
Configure Browser Settings
Browser changes are required before using the PanelView Explorer design environment. For optimal
performance, the Internet Explorer 7 browser or the Firefox 2.0 or 3.0 browser is recommended.
All Browsers
1. Verify that cookies are
enabled.
2. Turn off the pop-up blocker.
Mozilla Firefox 2.0 or 3.0
The Firefox browser requires changes before you can copy and paste data from a grid or state editor in
PanelView Explorer to Excel. The browser requires a preference named
signed.applets.codebase_principal_support. Without this preference, data will not paste into Excel.
1. Verify your Firefox browser
is open.
2. Enter the URL about:config.
3. Look for the preference:
signed.applets.codebase_prin
cipal_support
4. If the preference name
exists, skip to step 7..
Publication 2711C-QS001F-EN-P - November 201027
Page 28
Chapter 2 Make Terminal Connections
IMPORTANT
IMPORTANT
5. If the preference name does
not exist, right-click in the
main window and select
New>Boolean.
6. Type this preference name.signed.applets.codebase_principal_support
7. Enter true for the Value.
The first time you copy and
paste data from a PanelView
Explorer grid or state editor
to Excel, a security dialog
will open to alert you that a
script is requesting enhanced
abilities.
8. Check the Remember this
decision checkbox, and then
click the Allow button.
The Allow button prevents
the dialog from opening each
time you want to paste into
Excel. Checking the
Remember this decision
checkbox prevents
double-pasting from
occurring during copy and
paste operations.
Always check the URL in the dialog that opens before
clicking the Allow button. Only allow trusted sites such as
your local computer or PanelView Component device.
If you do not check the Remember this decision checkbox,
double-pasting will occur during copy and paste operations.
28Publication 2711C-QS001F-EN-P - November 2010
Page 29
Make Terminal Connections Chapter 2
Internet Explorer 7
Internet Explorer 6
Internet Explorer 6 and 7
The Windows clipboard is used to copy and paste data in applications such as Excel and text documents. To
copy and paste data between PanelView Explorer and Windows applications, you must enable your browser
to access the Windows clipboard.
1. Make sure Internet Explorer
is open.
2. Select Tools>Internet
Options.
3. Click the Security tab.
4. Click Local Intranet, then
5. In the Security Settings
the Custom Level button.
dialog, scroll down to
Scripting.
a. For Internet Explorer 7,
click Enable under
Allow Programmatic
clipboard access.
b. For Internet Explorer 6,
click Enable under
Allow paste operations
via script.
Publication 2711C-QS001F-EN-P - November 201029
Page 30
Chapter 2 Make Terminal Connections
Internet Explorer 6
Internet Explorer 7
6. Click the Sites button.
7. Click the Advanced button.
8. In the Add this website to
9. Click the Add button.
10. Click OK until you exit the
the zone field, enter the IP
address of your terminal, in
the format
http://10.90.95.13.
Internet Options dialog.
30Publication 2711C-QS001F-EN-P - November 2010
Page 31
Chapter
Open a New Application
Introduction
In this chapter, you will open a new application and modify settings that are global to the application.
TopicPage
Open a New Application32
Modify Application Settings35
Before You Begin
3
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
What You Need
PanelView Explorer Startup window launched in your web browser.
31Publication 2711C-QS001F-EN-P - November 201031
Page 32
Chapter 3 Open a New Application
TIP
page 32
Open a New
Application
Modify
Application
Settings
page 35
Follow These Steps
Complete these steps to open a new application, review the screens view, and modify global application
settings.
Open a New Application
Applications are created with default file names that you can change when saving the application. The default
file name is PVcApplication1. The number automatically increments as you create new applications.
1. Click the Create & Edit button in the PanelView Explorer Startup window.
You can set the design environment to appear in another language by clicking a
language link at the bottom of the window.
32Publication 2711C-QS001F-EN-P - November 2010
Page 33
The design environment opens in a separate window, showing the Screens view.
1
2
4
6
7
8
9
3
5
2. Review areas of screen.
This is where you will spend most of your time.
Open a New Application Chapter 3
#Screen areaDescription
1Navigation tabsProvides access to the different functional areas of an application.
2Application toolbarProvides common tools that are available to all views of the application. Drag your mouse over each tool
to see the purpose of each tool.
Application LanguageSelects a language for viewing and editing application components. Languages for an application are
defined and translated from the Languages navigation tab.
3Cursor controlsHides or shows the Controls or Properties panel to increase the workspace area.
4Screen listContains a list of screens in the application including the alarm banner and diagnostics banner.
The bullet indicates the startup screen for runtime operations.
5Screen workspaceContains objects that you drag to the screen from the object palette.
6Object paletteContains panels of objects that you can drag to the screen workspace. Click the cursor on a tab to open
or close a panel of objects. The palette can occupy 25, 50 or 75% of the Controls panel. Right-click on
the object palette heading to resize it. The object palette and screen list are resized accordingly.
Publication 2711C-QS001F-EN-P - November 201033
Page 34
Chapter 3 Open a New Application
#Screen areaDescription
7Screen toolbarContains tools that operate on selected objects in the screen workspace. Also contains a tool for turning
the screen grid on or off.
8Properties panelContains panels of properties to configure the appearance, navigation, common properties, or
connection tags of a selected object. Panels vary for each object. Click the cursor on a tab to open or
close a panel.
You can also change the screen properties by clicking a blank area of a screen. Screen properties
include name, description, grid spacing, and the screen background color.
9Status barProvides information about the terminal type, current actions, and Validation Report link after a
validation is performed.
34Publication 2711C-QS001F-EN-P - November 2010
Page 35
Open a New Application Chapter 3
Modify Application Settings
The Settings tab contains design-time settings that are global to an application. Changes made on this tab
affect all screens in the application.
1. Click the Settings tab.
2. Check the Default Font Bold
checkbox.
All text in the application
will be bold.
You are now ready to configure runtime communication for the application.
Publication 2711C-QS001F-EN-P - November 201035
Page 36
Chapter 3 Open a New Application
Notes:
36Publication 2711C-QS001F-EN-P - November 2010
Page 37
Configure Communication
Introduction
In this chapter, you will configure runtime communication settings for your application.
TopicPage
Configure DF1 Communication39
Configure Ethernet Communication40
Load Runtime Settings with Application42
Save the Application43
Chapter
4
Before You Begin
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
• Open a new application.
