Robinair 17680-2K User Manual

○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Operating Manual
Model 176802K
Refrigerant Recovery Station
Refrigerant Recovery Station
TO PREVENT PERSONAL INJURY AND/OR EQUIPMENT DAMAGE : BEFORE OPERATING THE REFRIGERANT RECOVERY STATION, READ AND FOL-
LOW THE OPERATING INSTRUCTIONS AND SAFETY PRECAUTIONS IN THIS MANUAL. This station should only be operated by qualified personnel. The operator must
be familiar with A/C-R systems, refrigerants, and the dangers of pressurized components. If the operator cannot read these instructions, safety precautions and instructions must be
read and discussed in the operator's native language. – Si el operador no puede leer inglés, las instrucciones de operación y las precauciones de
seguridad deberán leerse y comentarse en el idioma nativo del operador. – Si l'utilisateur ne peut lire l'anglais, les instructions et les consignes de sécurité doivent lui
être expliquées dans sa langue maternelle.
THE PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. OVERFILLING THE TANK MAY CAUSE VIOLENT EXPLOSION AND POSSIBLE INJURY OR DEA TH. Safety
devices require the use of only the following Robinair refrigerant tank: 17686 (50-lb. tank). Do not recover refrigerants into a nonrefillable storage container! Federal regulations re­quire refrigerant to be transported only in containers meeting DOT spec. 4BW or DOT spec. 4BA.
ALL HOSES MA Y CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause injury. W ear protective equipment, including safety goggles. Discon­nect hoses using extreme caution.
VERIFY ALL SAFETY DEVICES ARE FUNCTIONING CORRECTLY BEFORE OPERA T­ING THE STATION.
THIS UNIT CONTAINS MIXED REFRIGERANT WHICH CANNOT BE USED IN ANY A/C SYSTEM. This tank may contain hydrocarbons. Do not use around open flame or
spark-generating equipment.
Refrigerant: Mixed Serial No.: Date Code:
WARNING
2
ATTENTION!
Ce réservoir sous pression contient du frigorigène liquids. S’il est surchargé, ce réservoir peut exploser et causer des blessures ou la mort.
ATTENTION. Débrancher avant la maintenance.
© 2000 Robinair Division, SPX Corporation
Introduction
TABLE OF CONTENTS
Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Setup Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Diagram of Station’s Components Diagram of Control Panel
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Maintenance Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Replacement Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Troubleshooting Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
GLOSSARY OF TERMS
A/C . . . . . . . . . Air conditioning
A/C System . . The air conditioning system being serviced
Station . . . . . . The 176802K Scavenger™ Refrigerant Recovery Station
Tank . . . . . . . . The refrigerant tank
INTRODUCTION
The Scavenger™ Refrigerant Recovery Station removes contaminated or unknown refrigerant from automotive A/C systems to prevent the cross-contamination of a service station’s R-12 and R-134a supply.
It is designed specifically for use with a refrigerant identifier capable of determin­ing if the refrigerant is R-12, R-134A, or some other (unknown) refrigerant. In the case of an unknown refrigerant, the service technician can use this station to recover the refrigerant into a special 50-pound tank for transport to a disposal facility.
Model 176802K Scavenger™ Recovery Unit
3
Setup Instructions
To initially set up the station for operation:
1. Unpack all components and verify you have the following: (1) 50-pound refrigerant tank
(1) 96" Blue Enviro-Guard® Hose for R-12 (1) 96" Blue Enviro-Guard® Hose for R-134a (with adapter)
Please read this operating manual, and fill out and return the warranty registration card.
2. Connect the two 96" blue hoses to their respective 1/4" flare and 1/2" Acme inlet
NOTE:
The numbers in parentheses correspond to the callouts shown in the diagrams on page 5.
ports (7) on the back of the station. (Connect the hose ends without the valves to the station.)
The inlet ports on the back of the station are capped for shipment. Both hoses must be connected to the station during recovery, or the unused port must be capped. When not in use, the hoses can be wrapped around the station’s handle.
3. The station is equipped with its own regulator (6) that has an inlet with 1/4" female pipe thread. A male air line connector (not included) that matches your air system must be connected to the regulator.
