Description1
Important Safety Instructions3
Nameplate Data4
Planning for Installation4
Install the Solar Combiner Enclosure5
Wire the Solar Combiner Enclosure8
Dimensions10
Specifications12
Additional Resources12
The solar combiner enclosure combines inputs from multiple solar arrays into an
output circuit. Two catalog numbers are available.
Table 1 - Product Selection
Cat. No.Number of PolesVoltage Rating
1000-SB0066
1000-SB01212
600V DC (continuous duty)
Solar combiner enclosures support these features:
• Listed to UL 1741 – Inverters, Converters, Controllers, and
Interconnecting System Equipment for Use with Distributed Energy
Sources
• Line and load terminals marked for using 90 °C (194 °F) copper wire
• UL Type 3, 4/4X, 12, and 13 enclosure ratings
• Fuse holders and power distribution blocks
• Configured for positive and negative grounded arrays
2 Solar Combiner Enclosure
IMPORTANT
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SG I - 1 . 1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or
economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be
present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
These symbols are used in this publication.
Ground symbol
Direct current symbol
Rockwell Automation Publication 1000-IN002B-EN-P - April 2012
Solar Combiner Enclosure 3
IMPORTANT
IMPORTANT SAFETY
INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
This publication contains important instructions for 6- and 12-pole solar
combiner enclosures, catalog numbers 1000-SB006 and 1000-SB012, that must
be followed during installation and maintenance:
• Use 90 °C (194 °F) copper wire only.
• This product is intended for operation in an environment with a
maximum temperature rating of 40 °C (104 °F)
• For entry into the enclosure, use only UL-Listed raintight or wet location
hubs (for UL Type 3R, 12, and 13) that comply with the requirements in
the Standard for Conduit, Tubing, and Cable fittings (UL514B).
• Use only UL-Listed watertight hubs (for UL Type 4/4X) that comply
with the requirements in the Standard for Conduit, Tubing, and Cable
fittings (UL514B).
Bonding between conduit connections is not automatic and must be provided as part
of the installation.
SHOCK HAZARD: Disconnect and lock out power before entering or performing
maintenance on the enclosure.
SHOCK HAZARD: Normally-grounded conductors may be ungrounded and energized
when a ground fault is indicated.
SHOCK HAZARD: When the photovoltaic array is exposed to light, it supplies a DC
voltage to this equipment.
Follow National Electric Code, ANSI/NFPA 70, Requirements
The system installer is responsible for the following:
• Follow National Electric Code wiring methods
• Follow cUL certification requirements, including
CSA C22.2 No. 107.1-01, clause 154.5.2
• For Canadian installations, following the wiring methods per the
Canadian Electrical Code, Part II
• System grounding, if required by Section 250 of the National Electric
Code (DC input and output circuits are isolated from the enclosure)
• Install photovoltaic system grounding per the requirements of
Sections 690.41…690.47 of the National Electric Code
Rockwell Automation Publication 1000-IN002B-EN-P - April 2012
4 Solar Combiner Enclosure
The following product information is provided on the nameplate.
Table 2 - Nameplate Fields
FieldDescription
CATALOG NO.Catalog number
SERIESSeries letter of the product
A-B SERIAL NO.Product serial number
MAX. SYSTEM VOLTAGE [V]Voltage of the system in volts, max
MAX. AIR AMBIENT TEMP.Air ambient temperature in degrees Celsius, max
ENCL. TYPEUL enclosure type
RATED INPUTOperating output current, max
MAX. FUSE RATINGFuse rating, max
FUSE TYPEFuse type
WIRING DIAGRAMSchematic number
MAX. Isc PER STRING [A]Short circuit current per string, max
Nameplate Data
Figure 1 - Nameplate Sample
Each solar combiner enclosure has a nameplate on the enclosure or enclosure
door, similar to the example shown below.
Planning for Installation
When planning the location for your solar combiner enclosure, consider the
following:
• Conduits
• Type of installation
• Product dimensions (see pages 10
and 11)
• Mounting requirements
• Connection to other equipment
• Enclosure rating
• Environmental conditions
• Future needs
Environment and Enclosure
Most applications require installation in an industrial enclosure to reduce the
effects of electrical interference and environmental exposure. Locate your
controller as far a possible from power lines, load lines, and other sources of
electrical noise, such as hard-contact switches, relays, and AC motor drives.
Rockwell Automation Publication 1000-IN002B-EN-P - April 2012
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.