• Determine if you will be communicating with the MicroLogix 1100 controller using DF1
communication or Ethernet communication.
What You Need
• For Ethernet communication, you need the Ethernet IP address of the MicroLogix 1100 controller.
• For DF1 communication, know the station address of the MicroLogix 1100 controller on the DF1 link.
The default station address is 1 for the controller and 2 for the PanelView Component terminal.
37Publication 2711C-QS001F-EN-P - November 201037
Page 38
Chapter 4 Configure Communication
page 39
Configure DF1
Communication
Configure
Ethernet
Communication
page 40
Load Runtime
Settings with
Application
page 42
Save the
Application
page 43
Follow These Steps
Complete the appropriate steps to configure DF1 or Ethernet runtime communication settings for the
PanelView Component terminal and the MicroLogix 1100 controller.
38Publication 2711C-QS001F-EN-P - November 2010
Page 39
Configure Communication Chapter 4
Configure DF1 Communication
This topic shows how to configure runtime settings to enable DF1 point-to-point communication between
your PanelView Component terminal and a MicroLogix 1100 controller. The DF1 settings for the PanelView
Component terminal match the default settings of the MicroLogix controller.
1. Click the Communication
tab to open the
Communication view.
2. Select Serial under Protocol
and DF1 from the pull-down
list.
3. Under PanelView
Component Settings, verify
the Station Address is 2.
4. Under Controller Settings:
a. Accept the default name
PLC-1.
b. Select MicroLogix from
the Controller Type field.
c. Type 1 in the Address
field.
Publication 2711C-QS001F-EN-P - November 201039
Page 40
Chapter 4 Configure Communication
TIP
Configure Ethernet Communication
This topic shows how to configure runtime settings to enable Ethernet communication between your
PanelView Component terminal and a MicroLogix 1100 controller. It is not necessary to configure settings
for the terminal if using DHCP-enabled network IP addresses.
If the target terminal for an application uses a static IP network address, you would enter the
address on the USB/Ethernet tab.
1. Click the Communication
tab to open the
Communication view.
2. Select Ethernet under
Protocol.
3. Select Allen-Bradley
Micrologix/ENI from the
pull-down list.
40Publication 2711C-QS001F-EN-P - November 2010
Page 41
4. Under Controller Settings:
a. Accept the default name
PLC-1.
a. Verify that MicroLogix
1100 is selected in the
Controller Type field.
b. Type the IP address of the
controller in the Address
field.
Configure Communication Chapter 4
Publication 2711C-QS001F-EN-P - November 201041
Page 42
Chapter 4 Configure Communication
Load Runtime Settings with Application
This section does not apply to the sample application but is information that you may find helpful when
creating future applications. There may be times when you want to load an application on a terminal that has
a static IP network address. Static IP addresses for a terminal are entered on the USB/Ethernet tab of the
Communication tab. It is important that you load these communication settings with the application the first
time the application is loaded on the target terminal.
1. Click the Settings tab.
2. Check the Set Terminal On
First Load checkbox.
When the Set Terminal On First Load checkbox is checked, the first time the application is loaded to the
terminal, the communication settings and any other settings that you update under Runtime will be loaded
with the application.
42Publication 2711C-QS001F-EN-P - November 2010
Page 43
Configure Communication Chapter 4
TIP
Save the Application
The first time you save an application, a dialog opens where you can rename the application to something
more meaningful. By default, applications are saved to internal storage of the terminal. You can also save
applications to a USB flash drive or SD memory card if one is loaded in the terminal. All PanelView
Component terminals support a USB flash drive. The PanelView Component C600 and C1000 terminals also
support an SD memory card.
1. Click the Save Application
icon on the application
toolbar.
A dialog opens the first
time you save.
2. Replace the default name
with SampleApplication.
3. Accept Internal as the Save
to location.
4. Click Save to close the dialog
and save the application.
5. Click OK when you receive
notification that the
application has been saved.
Always save the application to internal storage if
you want to edit and run the application on the
terminal.
Publication 2711C-QS001F-EN-P - November 201043
Page 44
Chapter 4 Configure Communication
Notes:
44Publication 2711C-QS001F-EN-P - November 2010
Page 45
Chapter
Create Tags
Introduction
In this chapter, you will create tags used by the sample application. You must create tags before you can
assign them to objects.
TopicPage
Review Application Tags46
Open the Tags View47
Create External Tags47
5
Before You Begin
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
• Open a new application.
• Configure runtime communication settings for the application.
What You Need
• Runtime communication settings defined. Tags require the controller name defined on the
Communication tab. In this application, the controller settings use the default name PLC-1.
45Publication 2711C-QS001F-EN-P - November 201045
Page 46
Chapter 5 Create Tags
page 46
Review
Application Tags
Open the Tags
View
Create
External Tags
page 47
page 47
Follow These Steps
Complete these steps to enter application tags.
Review Application Tags
The sample application uses read and write tags to define how objects interact with the addresses of a
MicroLogix 1100 controller. You must create these tags before you can assign them to objects in the
application. Only objects that interact with the controller require a tag. Objects such as screen navigation
buttons, drawings, and screen text do not require tags.
The same tags are used when communicating to a MicroLogix 1100 controller using DF1 or Ethernet
communication.
Refer to this table when entering your application tags.
Application Tags
Tag NameData TypeTag AddressControllerDescription
Motor_StartBooleanB3:0/0PLC_1Starts the motor.
Motor_StopBooleanB3:0/1PLC_1Stops the motor.
Change_Speed16 bit integerN7:1PLC_1Changes the motor speed to a value
between 0 and 1000 rpm.
Motor_Status_IndBooleanB3:0/2PLC_1Reads the running or stopped status
Motor_Speed16 bit integerN7:0PLC_1Reads the current motor speed. Also
Motor_AutoManualBooleanB3:0/3PLC_1Changes the motor to auto or manual
of the motor.
used to trigger an alarm if the speed
rises above 850 or 900 rpm.
mode and also used to read the
current mode of the motor.
46Publication 2711C-QS001F-EN-P - November 2010
Page 47
Open the Tags View
Tag fieldsShows more tag fields
Adds a tag
1. Click the Tags tab to open
the tag editor.
2. Verify that the External tab
is selected.