4. The station is equipped with its own air line lubricator (4) to lubricate the air motor that runs the compressor inside the unit. This lubricator must be filled with
3
/4 oz. (22 ml) of pneumatic air line oil or detergent SAE #10 motor oil.
Unscrew the plastic bowl on the lubricator and fill with oil to approximately 1/2" below the top of the bowl. (Do not lose the o-ring on the top of the bowl.) Replace the bowl on the lubricator. Snug down, but do not overtighten.
IMPORTANT: The bowls for both the lubricator and regulator are made from polycarbonate. Oils used in the lubricator bowl must be compatible with polycarbonate. Some “fire resistant” oil additives are not compatible; do not expose bowls to acetone, trichloroethane, gasoline, alcohols, ketones, esters, chlorinated hydrocarbons, or toluene. Wash the bowls only with warm water or kerosene.
5. The tank supplied with the Scavenger™ is filled with 10 to 15 psi of dry nitrogen which must be removed before it can be used. Open the tank valve to release the nitrogen. Use a separate vacuum pump to pull a five-minute vacuum on the tank.
6. The tank is now ready to be connected to the recovery station. Place the tank on the platform just over the axle on the rear of the station. Tighten the black strap securely around the tank. Connect the black 3/8" hose (2) coming from the back of the station to the 3/8" flare fitting on the tank’s blue (LIQUID) valve.
4
7. Connect the yellow float switch cable to the tank.
© 2000 Robinair Division, SPX Corporation
Set Up Instructions
0
1 0
20
3
0
40
3
0
G
N
I
H
35
0
S
I
P
1
20
ROBINAIR
11
0
100
90
5
0
60
7
0
80
0
P
S
I
500
ROBINAIR
5 0
100
15
0
2
00
250
3
5 0
45
0
400
3
00
ROBINAIR
5
4
42
53
3
2
1
Diagram of Station’s Components
6
7
8
9
10
INST0195
1. Drain for Drip Pan
2. Black 3/8" Discharge Hose
3. Accumulator Oil Drain
4. Lubricator
5. Battery Clips
6. Regulator
7. Inlet Ports
Inlet Pressure Tank Pressure
11 12
0
5
40
0 3
ROBINAIR
20
1 0
0
3
0
I
M
A
D
60
7
0
80
90
10 0
110
20
1
0
35
I
S
N
P
H
G
A
S
U
E
N
I
Diagram of Control Panel
Start
Recover
ABCO
KANTLEAK
8. Blue Recovery Hoses
9. Float Cable
10. R-134a Service Coupler
11. Inlet Pressure Gauge
12. Tank Pressure Gauge
13. Control Panel Valve
14. Yellow/Green LED Lights
250
3
00
00
2
150
100
5 0
0
M
13
ROBINAIR
A
D
3 5
0
400
450
0
50
I
S
P
A
S
U
E
N
I
INST0116
Model 176802K Scavenger™ Recovery Unit
5
Operating Instructions
Wear safety goggles when working with refrigerants. Read and follow all warnings at the beginning of this manual before oper­ating this machine.
Connecting hoses to the wrong ports may cause personal injury and/or damage to the equipment. Check your vehicle’s A/C system operating manual for the correct hookup.
Handle battery connection cables with extreme caution — batter­ies generate explosive gases during normal battery operation. Working in the vicinity of a lead-acid or other automotive battery is dangerous. Wear complete eye protection. NEVER smoke or allow a spark or flame in the vicinity of a battery.
1. Run the vehicle’s A/C system for a few minutes before starting the recovery process. Tests show more refrigerant is recovered if this action is taken. Turn the
NOTE:
Numbers in parentheses correspond to callouts shown in the diagrams on page 5.
system off before proceeding.
2. Connect one of the station’s blue recovery hoses (8) to the low-side service port on the vehicle’s air conditioning system. The other blue recovery hose should not be connected to the vehicle’s system, but should remain connected to the back of the recovery station.
3. Open the tank valve with the 3/8" hose connected to it. Open the 3/8" hose valve.
WARNING
4. Turn the control panel valve (13) to START. This equalizes the pressure on both sides of the compressor, allowing easier starts.
5. Connect a compressed air line (120 psi minimum; 200 psi maximum) to the air inlet on the regulator (6) on the back of the station.