Create Tags Chapter 5
Create External Tags
Each tag occupies a separate row in the Tags view. The fields in each row define the attributes of a tag. Tags
are created with a default tag name, TAG0001, where the number increments with each new tag. As tags are
added, they are populated with defaults from the previous tag.
1. Click the Add Tag button to
add a tag.
2. Type Motor_Start in the Tag
Name field.
3. Select Boolean in the Data
Type field.
Publication 2711C-QS001F-EN-P - November 201047
Page 48
Chapter 5 Create Tags
4. Click in the Address field
and type B3:0/0.
5. Click in the Controller field
and select PLC-1.
This is the controller name
defined on the
Communication tab.
6. Optionally, enter the tag
description.
7. Repeat steps 1 through 6 to
add the other five tags.
Some fields populate with
data from the previous tag.
When done, the Tags view
must look like this.
8. Click the Save icon on the
application toolbar to save
the application.
48Publication 2711C-QS001F-EN-P - November 2010
Page 49
Create the Motor Status Screen
Introduction
In this chapter, you will create the Motor Status screen of the application.
TopicPage
Change the Screen Name51
Change the Grid Attributes52
Create the Start Motor Push Button52
Create the Stop Motor Push Button54
Create the Motor Speed Screen Button56
Chapter
6
Create a Goto Config Button58
Create the Motor Control List Selector59
Create the Motor Status Indicators64
Save the Motor Status Screen70
Before You Begin
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
• Open a new application.
• Configure runtime communication settings for the application.
• Create tags for the application.
What You Need
• Tags to assign to objects. These tags were defined in Chapter 5, Create Tags.
49Publication 2711C-QS001F-EN-P - November 201049
Page 50
Chapter 6 Create the Motor Status Screen
Change the
Screen Name
Change the
Grid Attributes
page 51
page 52
page 52
Create the Start
Motor Push
Button
Create the
Stop Motor
Push Button
Create the
Motor Speed
Screen Button
page 54
page 56
page 58
Create a Goto
Config Button
Create the
Motor Control
List Selector
Create the
Motor Status
Indicators
page 59
page 64
Save the
Motor Status
Screen
page 70
Follow These Steps
Complete these steps to create the Motor Status screen.
50Publication 2711C-QS001F-EN-P - November 2010
Page 51
Create the Motor Status Screen Chapter 6
Change the Screen Name
New applications open with the first screen created. Each screen is created with a default name, Screen_NN,
where NN is a number from 1 to 99. The first screen is named Screen_1. You can rename the screen using a
maximum of 50 characters.
1. Click the Screens tab to open
the Screens view.
2. Verify the screen border is
highlighted indicating the
screen is selected.
You can modify screen
properties as long as nothing
on the screen is selected.
3. Under Properties, click the
cursor next to Common.
4. In the Name field, type
MOTOR STATUS and press
Enter.
The updated screen name
appears above the screen
workspace and in the screens
list.
A bullet next to a screen
name indicates the startup
screen at runtime. The
startup screen is changed by
selecting a screen from the
Startup Screen pull-down
list.
Publication 2711C-QS001F-EN-P - November 201051
Page 52
Chapter 6 Create the Motor Status Screen
You can also click the object to
select it and then click on the
screen to drop the default size,
or click and drag to drop and
resize the object.
Change the Grid Attributes
For easier alignment and positioning of screen objects, you can adjust the grid settings of a screen. The
settings will vary with each PanelView Component terminal size.
1. In the toolbar above the
screen, scroll to the right.
2. Click the Toggle Snap to
Grid tool to display the
screen grid.
3. Under Properties, click the
cursor next to Screen.
4. Change the value from 10 to
5 in the Horizontal Grid
Spacing field.
5. Change the value from 10 to
5 in the Vertical Grid
Spacing field and press
Enter.
The grid is updated.
Create the Start Motor Push Button
1. Open the Entry tab of the
object palette if not open.
2. Drag the Momentary Push
Button to the lower left
corner of the screen.
You will also see the object
on the terminal.
52Publication 2711C-QS001F-EN-P - November 2010
Page 53
3. Resize the button by clicking
State 1
State 2
a corner handle and dragging
diagonally or move the
button by dragging it on the
screen.
4. Open the States editor.
a. Double-click object;
b. Or, right-click object
and select Edit States;
c. Or, click the Edit
Properties button on
the Appearance tab of
the Properties panel.
Each row is a state with a
default value, text, and
other format options.
Move the scroll bar to
view all the fields.
Create the Motor Status Screen Chapter 6
5. Edit state 1 (row 1).
a. Click in the Text field and
type START MOTOR.
b. Click the ... button in
the Background Color
field and select green
from the color palette.
c. Click the ... button in
the Text Color field and
select black.
6. Edit state 2 (row 2).
a. Type MOTOR
STARTED in the Text
field.
b. Select green as the
Background Color.
c. Select black as the Text
Color.
7. Click on row 1 to make this
the displayed state.
8. Click OK when done.
Publication 2711C-QS001F-EN-P - November 201053
Page 54
Chapter 6 Create the Motor Status Screen
9. Resize object if needed.
An asterisk * appears if
the text exceeds the size
of the object.
10. On the Appearance tab, set
the Border Width to 6.
11. Assign tags to the Start
Motor push button.
a. Make sure the push
button is selected.
b. Click the cursor next to
the Connections tab on
the Properties panel.
c. Click in the Write Tag
field and select
Motor_Start.
12. Verify the view the object on
the terminal.
Create the Stop Motor Push Button
The Stop Motor push button is created using a copy and paste operation.
1. Verify the Start Motor push
button is selected.
2. Click the Copy icon on the
Application toolbar or press
the Ctrl+C keys.
3. Click the Paste icon on the
toolbar or press the Ctrl+V
keys.
54Publication 2711C-QS001F-EN-P - November 2010
Page 55
4. Move the pasted button to
State 1
State 2
the right of the original push
button.
5. Double-click the object to
open the States editor.
6. Edit state 1 (row 1).
a. Replace the text with
STOP MOTOR.
b. Select red as the
Background Color.
c. Select white as the Text
Color.
7. Edit state 2 (row 2).
a. Replace the text with
MOTOR STOPPED.
Create the Motor Status Screen Chapter 6
b. Select red as the
Background Color.
c. Select white as the Text
Color.
8. Click row 1 to make this the
displayed state.
9. Click OK when done.
10. Assign tags to the Stop
Motor push button.
a. Verify the push button
is selected.
b. Open the Connections
tab.
c. Click in the Write Tag
field and select the
Motor_Stop tag.
11. Verify the view of the object
on the terminal.
Publication 2711C-QS001F-EN-P - November 201055
Page 56
Chapter 6 Create the Motor Status Screen
IMPORTANT
Create the Motor Speed Screen Button
The Motor Speed (Goto Screen) button lets you open the Motor Speed screen when the button is pressed.
You will create the button now, but will not link it to the Motor Speed screen until later, page 86.
The Motor Speed screen must be created before you can assign it to the button.
1. Open the Entry tab of the
object palette and scroll until
you see the Goto Screen
button.
2. Drag the Goto Screen
button to the lower right
corner of the screen and
resize.
3. On the Appearance tab of
the Properties panel:
a. Replace Goto with
MOTOR SPEED in the
Text field.
b. Select dark blue as the
Text Color.
c. Select cyan or light blue as
the Background Color.
d. Change the Border Width
to 6.
Scroll down to see all the
properties.
56Publication 2711C-QS001F-EN-P - November 2010
Page 57
4. Resize the Goto Screen
button if necessary to fit the
text.
5. Verify the view of the Motor
Speed (Goto Screen) button
on the terminal.
Create the Motor Status Screen Chapter 6
Publication 2711C-QS001F-EN-P - November 201057
Page 58
Chapter 6 Create the Motor Status Screen
Create a Goto Config Button
The Goto Config button lets you access the configuration mode screens of the terminal when the button is
pressed at runtime.
1. Click the Advanced cursor
on the object palette and
scroll down until you see the
Goto Config button.
2. Drag the Goto Config
button to the left of the
Motor Speed button and
resize.
3. On the Appearance tab of
the Properties panel:
a. Change Goto Config to
CONFIG SCREEN in
the Text field.
b. Accept the default colors
for the object.
c. Change the Border Width
to 6.
Another way to edit text is to
double-click the object or
right-click the object and
select Edit Text to open the
text editor.
58Publication 2711C-QS001F-EN-P - November 2010
Page 59
Create the Motor Status Screen Chapter 6
Create the Motor Control List Selector
The motor control list selector lets you switch the motor between manual and automatic mode.
1. Open the Entry tab of the
object palette.
2. Drag the List Selector object
to the area above the Start
Motor and Stop Motor push
buttons.
3. Double-click the object to
open the States editor.
The list selector is created
with four states. This
example uses only two.
Publication 2711C-QS001F-EN-P - November 201059
Page 60
Chapter 6 Create the Motor Status Screen
4. Select row 3, hold down the
Shift key, and select row 4.
5. Click the Delete button.
6. Edit state 1 (row 1).
a. Replace the Item1 text
with AUTOMATIC.
b. Set the Font Size to 17.
c. Click the ... button in the
Alignment field, and
select Center Left.
Scroll to the right to see all
the fields.
7. Edit state 2 (row 2).
a. Type 0 in the Value field.
b. Replace the Item2 text
with MANUAL.
c. Set the Font Size to 17.
d. Select Center Left in the
Alignment field.
8. Click row 1 to make this the
displayed state.
9. Click OK to close the editor.
60Publication 2711C-QS001F-EN-P - November 2010
Page 61
10. On the Appearance tab of
the Properties panel:
a. Select White as the List
Selection Text Color.
b. Select Black as the List
Selection Background
Color.
c. Change the Border Width
to 6.
d. Set the Border Style to
Raised.
11. On the List tab of the
Properties panel, set the
Number of Visible Rows
to 2.
Create the Motor Status Screen Chapter 6
12. On the Connections tab,
select Motor_AutoManual
for the Write tag and the
Indicator tag.
13. Resize the list selector if
necessary.
14. Verify the view of the object
on the terminal.
Publication 2711C-QS001F-EN-P - November 201061
Page 62
Chapter 6 Create the Motor Status Screen
List keys
Create List Keys for the Motor Control List Selector
Terminals with a touch screen, or without an attached keyboard, require the up and down list keys on the
screen to move the cursor in the list, and the Enter key to make a selection.
1. Open the Entry tab of the
object palette and scroll
down until you see the Key
object.
2. Drag the Key object below
the list selector and to the
left.
3. Resize the object.
4. Make two copies of the Key
object.
a. Select the key object.
b. Click the Copy tool on the
application toolbar or
press Ctrl+C.
c. Click the Paste tool twice
to paste two copies of the
object or press Ctrl+V
twice.
5. Move the pasted objects as
shown in the image above
and resize.
62Publication 2711C-QS001F-EN-P - November 2010
Page 63
6. Modify the key type of the
pasted key objects.
a. Select one of the pasted
key objects.
b. Open the Navigation tab
of the Properties panel.
c. Select Down as the Key
Type.
d. Select the other pasted
key object.
e. Select Enter as the Key
Type.
Create the Motor Status Screen Chapter 6
7. Verify the view of the objects
on the terminal.
Create a Heading for the Motor Control List Selector
1. Open the Drawing Tools tab
of the object palette.
2. Drag the Text tool above the
list selector object.
Publication 2711C-QS001F-EN-P - November 201063
Page 64
Chapter 6 Create the Motor Status Screen
3. On the Appearance tab:
a. Type SELECT MODE in
the Text box.
b. Set the Font Size to 16.
c. Check the Font Underline
checkbox.
d. Set the Border Style to
None.
4. Resize the object to fit the
text.
Create the Motor Status Indicators
The Motor Status box contains two multistate indicators. The Mode indicator shows whether the motor is in
Auto or Manual mode. The Status indicator shows whether the motor is running or stopped.
Create the Mode Indicator
1. Open the Display tab of the
object palette.
2. Drag the Multistate Indicator
object to the right of the
Motor Control list selector.
64Publication 2711C-QS001F-EN-P - November 2010
Page 65
3. Double-click the object to
State 1State 2
open the States editor.
The indicator is created with
four states. This example
uses only two.
4. Delete rows 3 and 4.
5. Edit state 1 (row 1).
a. Accept 0 as the Value.
b. Replace the MultiState0
text with MANUAL.
c. Select yellow as the
Background Color.
d. Select black as the Text
Color.