6. Connect the red power lead to the “+” (positive) post of the vehicle’s battery, or to another 12-volt power source. Then connect the black power lead to an engine ground, not the battery “-” (negative) terminal.
The compressor should start idling, and the yellow power LED and the green tank level LED will illuminate. If the green LED does not illuminate, the tank is full or the float cable is disconnected.
7. Turn the control panel valve (13) to RECOVER. There should be a change in the sound of the compressor. The inlet pressure gauge (11) should show a drop in pressure, and the tank pressure gauge (12) should rise.
8. When the inlet pressure reaches a vacuum, disconnect the air line. Wait five (5) minutes. If the inlet pressure rises above 0 (zero) psi, repeat Steps 4 through 8.
6
© 2000 Robinair Division, SPX Corporation
Operating Instructions
Sometimes refrigerant will pool inside the system. When the compressor is turned off, ambient heat will vaporize this pooled refrigerant, causing system pressure to rise again. The recovery process should be repeated until the system remains at a vacuum for at least two (2) minutes.
9. When the recovery process is complete, close the tank’s valve, close the hose valve, and disconnect the recovery hose from the vehicle.
10. Disconnect the compressed air line from the back of the station.
11. Disconnect the black power lead; disconnect the red power lead from the vehicle’s battery or the 12-volt power source.
12. After each recovery, carefully open the accumulator oil drain (3) and drain any
collected compressor oil into an appropriate container. Small amounts of refrigerant can remain in the accumulator and build up a slight
pressure — it is best to drain the accumulator when the inlet pressure is in a vacuum. There may not always be any oil to drain; it will vary from system to system. Dispose of the old compressor oil in an appropriate manner.
13. The tank’s float switch will automatically shut off the station when the tank is full.
To change a full tank in the middle of a recovery job,
A. Turn off the tank valve, close the ball valve in the 3/8" tank hose, and unscrew
and remove the float cable from the tank.
B. Disconnect the hose from the tank valve, and remove the tank from the
station. Replace it with a new tank. (Prepare new tanks by releasing the dry nitrogen charge and pulling a five-minute vacuum).
C. Reconnect the tank hose, open the tank valve with the 3/8" hose connected to it,
open the 3/8" hose valve, and reconnect the float cable. Recovery will proceed as soon as both valves are open.
IMPORTANT! To prevent equipment damage, do not use recovered
refrigerant in any A/C system. Send the full tank to a disposal facility ca­pable of handling mixed refrigerants.
Model 176802K Scavenger™ Recovery Unit
7
Maintenance Instructions
This station is designed to operate with a minimal amount of maintenance.
NOTE:
Numbers in parentheses correspond to callouts shown in the diagrams on page 5.
1. For correct lubrication of the air motor, the oil level in the air line lubricator (4) on the back of the station must be maintained above the bottom of the dip tube inside the lubricator’s bowl. Fill with 3/4 oz. (22 ml) of pneumatic air line oil or detergent SAE #10 motor oil.
To add oil, unscrew the plastic bowl on the lubricator and fill to approximately
1
/2" below the top of the bowl. (Do not lose the o-ring on the top of the bowl.)
Replace the bowl on the lubricator. Snug down, but do not overtighten.
IMPORTANT: The bowls for both the lubricator and regulator are made from polycarbonate. Oils used in the lubricator bowl must be compatible with polycarbonate. Some “fire resistant” oil additives are not compatible; do not expose bowls to acetone, trichloroethane, gasoline, alcohols, ketones, esters, chlorinated hydrocarbons, or toluene. Wash the bowls only with warm water or kerosene.
2. The drive air containing the lubrication oil is exhausted through a filter/ muffler inside the station. The oil condenses and collects in a drip pan at the bottom of the station. The drain (1) for the drip pan is located at the lower right front corner of the station. After refilling the lubricator, drain the used air line oil into an appropri­ate container. Dispose of the used oil according to local, state, and federal regula­tions.
REPLACEMENT PARTS LIST
Part Number Description
17686 . . . . . . . . . 50-pound Refrigerant Tank
68296 . . . . . . . . . 96" Recovery Hose (1/4" Flare)
37296 . . . . . . . . . 96" Recovery Hose (1/2" Acme)
18190A . . . . . . . . R-134a Service Coupler (Low Side)
TOLL-FREE
TECHNICAL SUPPORT LINE
1-800-822-5561
(United States and Canada)
8
© 2000 Robinair Division, SPX Corporation
Troubleshooting Tips
Unit runs for short time before building up high tank pressure, or compressor stalls.