Create the Motor Status Screen Chapter 6
6. Edit state 2 (row 2).
a. Accept 1 as the Value.
b. Replace the Multistate1
text with AUTO.
c. Select yellow as the
Background Color.
d. Select black as the Text
Color.
7. Click OK to close editor.
8. On the Appearance tab, set
the Border Style to Raised.
9. On the Connections tab,
select Motor_AutoManual as
the Read tag.
10. Resize the object to fit the
text for both states.
Publication 2711C-QS001F-EN-P - November 201065
Page 66
Chapter 6 Create the Motor Status Screen
Create a Heading for the Mode Indicator
1. Open the Drawing Tools tab
of the object palette.
2. Drag the Text tool above the
Mode indicator.
3. On the Appearance tab:
a. Type MODE in the Text
box.
b. Set the Font Size to 16.
c. Check the Font Underline
checkbox.
d. Set the Border Style to
None.
Scroll down to see all the
properties.
4. Resize the object to fit the
text.
66Publication 2711C-QS001F-EN-P - November 2010
Page 67
Create the Status Indicator
State 2
State 1
1. Select the Mode indicator
you just created.
2. Click the Copy tool or press
Ctrl+C.
3. Click the Paste tool or press
Ctrl+V.
4. Move the pasted object to
the right of the original
indicator object.
5. Double-click the pasted
object to open the States
editor.
Create the Motor Status Screen Chapter 6
6. Edit state 1 (row 1).
a. Replace the MANUAL
text with Stopping.
b. Select red as the
Background Color.
c. Accept black as the Text
Color.
d. Check the Font Italics
checkbox.
Scroll to the right to see all
fields.
7. Edit state 2 (row 2).
a. Replace the AUTO text
with Running.
b. Select green as the
Background Color.
c. Select white as the Text
Color.
d. Check the Font Italics
checkbox.
Publication 2711C-QS001F-EN-P - November 201067
Page 68
Chapter 6 Create the Motor Status Screen
8. Click OK to close the editor.
9. On the Connections tab of
the Properties panel, select
Motor_Status_Ind as the
Read Tag.
10. Resize and move object as
needed.
68Publication 2711C-QS001F-EN-P - November 2010
Page 69
Create a Heading for the Status Indicator
1. Select the heading for the
Mode Indicator.
2. Copy and paste the MODE
heading.
3. Move the pasted heading to
the right above the status
indicator.
4. On the Appearance tab,
replace the MODE text with
STATUS.
5. Resize object to fit text.
Create the Motor Status Screen Chapter 6
Create a Border Around the Indicators
1. Drag the Border tool from
the Drawing Tools tab to the
area of the indicators.
2. Move and resize the border
so that it surrounds the
indicators and headings.
3. On the Appearance tab:
a. Change the Border Width
to 5.
b. Select white as the
Background Color.
c. Uncheck the Use
Background Color for
Border checkbox.
4. Select the border and click
the Send to Back tool on
toolbar.
Publication 2711C-QS001F-EN-P - November 201069
Page 70
Chapter 6 Create the Motor Status Screen
Create a Heading for the Motor Status Indicators
1. Drag the Text tool above the
border just created.
2. On the Appearance tab:
a. Type MOTOR STATUS
in the Text box.
b. Set the Font Size to 16.
c. Check the Font Underline
checkbox.
d. Set the Border Style to
None.
3. Resize and move as the
object as needed.
Save the Motor Status Screen
You have just completed one of the application screens.
Click the Save icon on the
application toolbar.
The application is automatically
saved to internal storage of the
terminal under the name
SampleApplication.
In the next chapter, you will create the Motor Speed screen. You can stop here, if you like, and open the
QuickStart_TC6.cha application on the CD which contains the same screens as this sample application. You
can then skip to Chapter 9,
Validate and Run Application to validate and run the application.
70Publication 2711C-QS001F-EN-P - November 2010
Page 71
Create the Motor Speed Screen
Introduction
In this chapter, you will create and design the Motor Speed screen in the application.
TopicPage
Create a New Screen73
Create the Motor Status Screen Button74
Create a Numeric Entry Object75
Create a Heading for the Numeric Entry Object76
Create a Increment Decrement Object77
Chapter
7
Create Increment Decrement Keys78
Create a Bar Graph80
Create a Bar Graph Scale81
Create Text Labels for the Scale82
Create a Bar Graph Heading83
Create a Numeric Display84
Create a Heading for the Numeric Display85
Update the Motor Speed Screen Button86
Before You Begin
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
• Open a new application.
• Configure runtime communication settings for the application.
• Create tags for the application.
• Create the Motor Status screen.
71Publication 2711C-QS001F-EN-P - November 201071
Page 72
Chapter 7 Create the Motor Speed Screen
Create a New
Screen
Create the
Motor Status
Screen Button
page 73
page 74
page 75
Create a
Numeric Entry
Object
Create a Heading
for the Numeric
Entry Object
Create a Increment
Decrement Object
page 76
page 77
page 78
Create
Increment
Decrement Keys
Create a Bar
Graph
Create a Bar
Graph Scale
page 80
page 81
Create Text
Labels for the
Scale
page 82
Create a Bar
Graph Heading
Create a
Numeric Display
page 83
page 84
Create a Heading
for the Numeric
Display
page 85
Update the
Motor Speed
Screen Button
page 86
What You Need
• Tags to assign to objects. These tags were defined in the Tags view.
Follow These Steps
Complete these steps to create the Motor Speed screen.
72Publication 2711C-QS001F-EN-P - November 2010
Page 73
Create a New Screen
1. Click the Add button in the
Screen List to add a new
screen.
Screen 2 is added to the list
with a default name.
2. On the Screen tab of the
Properties panel, change the
Horizontal and Vertical Grid
Spacing from 10 to 5 and
press Enter.
The screen grid is
updated.
Create the Motor Speed Screen Chapter 7
3. Open the Common tab of
the Properties panel.
4. In the Name box, type
MOTOR SPEED and press
Enter.
The name appears in the
Screen List and above the
screen workspace.
Publication 2711C-QS001F-EN-P - November 201073
Page 74
Chapter 7 Create the Motor Speed Screen
Create the Motor Status Screen Button
A copy and paste operation copies the Motor Speed (Goto Screen) button from the Motor Status screen to
the Motor Speed screen.
1. Click on MOTOR STATUS
in the Screen List to open
the screen.
2. Select the MOTOR SPEED
button.
3. Click the Copy tool or press
Ctrl+C.
4. Click on MOTOR SPEED
in the Screen List.
5. Click in the screen area.
6. Click the Paste tool or press
Ctrl+V to paste the screen
button.
The button is pasted to
the same location as on
the original screen.
7. On the Appearance tab,
replace the text MOTOR
SPEED with MOTOR
STATUS and press Enter.
8. On the Navigation tab, select
the 1-MOTOR STATUS
screen from the Screen field.
This is the screen that will
display when the Motor
Status (Goto Screen)
button is pressed.
74Publication 2711C-QS001F-EN-P - November 2010
Page 75
Create the Motor Speed Screen Chapter 7
Create a Numeric Entry Object
The numeric entry object lets you change the speed of the motor in manual mode by entering an integer
value. The object does not display a value until runtime.
1. Open the Entry tab of the
object palette.
2. Drag the Numeric Entry
object to the left side of the
screen.
3. Resize the object.
4. On the Appearance tab of
the Properties panel:
a. Change the Border
Width to 6.
b. Set the Border Style to
Raised.
5. Open the Format tab:
a. Select Numeric as the
Keypad Type.
b. Type 1000 for the
Maximum Value.
c. Type 0 for the
Minimum Value.
d. Type 4 for the Numeric
Field Width.
6. On the Connections tab,
select Change_Speed as the
Write tag and the Indicator
tag.
Publication 2711C-QS001F-EN-P - November 201075
Page 76
Chapter 7 Create the Motor Speed Screen
Create a Heading for the Numeric Entry Object
This topic shows how to create a heading above the numeric entry object.
1. Open the Drawing Tools tab
of the object palette.
2. Drag the Text object above
the numeric entry object.
3. Resize the object.
4. On the Appearance tab:
a. Type ENTER SPEED in
the Text box.
b. Set the Font Size to 16.
c. Check the Font
Underline checkbox.
d. Set the Border Style to
None.
Scroll down to see all the
properties.
5. Resize the object to fit the
text if necessary.
76Publication 2711C-QS001F-EN-P - November 2010
Page 77
Create the Motor Speed Screen Chapter 7
Create a Increment Decrement Object
The numeric increment decrement object lets you increase or decrease the rpm speed of the motor in manual
mode using small or large steps when a key is pressed. The object does not display a value until runtime.
1. Open the Entry tab of the
object palette.
2. Drag the Numeric
Increment Decrement object
below the numeric entry
object.
3. Resize object as needed.
4. On the Format tab of the
Properties panel:
a. Select Integer as the
Data Type.
b. Type 1000 for the
Maximum Value.
c. Type 0 for the
Minimum Value.
d. Set the Course Step to
10.
e. Set the Fine Step to 1.
Scroll down to see all the
properties.
5. On the Connections tab,
select Change_Speed as the
Write tag and the Indicator
tag.
Publication 2711C-QS001F-EN-P - November 201077
Page 78
Chapter 7 Create the Motor Speed Screen
Create Increment Decrement Keys
Keys are used to increase or decrease the motor speed displayed in the numeric increment decrement object.
The double arrows increase or decrease the speed in 10 rpm increments. The single arrows increase or
decrease the speed in 1 rpm increments.
1. Open the Entry tab of the
object palette.
2. Drag the Key object below
the increment decrement
object on the left side.
3. Resize the object.
4. Open the Navigation tab of
the Properties panel.
a. Select Page Up from
the Key Type field.
b. Type NumericIncDec_1
in the Link Target field.
This links the key to the
increment decrement
object. The object name is
on the Common tab of
the Properties panel.
5. Click on the Page Up key
just created, then press
Ctrl+C then Ctrl+V to copy
and paste the key.
6. Move the pasted object to
right of the first key.
7. On the Navigation tab, select
Up as the Key Type.
78Publication 2711C-QS001F-EN-P - November 2010
Page 79
8. Click on the Up key just
created, then press Ctrl+C
then Ctrl+V to copy and
paste the key.
9. Move the pasted object to
right of the second key.
10. On the Navigation tab, select
Down as the Key Type.
11. Click on the Down key just
created, then copy and paste
the key.
12. Move the pasted object to
right of the third key.
Create the Motor Speed Screen Chapter 7
13. On the Navigation tab, select
Page Down as the Key Type.
Publication 2711C-QS001F-EN-P - November 201079
Page 80
Chapter 7 Create the Motor Speed Screen
Create a Bar Graph
The bar graph monitors and displays the speed of the motor in a graphic form.
1. Open the Display tab of the
object palette.
2. Drag the Bar Graph object
to the right side of the
screen.
3. Resize the bar graph.
4. On the Appearance tab, set
the Background Fill Style to
Crosshatch.
5. On the Bar tab:
a. Set the Maximum Value
to 1000.
b. Select Bottom for the
Fill From Direction.
6. On the Connections tab,
select Motor_Speed as the
Read Tag.
80Publication 2711C-QS001F-EN-P - November 2010
Page 81
Create a Bar Graph Scale
1. On the Display tab of the
object palette, drag the
Linear Scale object to the
screen.
Create the Motor Speed Screen Chapter 7
2. On the Appearance tab of
the Properties panel select
Left as the Tick Mark
Direction.
3. Resize and move the scale to
the left side of the bar graph.
Publication 2711C-QS001F-EN-P - November 201081
Page 82
Chapter 7 Create the Motor Speed Screen
Create Text Labels for the Scale
1. Open the Drawing Tools tab
of the object palette.
2. Drag the Text tool next to
the linear scale.
3. On the Appearance tab of
the Properties panel:
a. Type 1000 in the Text
field.
b. Set the Border Style to
None.
Scroll down to see all the
properties.
4. Resize the text object and
place it next to the top
tick-mark of the scale.
5. Press Ctrl+C then Ctrl+V to
copy and paste the text
object.
6. Move the pasted object to
align with the bottom
tick-mark of the scale.
7. On the Appearance tab,
replace 1000 with 0 in the
Text field and press Enter.
8. Move or resize the text label
as needed.
82Publication 2711C-QS001F-EN-P - November 2010
Page 83
Create a Bar Graph Heading
1. Drag another text object
from the object palette
above the bar graph.