Problem: Tank valve closed. Solution: Open the tank valve with 3/8" adapter, and open the 3/8" hose valve.
Compressor stalls during recovery. Problem: Insufficient supply of air pressure.
Solution: Supply air pressure should be a minimum of 120 psi and a maxi-
mum of 200 psi.
Problem: Insufficient supply of air volume. Solution: Minimum volume of supply air should be 10 CFM at 120 psi.
Problem: High tank pressure or full tank. Solution: Replace the tank with a new Scavenger
TM
tank.
Problem: Mechanical failure. Solution: Call the service center.
Compressor will not start. Problem: Pressure is not equalized inside the compressor.
Solution: Turn control panel valve to START. Problem: Insufficient supply of air pressure.
Solution: Supply air pressure should be a minimum of 120 psi and a maxi-
mum of 200 psi.
Problem: Insufficient supply of air volume. Solution: Minimum volume of supply air should be 10 CFM at 120 psi.
Problem: High tank pressure or full tank. Solution: Replace the tank with a new ScavengerTM tank.
Problem: Mechanical failure. Solution: Call the service center.
Problem: There is no power to the recovery station. Solution: Connect the red power lead to the “+” (positive) post of the
vehicle’s battery, or to another 12-volt power source. Connect the black power lead to an engine ground, not the battery “-” (nega­tive) terminal.
Model 176802K Scavenger™ Recovery Unit
9
WARRANTY
This product is warranted to be free from defects in workmanship, materials, and components for a period of one year from date of pur­chase. All parts and labor required to repair defective products covered under the warranty will be at no charge. The following restrictions apply:
1. The limited warranty applies to the original purchaser only.
2. The warranty applies to the product in normal usage situations only,
3. If the product fails, it will be repaired or replaced at the option of the
4. The manufacturer shall not be responsible for any additional costs
as described in the operating manual. The product must also be serviced and maintained as specified.
manufacturer. Equipment must be shipped prepaid to a service center. The manufacturer will pay return freight on in-warranty items only. Warranty service claims are subject to service center inspection for product defect(s).
associated with a product failure including, but not limited to, loss of work time, loss of refrigerant, and unauthorized shipping and/or labor charges.
5. All warranty service claims must be made within the specified war­ranty period. Proof-of-purchase date must be supplied to the manufac­turer.
6. Use of this equipment with unauthorized refrigerants will void our warranty. Authorized refrigerants are listed on the equipment or are available through our Technical Service Department.
This Limited Warranty does not apply if:
• The product, or product part, is broken by accident.
• The product is misused, tampered with, or modified.
• The product is used with any substance other than the specified refrigerant type.
10
© 2000 Robinair Division, SPX Corporation
Notes
Model 176802K Scavenger™ Recovery Unit
11
For assistance in servicing or using the Scavenger™ Refrigerant Recovery Station, call the toll-free Technical Support Line, 800-822-5561, in the U.S. and Canada, or visit our web site at www.robinair.com. In all other locations, contact your local distributor. To help us serve you better, be prepared to provide the model number, serial number, and date of purchase.
To validate your warranty, complete the warranty card attached to your unit and return it within ten days from date of purchase. In addition, returning the warranty card automatically registers you for
Service•Link, our three-phase support program:
• Toll-Free Service Line — By calling our toll-free Service Line, you
can talk directly to service technicians who can walk you through setup and operating procedures, as well as repair procedures should something go wrong.
• Nationwide Network of Authorized Service Centers — If you need assistance or service, call our toll-free Service Line for the location of the Service Center nearest you.
• Info Source — We’ll help you keep up to date with information on CFC/HCFC issues as they evolve.
SPX Corporation 655 Eisenhower Drive Owatonna MN 55060 Customer Service: 1-800-533-6127 Fax : 1-800-322-2890 Technical Service : 1-800-822-5561 Fax : 1-800-822-7805 Website : www.robinair.com
122941 (Rev. B, 4-28-04) Model 176802K Refrigerant Recovery Station © 2000 SPX Corporation
Loading...