2. On the Appearance tab:
a. Type MOTOR SPEED
in the Text box.
b. Set the Font Size to 16.
c. Check the Font
Underline checkbox.
d. Set the Border Style to
None.
Scroll down to see all the
properties.
Create the Motor Speed Screen Chapter 7
3. Resize the object to fit all the
text and place above bar
graph.
Publication 2711C-QS001F-EN-P - November 201083
Page 84
Chapter 7 Create the Motor Speed Screen
Create a Numeric Display
The numeric display object appears next to the bar graph and displays the speed of the motor as a numeric
value.
1. Open the Display tab of the
object palette.
2. Drag the Numeric Display
object to the right of the bar
graph.
3. On the Appearance tab:
a. Set the Text Color to
Black.
b. Set the Background
Color to White.
c. Uncheck the Use
Background Color for
Border checkbox.
d. Set the Border Color to
Red.
Scroll to see all fields.
4. On the Format tab, type 4 in
the Number of Digits field.
5. On the Connections tab,
select Motor_Speed as the
Read Tag.
6. Resize the object.
84Publication 2711C-QS001F-EN-P - November 2010
Page 85
Create a Heading for the Numeric Display
1. Open the Drawing Tools tab
of the object palette.
2. Drag the Text tool above the
numeric display object.
3. On the Appearance tab:
a. Type RPM in the Text
field.
b. Set the Border Style to
None.
Scroll to see all fields.
Create the Motor Speed Screen Chapter 7
4. Resize the object.
5. Click the Save icon to save
the application.
Publication 2711C-QS001F-EN-P - November 201085
Page 86
Chapter 7 Create the Motor Speed Screen
Update the Motor Speed Screen Button
You need to update the Motor Speed screen button on the Motor Status screen so that it displays the correct
screen when the button is pressed. The Motor Speed screen did not exist when you first created the screen
button so you must go back and update the object.
1. Click the MOTOR STATUS
screen in the Screen List to
open the screen.
2. Select the MOTOR SPEED
button.
3. Open the Navigation tab of
the Properties panel.
4. In the Screen Number field,
select 2 - MOTOR SPEED.
The button will now
display the correct screen
when pressed.
5. Click the Save icon to save
the application.
86Publication 2711C-QS001F-EN-P - November 2010
Page 87
Chapter
Create Alarms
Introduction
In this chapter, you will create alarms that will be triggered when the motor speed is at its ideal operating
speed or near its upper threshold.
TopicPage
Review Application Alarms88
Open the Alarms View89
Create Alarms89
8
Before You Begin
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
• Open a new application.
• Configure runtime communication settings for the application.
• Create tags for the application.
• Create the Motor Status screen.
• Create the Motor Speed screen.
What You Need
• Motor_speed tag defined in the Tags view. This tag will be the trigger for two alarms.
87Publication 2711C-QS001F-EN-P - November 201087
Page 88
Chapter 8 Create Alarms
page 88
Review
Application
Alarms
Open the
Alarms View
Create Alarms
page 89
page 89
Follow These Steps
Complete these steps to create alarms for the sample application.
Review Application Alarms
The speed of the motor in the sample application ranges from 0 to 1000 rpm. The tag that controls the speed
of the motor is MOTOR_SPEED. Two numeric alarms will alert you when the motor reaches its ideal
operating speed and when the speed nears its upper threshold.
• The first alarm is triggered when the value at the Motor_Speed tag rises to 850 or above. When the
alarm is triggered, the alarm banner opens and displays the message MOTOR AT IDEAL
OPERATING SPEED!
• The second alarm is triggered when the value at the Motor_Speed tag rises to 900 or above. When the
alarm is triggered, the alarm banner opens and displays the message MOTOR SPEED NEAR
THRESHOLD!
Application alarms
Trigger TagAlarm TypeEdge DetectionValueDeadband
Level
Motor_SpeedNumericRising8500PercentMOTOR AT IDEAL
Motor_SpeedNumericRising9000PercentMOTOR SPEED
Deadband
Mode
Message
OPERATING
SPEED!
NEAR
THRESHOLD!
88Publication 2711C-QS001F-EN-P - November 2010
Page 89
Open the Alarms View
Adds an alarm.Switches the view between typical
and advanced tag properties.
Alarm fields
1. Click the Alarms tab to
open the Alarms view.
Create Alarms Chapter 8
Create Alarms
Each alarm occupies a separate row in the Alarms view. The fields in each row define the properties of an
alarm. As alarms are created, the fields are populated with defaults from row 1.
1. Click the Add Alarm
button.
2. Click the Typical button to
view fewer properties.
3. Click in the Trigger field and
select Motor_Speed.
Publication 2711C-QS001F-EN-P - November 201089
Page 90
Chapter 8 Create Alarms
4. Click in the Alarm Type field
and select Numeric.
Verify that the Edge
Detection is Rising.
5. Type 850 as th e Value.
6. Type MOTOR AT IDEAL
OPERATING SPEED! in
the Message field.
You can also click the ...
button in the Message field
to type the text in the text
dialog.
7. Click the Add Alarm button
add to another alarm.
The second alarm is created
with many of the defaults
from the previous alarm.
90Publication 2711C-QS001F-EN-P - November 2010
Page 91
8. Edit the alarm fields.
c. Change the Value to 900.
d. Type MOTOR SPEED
NEAR THRESHOLD! in
the Message field.
9. Click the Save icon to save
the application.
Create Alarms Chapter 8
Publication 2711C-QS001F-EN-P - November 201091
Page 92
Chapter 8 Create Alarms
Notes:
92Publication 2711C-QS001F-EN-P - November 2010
Page 93
Chapter
9
Validate and Run Application
Introduction
In this chapter, you will validate the application for correct operation and run the application in the terminal
while connected to the MicroLogix 1100 controller.
TopicPage
Validate the Application95
Connect Terminal to Controller96
Download Ladder Logic to Controller96
Run the Application97
Run the Motor in Manual Mode98
Run the Motor in Automatic Mode101
Go to Configuration Mode102
Before You Begin
• Review the sample application.
• Connect your terminal to your computer and launch the PanelView Explorer software.
• Configure browser settings.
• Open a new application.
• Configure runtime communication settings for the application.
• Create tags for the application.
• Create the Motor Status screen.
• Create the Motor Speed screen.
• Create alarms.
What You Need
• Saved and validated application.
• Connected MicroLogix 1100 controller in run mode with required loaded ladder logic file,
QuickStart.rss.
93Publication 2711C-QS001F-EN-P - November 201093
Page 94
Chapter 9 Validate and Run Application
page 97
Validate the
Application
Connect Terminal
to Controller
Download Ladder
Logic to
Controller
page 96
page 96
page 97
Run the
Application
Run the Motor in
Manual Mode
Run the Motor in
Automatic Mode
page 98
page 101
Go to
Configuration
Mode
page 102
Follow These Steps
Complete these steps to run the sample application on the terminal while connected to the MicroLogix
controller.
About the MicroLogix Controller
For the purpose of this quick start, the MicroLogix 1100 and PanelView components are not mounted in a
panel but are in a desktop configuration. This quick start does not provide MicroLogix specific information,
such as wiring, mounting, configuring, or loading the ladder logic file, QuickStart.rss.
For more information on the MicroLogix 1100 controller, refer to the Additional Resources in the preface of
this quick start.
94Publication 2711C-QS001F-EN-P - November 2010
Page 95
Validate and Run Application Chapter 9
ATTENTION
Running a non-validated application may result in
unexpected behavior.
Validate the Application
Before you can run an application on the PanelView Component, it is strongly recommended that you
validate the application for errors and warnings. The application does not need to be error-free to run,
however, it is good practice to fix both errors and warnings to ensure expected system behavior. Validation is
not supported in PVc DesignStation 2.0 .
1. Click the Validate icon on
the application toolbar.
If the application passes
validation, the Validation
Results dialog looks like this.
If the application detects
warnings or errors, the
Validation Results dialog
might look like this. For
each warning or error, the
message identifies the
problem and its location.
Correct the problem and
then revalidate the
application.
The status bar shows a
Validation Reports link
that you can open. It
always shows the results
of the last validation.
2. Click Close.
3. Click the Save icon to save
the application.
4. Click the Close Application
icon to close the application.
Publication 2711C-QS001F-EN-P - November 201095
Page 96
Chapter 9 Validate and Run Application
Ethernet Cable
Ethernet Port
10/100Base-T
Channel 0 Port
RS-232/485
8-pin Mini DIN
1761-CBL-PM02 Cable
RS-232 Serial Port
9-pin D-shell
To Ethernet DHCP-enabled Network
DF1 Connection
Ethernet Cable
Ethernet Port
10/100Base-T
Channel 1 Port
Ethernet 10/100Base-T
Ethernet Cable
Ethernet Cable
To Ethernet DHCP-enabled Network
Connect Terminal to Controller
DF1 Connection to MicroLogix Controller using 1761-CBL-PM02
For DF1 runtime operation, you will need to connect the 1761-CBL-PM02 between the RS-232 serial port of
the terminal and the Channel 0 port of the MicroLogix 1100 controller.
Ethernet Connection to MicroLogix Controller using Ethernet Cables
The MicroLogix 1100 controller and the PanelView Component terminal have only one Ethernet port. To
run the sample application from the Startup window of your browser, you will need an Ethernet switch. Use
standard Ethernet cables or the Ethernet crossover CAT5 cable, 2711P-CBL-EX04 to make the connections.
Download Ladder Logic to Controller
Before running the sample application, you must download the ladder logic file, QuickStart.rss, to the
MicroLogix controller. This ladder logic file is on the CD that ships with your terminal. The controller must
be in Run mode before you can run the sample application on the terminal.
96Publication 2711C-QS001F-EN-P - November 2010
Page 97
Validate and Run Application Chapter 9
Run the Application
This topic shows you how to run the sample application from the PanelView Explorer Startup window.
1. Verify the PanelView
Explorer Startup window is
open.
2. Select the SampleApplication
just created.
3. Click the Run button.
While the application is
loading on the terminal,
you will see:
Loading Application...
The Motor Status screen
opens, which is the
startup screen.
When the motor is
stopped, the Status
indicator displays
Stopping.
4. Verify the motor is stopped
by pressing the Stop Motor
button.
Publication 2711C-QS001F-EN-P - November 201097
Page 98
Chapter 9 Validate and Run Application
Run the Motor in Manual Mode
In manual mode, you have control of the motor. You can change the motor speed by using the numeric entry
object or the numeric increment decrement object. The numeric entry object opens a keypad where you enter
a new value. The numeric increment decrement object lets you change the motor speed in steps using keys.
To view the new motor speed, you must restart the motor.
The alarm banner will pop up over the displayed screen if the motor speed rises to 850 or above. Click the
Ack button to acknowledge each alarm and close the banner.
1. Press the Start Motor button
to start the motor.
The indicators shows the
motor is running and in
manual mode.
2. Press the Motor Speed
button to go to the Motor
Speed screen.
The numeric entry objects
show the current speed,
which is also displayed in
the bar graph and
numeric display.
98Publication 2711C-QS001F-EN-P - November 2010
Page 99
3. Press the numeric entry
78 9
45 6
12 3
0
Esc
Enter key
Numeric
Entry
251
object to enter a speed.
A numeric keypad opens
with the current speed
highlighted.
4. Enter 550 by pressing the
number keys.
5. Press the Enter key to save
the new speed and close the
keypad.
The speed is updated in
both numeric objects.
You must restart the
motor to see the new
speed in the numeric
display and bar graph.
Validate and Run Application Chapter 9
6. Verify the new speed.
a. Press the Motor Status
button to return to the
Motor Status screen.
b. Press the Stop Motor
button.
c. Press the Start Motor
button.
d. Press the Motor Speed
button to return to the
Motor Speed screen.
The bar graph and
numeric display update to
the new speed.
Publication 2711C-QS001F-EN-P - November 201099
Page 100
Chapter 9 Validate and Run Application
Page Up
Page Down
Up
7. Update the motor speed
in steps using the
numeric increment
decrement object.
a. Press the page up key
twice to increase the
speed by 20 rpm.
b. Press the up key three
times to increase the
speed by 3 rpm.
c. Press the page down
key once to decrease
the speed by 10 rpm.
The speed value is 563.
8. Repeat step 5 to verify the
new motor speed is
updated in the numeric
display and bar graph.
9. Press the Motor Status
button to return to the
Motor Status screen.
100Publication 2711C-QS001F-EN-P - November 2010
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.